INEL4406 Transformers and Electric Machines Laboratory

Laboratory Session 5. Three-Phase Transformer; Voltage and


Current Relationships and Connections

Julin A. Lpez Rentas


Sergio G. Sez Rodriguez
March 7, 2017
Introduction
Experiment 5.1 The Wye-Wye Three-Phase Transformer Bank

Procedure

Step 1: Connect the circuit shown in figure 5.8. Neutral connection will not be used. Use
the fixed output of the power supply as your power source. The single-phase
transformer ratio to be used is 1:1 and R1=R2=R3= 600 Ohms.
Step 2; Find out both phase and line currents at primarys and secondarys windings.
Step 3: Connect the AC voltmeters according to the measurements you need to make.
Step 4: Turn on the power supply and complete the columns marked as Y-Y in the
Table 5.1.
Step 5: Turn off the power supply.

Question 1: In case of Figure 5.2b, Figure 5.2c, which is safe, connected.

Question 2: Figure 5.4b and Figure 5.4c are incorrect and Figure 5.4d is correct. Can
you explain the reasons?

Question 3: Which figure (Figure 5.5b or Figure 5.5c) is right connected so the voltage
system is balanced?
Question 4: Which one (Figure 5.6a or Figure 5.6b) is agreed with the American
standards?
Experiment 5.2 The Wye-Delta Three-Phase Transformer Bank

Procedure

Step 1: Connect the circuit shown in figure 5.8. Neutral connection will not be used. Use
the fixed output of the power supply as your power source. The single-phase
transformer ratio to be used is 1:3 . The 120V winding is the primary and the 208V
winding is the secondary.
R1=R2=R3= 600 Ohms
L1=L2=L3= 300 Ohms
Step 2: Substitute the AC ammeters by the marked lead.
Step 3: Connect the AC voltmeters according to the measurements you need to make.
Step 4: Turn on the power supply and complete the columns marked as Y- in the
Table 5.1.
Step 5: Turn off the power supply.
Experiment 5.3 The Delta-Wye Three-phase Transformer Bank

Procedure

Step 1- Connect the circuit shown in Figure 5.14. Neutral connection will not be used.
Use the variable output of the power supply as your power source. The single-phase
transformer ratio to be used is 3: 1 Adjust the power supply line-to-line voltage to
120V. R=600 ohm and L=300 ohm.
Step 2- Measure the secondary windings line and phase currents. Also measure the
primary windings line and phase currents
Step 3- Connect the AC voltmeters according to the measurements you need to make
Step 4- Turn on then power supply and complete the columns marked as Delta-Y in the
Table 5.1
Step 5- Turn off the power supply
Experiment 5.4 The Delta-Delta Three-Phase Transformer Bank

Procedure

Step 1- Connect the circuit shown in Figure 5.12 Neutral connection will not be used.
Use the foxed output of the power supply as your power source. The single-phase
transformer ratio to be used is 3: 1 R1=R2=R3=85.7 ohm
CautionThe delta should never be closed until a test is first made to determine that
the voltage within the delta is zero. If not and the delta is closed on itself, the resulting
current will be of Short-Circuit magnitude with resulting damage to the transformers.
Step2- Substitute the AC ammeter by the marked leads (one at a time)
Step3- Connect the AC voltmeters according to the measurements you need to make
Step 4- Turn the power supply and complete the columns marked as delta-delta in the
table 5.1
Step 5- Turn off the power supply
Y-Y Y- -Y -
Single Transformer VLN 1:1 1:3 3:1 3:1
Ratio
Transformer Bank VLL 1:1 1:3 3:1 3:1
Ratio
W1 17.21 35.87 26.13 75.96
W2 19.30 93.92 64.01 113.64
P3phase W1 +W2 36.51 129.79 90.14 189.6
Q3phase (W1- W2)3 -3.62 -100.55 -65.61 -65.26
lS3phasel 2 + 2 36.69 164.18 111.49 200.51
P3phase 0.9951 0.7905 0.8085 0.9456
PF lS3phasel
Secondary Windings 207.2 205.3 310.12 310.12
VLL
Secondary Windings 118.3 205.3 181.4 181.4
Vphase
Secondary Windings IL 0.182 0.731 0.772 0.784
Secondary Windings 0.182 0.415 0.772 0.784
Iphase
Primary Windings VLL 212.4 212.1 212.3 212.22
Primary Windings Vphase 105.2 120 212.3 212.21
Primary Windings IL 0.179 0.431 0.190 0.545
Primary Windings Iphase 0.183 0.198 0.322 0.545
Maximum 3 phase
Power
Conclusion