Académique Documents
Professionnel Documents
Culture Documents
7, July 1983
ELECTRICAL ASPECTS OF TESTING
INSULATING GLOVES
Abstract - Electrical aspects of testing photographs of negative and positive coronas have
insulating gloves (used in live line maintenance) are shown that with proper grading, negative streamers
discussed with a major emphasis on the electrical could be controlled so that the cuff to water line
stresses that occur at the water surface near the clearance was reduced, enabling more of the glove to
cuff of the glove. Methods are presented for be tested. Later, in 1981, work in this area was
reducing corona and ozone damage to natural rubber further continued at APCo's Roanoke, Virginia
insulating gloves during in-service AC electrical facilities using a specially constructed test
testing. Also, improvements made in AC and DC glove container. Tests were performed with an AC and DC
tests show a reduction in the cuff to water line source and in each case means were found to reduce the
clearance for Class 4 gloves from 15.2 to 7.6 cm, cuff to water line clearance. The Roanoke tests
enabling an additional 18% of the glove to be tested. showed that in AC testing, visual corona started at
about 10 kV which meant that some effects of corona
1. INTRODUCTION damage may occur at test voltages above 10 kV. This
was substantiated by the retest experience from
Insulating gloves used for live line maintenance several utilities. It was found that in retesting
work are electrically tested according to Standards Class 2 gloves at 20 kV AC, about 50% of the
[1,2,3] for acceptance and for in-service testing. electrical breakdown failures of the gloves occurred
Both tests have the same test voltage requirements. around the cuff at the water surface where corona can
For example, in the case of Class 2 gloves, the be observed.
Acceptance Standard [1] proof test voltage (20 kV AC The aim of this paper is to discuss electrical
or 50 kV DC) is the same as the retest voltage in the aspects of testing insulating gloves with a major
In-Service Standard [2]. The tests are meant to be emphasis on the electrical stresses that occur at the
nondestructive. However, there is evidence that the water surface near the cuff of the glove. The results
AC tests are suspected of causing damage even to from Huntington and Roanoke tests were used to
Class 2 gloves. This is quite evident in Class 4 describe the electrical stresses that cause corona
gloves. In fact, the standards give some recognition effects on gloves. The paper discusses AC and DC
to the nature of the damage by mentioning "corona tests. Also, some practical suggestions are given for
cutting" and "ozone checking. " Also, gloves and the reduction of electrical stresses so that in both
sleeves are classified in the standard as Type I AC and DC tests, the length of glove cuff above the
natural rubber and Type II ozone resistant (made from water line can be reduced enabling as much as an
synthetic material). The practice, perhaps in the additional 20% of the glove to be tested.
majority of utilities that use Class 4 gloves, is to More work is needed to provide the information on
retest the gloves with a DC rather than an AC source. the magnitude of electrical stresses that exist around
However, even though DC may be a solution for the glove below, at and above the water level for both
retesting gloves periodically, a number of utilities AC and DC tests. Also, a number of questions are
would like to proof test or certify new gloves with being raised in regard to the adequacy and correctness
an AC test. of the existing Standards for glove testing and for
The problem in AC testing of natural rubber that matter, the testing of sleeves and other
gloves lies in the test equipment. Due to the test insulating protective equipment.
electrode configuratioIn in the wet (water to water)
test set, the electrical stresses at the water 2. AC TEST CONSIDERATIONS
surf ace and the cuf f of the glove can reach a- level
at which the surrounding air is ionized, resulting in A. Electrical Stresses
the production of ozone and corona [4,5]. Some work
investigating this phenomenon was made by American A common method of testing the electrical
Electric Power Service Corp. (AEPSC) back in 1974 strength of gloves involves applying a test voltage to
when tests with Class 4 gloves were conducted at water electrodes, one outside and one inside of the
Appalachian Power Company's (APCo) Huntington, W. glove. In general, since the electrical breakdown of
Virginia glove test facility. At that time, special the glove varies with the thickness of the rubber [6],
grading rings were first installed on the inside and this type of test is used to identify imperfections
outside of a glove to reduce corona effects. Also, such as cuts, scratches or other damage to the glove.
The permittivity of water is relatively 80 times that
of air, causing a reduction of the electric field in
the water. Some intensification of the field will
occur in areas such as the finger tips and between the
fingers of the glove. The electrical field is also
intensified at the water surface, due to the shape of
the water meniscus. This field intensification can
83 WM 174-0 A paper recommended and approved by break down the air, causing corona effects.
the IEEE Transmission and Distribution Committee Consequently, the electrical stresses at the water
of the IEEE Power Engineering Society for presen- surface can cause major problems in testing gloves.
tation at the IEEE/PES 1983 Winter Meeting, New Therefore, further discussions will be limited to the
York, New York, January 30-February 4, 1983. control of electrical stresses at and above the water
level.
Manuscript submitted August 30, 1982; made avail-
able for printing November 16, 1982.
3. DC TEST CONSIDERATIONS
A. Electrical Stresses
There is a difference in the electrical phenomena
Photo 1 Photo 2 during AC and DC testing of gloves. In AC testing,
there is an intense time changing electric field
Class 4 Gloves Before Visual Corona Starts at present in the water, air and glove in the area of the
Testing Left Glove Shown 10 kVAC on Right Glove. water meniscus which causes corona discharge.
With Water Grading Rings Both Gloves Have 10.2cm However, with a constant DC voltage (less than 2%
of Cuff Above Water
ripple), this intense electric field is static
(stationary).
The following explanation of DC phenomena is
given in the attempt to describe this method of
testing gloves. During DC testing, the stationary
electric field is of such intensity that ionized
particles are created about the water meniscus areas.
However, since the electric field is static, the
particles are suspended or held in place about the
water meniscus in the form of nonvisible space
charges. These space charges exist about the water
meniscus areas on the negative and positive energized
water inside and outside of the glove. These space
charges act as an extension of the water electrode at
Photo 3 Photo 4 the glove cuff, smoothing out the electric field about
the area.
20 kV AC Corona 35 kV AC Right Glove Further increase in voltage tends to enlarge the
Begins on Left Glove Flashes Over in Air size of the space charge causing it to develop farther
up the cuff. Eventually, at the flashover voltage, a
discharge will occur in the air over the glove cuff
as the space charges on either side of the glove cuff
reach the top and merge.
Consequently, during the course of DC testing of
gloves, there are no detectable visible or audible
electrical discharges or is there any appreciable
generation of ozone. Of course, during a flashover or
a glove puncture, a visual and audible discharge will
occur. It should be noted that a widely fluctuating
DC source can cause some corona generation. Most
commercial glove testers,however, do not have this
problem since they operate in accordance to the
Photo 5 Photo 6
Standard's recommended DC voltage of less than 2%
40 kV AC on Left Glove 45 kV AC Negative ripple.
Right Glove Deenergized Corona on Left Glove
4. ROANOKE TEST CONFIGURATION