Vous êtes sur la page 1sur 5

2364 IEEE Transactions on Power Apparatus and Systems, Vol. PAS-102, No.

7, July 1983
ELECTRICAL ASPECTS OF TESTING
INSULATING GLOVES

Nestor Kolcio, Senior Member Richard A. Peszlen, Member


American Electric Power Service Corporation
180 East Broad Street
Columbus, Ohio 43215

Abstract - Electrical aspects of testing photographs of negative and positive coronas have
insulating gloves (used in live line maintenance) are shown that with proper grading, negative streamers
discussed with a major emphasis on the electrical could be controlled so that the cuff to water line
stresses that occur at the water surface near the clearance was reduced, enabling more of the glove to
cuff of the glove. Methods are presented for be tested. Later, in 1981, work in this area was
reducing corona and ozone damage to natural rubber further continued at APCo's Roanoke, Virginia
insulating gloves during in-service AC electrical facilities using a specially constructed test
testing. Also, improvements made in AC and DC glove container. Tests were performed with an AC and DC
tests show a reduction in the cuff to water line source and in each case means were found to reduce the
clearance for Class 4 gloves from 15.2 to 7.6 cm, cuff to water line clearance. The Roanoke tests
enabling an additional 18% of the glove to be tested. showed that in AC testing, visual corona started at
about 10 kV which meant that some effects of corona
1. INTRODUCTION damage may occur at test voltages above 10 kV. This
was substantiated by the retest experience from
Insulating gloves used for live line maintenance several utilities. It was found that in retesting
work are electrically tested according to Standards Class 2 gloves at 20 kV AC, about 50% of the
[1,2,3] for acceptance and for in-service testing. electrical breakdown failures of the gloves occurred
Both tests have the same test voltage requirements. around the cuff at the water surface where corona can
For example, in the case of Class 2 gloves, the be observed.
Acceptance Standard [1] proof test voltage (20 kV AC The aim of this paper is to discuss electrical
or 50 kV DC) is the same as the retest voltage in the aspects of testing insulating gloves with a major
In-Service Standard [2]. The tests are meant to be emphasis on the electrical stresses that occur at the
nondestructive. However, there is evidence that the water surface near the cuff of the glove. The results
AC tests are suspected of causing damage even to from Huntington and Roanoke tests were used to
Class 2 gloves. This is quite evident in Class 4 describe the electrical stresses that cause corona
gloves. In fact, the standards give some recognition effects on gloves. The paper discusses AC and DC
to the nature of the damage by mentioning "corona tests. Also, some practical suggestions are given for
cutting" and "ozone checking. " Also, gloves and the reduction of electrical stresses so that in both
sleeves are classified in the standard as Type I AC and DC tests, the length of glove cuff above the
natural rubber and Type II ozone resistant (made from water line can be reduced enabling as much as an
synthetic material). The practice, perhaps in the additional 20% of the glove to be tested.
majority of utilities that use Class 4 gloves, is to More work is needed to provide the information on
retest the gloves with a DC rather than an AC source. the magnitude of electrical stresses that exist around
However, even though DC may be a solution for the glove below, at and above the water level for both
retesting gloves periodically, a number of utilities AC and DC tests. Also, a number of questions are
would like to proof test or certify new gloves with being raised in regard to the adequacy and correctness
an AC test. of the existing Standards for glove testing and for
The problem in AC testing of natural rubber that matter, the testing of sleeves and other
gloves lies in the test equipment. Due to the test insulating protective equipment.
electrode configuratioIn in the wet (water to water)
test set, the electrical stresses at the water 2. AC TEST CONSIDERATIONS
surf ace and the cuf f of the glove can reach a- level
at which the surrounding air is ionized, resulting in A. Electrical Stresses
the production of ozone and corona [4,5]. Some work
investigating this phenomenon was made by American A common method of testing the electrical
Electric Power Service Corp. (AEPSC) back in 1974 strength of gloves involves applying a test voltage to
when tests with Class 4 gloves were conducted at water electrodes, one outside and one inside of the
Appalachian Power Company's (APCo) Huntington, W. glove. In general, since the electrical breakdown of
Virginia glove test facility. At that time, special the glove varies with the thickness of the rubber [6],
grading rings were first installed on the inside and this type of test is used to identify imperfections
outside of a glove to reduce corona effects. Also, such as cuts, scratches or other damage to the glove.
The permittivity of water is relatively 80 times that
of air, causing a reduction of the electric field in
the water. Some intensification of the field will
occur in areas such as the finger tips and between the
fingers of the glove. The electrical field is also
intensified at the water surface, due to the shape of
the water meniscus. This field intensification can
83 WM 174-0 A paper recommended and approved by break down the air, causing corona effects.
the IEEE Transmission and Distribution Committee Consequently, the electrical stresses at the water
of the IEEE Power Engineering Society for presen- surface can cause major problems in testing gloves.
tation at the IEEE/PES 1983 Winter Meeting, New Therefore, further discussions will be limited to the
York, New York, January 30-February 4, 1983. control of electrical stresses at and above the water
level.
Manuscript submitted August 30, 1982; made avail-
able for printing November 16, 1982.

0018-9510/83/0700-2364$01.00 1983 IEEE


2365
Cross Section of Cross Section of accelerated by the intense time changing electric
Glove Without Modified Glove field about the water meniscus causing them to
Modifications collide into gas molecules which can result in the
excitation or ionization of the gases. Reactive
A B compounds are formed as a result of the excitation
and ionization processes. Ozone, which results from
ionized oxygen, is one of these reactive compounds
which is detrimental to natural rubber gloves.
In addition, the intense time changing (60 Hz)
electric field is also present in the water at this
potential. The electric field perturbs the water
surrounding the glove cuff, causing ripples that
emanate outward on the water surface. As the voltage
is increased, it enhances the rippling activity in the
water.
At about 30 kV AC, the electric field reaches
such an intensity that it breaks up the water
meniscus around the cuff into a spray of water
droplets. Then at around 35 kV AC, streamers may be
observed tracking upward along the glove cuff,
emanating from the water droplets and glow discharge.
The audible sizzling hiss and crackle of corona
discharge activity and the strong smell of ozone can
be quite prevalent at this stage. Eventually, as the
voltage is raised the streamer activity will track to
the top of the interior and exterior of the cuff
causing a flashover.
B. Controlling Electrical Stresses at Water Meniscus
The high electrical stresses which exist in the
region around the water surface, air, and glove cuff
Figure 1 Reduction of Electrical Stresses can be reduced by altering the shape of the water
at and Above the Water Level meniscus. This was easily accomplished by
fabricating two unique water surface grading rings.
As shown in Figure lB these rings were specially
Figure IA provides an enlarged cross-sectional shaped to provide a gradual smooth curve to the water
view of the glove in its testing position. It can be surface around the areas where it comes in contact
seen that the surface of the water around the inside with the interior and exterior of the glove cuff.
and outside of the glove cuff and around the metal Therefore, the electric field intensity is reduced
rod electrode curves concavely upward into a around these areas and the resulting electrical
meniscus. This meniscus is due to the hydrophilic stress in the air, water and glove cuff is minimized.
and capillary action of the water at these surfaces.
The water meniscus resembles a sharp water lip or C. Comparison of AC Testing With and Without Grading
edge protruding above the surface of the water and Rings
clinging around the edges of the glove cuff and metal
rod electrode surfaces. This action of the water The grading rings were first used in 1974 at
around the rod electrode is beneficial because it APCo's Huntington, W. Virginia test facility during
smooths out the transition from one conductive medium AEP's effort to develop 40 kV AC glove testing
(the metal rod electrode) to another conductive procedures.
medium (the surface of the water). Thus, during To verify the effectiveness of the water grading
testing, the water meniscus about the rod electrode rings, photographs, shown in Figure 2, were taken of
will help to reduce the concentration of the electric two Class 4 gloves (one with and one without water
field thereby minimizing electrical stresses in the grading rings) at various voltage levels in a
air and water in this region. commercial glove tester. Photo 1 displays the two
However, the water meniscus which exists around gloves prior to testing, showing clearly the outside
the interior and exterior of the glove cuff is an water grading ring (interior ring not visible)
undesirable characteristic. It represents a sharp installed on the left glove, to be noted as gr-glove.
discontinuity in the electric field existing around a Both gloves were carefully positioned so that 10.2 cm
conductor and an insulator. During testing, the of the glove cuff was exposed above the water
water meniscus will tend to intensify the electric surface.
field in the air, water and glove cuff in this The same voltage was applied to both gloves till
region. As a result, these highly electrically at about 10 kV AC (rms) visual cororia appeared (Photo
stressed areas are prone to the effects of corona. 2) on the right glove with no rings. At 20 kV AC
The presence of corona can be noted during the visual corona was noted on the left gr-glove as shown
initial stages of testing a Class 4 glove. For in Photo 3. Corona and streamer activity rapidly
example, during the Roanoke tests, even at a increased on the glove without the rings as the
potential of 10 to 15 kV AC, the electrical stresses voltage was further raised. Then as seen in Photo 4,
were high enough in the air just above the water the right glove flashed over at 35 kV AC. The right
meniscus around the glove cuff to exceed the glove was deenergized and the test on the gr-glove
dielectric strength of air (30 kV/cm). The resulting continued. Photo 5 Shows the corona activity on the
breakdown in the air manifested itself in the form of gr-glove when 40 kV AC was reached. The corona
visible and audible corona. activity present during just the positive or negative
The presence of audible and visual corona is due half cycle at 45 kV AC is shown in Photos 6 and 7. In
to excitation and ionization of the gases that Photograph 6, the negative corona manifests itself
comprise air. Free electrons, present in air, are mainly in the form of negative streamers, whereas the
2366

positive corona shown in Photograph 7 appears as a


solid glow discharge. Lastly, Photo 8 captures a
flashover which occurred in the air over the top of
the cuff at 50 kV AC on the gr-glove. This indicates
a considerable improvement in the breakdown
capabilities over that of the glove without grading
rings.

3. DC TEST CONSIDERATIONS

A. Electrical Stresses
There is a difference in the electrical phenomena
Photo 1 Photo 2 during AC and DC testing of gloves. In AC testing,
there is an intense time changing electric field
Class 4 Gloves Before Visual Corona Starts at present in the water, air and glove in the area of the
Testing Left Glove Shown 10 kVAC on Right Glove. water meniscus which causes corona discharge.
With Water Grading Rings Both Gloves Have 10.2cm However, with a constant DC voltage (less than 2%
of Cuff Above Water
ripple), this intense electric field is static
(stationary).
The following explanation of DC phenomena is
given in the attempt to describe this method of
testing gloves. During DC testing, the stationary
electric field is of such intensity that ionized
particles are created about the water meniscus areas.
However, since the electric field is static, the
particles are suspended or held in place about the
water meniscus in the form of nonvisible space
charges. These space charges exist about the water
meniscus areas on the negative and positive energized
water inside and outside of the glove. These space
charges act as an extension of the water electrode at
Photo 3 Photo 4 the glove cuff, smoothing out the electric field about
the area.
20 kV AC Corona 35 kV AC Right Glove Further increase in voltage tends to enlarge the
Begins on Left Glove Flashes Over in Air size of the space charge causing it to develop farther
up the cuff. Eventually, at the flashover voltage, a
discharge will occur in the air over the glove cuff
as the space charges on either side of the glove cuff
reach the top and merge.
Consequently, during the course of DC testing of
gloves, there are no detectable visible or audible
electrical discharges or is there any appreciable
generation of ozone. Of course, during a flashover or
a glove puncture, a visual and audible discharge will
occur. It should be noted that a widely fluctuating
DC source can cause some corona generation. Most
commercial glove testers,however, do not have this
problem since they operate in accordance to the
Photo 5 Photo 6
Standard's recommended DC voltage of less than 2%
40 kV AC on Left Glove 45 kV AC Negative ripple.
Right Glove Deenergized Corona on Left Glove
4. ROANOKE TEST CONFIGURATION

Both AC and DC glove tests were conducted at the


APCo, Roanoke, Virginia, facility and were performed
in a specially constructed clear plastic container as
shown in Figure 3. During the tests, a variable 50 kV
AC or a 120 kV DC source was used to energize the
water by means of two electrodes: 1) a flat metal
plate electrode residing under the water outside of
the glove; and 2) a metal rod electrode situated down
in the water inside of the glove. It should be noted
that a certain portion of the glove cuff must remain
above the water during testing to provide a suitable
Photo 7 Photo 8 insulating distance between the two water electrodes.
Standards for Class 4 gloves require the cuff to water
45 kV AC Positive 50 kV AC Flashover line distance of 12.7 cm for AC and 15.3 cm for DC
Corona on Left Glove Occurs in Air on testing. In AC tests, steps were taken to avoid
Left Glove damage or puncture of the glove by utilizing a Class
4-Type II ozone resistant glove. This one glove
tester provided an excellent opportunity to observe
Figure 2 Photographs of Huntington Glove Tests corona and to try out various schemes for controlling
electrical stresses.
2367
Key: level. The corona and streamer activity was very
GS-Insulating Support Strap and Clip WL-Water Level intense while holding at 40 kV AC for 3 minutes.
CL-Length of Glove Above Water A -Air Corona activity produced several intermittent
El-Rod Electrode W -Water discharges while holding at this voltage. As the
E2-Plate Electrode G -Glove voltage was raised, corona activity increased until at
PC-Covered Clear Plastic Container 48 kV AC, streamers on either side of the glove cuff
met at the top causing a flashover.
The same test arrangement was used in Test No. 2
as in Test No. I (with 12.7 cm of cuff above the
water) except this time two nonconductive synthetic
rubber rings were used. One ring 1.4 cm in diameter
was installed around the inside and the other ring
1.9 cm in diameter was put around the outside of the
glove cuff at the water level to reduce electrical
stresses at the water edge to glove cuff surfaces.
The corona glow was first noted at 13.8 kV AC.
Streamers did not appear until the test level of 40
kV AC was reached. After holding at the test level
for 3 minutes, the voltage was raised until a
flashover occurred at 54.4 kV AC.
In Test No. 3, everything was kept the same as
in Test No. 2, except the length of cuff exposed
above the water was reduced from 12.7 to 6.4 cm. As
shown in Table I, the corona glow was noted at 15.6 kV
AC, and streamers appeared at 28.8 kV AC. A flashover
occurred at 34.4 kV AC. Consequently, the 6.4 cm of
cuff exposed above the water did not have sufficient
clearance for testing the class 4 gloves.
In Test No. 4, the only change from Test No. 3
was that the length of the cuff exposed above the
water was increased from 6.4 to 7.6 cm. Corona was
Figure 3 Roanoke Glove Testing Apparatus observed at 14.6 kV AC. As in Test No. 2, the
streamer activity was first noted at 40 kV AC and the
flashover occurred at 47 kV AC. Thus, by using the
grading rings and 7.6 cm of the cuff exposed above the
water, an additional 5.1 cm of the glove cuff could be
5. RESULTS OF ROANOKE AC TESTS tested.
Table I summarizes the results of the Roanoke, 6. RESULTS OF ROANOKE DC TESTS
Virginia tests performed on an 46 cm, EPDM, Class 4
synthetic glove. Four observations were made In the three DC tests summarized in Table I, the
which were critical to all the tests: 1) voltage following items were observed and noted: 1) the
when visual corona begins; 2) voltage when streamers presence of audible or visual corona; 2) the ability
occur; 3) reaching and maintaining the 40 kV AC for to maintain 70 kV DC for 3 minutes as per the
three minutes as per the standards; and 4) the Standards; and 3) the flashover voltage level.
voltage required to produce a flashover in the air For the DC Test No. 1, the exact same set-up was
above the water inside and outside of the glove. used as in Test No.4 of the AC testing, except the
high voltage source used was DC with the inside
electrode (-) and the outside electrode (+).
As the voltage was increased up to the test level
Table I Roanoke Results of 70 kV DC, there was no observable corona or
streamer activity causing the test to be quieter than
Key:R -Water grading rings CSL-Visual corona start the previous AC tests. After the test level was
SG-Synthetic glove OS -Onset of streamers maintained for 3 minutes, the voltage was increased
WV-Withstand voltage NRC-Natural rubber glove until a flashover occurred at 83 kV DC between the
CL-Cuff length in air FOL-Flashover in air inside rod electrode and a metal pin in one of the
glove support clips. At this point, the inside rod
Test AC Tests (kV AC) DC Tests (kV DC) electrode was taped with 1-1/2 turns of electrical
# 1 2 3 4 1 2 3 tape and the test was repeated. This time a flashover
SG SG(R) SG(R) SG(R) SG(R) NRG NRG occurred at 93 kV DC, an improvement of 10 kV DC over
CL 12.7cm 12.7cm 6.4cm 7.6cm 7.6cm 7.6cm 5.1cm the previous run.
CSL 10.8 13.8 15.6 14.6 In DC Test No. 2, a Type I natural rubber glove
OS 33.5 40.0 28.8 40.0 without grading rings was used in place of the Type II
WV 40.0 40.0 40.0 70.0 70.0 synthetic glove of Test No. 1, while still maintaining
FOL 48.0 54.4 34.4 47.0 93.0 90.0 63.0 the 7.6 cm of cuff exposed above the water. The
results were no different from DC Test No. 1. No
visible or audible corona was observed during the
In Test No. 1, a Class 4 glove was tested in test. At 70 kV DC, the voltage was held for 3 minutes
accordance to the 'Standard's procedure with 12.7 cm and a flashover occurred at 90 kV DC.
of the cuff exposed above the water and without such The same natural rubber Class 4 glove was used in
devices as grading rings to reduce the electrical DC Test No. 3. Here the cuff to water distance was
stress on the glove. reduced from 7.6 to 5.1 cm. At 63 kV, a flashover
The visual glow of corona was observed at 10i8 occurred in the air over the cuff. Consequently, the
kV AC. At 33.5 kV AC, thin violet-blue streamers required test level of 70 kV DC could not be achieved
appeared measuring about 4 cm long from the water using 5.1 cm of cuff exposed above the water.
2368
7. DISCUSSION the minimum breakdown level of Class 4 gloves could
be increased from the current 50 kV AC to at least 65
The results from Huntington and Roanoke AC tests to 70 kV AC. More work is needed to explore the AC
have demonstrated that by reducing the breakdown of gloves when corona suppression schemes
electrical stresses at the water surface, about the are employed. Likewise, more information is required
cuff of the glove, testing of gloves can be achieved to determine AC and DC electrical stresses that exist
without the corona and ozone damage experienced across gloves in the water electrodes.
before. Thus the argument relating to the adequacy
of AC vs. DC testing can be directed toward the 8. CONCLUSIONS
Standards. Comments expressed by a number of persons
associated with glove testing indicated that DC seems 1) The major electrical stresses that occur in AC
to be more sensitive than AC in identifying damage in glove testing is not below but above the surface
gloves. In one case, [7], 36 Class 1 gloves, of the water about the cuff.
previously condemned by inspection were tested to the 2) Tests have shown that electrical stresses about
AC breakdown level (20 kV AC). Only two of these the glove cuff are high enough to ionize the air
gloves failed where the defects were previously and cause corona effects. Visual corona activity
identified. The remainder of the other gloves either was first observed at about 10 kV AC and further
flashed over or failed through some spot where no increases in the voltage intensified this
defect was noticeable. Likewise a DC breakdown test activity.
(at 60 kV DC) on eleven Class gloves showed that 3) One prominent effect of corona is the generation
eight gloves failed at defects previously identified of ozone which is detrimental to natural rubber
during inspection. Is DC really more sensitive than gloves. The effect of ozone can be reduced with
AC in identifying glove defects? Perhaps not. The proper ventilation.
glove breakdown is related to the voltage or to the 4) One way to reduce corona activity is to minimize
electrical stress applied. At 20 kV AC, the gloves the electrical stresses at the water surface. The
were subjected to certain electrical stress in the introduction of grading rings proved to be
water electrodes. At 60 kV DC, it appears that the effective in minimizing corona.
electrical stress was much higher than at 20 kV AC, 5) Grading rings contour the water surface about the
resulting in the increased rate of glove failures. cuff controlling negative streamers so that the
The above examiple is of interest because it cuff to water line clearance could be reduced,
gives results from actual glove tests. More enabling an additional 18% of the glove to be
importantly it may exemplify the nature of stresses tested.
associated with the current AC and DC glove test 6) During DC testing of Class 4 gloves, there were no
standards. Table II shows the Standard [1] detectable audible or visual corona effects.
requirements for AC and DC proof test and minimum 7) Insulating the rod electrode exposed above the
breakdown voltage. water can increase the flashover level of a glove
by 10 kV DC.
Table II ACKNOWLEDGMENTS
Proof Test Voltage Minimum Breakdown The authors would like to express their
Class kV AC kV DC kV AC kV DC appreciation to A. Q. Croy, J. K. Reid, A. B. Purdy,
R. L. Jamison, and H. A. Mutter for their
1 10 40 20 60 contributions during the AC/DC testing of insulating
gloves conducted in APCo's Roanoke, Virginia facility.
2 20 50 30 70
REFERENCES
3 30 60 40 80
[1] ANSI/ASTM Standard D 120-79a, " Standard
4 40 70 50 90 Specification for Rubber Insulating Gloves."
[2] ANSI/ASTM Standard F 496-79a, " Standard
Specification for the In-Service Care of
For example, a Class 1 glove is AC proof tested at 10 Insulating Gloves and Sleeves."
kV, AC whereas in DC it is 40 kV DC. Why is there
such a difference in magnitude? Does the Standard [3] CSA Standard Z259.4 "Rubber Insulating Gloves
imply that the electrical stress in water at 10 kV AC and Mitts."
is equivalent to 40 kV DC? The minimum breakdown
voltage for a Class 1 glove is 20 kV AC and 60 kV DC. [4] J. M. Meek and J. D. Craggs, " Electrical
Once again,, one would expect that the electrical Breakdown of Gases," New York, John Wiley &
stress causing breakdown would be equivalent. Of Sons, Ltd., 1978.
course they should be equivalent; but are they?
In-AC testing, the dominant electrical stress is [5] S. Whitehead', "Dielectric Breakdown of Solids,"
on the water surface about the cuff of the glove. Oxford, Oxford University Press, 1953.
Therefore, in this area the corona and ozone
influences the breakdown level of the glove. [6] E. Nasser, "Fundamentals of Gaseous Ionization
Consequently, a good number of glove punctures during and Plasma Electronics," New York, John Wiley &
testing will occur at the area affected by corona and Sons, Inc., 1971.
ozone. It is expected that the minimum breakdown
level of gloves during AC testing can be increased [7] W. H. Meade and M. R. Gavin, "Testing Lineman's
(above 20 kV AC for Class 1) when means are utilized Rubber Protective Equipment," Record of the
to reduce the corona effects. This is perhaps most 75th Meeting of the Accident Prevention
evident in the Class 4 gloves where the corona Committee, Edison Electric Institute, Tampa,
effects are prominient. Judging from the results in Florida, April 23, 1963.
the Huntington tests, it appears that with proper
corona control (such as the use of grading rings),

Vous aimerez peut-être aussi