Functions and characteristics 7
Dimensions 33
Order forms 91
55
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS100/1600 or
Masterpact NW devices
Electrical interlocking by the IVE unit
Recommended electrical control system
L1 L2
11 12 13 14 15 16
84 84
N
SDE"N" SDE"R"
(2) (2) IVE
81 81
R
1 2 3 4 5 6 7 8 9 10
ON OR FN FR
CN 1 + CN 1 +
CN 2 CN 2
(1) : the normal and replacement source transfer orders must be interlocked electrically
(2) : operating diagram: the SDE fault-trip signals are transmitted to the IVE unit. The SDE
auxiliary contacts are mounted in the circuit breakers.
Legends Note:
ON "Normal source opening order Diagram shown with circuits de-energised, circuit breakers
OR "Replacement source opening order open and relays in normal position.
FN "Normal source closing order
FR Replacement source closing order
L1 Normal source fault-trip signal
L2 Replacement source fault-trip signal
N Normal source auxiliary wiring connector
R Replacement source auxiliary wiring connector
56
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS100/630 devices
Diagram no. 51201177
Source-changeover system without automatic-control system
Without auxiliaries for emergency off
Local reset
NORMAL
11 12 13 14 15 16
N
IVE
R
1 2 3 4 5 6 7 8 9 10
22 24 82 84 B2 A2 A4 B4
QN
OF2 Voluntary remote reset
MT
trip unit
SDE
11 12 13 14 15 16
N
IVE
R
21 81 A1 L1
1 2 3 4 5 6 7 8 9 10
RN RR
REPLACEMENT
22 24 82 84 B2 A2 A4 B4
Automatic reset
QR
OF2
(1)
MT N
trip unit
SDE IVE
(1)
R
1 2 3 4 5 6 7 8 9 10
21 81 A1 L1
57
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS100/630 devices
Diagram no. 51201178
Source-changeover system without automatic-control system
With emergency off by MN release and automatic reset
NORMAL
CN1 . CN1 +
D1
F1
D1 22 24 82 84 B2 A2 A4 B4
QN
OF2
MT
trip unit
SDE
MN
BP
D4 21 81 A1 L1
KA3
KA3
D4
REPLACEMENT
D1
D1 22 24 82 84 B2 A2 A4 B4 Automatic reset
QR
OF2
(1)
MT N
trip unit
SDE IVE
(1)
MN R
1 2 3 4 5 6 7 8 9 10
D4 21 81 A1 L1 KA3 KA3
D4
58
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS100/630 devices
Diagram no. 51201179
Source-changeover system without automatic-control system
With emergency off by MX release / automatic reset
NORMAL
CN3 . CN3 +
(2) CN4 . CN4
C1
F1
C1 22 24 82 84 B2 A2 A4 B4
opening
order
QN
OF2 KA1
MT KA1
trip unit
SDE
MX
CN5 . CN5 +
C2 21 81 A1 L1 (2) CN6 . CN6
C2 F2
opening
order
REPLACEMENT
KA2
KA2
C1
C1 22 24 82 84 B2 A2 A4 B4
Automatic reset
QR
OF2
(1)
MT N
trip unit
SDE IVE
(1)
MX R
1 2 3 4 5 6 7 8 9 10
KA1
C2 21 81 A1 L1
(3) KA2
C2
59
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS630b/1600 devices
Diagram no. 51201180
Electrical interlocking with lockout after a fault
Transfer to normal OR FN
source
(1)
312
314
(1)
B4
A4
A2
82
84
12
14
312
314
B4
A4
A2
82
84
12
14
CE1
CE1
OF1
QN
SDE1
OF1
QR
SDE1
Electrical
operation
Electrical
operation
A1
81
11
311
A1
81
11
311
(1)
(1)
60
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS630b/1600 devices
Diagram no. 51201181
Electrical interlocking with lockout after a fault and emergency off by shunt release
OR FN
Transfer to
normal source
KA3 KA3
(1)
C12
312
314
(1)
B4
A4
A2
82
84
12
14
C12
312
314
B4
A4
A2
82
84
12
14
CE1
CE1 BP
OF1
QN
SDE1
OF1
QR
Electrical SDE1
operation
MX Electrical
operation
MX
C11
A1
81
11
311
C11
A1
81
11
(1) 311
(1)
KA3
61
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS630b/1600 devices
Diagram no. 51201182
Electrical interlocking with lockout after a fault and emergency off by undervoltage
OR FN
Transfer to
normal source
KA3 KA3
(1)
(1)
312
314
D2
B4
A4
A2
82
84
12
14
312
314
D2
B4
A4
A2
82
84
12
14
CE1
CE1 BP
QN OF1
SDE1
OF1
QR
SDE1
Electrical
operation
MN Electrical
operation
MN
D1
A1
81
11
311
D1
A1
81
11
311
(1)
(1)
KA3
Legends
QN Normal source Compact NS630b to 1600
QR Replacement source Compact NS NS630b to 1600
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
CE1 connected-position indication contact (carriage switch)
F1 auxiliary power supply circuit breaker
MN undervoltage release
BP emergency off button with latching
KA3 auxiliary relay
ON Normal source opening order
OR Replacement source opening order
FN Normal source closing order (0.25 second delay)
FR "Replacement source closing order (0.25 second delay)
States permitted by mechanical interlocking system
Wiring colour codes Normal Replacement
0 0
RD red
GN green 1 0
BK black 0 1
VT violet
YE yellow Note:
GY grey Diagram shown with circuit breakers in connected position,
WH white open, charged, and ready to close.
BN brown Auxiliary power supply = supply voltage of auxiliary relays
(KA...) = supply voltage of electrical auxiliaries (electrical
operation, MCH, MX, MN...).
62
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS630b/1600 devices
Diagram no. 51201183
Electrical interlocking by IVE with lockout after a fault
CN1 . CN1 +
N R Auxiliary
power supply CN2 . CN2
F1
(2)
N
BN
BK
WH
GN
RD
VT
IVE
(2)
R
BN
BK
WH
GN
RD
VT
(1)
312
314
1 2 3 4 5 6 7 8 9 10
B4
A4
A2
12
14
ON OR FN FR
(1)
Transfer to
replacement source
312
314
B4
A4
A2
82
84
12
14
CE1
CE1
Transfer to normal
OF1 source
QN
SDE
QR OF1
Electrical
operation SDE
Electrical
operation
81
A1
11
311
(1)
GY
81
A1
11
311
YE
(1)
GY
YE
Legends
QN Normal source Compact NS630b to 1600
QR Replacement source Compact NS NS630b to 1600
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
CE1 connected-position indication contact (carriage switch)
F1 auxiliary power supply circuit breaker
IVE electrical interlocking and terminal block unit
ON Normal source opening order
OR Replacement source opening order
FN Normal source closing order (0.25 second delay)
FR Replacement source closing order (0.25 second delay)
63
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS630b/1600 devices
Electrical interlocking by IVE with lockout after a fault and emergency off by shunt release
CN1 . CN1 +
N R Auxiliary
power supply CN2 . CN2
KA3
F1
(2)
N
BN
BK
WH
GN
RD
VT
IVE
(2)
R
BN
BK
WH
GN
RD
VT
(1)
C12
1 2 3 4 5 6 7 8 9 10
312
314
B4
A4
A2
12
14
ON OR FN FR
(1)
Transfer to
replacement source
C12
312
314
B4
A4
A2
82
84
12
14
CE1
CE1
Transfer to normal
OF1 source
QN
SDE
OF1
QR
Electrical
operation SDE KA3
MX Electrical
operation
MX
C11
81
A1
11
311
BP
(1)
C11
81
A1
11
311
GY
YE
(1)
KA3
GY
YE
Lgende
QN Normal source Compact NS630b to 1600
QR Replacement source Compact NS NS630b to 1600
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
CE1 connected-position indication contact (carriage switch)
F1 auxiliary power supply circuit breaker
IVE electrical interlocking and terminal block unit
MX shunt release
BP emergency off button with latching
KA3 auxiliary relay
ON Normal source opening order
OR Replacement source opening order
FN Normal source closing order (0.25 second delay)
FR Replacement source closing order (0.25 second delay) States permitted by mechanical interlocking system
Normal Replacement
Wiring colour codes 0 0
RD red 1 0
GN green 0 1
BK black
Note:
VT violet
Diagram shown with circuit breakers in connected position,
YE yellow
open, charged, and ready to close.
GY grey
Auxiliary power supply = supply voltage of auxiliary relays
WH white
(KA...) = supply voltage of electrical auxiliaries (electrical
BN brown
operation, MCH, MX, MN...).
64
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS630b/1600 devices
Diagram no. 51201185
Electrical interlocking by IVE with lockout after a fault and emergency off by undervoltage release
E59543
CN1 . CN1 +
N R Auxiliary
Alimentation
Auxilliary
power CN2 . CN2
powersupply
auxiliaire
supply
KA3
F1
(2)
N
BN
BK
WH
GN
RD
VT
IVE
(2)
R
BN
BK
WH
GN
RD
VT
(1)
1 2 3 4 5 6 7 8 9 10
312
314
D2
B4
A4
A2
12
14
ON OR FN FR
(1)
Transfer
Transfer to
Transfert vers
to
replacement source
312
314
le Remplacement
replacement source
D2
B4
A4
A2
82
84
12
14
CE1
CE1
Transfertto
Transfer vers
normal
OF1 le Normal
source
normal source
QN
SDE
OF1
QR
Electrical
operation SDE KA3
MN Electrical
operation
MN
81
A1
D1
11
311
BP
(1)
A1
D1
81
11
311
GY
YE
(1)
KA3
GY
YE
Legends
QN Normal source Compact NS630b to 1600
QR Replacement source Compact NS NS630b to 1600
MCH spring-charging motor
MX standard opening release
XF standard closing release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
CE1 connected-position indication contact (carriage switch)
F1 auxiliary power supply circuit breaker
IVE electrical interlocking and terminal block unit
MN undervoltage release
BP emergency off button with latching
KA3 auxiliary relay
ON Normal source opening order States permitted by mechanical interlocking system
OR Replacement source opening order Normal Replacement
FN Normal source closing order (0.25 second delay) 0 0
FR Replacement source closing order (0.25 second delay) 1 0
0 1
Wiring colour codes
RD red
GN green Note:
BK black Diagram shown with circuit breakers in connected position,
VT violet open, charged, and ready to close.
YE yellow Auxiliary power supply = supply voltage of auxiliary relays
GY grey (KA...) = supply voltage of electrical auxiliaries (electrical
WH white operation, MCH, MX, MN...).
BN brown
65
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS630b/1600 devices
Diagram no. 51201186
Automatic-control system without IVE for permanent replacement source without lockout after a fault
F1
KA2
S1
F3
OFF Auto N R
KM2
KM1
KA1 KM2 KM1 KA1 KA2
F2
(1)
312
314
B4
A4
A2
82
84
12
14
(1)
312
314
B4
A4
A2
82
84
12
CE1 14
KA1
CE1
OF1
QN
SDE
OF1
QR
Electrical SDE
operation
Electrical
operation
A1
81
11
311
(1)
A1
81
11
311
66
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS630b/1600 devices
Diagram no. 51201187
Automatic-control system for replacement source generator set without lockout after a fault
N1 REPLACEMENT SOURCE
genset
G automatic-control genset startup order CN1 . CN1 +
system Auxiliary
power supply CN2 . CN2
genset genset
monitoring fault F1
KA3
genset genset
voltage voltage
monitoring fault
S1
OFF Auto N R
KM2 KM1
KM2 KM1 KA1 KA2
KA2
F3 (1)
312
314
C2
B4
A2
82
84
12
14
KA1 KA3
F2 (1)
CE1
312
314
B4
A4
A2
82
84
12
14
OF1 CE1
QN
SDE1
OF1
QR
Electrical
operation SDE1
KA1
Electrical
operation
A1
81
11
311
(1)
A1
81
11
311
KM1 KM2
(1)
Legends
QN Normal source Compact NS630b to 1600
QR Replacement source Compact NS NS630b to 1600
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
CE1 connected-position indication contact (carriage switch)
F1 auxiliary power supply circuit breaker
F2/F3 circuit breaker (high breaking capacity)
S1 control switches
KA1 auxiliary relays - UN presence detection
KA2 auxiliary relays - UR presence detection
KA3 auxiliary relays - generator set startup if UN absent
KM1 contactors with 0.25 second delay (for transfer to Replacement source)
KM2 contactors with 0.25 second delay (for transfer to Normal source)
States permitted by mechanical interlocking system
Wiring colour codes Normal Replacement
0 0
RD red
GN green 1 0
BK black 0 1
VT violet
YE yellow Note:
GY grey Diagram shown with circuit breakers in connected position,
WH white open, charged, and ready to close.
BN brown Auxiliary power supply = supply voltage of auxiliary relays
(KA...) = supply voltage of electrical auxiliaries (electrical
operation, MCH, MX, MN...).
67
Electrical diagrams Remote-operated
source-changeover systems
2 Masterpact NW devices
Diagram no. 51201139
Electrical interlocking with lockout after a fault
Transfer to OR FN
normal source
(1)
252
254
312
314
C2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
(1)
252
254
312
314
C2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
CE1
CE1
MCH
PF
CH
MX XF MCH
CH
MX XF
B1
C1
A1
251
81
11
21
31
41
311
(1)
B1
C1
A1
251
81
11
21
31
41
311
(1)
Legends
QN Normal source Masterpact NW
QR Replacement source Masterpact NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH springs charged indication contact
F1 auxiliary power supply circuit breaker
ON Normal source opening order
OR Replacement source opening order
FN Normal source closing order (0.25 second delay) States permitted by mechanical interlocking system
FR Replacement source closing order (0.25 second delay) Normal Replacement
0 0
1 0
0 1
Note:
Diagram shown with circuit breakers in connected position,
open, charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays
(KA...) = supply voltage of electrical auxiliaries (MCH, MX,
MN...).
68
Electrical diagrams Remote-operated
source-changeover systems
2 Masterpact NW devices
Diagram no. 51201140
Electrical interlocking with lockout after a fault and emergency off by shunt release
CN1 . CN1 +
Auxiliary
power supply CN2 . CN2
N R Transfer to
replacement source
F1
ON FR
Transfer to OR
KA3
normal source KA3
(1)
C12
252
254
312
314
C2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
(1)
C12
252
254
312
314
C2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
CE1
CE1 BP
MCH
PF
CH
MX XF MX2 MCH
CH
MX XF MX2
B1
C1
A1
251
C11
81
11
21
31
41
311
(1)
C11
B1
C1
A1
251
81
11
21
31
41
311
(1)
KA3
Legends
QN Normal source Masterpact NW
QR Replacement source Masterpact NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH springs charged indication contact
F1 auxiliary power supply circuit breaker
MX2 shunt release
BP emergency off button with latching
KA3 time delay for genset startup order to avoid starting the genset for transient UN disturbances States permitted by mechanical interlocking system
S1 control switches Normal Replacement
ON Normal source opening order 0 0
OR Replacement source opening order 1 0
FN Normal source closing order (0.25 second delay) 0 1
FR Replacement source closing order (0.25 second delay)
Note:
Diagram shown with circuit breakers in connected position,
open, charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays
(KA...) = supply voltage of electrical auxiliaries (MCH, MX,
MN...).
69
Electrical diagrams Remote-operated
source-changeover systems
2 Masterpact NW devices
Diagram no. 51201141
Electrical interlocking with lockout after a fault and emergency off by undervoltage release
CN1 . CN1 +
Auxiliary
power supply CN2 . CN2
N R Transfer to
replacement source F1
ON FR
OR
Transfer to KA3 KA3
normal source
(1)
254
252
312
314
C2
D2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
(1)
254
252
312
314
C2
D2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
CE1
CE1
BP
OF1 OF2 OF3 OF4
QN
SDE1
OF1 OF2 OF3 OF4
QR
PF
SDE1
MCH
PF
CH
MX XF MN MCH
CH
MX XF MN
B1
C1
A1
251
D1
81
11
21
31
41
311
(1)
B1
C1
A1
251
D1
81
11
21
31
41
311
(1)
Legends
QN Normal source Masterpact NW
QR Replacement source Masterpact NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
MN undervoltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH springs charged indication contact
F1 auxiliary power supply circuit breaker
BP emergency off button with latching
S1 control switches States permitted by mechanical interlocking system
KA3 auxiliary relay Normal Replacement
ON Normal source opening order 0 0
OR Replacement source opening order 1 0
FN Normal source closing order (0.25 second delay) 0 1
FR Replacement source closing order (0.25 second delay)
Note:
Diagram shown with circuit breakers in connected position,
open, charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays
(KA...) = supply voltage of electrical auxiliaries (MCH, MX,
MN...).
70
Electrical diagrams Remote-operated
source-changeover systems
2 Masterpact NW devices
Diagram no. 51201142
Electrical interlocking by IVE with lockout after a fault
CN1 . CN1 +
Auxiliary
power supply CN2 . CN2
N R
F1
(3)
N
VT
WH
GN
RD
BK
IVE
(3)
R
VT
WH
GN
RD
BK
(2)
252
254
312
314
1 2 3 4 5 6 7 8 9 10
C2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
ON OR FN FR
(2)
Transfer to
replacement source
252
254
312
314
C2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
CE1
CE1
Transfer to
OF1 OF2 OF3 OF4 normal source
QN
SDE1
MCH
PF
CH
MX XF MCH
CH
MX XF
B1
C1
A1
251
81
11
21
31
41
311
(1) (2)
B1
C1
A1
251
81
11
21
31
41
311
(1) (2)
GY
GY
BN
BN
YE
YE
(1) Not to be wired for the without lockout after a fault solution
(2) Not to be wired on fixed version
(3) Prefabricated wiring supplied
Legends
QN "Normal source Masterpact NW
QR Replacement source Masterpact NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH springs charged indication contact
IVE electrical interlocking and terminal block unit
F1 auxiliary power supply circuit breaker
ON Normal source opening order
OR Replacement source opening order States permitted by mechanical interlocking system
FN Normal source closing order (0.25 second delay) Normal Replacement
FR Replacement source closing order (0.25 second delay) 0 0
1 0
Wiring colour codes 0 1
RD red
GN green
BK black
VT violet Note:
YE yellow Diagram shown with circuit breakers in connected position,
GY grey open, charged, and ready to close.
WH white Auxiliary power supply = supply voltage of auxiliary relays
BN brown (KA...) = supply voltage of electrical auxiliaries (MCH, MX,
MN...).
71
Electrical diagrams Remote-operated
source-changeover systems
2 Masterpact NW devices
Diagram no. 51201143
Electrical interlocking by IVE with lockout after a fault and emergency off by shunt release
CN1 . CN1 +
Auxiliary
N R power supply CN2 . CN2
F1
KA3
(3)
N
WH
GN
RD
BK
VT
IVE
(3)
R
WH
GN
RD
BK
VT
(2)
C12
252
254
312
314
1 2 3 4 5 6 7 8 9 10
C2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
ON OR FN FR
(2) Transfer to
replacement source
C12
252
254
312
314
C2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
CE1
CE1
Transfer to
OF1 OF2 OF3 OF4 normal source
QN
SDE1
OF1 OF2 OF3 OF4
QR
PF
SDE1 KA3
MCH
PF
CH
MX XF MX2 MCH
BP
CH
MX XF MX2
B1
C1
A1
251
C11
81
11
21
31
41
311
(1) (2)
C11
B1
C1
A1
251
81
11
21
31
41
311
(1) (2)
GY
GY
BN
BN
YE
YE
KA3
(1) Not to be wired for the without lockout after a fault solution
(2) Not to be wired on fixed version
(3) Prefabricated wiring supplied
Legends
QN Normal source Masterpact NW
QR Replacement source Masterpact NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH springs charged indication contact
IVE electrical interlocking and terminal block unit
F1 auxiliary power supply circuit breaker
BP emergency off button with latching
KA3 auxiliary relay
ON Normal source opening order
OR Replacement source opening order States permitted by mechanical interlocking system
FN Normal source closing order (0.25 second delay) Normal Replacement
FR Replacement source closing order (0.25 second delay) 0 0
1 0
Wiring colour codes 0 1
RD red
GN green
BK black Note:
VT violet Diagram shown with circuit breakers in connected position,
YE yellow open, charged, and ready to close.
GY grey Auxiliary power supply = supply voltage of auxiliary relays
WH white (KA...) = supply voltage of electrical auxiliaries (MCH, MX,
BN brown MN...).
72
Electrical diagrams Remote-operated
source-changeover systems
2 Masterpact NW devices
Diagram no. 51201144
Electrical interlocking by IVE with lockout after a fault and emergency off by undervoltage release
CN1 . CN1 +
Auxiliary
N R power supply CN2 . CN2
F1
KA3
(3)
N
WH
GN
RD
BK
VT
IVE
(3)
R
WH
GN
RD
BK
VT
(2)
254
252
312
314
1 2 3 4 5 6 7 8 9 10
C2
D2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
ON OR FN FR
(2) Transfer to
replacement source
254
252
312
314
C2
D2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
CE1
CE1
Transfer to
OF1 OF2 OF3 OF4 normal source
QN
SDE1
OF1 OF2 OF3 OF4
QR
PF
SDE1 KA3
MCH
PF
CH
MX XF MN MCH
BP
CH
MX XF MN
B1
C1
A1
251
D1
81
11
21
31
41
311
(1) (2)
D1
B1
C1
A1
251
81
11
21
31
41
311
(1) (2)
GY
GY
BN
BN
YE
YE
KA3
(1) Not to be wired for the without lockout after a fault solution
(2) Not to be wired on fixed version
(3) Prefabricated wiring supplied
Legends
QN Normal source Masterpact NW
QR Replacement source Masterpact NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
MN undervoltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH springs charged indication contact
IVE electrical interlocking and terminal block unit
F1 auxiliary power supply circuit breaker
BP emergency off button with latching
S1 control switches
KA3 auxiliary relay States permitted by mechanical interlocking system
ON Normal source opening order Normal Replacement
OR Replacement source opening order 0 0
FN Normal source closing order (0.25 second delay) 1 0
FR Replacement source closing order (0.25 second delay)
0 1
Wiring colour codes
RD red
GN green Note:
BK black Diagram shown with circuit breakers in connected position,
VT violet open, charged, and ready to close.
YE yellow Auxiliary power supply = supply voltage of auxiliary relays
GY grey (KA...) = supply voltage of electrical auxiliaries (MCH, MX,
WH white MN...).
BN brown
73
Electrical diagrams Remote-operated
source-changeover systems
2 Masterpact NW devices
Diagram no. 51156226
Automatic-control system without IVE for permanent replacement source without lockout after a fault
N R
CN1 . CN1 +
Auxiliary
power supply CN2 . CN2
F1
S1
KA2
OFF Auto N R
F3
KM2 KM1
KM2 KM1 KA1 KA2
KA1
(1)
F2
252
254
312
314
C2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
252 (1)
254
312
314
C2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
CE1
CE1
MCH KA1
PF
CH
MX XF MCH
CH
MX XF
B1
C1
A1
251
81
11
21
31
41
311
(1)
B1
C1
A1
251
81
11
21
31
41
311
(1)
KM1 KM2
Legends
QN Normal source Masterpact NW
QR Replacement source Masterpact NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH springs charged indication contact
F1 auxiliary power supply circuit breaker
F2/F3 circuit breaker (high breaking capacity)
S1 control switches
KA1 auxiliary relays - UN presence detection States permitted by mechanical interlocking system
KA2 auxiliary relays - UR presence detection Normal Replacement
KA3 auxiliary relays - generator set startup if UN absent 0 0
KM1 contactors with 0.25 second delay (for transfer to Replacement source) 1 0
KM2 contactors with 0.25 second delay (for transfer to Normal source) 0 1
Note:
Diagram shown with circuit breakers in connected position,
open, charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays
(KA...) = supply voltage of electrical auxiliaries (MCH, MX,
MN...).
74
Electrical diagrams Remote-operated
source-changeover systems
2 Masterpact NW devices
Diagram no. 51156227
Automatic-control system for replacement source generator set without lockout after a fault
N1
REPLACEMENT SOURCE
genset genset
monitoring fault F1
KA3
genset genset
voltage voltage
monitoring fault
S1
OFF Auto N R
KM2 KM1
KM2 KM1 KA1 KA2
KA2
(1)
F3
252
254
312
314
C2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
(1)
KA1 KA3
252
254
312
314
C2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
F2
CE1
CE1
MCH KA1
PF
CH
MX XF MCH
CH
MX XF
B1
C1
A1
251
81
11
21
31
41
311
(1)
B1
C1
A1
251
81
11
21
31
41
311
(1)
KM1 KM2
Legends
QN Normal source Masterpact NW
QR Replacement source Masterpact NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH springs charged indication contact
F1 auxiliary power supply circuit breaker
F2/F3 circuit breaker (high breaking capacity)
S1 control switches
KA1 auxiliary relays - UN presence detection States permitted by mechanical interlocking system
KA2 auxiliary relays - UR presence detection Normal Replacement
KA3 auxiliary relays - generator set startup if UN absent 0 0
KM1 contactors with 0.25 second delay (for transfer to Replacement source) 1 0
KM2 contactors with 0.25 second delay (for transfer to Normal source) 0 1
Note:
Diagram shown with circuit breakers in connected position,
open, charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays
(KA...) = supply voltage of electrical auxiliaries (MCH, MX,
MN...).
75
Electrical diagrams Remote-operated
source-changeover systems
2 Masterpact NW devices
Diagram no. 51156904
Automatic-control system for permanent replacement source with lockout after a fault (with MN)
CN1 . CN1 +
N R Auxiliary
power supply CN2 . CN2
F1
KA1
S1
OFF R Auto N
KA1 KA1
KA3 KA2
11 12 13 14 15 16
(3)
N
WH
VT
BK
GN
RD
IVE
(3)
R
WH
VT
BK
GN
RD
(2)
254
252
312
314
D2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
1 2 3 4 5 6 7 8 9 10
(2)
254
252
312
314
D2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
CE1
CE1
MCH
PF
CH
MN XF MCH
CH
MN XF
B1
D1
A1
251
81
11
21
31
41
311
(1) (2)
B1
D1
A1
251
81
11
21
31
41
311
GY
BN
YE
(1) (2)
GY
BN
YE
(1) Not to be wired for the without lockout after a fault solution
(2) Not to be wired on fixed version
(3) Prefabricated wiring supplied
Legends
QN Normal source Masterpact NW
QR Replacement source Masterpact NW
MCH spring-charging motor
XF standard closing voltage release
MN undervoltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH springs charged indication contact
IVE electrical interlocking and terminal block unit
F1 auxiliary power supply circuit breaker States permitted by mechanical interlocking system
F2 circuit breaker (high breaking capacity) Normal Replacement
S1 control switches 0 0
KA1 auxiliary relays 1 0
KA2 auxiliary relays
0 1
KA3 auxiliary relays
Wiring colour codes
RD red Note:
GN green Diagram shown with circuit breakers in connected position,
BK black open, charged, and ready to close.
VT violet Auxiliary power supply = supply voltage of auxiliary relays
YE yellow (KA...) = supply voltage of electrical auxiliaries (MCH, MX,
GY grey MN...).
WH white
BN brown
76
Electrical diagrams Remote-operated
source-changeover systems
2 Masterpact NW devices
Diagram no. 51156905
Automatic-control system for replacement source generator set with lockout after a fault (with MN)
N
CN1 . CN1 +
Auxiliary
KA1 power supply CN2 . CN2
REPLACEMENT SOURCE
F1
genset
G automatic-control genset startup order
system
S1
KA3 KA2
11 12 13 14 15 16
(3)
N
WH
GN
RD
BK
VT
IVE
(3)
R
WH
GN
RD
BK
VT
(2)
254
252
312
314
D2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
1 2 3 4 5 6 7 8 9 10
(2)
254
252
312
314
D2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
CE1
KA2 KA3 KA2 KA3
CE1
MCH
PF
CH
MN XF MCH
CH
MN XF
B1
D1
A1
251
81
11
21
31
41
311
(1) (2)
B1
D1
A1
251
81
11
21
31
41
311
GY
BN
YE
(1) (2)
GY
BN
YE
(1) Not to be wired for the without lockout after a fault solution
(2) Not to be wired on fixed version
(3) Prefabricated wiring supplied
Legends
QN Normal source Masterpact NW
QR Replacement source Masterpact NW
MCH spring-charging motor
XF standard closing voltage release
MN undervoltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH springs charged indication contact
F1 auxiliary power supply circuit breaker States permitted by mechanical interlocking system
F2 circuit breaker (high breaking capacity) Normal Replacement
S1 control switches 0 0
KA1 auxiliary relay
KA2 time delay for genset startup order to avoid starting the genset for transient UN disturbances 1 0
KA3 auxiliary relay 0 1
Wiring colour codes
RD red Note:
GN green Diagram shown with circuit breakers in connected position,
BK black open, charged, and ready to close.
VT violet
Auxiliary power supply = supply voltage of auxiliary relays
YE yellow
(KA...) = supply voltage of electrical auxiliaries (MCH, MX,
GY grey
WH white MN...).
BN brown
77
Electrical diagrams Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156906
2 Normal sources and 1 Replacement source: electrical interlocking without lockout after a fault
N1 N2 R CN1 . CN1 +
Auxiliary
power supply CN2 . CN2
F1
t1
t2
252
254
312
314
322
324
C2
B3
B2
A2
12
14
22
24
32
34
42
44
252
254
312
314
322
324
C2
B3
B2
A2
12
14
22
24
32
34
42
44
CE1 CE2
252
254
312
314
322
324
C2
B3
B2
A2
12
14
22
24
32
34
42
44
CE1 CE2
CH
MX XF MCH
PF
CH
MX XF
MCH
C1
A1
251
21
B1
321
11
31
41
CH
311
MX XF
C1
A1
251
21
B1
321
11
31
41
311
C1
A1
251
21
B1
321
11
31
41
311
Legends
QN... Normal source Masterpact NW
QR Replacement source Masterpact NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
OF... breaker ON/OFF indication contact
PF ready-to-close contact
CE connected-position indication contact (carriage switch)
CH springs charged indication contact
F1 auxiliary power supply circuit breaker
t1 order for transfer from R to N1 + N2
(QN1 and QN2 closing time delay = 0.25 sec. minimum)
t2 order for transfer from N1 + N2to R
(QR closing time delay = 0.25 sec. minimum) States permitted by mechanical interlocking system
Normal 1 Normal 2 Replacement
0 0 0
1 1 0
0 0 1
1 0 0
0 1 0
Note:
Diagram shown with circuit breakers in connected position,
open, charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays
(KA...) = supply voltage of electrical auxiliaries (MCH, MX,
MN...).
78
Electrical diagrams Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156907
2 Normal sources and 1 Replacement source: electrical interlocking with lockout after a fault
N1 N2 R CN1 . CN1 +
Auxiliary
power supply CN2 . CN2
F1
t1
t2
KA1
KA1
KA1
KA2
252
254
312
314
C2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
KA2
KA2
252
254
312
314
C2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
CE1
252
254
312
314
C2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
CE1
CH
MX XF MCH
251
11
C1
81
21
B1
A1
311
31
41
CH
MX XF
251
C1
81
21
B1
A1
311
31
41
11
251
C1
81
21
B1
A1
311
31
41
11
Legends
QN... Normal source Masterpact NW
QR Replacement source Masterpact NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH springs charged indication contact
F1 auxiliary power supply circuit breaker
S1 control switches
S2 source selection switches
t1 order for transfer from R to N1 + N2 States permitted by mechanical interlocking system
(QN1 and QN2 closing time delay = 0.25 sec. minimum) Normal 1 Normal 2 Replacement
t2 order for transfer from N1 + N2to R 0 0 0
(QR closing time delay = 0.25 sec. minimumm) 1 1 0
0 0 1
1 0 0
0 1 0
Note:
Diagram shown with circuit breakers in connected position,
open, charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays
(KA...) = supply voltage of electrical auxiliaries (MCH, MX,
MN...).
79
Electrical diagrams Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156908
2 Normal sources and 1 Replacement source: automatic-control system for generator set without
lockout after a fault (with MN)
N1 N2
CN1 . CN1 +
REPLACEMENT SOURCE Auxiliary
power supply CN2 . CN2
genset
G automatic-control genset startup order
system
F1
genset genset
monitoring fault S1
OFF R Auto N
genset genset
voltage voltage
monitoring fault
F2
S2
F2
KA2
KA2 KA4 KA2 KA2 KA2 N1 N2
F2
KA1 KA1 KA4 KA4 N1+N2
KA3 KA3
F2 KA1
KA5 KA6
KA6
KA5
254
252
312
314
322
324
D2
B3
B2
A2
12
14
22
24
32
34
42
44
254
252
312
314
322
324
D2
B3
B2
A2
12
14
22
24
32
34
42
44
CE1 CE2
254
252
312
314
322
324
D2
B3
B2
A2
12
14
22
24
32
34
42
44
CE1 CE2
CH MN XF MCH
PF
CH MN XF MCH
321
D1
311
21
B1
A1
251
31
41
11
CH MN XF
251
321
D1
311
21
B1
A1
31
41
11
D1
311
21
B1
A1
321
251
31
41
11
Legends
QN... Normal source Masterpact NW
QR Replacement source Masterpact NW
MCH spring-charging motor
XF standard closing voltage release
MN undervoltage release
OF... breaker ON/OFF indication contact
PF ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH springs charged indication contact
F1 auxiliary power supply circuit breaker States permitted by mechanical interlocking system
F2/F3 circuit breaker (high breaking capacity) Normal 1 Normal 2 Replacement
S1 control switches 0 0 0
S2 source selection switches 1 1 0
KA1 auxiliary relay 0 0 1
KA2 auxiliary relays with 10 to 180 sec. time delay 1 0 0
KA3 auxiliary relays with 0.1 to 30 sec. time delay 0 1 0
KA4 auxiliary relay
KA5 auxiliary relays with 0.25 sec. time delay Note:
KA6 auxiliary relays with 0.25 sec. time delay Diagram shown with circuit breakers in connected position,
open, charge.
Auxiliary power supply = supply voltage of auxiliary relays
(KA...) = supply voltage of electrical auxiliaries (MCH, MX,
MN...).
80
Electrical diagrams Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156909
2 Normal sources and 1 Replacement source: automatic-control system for generator set with lockout
after a fault (with MN))
N1 N2
CN1 . CN1 +
REPLACEMENT SOURCE Auxiliary
power supply CN2 . CN2
genset
G automatic-control genset startup order
system
F1
genset genset
monitoring fault S1
F2
S2
F2
KA2 KA2
KA2 N1 N2
KA4 KA2 KA2
F2
KA1 KA1 N1+N2
KA3 KA4 KA4 KA3
KA1
F2
KA5 KA7
KA6
KA6
KA8
KA7 KA8
KA7 KA8 KA5
254
252
312
314
322
324
332
334
D2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
254
252
312
314
322
324
332
334
D2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
254
252
312
314
322
324
332
334
D2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
CE1 CE2 CE3
CH MN XF MCH
B1
D1
A1
251
81
11
21
31
41
311
321
331
CH MN XF
B1
D1
A1
251
81
11
21
31
41
311
321
331
B1
D1
A1
251
81
11
21
31
41
311
321
331
Legends
QN... Normal source Masterpact NW
QR Replacement source Masterpact NW
MCH spring-charging motor
XF standard closing voltage release
MN undervoltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH springs charged indication contact States permitted by mechanical interlocking system
F1 auxiliary power supply circuit breaker Normal 1 Normal 2 Replacement
F2/F3 circuit breaker (high breaking capacity) 0 0 0
S1 control switches 1 1 0
S2 source selection switches 0 0 1
KA1 auxiliary relay 1 0 0
KA2 auxiliary relays with 10 to 180 sec. time delay 0 1 0
KA3 auxiliary relays with 0.1 to 30 sec. time delay
KA4 auxiliary relay
Note:
KA5 auxiliary relays with 0.25 sec. time delay
Diagram shown with circuit breakers in connected position,
KA6 auxiliary relays with 0.25 sec. time delay
open, charge.
KA7 auxiliary relay
Auxiliary power supply = supply voltage of auxiliary relays
KA8 auxiliary relay
(KA...) = supply voltage of electrical auxiliaries (MCH, MX,
MN...).
81
Electrical diagrams Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156910
3 sources with only 1 device closed: electrical interlocking without lockout after a fault
SOURCE 1
SOURCE 2
SOURCE 3 Auxiliary CN1 . CN1 +
power supply CN2 . CN2
F1
t1
t2
t3
252
254
312
314
322
324
C2
B3
B2
A2
12
14
22
24
32
34
42
44
252
254
312
314
322
324
C2
B3
B2
A2
12
14
22
24
32
34
42
44
CE1 CE2
252
254
312
314
322
324
C2
B3
B2
A2
12
14
22
24
32
34
42
44
CE1 CE2
CH
MX XF MCH
PF
CH
MX XF MCH
251
321
C1
21
B1
A1
311
31
41
11
CH
MX XF
251
321
C1
B1
A1
21
311
31
41
11
251
321
C1
B1
A1
311
31
41
11
21
Legends
QS... Source Masterpact NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
OF... breaker ON/OFF indication contact
PF ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH springs charged indication contact
F1 auxiliary power supply circuit breaker
t1 order for transfer to Source 1
(QS1 closing time delay = 0.25 sec. minimum)
t2 order for transfer to Source 2
(QS2 closing time delay = 0.25 sec. minimum)
t3 order for transfer to Source 3 States permitted by mechanical interlocking system
(QS3 closing time delay = 0.25 sec. minimum) Source 1 Source 2 Source 3
0 0 0
1 0 0
0 1 0
0 0 1
Note:
Diagram shown with circuit breakers in connected position,
open, charge.
Auxiliary power supply = supply voltage of auxiliary relays
(KA...) = supply voltage of electrical auxiliaries (MCH, MX,
MN...).
82
Electrical diagrams Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156911
3 sources with only 1 device closed: electrical interlocking with lockout after a fault
SOURCE 1
SOURCE 2
SOURCE 3 Auxiliary CN1 . CN1 +
power supply CN2 . CN2
F1
t1
t2
t3
KA1
KA2
KA1 KA1
252
254
312
314
322
324
C2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
KA3
KA2 KA2
252
254
312
314
322
324
C2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
CE1 CE2
KA3 KA3
252
254
312
314
322
324
C2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
CE1 CE2
CH MX XF MCH
251
321
C1
81
21
B1
A1
311
31
41
11
CH MX XF
251
321
C1
81
21
B1
A1
311
31
41
11
251
321
C1
81
21
B1
A1
311
31
41
11
Legends
QS... Source Masterpact NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH springs charged indication contact
F1 auxiliary power supply circuit breaker
t1 order for transfer to Source 1
(QS1 closing time delay = 0.25 sec. minimum)
t2 order for transfer to Source 2
(QS2 closing time delay = 0.25 sec. minimum) States permitted by mechanical interlocking system
t3 order for transfer to Source 3 Source 1 Source 2 Source 3
(QS3 closing time delay = 0.25 sec. minimum) 0 0 0
KA1 auxiliary relays 1 0 0
KA2 auxiliary relays 0 1 0
KA3 auxiliary relays 0 0 1
Note:
Diagram shown with circuit breakers in connected position,
open, charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays
(KA...) = supply voltage of electrical auxiliaries (MCH, MX,
MN...).
83
Electrical diagrams Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156912
2 sources and 1 coupling: electrical interlocking without lockout after a fault
SOURCE 1 SOURCE 2
Auxiliary CN1 . CN1 +
power supply CN2 . CN2
F1
COUPLING
t1
t2
t3
t4
252
254
312
314
322
324
C2
B3
B2
A2
12
14
22
24
32
34
42
44
252
254
312
314
322
324
C2
B3
B2
A2
12
14
22
24
32
34
42
44
CE1 CE2
252
254
312
314
322
324
C2
B3
B2
A2
12
14
22
24
32
34
42
44
CE1 CE2
CH MX XF MCH
PF
CH MX XF MCH
251
321
C1
21
B1
A1
311
31
41
11
CH MX XF
251
321
C1
21
B1
A1
311
31
41
11
251
321
C1
21
B1
A1
311
31
41
11
Legends
QS... Source Masterpact NW
QC Coupling Masterpact NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
OF... breaker ON/OFF indication contact
PF ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH springs charged indication contact
F1 auxiliary power supply circuit breaker
t1 coupling order for Source 1 failure
(QC closing time delay = 0.25 sec. minimum) States permitted by mechanical interlocking system
t2 coupling order for Source 2 failure Source 1 Source 2 Coupling
(QC closing time delay = 0.25 sec. minimum) 0 0 0
t3 coupling order for Source 1 restored 1 1 0
(QS1 closing time delay = 0.25 sec. minimum)
1 0 1
t4 coupling order for Source 2 restored
(QS2 closing time delay = 0.25 sec. minimum) 0 1 1
1 0 0
0 1 0
0 0 1
Note:
Diagram shown with circuit breakers in connected position,
open, charge.
Auxiliary power supply = supply voltage of auxiliary relays
(KA...) = supply voltage of electrical auxiliaries (MCH, MX,
MN...).
84
Electrical diagrams Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156913
2 sources and 1 coupling: electrical interlocking with lockout after a fault
SOURCE 1 SOURCE 2
Auxiliary CN1 . CN1 +
power supply CN2 . CN2
F1
COUPLING
t1
t2
t3
t4
KA1
KA2
KA1 KA1
252
254
312
314
322
324
C2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
KA3
KA2 KA2
252
254
312
314
322
324
C2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
CE1 CE2
KA3 KA3
252
254
312
314
322
324
C2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
CE1 CE2
CH MX XF MCH
251
C1
321
81
21
B1
A1
311
31
41
11
CH MX XF
251
C1
321
81
21
B1
A1
311
31
41
11
251
C1
321
81
21
B1
A1
311
31
41
11
Legends
QS... Source Masterpact NW
QC Coupling Masterpact NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH springs charged indication contact
F1 auxiliary power supply circuit breaker
t1 coupling order for Source 1 failure States permitted by mechanical interlocking system
(QC closing time delay = 0.25 sec. minimum) Source 1 Source 2 Coupling
t2 coupling order for Source 2 failure 0 0 0
(QC closing time delay = 0.25 sec. minimum) 1 1 0
t3 coupling order for Source 1 restored
1 0 1
(QS1 closing time delay = 0.25 sec. minimum)
t4 coupling order for Source 2 restored 0 1 1
(QS2 closing time delay = 0.25 sec. minimum) 1 0 0
KA1 auxiliary relays 0 1 0
KA2 auxiliary relays 0 0 1
KA3 auxiliary relays
Note:
Diagram shown with circuit breakers in connected position,
open, charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays
(KA...) = supply voltage of electrical auxiliaries (MCH, MX,
MN...).
85
Electrical diagrams Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156914
2 sources and 1 coupling: automatic-control system with lockout after a fault
SOURCE 1 SOURCE 2
S1
forced
KA1
OFF
auto
KA2 KA1
F3 KA2
KA3
KA3 S2
KA4
KA4
S1 + S2
S1 + C
S2 + C
F2
KA5 KA6
KA7
KA5
KA5
KA6
KA6
COUPLING
KA7 KA7
F2
252
254
312
314
322
324
C2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
F2
252
254
312
314
322
324
C2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
CE1 CE2
252
254
312
314
322
324
C2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
CE1 CE2
CH MX XF MCH
B1
C1
A1
251
81
11
21
31
41
311
321
CH MX XF
B1
C1
A1
251
81
11
21
31
41
311
321
B1
C1
A1
251
81
11
21
31
41
311
321
Legends
QS... Source Masterpact NW
QC Coupling Masterpact NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault trip indication contact
PF ready-to-close contact
CE... connected-position indication contact (carriage switch) States permitted by mechanical interlocking system
CH springs charged indication contact Source 1 Source 2 Coupling
F1 auxiliary power supply circuit breaker 0 0 0
F2/F3 circuit breaker (high breaking capacity) 1 1 0
S1 control switches 1 0 1
S2 source selection switches 0 1 1
KA1 auxiliary relays with 10 to 180 sec. time delay 1 0 0
KA2 auxiliary relays with 0.1 to 30 sec. time delay
0 1 0
KA3 auxiliary relays with 10 to 180 sec. time delay
KA4 auxiliary relays with 0.1 to 30 sec. time delay 0 0 1
KA5 auxiliary relays with 0.25 sec. time delay
KA6 auxiliary relays with 0.25 sec. time delay Note:
KA7 auxiliary relays with 0.25 sec. time delay Diagram shown with circuit breakers in connected position,
open, charge.
Auxiliary power supply = supply voltage of auxiliary relays
(KA...) = supply voltage of electrical auxiliaries (MCH, MX,
MN...).
86
Electrical diagrams Source-changeover systems
with automatic controllers
2 Compact NS100/1600 or
Masterpact NW devices
Source-changeover system with BA controller
Coupling
selector
N R N
R
auto stop
23 22
14 13 16 15 11 12 10 9 5 7 6 8
1 3 5 1 3 5
Q1 Q2
2 4 6 2 4 6 Transfer conditions
ACP 2 N O L 17 18 20 21 R E 25
24 N O L 9 10 R E 25
N R if contact closed
24 N O L R E 25
Terminals 20 and 21:
stop
additional control contact
N (not part of controller).
23 22
R auto
17 18 20
BA
21
11 12 13 14 15 16 10 9 8 7 6 5
11 12 13 14 15 16
N
IVE
R
1 2 3 4 5 6 7 8 9 10
remove jumpers
for NS630b/1600 and
Masterpact NT/NW
87
Electrical diagrams Source-changeover systems
with automatic controllers
2 Compact NS100/1600 or
Masterpact NW devices
Source-changeover system with UA controller
Load shedding and genset management
14 13 16 15 11 12 10 9 5 7 6 8
1 3 5 1 3 5
Q1 Q2
Contacts shown with normal supply healthy; normal
2 4 6 2 4 6
breaker in ON position.
ACP
Transfer conditions
24 N O L 9 10 R E 25
24 N O L 17 18 20 21 R E 25
A
B
C
01
/ voltage
N
voir tableau contrle de A=0 1 phase control if contact closed
N R
la tension "Normal" UN A=1 3 phases control
EJP / voluntary
B=0 N=off fault voluntary transfer
B=1 N=on generator
24 N O L R E 25 C=0 t6=20s t max
stop C=1 t6=180s start generator
N
23 22
R auto
Terminals 20 and 21:
additional control contact
(not part of controller).
UA
17 18 20
11 12 13 14 15 16 10 9 8 7 6 5
A=0
1L1 3L2 5L3 1L1 3L2 5L3 1L1 3L2 5L3
11 12 13 14 15 16
Q1 Q1 Q1
N
IVE
R
A=1 1L1 3L2 5L3 1L1 3L2 5L3
1 2 3 4 5 6 7 8 9 10
Q1 Q1
enlever
pour NS630b/1600 et Replacement source voltage UR test
Masterpact NW
The single-phase check for UR is
implemented across terminals 1 and 5 of
circuit breaker Q2.
Legends Note:
Q1 : circuit breaker supplying and protecting the automatic-control circuits for the Normal Diagram shown with circuits de-energised, circuit breakers
source open and relays in normal position.
Q2: circuit breaker supplying and protecting the automatic-control circuits for the
Replacement source
ACP: auxiliaries control plate
UA: automatic controller
IVE: electrical interlocking and terminal block unit
88
Electrical diagrams Source-changeover systems
with automatic controllers
2 Compact NS100/1600 or
Masterpact NW devices
Controller settings Using communication functions
boucle COM
COM loop
24 N O L 17 18 20 21 R E 25 2
4 6
8
A
1
10
24 N O L 17 18 20 21 R E 25 2
4 6
8
12 1
B 14
5 A 10
C + 0v 24v 3 7
B 14
5
12
01 1 9 C + 0v 24v 3 7
24v 0v + 15
13
11 01 1 9
N / voltage 24v 0v + 15
13
11
N/ voltage
A=0 1 phase control N R
BBus
A=1 3 phase control if contact closed A=0 1 phase control N R
BBus
A=1 3 phase control if contact closed
EJP / voluntary transfer
EJP / voluntary transfer
B=0 N=off fault voluntary transfer
B=1 N=on generator B=0 N=off fault voluntary transfert
B=1 N=on generator
C=0 t6=20s t max
C=1 t6=180s start generator C=0 t6=20s t max
C=1 t6=180s start generator
89
Electrical diagram Source-changeover systems
with automatic controllers
2 Masterpact NW devices
Diagram no. 51156903
Electrical interlocking with lockout after a fault
source management
N 1IA038
(3)
N R N
BA/UA controller
WH
VT
BK
GN
RD
for 2 devices
(3) N 1IA036
R
RD
WH
VT
BK
GN
(2)
252
254
312
314
C2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
(2)
252
254
312
314
C2
B3
B2
A2
82
84
12
14
22
24
32
34
42
44
CE1
CE1
SDE1
QR OF1 OF2 OF3 OF4
PF
SDE1
MCH
PF
CH
MX XF MCH
CH
MX XF
B1
C1
A1
251
81
11
21
31
41
311
(1) (2)
B1
C1
A1
251
81
11
21
31
41
311
GY
BN
YE
(1) (2)
GY
BN
YE
(1) Not to be wired for the without lockout after a fault solution
(2) Not to be wired on fixed version
(3) Prefabricated wiring supplied
Legends
QN Normal source Masterpact NW
QR Replacement source Masterpact NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH springs charged indication contact
IVE electrical interlocking and terminal block unit
90