Part 1. Load Estimating | Chapter 3.

Heat Storage, Diversity And Stratification

TABLE 10-STORAGE LOAD FACTORS, SOLAR HEAT GAIN THRU GLASS


WITH BARE GLASS OR WITH EXTERNAL SHADE
16 Hour Operation, Constant Space Temperature
WEIGHT SUN TIME
EXPOSURE (lb per sq AM PM EXPOSURE
(North Lat) ft of floor area) 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 (South Lat)
150 & over .28 .37 .42 .41 .38 .36 .33 .31 .23 .22 .20 .19 .17 .15 .14 .12
Northeast 100 .28 .39 .45 .45 .41 .39 .31 .27 .22 .21 .19 .17 .16 .14 .12 .10 Southeast
30 .33 .57 .66 .62 .46 .33 .26 .21 .18 .16 .14 .12 .09 .06 .04 .03
150 & over .29 .38 .44 .48 .48 .46 .41 .36 .28 .26 .23 .22 .20 .18 .16 .14
East 100 .27 .38 .48 .54 .52 .48 .41 .35 .28 .25 .23 .20 .18 .15 .14 .12 East
30 .29 .51 .68 .74 .69 .53 .38 .27 .22 .18 .15 .12 .09 .06 .04 .03
150 & over .24 .29 .35 .43 .49 .53 .53 .51 .39 .35 .32 .29 .26 .23 .21 .19
Southeast 100 .19 .24 .33 .44 .52 .57 .57 .53 .41 .36 .31 .27 .24 .21 .18 .16 Northeast
30 .03 .20 .41 .60 .73 .77 .72 .60 .44 .32 .23 .18 .14 .09 .07 .05
150 & over .33 .31 .32 .37 .43 .49 .55 .60 .57 .51 .48 .42 .37 .33 .29 .26
South 100 .27 .24 .28 .34 .42 .50 .58 .60 .60 .57 .53 .45 .37 .31 .27 .23 North
30 .06 .04 .15 .31 .49 .65 .75 .82 .81 .75 .61 .42 .28 .19 .13 .09
150 & over .35 .32 .30 .28 .26 .28 .30 .37 .43 .47 .46 .40 .34 .30 .27 .24
Southwest 100 .31 .28 .25 .24 .22 .26 .33 .40 .46 .50 .53 .51 .44 .35 .29 .26 Northwest
30 .11 .10 .10 .09 .10 .14 .35 .54 .68 .78 .78 .68 .46 .29 .20 .14
150 & over .38 .34 .32 .28 .26 .25 .23 .25 .26 .27 .36 .42 .44 .38 .33 .29
West 100 .34 .31 .28 .25 .23 .22 .21 .21 .23 .30 .40 .48 .51 .43 .35 .30 West
30 .17 .14 .13 .11 .11 .10 .10 .15 .29 .49 .67 .76 .75 .53 .33 .22
150 & over .33 .30 .28 .26 .24 .23 .22 .20 .18 .17 .25 .34 .39 .34 .29 .26
Northwest 100 .30 .28 .25 .23 .22 .20 .19 .17 .17 .19 .29 .40 .46 .40 .32 .26 Southwest
30 .18 .14 .12 .12 .12 .12 .12 .11 .13 .27 .48 .65 .73 .49 .31 .21
North 150 & over .31 .57 .64 .68 .72 .73 .73 .74 .74 .75 .76 .78 .78 .59 .52 .46 South
and 100 .30 .47 .60 .67 .72 .74 .77 .78 .79 .80 .81 .82 .83 .60 .51 .44 and
Shade 30 .04 .07 .53 .70 .78 .84 .88 .91 .93 .95 .97 .98 .99 .62 .34 .24 Shade
Equation: Cooling Load, Btu/hr = [Peak solar heat gain, Btu/(hr) (sq ft), (Table 6)]
[Window area, sq ft]
[Shade factor, Haze factor, etc., (Chapter 4)]
[Storage factor, (above Table at desired time)]

Bare glass-Any window with no inside shading device. Windows with shading devices on the outside or shaded by external projections are
considered bare glass.
These factors apply when maintaining a CONSTANT TEMPERATURE in the space during the operating period. Where the temperature is
allowed to swing, additional storage will result during peak load periods. Refer to Table 13 for applicable storage factors.
Weight per sq ft of floor- (Weight of Outside Walls, lb) + (Weight of Partitions, Floor and Ceiling, lb)
Room on Bldg Exterior (One or more outside walls) =
Floor Area in Room, sq ft
(Weight of Partitions, Floor and Ceiling, lb)
Room in Bldg Interior (No outside walls) =
Floor Area in Room, sq ft
(Weight of Outside Walls, lb) + (Weight of Floor, lb) + (Weight of Partitions and Ceiling, lb)
Basement Room (Floor on ground) =
Floor Area in Room, sq ft
(Weight of Outside Wall, Partitons, Floors, Ceilings, Structural Members and Supports,lb)
Entire Building or Zone =
Air Conditioned Floor Area, sq ft

With rug on floor-Weight of floor should be multiplied by 0.50 to compensate for insulating effect of rug.
Weights per sq ft of common types of construction are contained in Tables 21 thru 33, pages 66 thru 76.