Vous êtes sur la page 1sur 53

8DA10 and 8DB10

Single and Double Busbar


Flexible and powerful
Infrastructure & Cities

Welcome!

Siemens AG 2008

Page 2 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
Main Applications for Medium-Voltage Switchgear

Power generation
Power stations
G

Power transmission
High and extra-high voltage > 72 kV
Primary distribution level 8DAB10 NXPLUS NXPLUS C
Medium voltage up to 40.5 kV x x
up to 40 kA (3s)
x x x x x x x

Secondary distribution level 8DJ10/20 8DH10 SIMOSEC


Medium voltage up to 24 kV x
up to 25 kA (1s)

Distribution level
Low voltage < 1 kV
Siemens AG 2008

Page 3 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA/B10
Content

Technical features and general information


Technical Data
Typical Overview, fixtures and fittings
Panel Desgin
Circuit-breaker Panel
Busbar
Operation
Metering
Low-Voltage Compartment
Cable Connection
Feeder Earthing, Cable Testing
Interlocks
Classification according to IEC 62 271-200
Customers Benefit
Siemens AG 2008

Page 4 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA/B10
Technical Features

Up to 40.5 kV, 40 kA (3s),


5000 A busbar, 2500 A feeder
Metal-enclosed
Single-busbar system ( 8DA10 )
Double-busbar-system ( 8DB10 )
Gas-insulated
Hermetically single-pole enclosed
Factory-assembled, type-tested switchgear
according to IEC 62 271-200

Siemens AG 2008

Page 5 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA/B10
General Information

Market introduction in March 1982


Worldwide successful operation
The gas-insulated circuit-breaker switchgear for application in nearly all
branches like Airports & Ports Automotive Buildings
Cement Industries Chemicals & Pharma Mining
Oil & Gas Paper Industries Steel & Aluminium
Utilities Transportation & Railways
More than 63,900 panels 8DA/B (September 2011) delivered
Our experiences are based on more than 130,000 delivered panels for gas-insulated
circuit-breaker switchgear (primary distribution level)

Siemens AG 2008

Page 6 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA10
Technical Data

Rated voltage kV 12 24 36 40,5

Rated frequency Hz 50/60 50/60 50/60 50/60


Rated short-duration power-frequency withstand voltage kV 20 50 70 85
Rated lightning impulse withstand voltage kV 75 125 170 185
Rated peak withstand current kA 100 100 100 100
Rated short-circuit making current kA 100 100 100 100
Rated short-time withstand current, 3 s kA 40 40 40 40
Rated short-circuit breaking current kA 40 40 40 40
Rated normal current of busbar A 5000 5000 5000 5000
Rated normal current of feeder A 2500 2500 2500 2500
Degree of protection Primary part IP65 IP65 IP65 IP65
Secondary part IP3XD IP3XD IP3XD IP3XD
Dimensions
Width mm 600 600 600 600
Depth mm 1625 1625 1625 1625
Height ( Standard ) mm 2350 2350 2350 2350

Siemens AG 2008

Page 7 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DB10
Technical Data

Rated voltage kV 12 24 36 40,5

Rated frequency Hz 50/60 50/60 50/60 50/60


Rated short-duration power-frequency withstand voltage kV 20 50 70 85
Rated lightning impulse withstand voltage kV 75 125 170 185
Rated peak withstand current kA 100 100 100 100
Rated short-circuit making current kA 100 100 100 100
Rated short-time withstand current, 3 s kA 40 40 40 40
Rated short-circuit breaking current kA 40 40 40 40
Rated normal current of busbar A 5000 5000 5000 5000
Rated normal current of feeder A 2500 2500 2500 2500
Degree of protection Primary part IP65 IP65 IP65 IP65
Secondary part IP3XD IP3XD IP3XD IP3XD
Dimensions
Width mm 600 600 600 600

Depth mm 2665 2665 2665 2665


Height ( Standard ) mm 2350 2350 2350 2350

Siemens AG 2008

Page 8 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA11/8DA12 ( Traction Power Supply )
Technical Data

Rated voltage kV 15 25
Rated operation voltage kV 17,5 27,5
Rated frequency Hz 16,7 50/60

Rated short-duration power-frequency withstand voltage Earth kV 50 95


Isolation kV 60 110

Rated lightning impulse withstand voltage Earth kV 125 200


Isolation kV 145 220

Rated short-circuit making current kA 80 80


Rated short-circuit breaking current kA 31,5 31,5
Rated normal current of busbar A 2500 2500
Rated normal current of feeder A 2000 2000
Degree of protection Primary part IP65 IP65
Secondary part IP3XD IP3XD

Dimensions
Width mm 600 600
Depth ( 1-pole, 2-pole ) mm 865/1245 865/1245
Height ( Standard ) mm 2350 2350

Siemens AG 2008

Page 9 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA10
Typical Overview

Circuit-breaker Panel Disconnector Panel Bus Sectionalizer

Siemens AG 2008

Page 10 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA10
Fixtures and Fittings Circuit-breaker Panel

Siemens AG 2008

Page 11 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA10
Fixtures and Fittings Disconnector Panel

Siemens AG 2008

Page 12 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA10
Fixtures and Fittings Bus Sectionalizer

Siemens AG 2008

Page 13 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA10 Fixtures and Fittings
Bus Sectionalizer without additonal required space

Siemens AG 2008

Page 14 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
Circuit-Breaker Panel 8DA10
Single-Busbar System

Low-voltage compartment
Installation of secondary
devices
Busbar housing
Operating mechanism for Light-metal vessel
three-position switch
Disconnector and earthing
switch
Circuit-breaker
Operating mechanism housing
for circuit-breaker Light-metal vessel
Vacuum switching
technology
Cable connection
Inside-cone system

Siemens AG 2008

Page 15 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
Circuit-Breaker Panel 8DB10
Double-Busbar System

Low-voltage compartment
Installation of secondary Busbar housing
devices Light-metal vessel

Operating mechanism for Three-position


three-position switch switch housing
Disconnector and earthing Light-metal vessel
switch
Operating mechanism
Circuit-breaker
for circuit-breaker
housing
Vacuum switching
Light-metal vessel
technology

Cable connection
Inside-cone system

Siemens AG 2008

Page 16 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
Circuit-Breaker Panel 8DA11/12
1-Pole and 2-Pole Traction Systems

Low-voltage compartment
Installation of secondary
devices
Busbar housing
Operating mechanism for Light-metal vessel
three-position switch
Disconnector and earthing
switch
Circuit-breaker
housing
Operating mechanism Light-metal vessel
for circuit-breaker
Vacuum switching
technology Cable connection
Inside-cone system

Siemens AG 2008

Page 17 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA/B10
Busbar current up to 5000A

Busbar 5000 A
Example 8DA10

Twin busbar housing

Busbar up to 4000 A Busbar

Busbar housing
Busbar
Three-position switch

Pole housing

Siemens AG 2008

Page 18 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA10
Operation of Three-position Switch

Switch position indicator


Disconnector switch
Operating shaft
Earthing switch
Operating shaft
Disconnector switch Switch position indicator
Earthing switch
Switch position indicator
Circuit-breaker switch
Preselection key

Siemens AG 2008

Page 19 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA10
Operation

Switch position indicator


Disconnector switch
Switch position indicator
Operating shaft
Circuit-breaker switch
Disconnector switch /
Earthing switch
Raedy-for-service indicator
Filling valve Preselection key

Switch position indicator


Earthing switch
Opening for charging the ON pushbutton
circuit-breaker spring by hand Circiut-breaker switch

Spring charged indicator OFF pushbutton


Circiut-breaker switch

De-earthing interlock
Counter
Siemens AG 2008

Page 20 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA/B10
Current Measurement

Ring-core current transformers


Main circuit as primary part
without dielectric and thermal
problems
Secondary part accessible Current transformer
Fitted at busbar
outside the enclosure without
danger
Current transformer
Free of dielectrically stressed Fitted at pole
cast-resin parts housing

Current transformer
Fitted at cable
housing

Current transformer
Fitted at cable

Siemens AG 2008

Page 21 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA/B10
Voltage Measurement

Voltage transformer Voltage


Transformer
Single-pole insulated
Fitted at busbar
Metal-enclosed
Type 4MT3
Plug-in type Type 4MU4
At the busbar:
Surge-proof for 80 % UP
repeat test with connected
transformer

Voltage
Transformer
Fitted at cabel
housing
Type 4MT7
Type 4MU3
Siemens AG 2008

Page 22 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA/B10
Low-Voltage Compartment

Height: 850 mm
1200 mm (option)
Removable, bus wires and control
cables plugged in (via 6 or 10-pole
coded module plug connectors)
Panel control via conventional control
devices or digital bay controller
Customer-specific equipment
(protection, control, metering,
annunciation)
Wiring in H07VK, optionally also heat-
resistant and halogen-free

Siemens AG 2008

Page 23 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA/B10
Panel Connection Inside Cone according to IEC 50 181

Maintenance-free due to inside


cone plug-in system
For connection type sizes
2, 3 und 4 (depending on cable
cross section)
1 to 6 cables possible per phase
Cable connection with different
connection types / sizes realisable
Plug-in voltage transformer and
surge arrester realisable

Single cable connection Multiple cable connection

Siemens AG 2008

Page 24 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA/B10
Fully Insulated Bar Connections

Fully insulated bar Gas-insulated bar


for rated normal current up to 2500 A for rated normal current up to 2500 A

Siemens AG 2008

Page 25 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA/B10
Cable Earthing with the Circuit-Breaker

1) Close three-position switch / Earthed position


Earthing prepared
Electrical OFF-signals are suppressed
1) 2) Close circuit-breaker switch / ON position
Outgoing / Feeder earthed
3) Secure switch position Outgoing/Feeder earthed
with padlock
Circuit-breaker is blocked mechanically
2) 3)
Signal: Outgoing / Feeder earthed (option)

Siemens AG 2008

Page 26 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA/B10
Cable testing

Cable test with DC voltage or


AC voltage 0.1 Hz
Three-position switch and circuit-
breaker in OFF position
Cable fault location with lightning
impulse voltage
Full operating voltage at the busbar

Siemens AG 2008

Page 27 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DB10
Typical Overview

Circuit-breaker Panel Bus Coupler Bus Sectionalizer

Siemens AG 2008

Page 28 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DB10
Fixtures and Fittings Circuit-breaker Panel

Siemens AG 2008

Page 29 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DB10
Fixtures and Fittings Bus Coupler

Siemens AG 2008

Page 30 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DB10
Fixtures and Fittings Bus Sectionalizer

Siemens AG 2008

Page 31 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DB10
Operation

Filling valves
Switch position indicator
Raedy-for-service indicators Disconnector switch BB2
Switch position indicator
Disconnector switch BB1 Operating shaft
Switch position indicator Disconnector switch BB2
Circuit-breaker switch
Preselection key
Switch position indicator
Earthing

Opening for charging the ON pushbutton


circuit-breaker spring by hand Circiut-breaker switch

Spring charged indicator OFF pushbutton


Circiut-breaker switch

Counter De-earthing interlock

Siemens AG 2008

Page 32 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA/B10
Interlocks (Selection)

Interlocks are designed according to IEC 62 271-200


Standard interlocks
Three-position disconnector against circuit-breaker mechanical
Disconnector against earthing switch (within three-position disconnector) mechanical
Locking device at the circuit-breaker switch
Locking device at the three-position disconnector switch
Additional interlocks
Electromagnetic interlock at the three-position switch / disconnector switch
Electromagnetic interlock at the three-position switch / earthing switch

Siemens AG 2008

Page 33 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
Special feature - Single-pole enclosure

Example 8DA10
L3 L2 L1

Advantage of single-pole enclosure


Exclude phase-to-phase short circuits.
In worst case only phase-to-earth short circuits could
happen.
Minimizing of fault risks.

Siemens AG 2008

Page 34 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
Special feature - Multiple-Vessel-Principle 8DA10

Busbar and circuit-breaker are single-pole enclosed


within different vessels
Measures in case of faults at circuit-breaker or cable
connection:
Shut down of the busbar is not necessary
Replacement of panels is possible, while
busbar is under high voltage operation

Single-phase enclosure
2 Compartments
6 Vessels
Shut down is only for the damaged panel necessary

Siemens AG 2008

Page 35 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
Special feature - Multiple-Vessel-Principle 8DB10

Busbar and switching devices are single-pole enclosed


within different vessels
Measures in case of faults at switching devices or
cable connection:
Shut down of the busbar is not necessary
Replacement of panels is possible, while
busbar is under high voltage operation

Single-phase enclosure
5 Compartments
15 Vessels
Shut down is only for the damaged panel necessary

Siemens AG 2008

Page 36 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
Special feature - Multiple-Vessel-Principle

Statement 8DA10 and 8DB10

Maximum reliability of supply


No disconnecting of the busbar while outgoing feeder will be
repaired or replaced.
Extension 8DB10 without shutdown of the busbar.

Siemens AG 2008

Page 37 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA/B10
Classification according to IEC 62 271-200

Partition Class: PM
Loss of Service Continuity Category: LSC 2B
Accessibility of Compartments:
Busbar compartment: tool-based
Switching device compartment: tool-based
Low-voltage compartment: tool-based
Cable compartment: tool-based
Internal arc classification: IAC A FLR 40 kA 1 s

Siemens AG 2008

Page 38 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA/B10
Customers Benefit

Security of Operation, Reliability


Personal Safety
Environmental Independence
Compactness
Maintenance-free Design for Devices
Economy, Ecology

Siemens AG 2008

Page 39 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA/B10
Security of Operation, Reliability

Our solution Your benefit


Hermetically enclosed system Two and three-phase short circuits not
Current transformers outside the gas possible because of single-phase
compartments encapsulation

Metal-enclosed voltage transformers Independent of the environment,


plugged in from outside maintenance-free,
no condensation, no oxidation
Hermetically enclosed busbar system
Fast transformer replacement possible
Modular design
No dielectric and dynamic stress for
Minimum use of insulating material current transformers
Type and routine tests, quality Restriction of failure by compartment
management
Reduced fire load
NC production processes
MTBF (> 3,000 years at the moment)

Siemens AG 2008

Page 40 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA/B10
Maximum Security of Operation

Separate compartments for busbar and circuit-breaker offer a


maximum degree of availability

Busbar ( in operation )
Attention: High voltage

Feeder earthed ( earthing )

Circuit-breaker
Access without danger to current
transformer, feeder voltage transformer,
cable plugs, operating mechanisms

Siemens AG 2008

Page 41 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA/B10
Personal Safety

Our solution Your benefit


Hermetically enclosed system Touching of live parts excluded,
Internal arc classified according to extremely high degree of protection of the
IEC 62 271-200 for 1 s primary part

Logical mechanical interlocks Accidental opening of vessel excluded

Capacitive voltage detection system Access to switching devices not required


due to maintenance-free design
Make-proof earthing through
the circuit-breaker Maloperation excluded
Verification of safe isolation from supply
without opening the enclosure

Siemens AG 2008

Page 42 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA/B10
Environmental Independence

Our solution Your benefit


Hermetically encapsulation Insensitive to aggressive environments
Hermetically enclosed pressure system (salt water, tropical areas, dust, humidity,
chemical pollutants),
Maintenance-free switching no oxidation of contacts and bolted joints,
devices and operating no condensation,
mechanisms, no pollution layers on insulators,
no adjustment and lubrication no resinifying grease
Hermetically enclosed busbar system Continuous insulation quality
Enclosed cable plugs, No ingress of foreign bodies, small
animals
screened, independent of
the environment Independent of site altitude

Siemens AG 2008

Page 43 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA/B10
Compactness

Our solution Your benefit


SF6-insulation, Minimum space requirements,
compact construction building volume saved, efficient use of
Combined disconnector and earthing existing rooms, reduced volume for new
switch, constructions, compact design reduces
compact switch design transport and installation costs to a minimum

SIPROTEC bay controller: Digital Economic use of space in urban areas,


control, interlocking and protection installation in conurbation, load centres to
system, minimise transmission losses
compact secondary systems with high
functional density

Siemens AG 2008

Page 44 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA/B10
Maintenance-free Design for Devices

Our solution Your benefit


Hermetically enclosed pressure system Maximum reliability of supply and
Maintenance-free switching devices and availability,
operating mechanisms, no shutdowns for maintenance
no adjustment and lubrication Sealed for lifetime
Hermetically enclosed busbar system (according IEC 62 271-200)

Enclosed cable plugs, Low maintenance costs,


screened, independent of the environment minimized operational costs
Highly economic investment

Siemens AG 2008

Page 45 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA/B10
Economy, Ecology

Our solution Your benefit


Maintenance-free switchgear Minimized operator expenses,
Compact construction high availability

Economic production Reduced transport costs

SF6 only used in hermetically sealed Minimum requirements regarding the


pressure system building

100 % SF6-recycling by means of Minimized transmission losses by


special tools installation in load centres

Identified, recyclable insulating material Reliable, calculable disposal

Listing of all materials used

Siemens AG 2008

Page 46 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA/B10
MTBF (1)

The term major failures and minor failures are taken from the CIGRE publication of the work
group 13.06 Reliability of High Voltage Switchgears.

Definition:

MTBF
Meantime between failure

Major failure (MF)


Complete failure of a panel which causes the lack of one or more of its fundamental
functions.
NOTE: A major failure will result in an immediate change in the system operating e.g. the backup protective
equipment being required to remove the fault, or will result in mandatory removal from service for non scheduled
maintenance (Intervention required within 30 minutes).

Minor failure (mF)


Failure of a panel other than a major failure or any failure, even complete, of a constructional element or a sub-
assembly which does not cause a major failure of the panel.

MTTF
Meantime to failure

Siemens AG 2008

Page 47 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA/B10
MTBF (2)

Download from the Intranet

Siemens AG 2008

Page 48 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA/B10
References Selected Projects (1)

Kulmbach / Germany
8DA10 / 16 panels
24 kV / 16 kA (3s) / 1250 A

First SIEMENS gas-insulated


medium-voltage switchgear
(March 1982)

Siemens AG 2008

Page 49 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA/B10
References Selected Projects (2)

Tibet / China
8DA10
205 panels
40.5 kV / 31.5 kA (3s) / 1250 A

Site altitude: 3000 5000 m

Siemens AG 2008

Page 50 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA/B10
References Selected Projects (3)

GECOL / Libya
8DA10 and 8DB10
1398 panels
36 kV / 40 kA (3s) / 2500 A

Siemens AG 2008

Page 51 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
8DA/B10
References Selected Projects (4)

Emirates Palace Hotel


8DB10
117 panels
12 kV / 31,5 kA (3s) / 2500 A

Siemens AG 2008

Page 52 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2
Thanks for
your attention.

8DA/B10, the gas-insulated switchgear up to

40,5 kV, 40 kA (3 s), 5000 A busbar, 2500 A feeder

Siemens AG 2008

Page 53 October 1st 2011 8DA/B10 Infrastructure & Cities Sector / IC LMV MV 2

Vous aimerez peut-être aussi