3 Electric wiring

Electric wiring include two parts: Controller main circuit terminal wirings and
main control board wirings.

1) Main circuit connection and terminal function Contactor


a) main circuit: VFD 37A
C on ta cto r at

Incoming
R U
th e o u tp u t sid e

MT
Motor
S V
400V
T W
3~
28A
Breaker B rak e
NICE1000 R e s is to r

60A +

PB

Fig. 3-3 Main Circuit Wiring

b) terminal function:

Terminal Name Description


3-phase power input
R,S,T Input 3-phase AC380V
terminal
Positive and negative Terminal of external brake unit for
(+),(-)
terminals of DC bus controller above 37KW.
For controller below 30kW(include 30kW)
P(+),PB Terminals for brake resistor
they are for brake unit
U,V,W controller output terminal Connect 3-phase motor
PE Terminal for grounding Grounding terminal

Note:

Select the recommended resistor according to section 3.3.2.

Controller output circuit grounding or short circuit is absolutely


not permitted.

Controller output cables of U, V and W should be in metal pipe


with grounding, and divided or vertical with control circuit cables.

If the cables between the motor and the controller are too long,
electrical resonance may occur due to the distributed capacitance,
which may result in damaging the motor insulation or big leakage

23