Vous êtes sur la page 1sur 22

SIPROTEC 5 /

DIGSI 5 Basic Course


11 DIGSI 5 - Control Functions
www.siemens.com/poweracademy Copyright Siemens AG 2012. All rights reserved.
Training Objective

What you will learn


How the control function is designed in SIPROTEC 5
To understand the basic principles for user defined functions
Where the differences are compared to SIPROTEC 4

Copyright Siemens AG 2012. All rights reserved.


How to use DIGSI 5 for these purposes
How the SIPROTEC 5 devices work in a Substation Automation Environment

11 DIGSI 5 - Control Functions


Version: D_01_Page 2 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
Content

Content

Introduction

Copyright Siemens AG 2012. All rights reserved.


Structure of Control Function
Description of Details
Differences to SIPROTEC 4
User defined signals
(Presentation with DIGSI 5)

11 DIGSI 5 - Control Functions


Version: D_01_Page 3 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
Introduction

Device architecture is based on IEC 61850 model


IEC 61850 is the substation automation protocol

Copyright Siemens AG 2012. All rights reserved.


Goals:
Full integration of protection and substation automation
Full support of IEC 61850 edition 2
Satisfy customers with high level IEC 61850 requirements
(flexible engineering)
Less engineering effort for standard engineering tasks
Do not bother customers with IEC 61850 details if they dont need it

11 DIGSI 5 - Control Functions


Version: D_01_Page 4 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
Content

Content

Introduction

Copyright Siemens AG 2012. All rights reserved.


Structure of Control Function
Description of Details
Differences to SIPROTEC 4
User defined signals
(Presentation with DIGSI 5)

11 DIGSI 5 - Control Functions


Version: D_01_Page 5 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
Structure of control function

Command
Source: Device-HMI,
Station, Control Center,
CFC, DIGSI

Parameter: (settings) Command Command

Copyright Siemens AG 2012. All rights reserved.


Output time issued protocol
Chatter blocking Parameter:
BI
Info about Interlocking Conditions
Pos Pos (engineered in CFC)
CB position
(Position of
breaker)
Function Function Function
BI
Block Circuit Block Block
BO Breaker Control Info about Interlocking
Pos XCBR Pos CSWI CILO
(command releases
to breaker)
BO

routing Evaluation of:


Parameter (settings):
to BI/BO Switching authority (local/remote)
Command type, Switching mode (interlocked/uninterlocked)
SW-Filter time, Interlocking conditions
Feedback monitoring time, Double operation blocking
SBO timeout Blocking by protection
11 DIGSI 5 - Control Functions
Version: D_01_Page 6 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
Content

Content

Introduction

Copyright Siemens AG 2012. All rights reserved.


Structure of Control Function
Description of Details
Differences to SIPROTEC 4
User defined signals
(Presentation with DIGSI 5)

11 DIGSI 5 - Control Functions


Version: D_01_Page 7 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
Representation of Control Structure in DIGSI 5
Example 1: Circuit Breaker

Representation of CB in routing matrix

XCBR

Copyright Siemens AG 2012. All rights reserved.


CSWI

CILO

New: Circuit Breaker includes protection function blocks

11 DIGSI 5 - Control Functions


Version: D_01_Page 8 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
Representation of Control Structure in DIGSI 5
Example 2: Disconnector

Copyright Siemens AG 2012. All rights reserved.


CSWI

CILO

XSWI

11 DIGSI 5 - Control Functions


Version: D_01_Page 9 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
Engineering Basic Definitions

Function Blocks Settings


Signals Properties

Function
Group

Copyright Siemens AG 2012. All rights reserved.


Function
Block

Signal

11 DIGSI 5 - Control Functions


Version: D_01_Page 10 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
Representation of Control Structur in DIGSI 5
Details of Circuit Breaker (1/2)

Possibility for external aquisition


blocking (Knebelschalter)

Copyright Siemens AG 2012. All rights reserved.


Physical position as connected to
binary inputs and outputs of device
For use in interlocking conditions

Control Command for CB


Select logging options (for example
event log)
For transmission to system interface
Use these signals for outputs of
interlocking CFC plans

11 DIGSI 5 - Control Functions


Version: D_01_Page 11 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
Details of Circuit Breaker (2/2)
Position

Copyright Siemens AG 2012. All rights reserved.


Connect to binary inputs

Use this information in interlocking


CFC plans or to connect to LEDs
Connect to binary inputs

11 DIGSI 5 - Control Functions


Version: D_01_Page 12 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
Single Line and Topology View

Copyright Siemens AG 2012. All rights reserved.


Topology tree is
read-only in step 1

11 DIGSI 5 - Control Functions


Version: D_01_Page 13 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
Content

Content

Introduction

Copyright Siemens AG 2012. All rights reserved.


Structure of Control Function
Description of Details
Differences to SIPROTEC 4
User defined signals
(Presentation with DIGSI 5)

11 DIGSI 5 - Control Functions


Version: D_01_Page 14 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
Main Differences to SIPROTEC 4

Automatic GOOSE configuration


Protection and Control use the same Circuit Breaker model

Copyright Siemens AG 2012. All rights reserved.


Single Line Editor for system view
Topology Tree (read-only in first release)
Supports IEC61850 Edition 2
More details of IEC 61850 usable

11 DIGSI 5 - Control Functions


Version: D_01_Page 15 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
Content

Content

Introduction

Copyright Siemens AG 2012. All rights reserved.


Structure of Control Function
Description of Details
Differences to SIPROTEC 4
User defined signals
(Presentation with DIGSI 5)

11 DIGSI 5 - Control Functions


Version: D_01_Page 16 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
Signal Types (1/2)
What do I have to do if I need a.

SIPROTEC 4 Information Catalog SIPROTEC 5 Library

Information type SPS (Single Point Status)


Protocol text or transient indication (Wischermeldung) is a
setting
No differentiation external / internal signal

Copyright Siemens AG 2012. All rights reserved.


Not necessary any longer

Circuit breaker or disconnect switch status only

SPS (if source = BI or CFC), SPC (if source =


Communication)
Binary Counter Reading BCR
Not necessary any longer

SPS (if source = BI or CFC), SPC (if source =


Communication)

Function Group / Block Transformer Tap Changer

11 DIGSI 5 - Control Functions


Version: D_01_Page 17 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
Signal Types (2/2)

SIPROTEC 4 Information Catalog SIPROTEC 5 Library

Copyright Siemens AG 2012. All rights reserved.


Circuit breaker or disconnector switch status only

Circuit breaker or disconnector switch

Measured Value (result of CFC / GOOSE-Communication)

Contained in every function group line (Wp+, Wq+, Wp-,


Wq-)metered value
Pulse

11 DIGSI 5 - Control Functions


Version: D_01_Page 18 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
Grouping of signals in
User Defined Function Group (1/2)

Copyright Siemens AG 2012. All rights reserved.


User defined Function block for
grouping of information

Command with Single Feedback

Routing of single feedback to


binary input

Command with Double Feedback

Routing of double feedback to


binary inputs

11 DIGSI 5 - Control Functions


Version: D_01_Page 19 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
Grouping of signals in
User Defined Function Group (2/2)

Copyright Siemens AG 2012. All rights reserved.


Routing of command output to relays
Same options for both types!
Off: Set relay when command is off
On: Set relay when command is on
Cc: Common contact; set relay when
command is off or on
BF: Busy Flag; set relay when
command is off or on, starting
with select and ending with end
of feedback monitoring time

All routings are allowed to be


multiple.

11 DIGSI 5 - Control Functions


Version: D_01_Page 20 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
Content

Content

Introduction

Copyright Siemens AG 2012. All rights reserved.


Structure of Control Function
Description of Details
Differences to SIPROTEC 4
User defined signals
Presentation with DIGSI 5

11 DIGSI 5 - Control Functions


Version: D_01_Page 21 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
What will be shown in DIGSI 5?

Select Single Line Template


Create circuit breaker and disconnect switch objects in the device
Connect switches and CTs / VTs in Single Line to device objects

Copyright Siemens AG 2012. All rights reserved.


Engineering of breaker and disconnect switch:
Connect to BI / BO
Create interlocking logic in CFC
Route position information to event log
Create Display Page from Single Line Editor picture

Use GOOSE messages for interlocking


Show complete settings and properties of switches (for example chatter
blocking, filter times)
Create new single point / double point indications

11 DIGSI 5 - Control Functions


Version: D_01_Page 22 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course

Vous aimerez peut-être aussi