PRODUCT SHEET

Proportioning Devices
Wide-Range Proportioners | KWR Wide-Range Proportioner

Approvals
RUS

Material Bronze or stainless steel

Connection Type Wafer

Max. Working pressure 16 bar

Weight See table

For mixing performance accuracy, it is recommended to install the


KWR within a straight pipe section 7 diameters long upstream and 5
diameters long downstream.

FOAM CONCENTRATE INLET

D MIXING RATIO REGULATOR


A
B

WATER SUPPLY FOAM CONCENTRATE OUTLET

WAFER MOUNTED
C

Flow rate Q @ Max


Dimensions Weight (kg)
Part number min. max.1 Foam type Q
A (mm) B C (mm) D (inch/DN) l/min l/min Bar2
Model KWR Standard version - Loose
KWR100/50A 209 4" / DN100 70 2" / DN50 75 2,500 Any 1.9 14.0
KWR150/50A 241 6" / DN150 70 2" / DN50 100 5,600 Any 2.3 22.0
KWR200/80A 291 8" / DN200 82 3" / DN80 125 10,600 Any 2.7 38.0
KWR250/80A 323 10" / DN250 82 3" / DN80 150 16,100 Any 2.8 46.0
Model KWR Standard version - Pre-Assembled to bladder tank
KWR100/50C 209 4" / DN100 N/A 2" / DN50 75 2,500 Any 1.9 N/A
KWR150/50C 241 6" / DN150 N/A 2" / DN50 100 5,600 Any 2.3 N/A
KWR200/80C 291 8" / DN200 N/A 3" / DN80 125 10,600 Any 2.7 N/A
KWR250/80C 323 10" / DN250 N/A 3" / DN80 150 16,100 Any 2.8 N/A
1 The KWR can work at higher flowrates with larger pressure drop
2 The pressure drop at the minimum flowrate is approximately 0.3 bar
SP2.3.2.2a/0417/en

Note: This document contains basic product information only. Information, photos and drawings are not contractually binding.
In all cases, the manufacturers full technical documentation remains the reference document.
The contents of this publication are subject to modifications without notice. All rights reserved.

K.C. Antincendi S.r.l. | Via Pavia 76 | 27042 Bressana Bottarone (PV) | Italy | info@kcantincendi.com
PRODUCT SHEET

Proportioning Devices
Wide-Range Proportioners | KWR Wide-Range Proportioner

KWR 100/50 PRESSURE DROP CHART KWR 150/50 PRESSURE DROP CHART
2.0 2.5

1.8
1.6 2.0
Pressure drop (lbar)

Pressure drop (lbar)


1.4
1.2 1.5

1.0
0.8 1.0

0.6
0.4 0.5

0.2
0.0 0.0
0 1,000 2,000 3,000 0 1,000 2,000 3,000 4,000 5,000 6,000

Flow rate (l/min) Flow rate (l/min)

KWR 200/80 PRESSURE DROP CHART KWR 250/80 PRESSURE DROP CHART
3.0 3.0

2.5 2.5
Pressure drop (lbar)

Pressure drop (lbar)

2.0 2.0

1.5 1.5

1.0 1.0

0.5 0.5

0.0 0.0
0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000

Flow rate (l/min) Flow rate (l/min)


SP2.3.2.2b/0417/en

Note: This document contains basic product information only. Information, photos and drawings are not contractually binding.
In all cases, the manufacturers full technical documentation remains the reference document.
The contents of this publication are subject to modifications without notice. All rights reserved.

K.C. Antincendi S.r.l. | Via Pavia 76 | 27042 Bressana Bottarone (PV) | Italy | info@kcantincendi.com