Project: Estudio CC y Coord.

Protección ETAP Page: 1


Location: Los Bronces 16.1.0C Date: 10-10-2017
Contract: SN: ANGLOAMCAN
Engineer: Revision: Base
Study Case: TODO
Filename: ETAP_LB_2017_RA22 Config.: Solo lineas

LOAD FLOW REPORT

Bus Voltage Generation Load Load Flow XFMR


ID kV % Mag. Ang. MW Mvar MW Mvar ID MW Mvar Amp %PF %Tap

,2 220.000 100.694 -0.6 0 0 0 0 Barra Confluencia 2 0.000 0.000 0.0 0.0


,,2 220.000 100.694 -0.6 0 0 0 0 Barra Confluencia 2 0.000 0.000 0.0 0.0
.2 220.000 100.694 -0.6 0 0 0 0 Barra Santa Filomena -17.141 11.733 54.1 -82.5
Barra Confluencia 2 17.141 -11.733 54.1 -82.5
Barra Confluencia1 220.000 100.694 -0.6 0 0 0 0 Barra Confluencia 2 0.000 0.000 0.0 0.0
Barra Confluencia 2 220.000 100.694 -0.6 0 0 0 0 Barra Confluencia1 0.000 0.000 0.0 0.0
Bus216 17.141 -11.733 54.1 -82.5
,2 0.000 0.000 0.0 0.0
,,2 0.000 0.000 0.0 0.0
.2 -17.141 11.733 54.1 -82.5
Barra Maitenes 66 66.000 99.861 -3.3 0 0 0 0 Tap OFF PHI 13.448 1.047 118.2 99.7
Barra San Francisco 12.701 1.038 111.6 99.7
Barra San Francisco 12.701 1.038 111.6 99.7
Bus218 -12.949 -1.057 113.8 99.7

& T01 220 kV2


Bus217 -12.949 -1.057 113.8 99.7

& T02 220 kV2


Bus219 -12.951 -1.009 113.8 99.7

& T02 220 kV3


Barra Maitenes 220 220.000 100.810 -0.7 0 0 0 0 Bus216 -17.132 9.476 51.0 -87.5
Barra Tortolas -21.794 18.043 73.7 -77.0
T02 220 kV3 12.976 -9.199 41.4 -81.6
T02 220 kV2 12.975 -9.160 41.3 -81.7
T01 220 kV2 12.975 -9.160 41.3 -81.7
Barra PHI 66.000 98.892 -4.1 0 0 2.445 0.000 Tap OFF PHI -2.445 0.000 21.6 100.0
* Barra Polpaico 220.000 100.000 0.0 39.082 -45.620 0 0 Barra Santa Filomena 17.185 -19.748 68.7 -65.6
Barra Tortolas 21.897 -25.872 89.0 -64.6
Barra SAG 1 66.000 98.137 -4.8 0 0 35.828 2.873 Barra Seccion Linea 3 -11.462 -1.265 102.8 99.4
Barra Seccion Linea 6 -11.825 -0.369 105.5 100.0
Barra San Francisco -12.542 -1.239 112.3 99.5
Barra San Francisco 66.000 98.547 -4.3 0 0 0 0 Tap OFF PHI -10.853 -0.982 96.7 99.6
Barra Seccion Linea 3 11.500 1.283 102.7 99.4
Barra Seccion Linea 6 11.871 0.389 105.4 99.9
Barra Maitenes 66 -12.552 -0.972 111.7 99.7
Barra Maitenes 66 -12.552 -0.972 111.7 99.7
Barra SAG 1 12.585 1.255 112.3 99.5
Project: Estudio CC y Coord. Protección ETAP Page: 2
Location: Los Bronces 16.1.0C Date: 10-10-2017
Contract: SN: ANGLOAMCAN
Engineer: Revision: Base
Study Case: TODO
Filename: ETAP_LB_2017_RA22 Config.: Solo lineas

Bus Voltage Generation Load Load Flow XFMR


ID kV % Mag. Ang. MW Mvar MW Mvar ID MW Mvar Amp %PF %Tap

Barra Santa Filomena 220.000 100.400 -0.3 0 0 0 0 Barra Polpaico -17.160 15.772 60.9 -73.6
.2 17.160 -15.772 60.9 -73.6
Barra Seccion Linea 3 66.000 98.207 -4.7 0 0 0 0 Barra SAG 1 11.469 1.267 102.8 99.4
Barra San Francisco -11.469 -1.267 102.8 99.4
Barra Seccion Linea 6 66.000 98.402 -4.5 0 0 0 0 Barra San Francisco -11.855 -0.380 105.4 99.9
Barra SAG 1 11.855 0.380 105.4 99.9
Barra Tortolas 220.000 100.252 -0.2 0 0 0 0 Barra Polpaico -21.876 23.148 83.4 -68.7
Barra Maitenes 220 21.876 -23.148 83.4 -68.7
Bus216 220.000 100.694 -0.6 0 0 0 0 Barra Maitenes 220 17.141 -11.733 54.1 -82.5
Barra Confluencia 2 -17.141 11.733 54.1 -82.5
Bus217 15.000 95.662 -32.4 0 0 0.000 -10.982 T02 220 kV2 0.000 10.982 441.8 0.0

& Barra Maitenes 66


Bus218 15.000 95.662 -32.4 0 0 0.000 -10.982 T01 220 kV2 0.000 10.982 441.8 0.0

& Barra Maitenes 66


Bus219 15.000 95.593 -32.4 0 0 0.000 -10.966 T02 220 kV3 0.000 10.966 441.5 0.0

& Barra Maitenes 66


T01 220 kV2 220.000 100.810 -0.7 0 0 0 0 Barra Maitenes 220 -12.975 9.160 41.3 -81.7
Barra Maitenes 66 12.975 -9.160 41.3 -81.7 7.500

& Bus218
T02 220 kV2 220.000 100.810 -0.7 0 0 0 0 Barra Maitenes 220 -12.975 9.160 41.3 -81.7
Barra Maitenes 66 12.975 -9.160 41.3 -81.7 7.500

& Bus217
T02 220 kV3 220.000 100.810 -0.7 0 0 0 0 Barra Maitenes 220 -12.976 9.199 41.4 -81.6
Barra Maitenes 66 12.976 -9.199 41.4 -81.6 7.500

& Bus219
Tap OFF PHI 66.000 98.897 -4.0 0 0 0 0 Barra Maitenes 66 -13.332 -0.981 118.2 99.7
Barra San Francisco 10.887 0.985 96.7 99.6
Barra PHI 2.445 -0.003 21.6 100.0
* Indicates a voltage regulated bus ( voltage controlled or swing type machine connected to it)
# Indicates a bus with a load mismatch of more than 0.1 MVA