MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

Content
1. Outdoor units lineup ..........................................................2 
2. Nomenclature ....................................................................3 
3.Features ..............................................................................4 
4. Description of main components ....................................8 
5. Specifications..................................................................10 
6. Dimensions......................................................................14 
7. Piping Diagram................................................................15 
8. Wiring Diagram ...............................................................16 
9. Electric Characteristics ..................................................19 
10. Capacity Tables .............................................................20 
11. Operation Limits ............................................................26 
12. Water Pressure Drop ....................................................28 
13. Sound Level...................................................................31 
14.  Exploded View ..............................................................32 
15.  Installation ....................................................................38 
16.  Checking and Starting Up the Unit .............................51 
17.  Running and Maintenance ..........................................53 
18. Controller .......................................................................56 
19.Troubleshooting .............................................................69 
20. Optional Accessories ...................................................94 

※ Manufacture reserves the right to discontinue, or change at any time, specifications or designs without notices
and without incurring obligations.
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

1. Outdoor units lineup

MGC-V5W/D2N1, MGC-V7W/D2N1

Power Supply Compressor Heat Hydraulic


Model Capacity A/C mode Refrigerant
(V/Ph/Hz) type exchanger module
MGC-V5W/D2N1 220-240/1 /50 5.0kW DC Inverter Plate type Heat pump Built-in R410A
MGC-V7W/D2N1 220-240/1/50 7.0kW DC Inverter Plate type Heat pump Built-in R410A

MGC-V10W/D2N1, MGC-V12W/D2RN1
MGC-V14W/D2RN1, MGC-V16W/D2RN1

Power Supply Compressor Heat Hydraulic


Model Capacity A/C mode Refrigerant
(V/Ph/Hz) type exchanger module
MGC-V10W/D2N1 220-240/1/50 10.0 DC Inverter Plate type Heat pump Built-in R410A
MGC-V12W/D2RN1 380-415/3/50 11.2 DC Inverter Plate type Heat pump Built-in R410A
MGC-V14W/D2RN1 380-415/3/50 12.5 DC Inverter Plate type Heat pump Built-in R410A
MGC-V16W/D2RN1 380-415/3/50 14.5 DC Inverter Plate type Heat pump Built-in R410A

2
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

2. Nomenclature

M G C - V 5 W / D2 R N1
Refrigerant Type
N1:R410A Omit for R22

Power Supply
R:380~415V, 3Ph ,50Hz
Omit for 220~240V,1Ph,50Hz

D2: Full DC Compressor & Fan Motor


Outdoor Unit
Nominal Cooling Capacity (kW)

Compressor Type
D: Digital scroll compressor
F: Fixed scroll compressor
V: Inverter compressor

Design Series Code


A: Split chiller
C: Unitary chiller

Light Chiller System


Midea

3
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

3.Features
3.1 High efficient DC inverter compressor

Full DC inverter mini chiller adopts highly intelligent inverter-driven compressor. This advanced technology
enables the output of the outdoor unit to be modulated by the real heat load demands..
This advanced system ensures precise temperature regulation and highly efficient energy usage, making a
significant contribution to limiting the impact on the environment.

Highly Efficient DC Motor:


- Creative motor core design
- High density neodymium magnet
- Concentrated type stator
-Wider operating frequency range

Better balance and Extremely Low Vibration:


- Twin eccentric cams
- 2 balance weights

Highly Stable Moving Parts:


- Optimal material matching rollers and vanes
-Optimize compressor drive technology
Compressor
- Highly robust bearings
(Twin Rotary) structure
-Compact structure

3.2 High performance heat exchanger

The new designed window fins enlarge the heat-exchanging area,


which decrease the air resistance, save more power and enhance heat New design Original design

exchange performance.
Hydrophilic film fins and inner-threaded copper pipes optimize heat High efficiency inner-thread pipe,
enhance heat transfer.

exchange efficiency.

3.3 Low-operating sound design

Optimally design fan shape and new designed discharge air grille and air deflector, making higher air volume
and reduces running noise..
Air deflector

New grille

New fan

4
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

3.4 High efficiency

EER
3.39 3.31
3.5 3.23 3.21 3.20
3.11

2.5

1.5

0.5

0
5kW 7kW 10kW 12kW 14kW 16kW

COP
3.5
3.5 3.31 3.30
3.24 3.25
3.2

2.5

1.5

0.5

0
5kW 7kW 10kW 12kW 14kW 16kW
 

3.5 Wide operation temperature range 
Stable and safe running at wide ambient temperature range, cooling performance from -5 ˚C to 46˚C,
heating from -15˚C to 27˚C.

COOLING MODE
-5°C 46°C

HEATING MODE
-15°C 27°C

-20 -10 0 10 20 30 40 50 °C(D.B.)


Outdoor temp.

3.6 Energy saving and high reliability

By adopting high efficiency plate heat exchanger, the energy consumption can be reduced.

5
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

a. Metallic protective cabinet with rustproof polyester paint;


b. Built-in with voltage protection, current protection, anti-freezing protection, water flow protection and
etc., effectively guarantee the system to work safely.
3.7 User friendly remote control

Switch SW4_1(10kW) or SW3_1(12-16kW) on the PCB to ON to enable the following remote control
functions. The setting is not default at factory.
 Remote shut down
 Remote cooling and heating
 
 
Note: When all controller controls together, the unit will work according to the last order.
5/7kW will be available soon.

3.8 Flexible and convenient control

 Built-in electronic controller at factory.


Compact devices with advanced function and friendly user interface.

 The chiller can be controlled by wired controller (KJR-120F/BMK-E)


also which is optional chosen.

Note: When connecting wired controller, outdoor unit control panel is mainly used for display which can
check parameters and inquiry, and can’t be used to set mode and temperature.

 Built-in water pressure gauge. Inspect the water pressure all the time.

3.9 Integrated and compact design

Fully integrated and built-in hydraulic module, such as expansion tank, plate type of heat exchanger,
water circulating pump, etc. It saves installation space and cost.

3.10 EXV control flow more precisely

Patented liquid distribution components to maximize performance and minimize defrost impact.
Stable and accurate gas flow control. EXV achieves 500 pulses to adjust flow precisely. Ensure the
temperature-control precisely and steadily to provide a comfortable environment.

6
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

Fast respond resulting in higher efficiency and improved reliability.

100%
95%
90%
85%
80%
75%
70%
65%
60%
55%
50%
45%
40%
35%
30%
25%
20%
15%
10%

3.11 Water pump starts/stops compulsory function

Press “Check” button for 3 seconds to start the water pump operating when the unit is standby. Press
“Check” button for 3 seconds again to stop the water pump.

7
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

4. Description of main components


Structure
Panels and base are made from galvanized steel plate painted with epoxy power to ensure total resistance
to atmospheric pollution, condensate collection pan as standard.
Condenser coils:
The coils are made from high performance and seamless copper tuber and high surface area aluminum fins
to ensure optimum heat exchange capability. Condenser coil protection grill is standard.
Fan motor:
To achieve high efficiency heat exchange, the unit is equipment with the high performance axial-flow fans.
The fan is driven directly by weather proof motor to ensure reliable operation, the fan motor is six-pole
electric motor with built-in thermal cut-out.
Evaporator:
The heat exchanger is made of AISI 316 stainless steel to ensure high heat exchange efficiency, complete
with electric heater and differential pressure switch. The complete heat exchanger is insulated with thermal
insulation closed cell rubber foam to give optimum thermal insulation.
Hydraulic module:
It is fully integrated and equipped with key hydraulic components such as expansion tank, plate type of
heat-exchanger, water circulating pump.
The water pressure difference switch is provided in the units to protect against damage to the water pump.
Power and control electrical panel
Power and control electrical panel constructed in accordance with IEC 204-1/EN60335-2-40, complete with
compressor contactor, control via control panel.
11
1
12

2
3
13
4
5
6
7
8

10

5/7KW
1 Electrical panel
2 Display panel
3 Plate heat exchanger
4 4-way valve
5 High pressure switch
6 Low pressure switch
7 Water Pump
8 Accumulator
9 Water flow switch
10 Compressor
11 Condenser
12 Expansion tank
13 Axial-flow fan

8
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

1
2
11
3
4
12
5 13
6 14
15
7 16
17
18
8 19
9
10

10~16KW

1 Operation panel 11 Electrical panel


2 Water manometer 12 High pressure switch
3 Automatic discharge valve 13 4-ways valve
4 Axial-flow fan 14 Expansion tank
5 Differential pressure switch 15 Pump
6 Condenser 16 Low pressure switch
7 Accumulater 17 Storage tank
8 Security discharge 18 Compressor
9 Electric expansive valve 19 Water supply valve
10 Plate heat exchanger

9
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

5. Specifications
Model MGC-V5W/D2N1 MGC-V7W/D2N1
Power supply V-Ph-Hz 220-240, 1, 50 220-240, 1, 50
Capacity kW 5.0 7.0
Cooling*(1)
Input kW 1.55 2.25
Capacity kW 6.57 7.88
Cooling*(2)
Input kW 1.27 1.84
Capacity kW 5.5 8.0
Heating*(3)
Input kW 1.7 2.5
Capacity kW 6.32 8.29
Heating*(4)
Input kW 1.52 2.13
EER*(1) kW/kW 3.23 3.11
EER*(2) kW/kW 5.16 4.28
Max. input consumption kW 2.8 3.0
Max. input current A 14.6 15.6
Model SNB172FJGMC SNB172FJGMC
Type ROTARY ROTARY
Brand Mitsubishi Electric Mitsubishi Electric
Capacity kW 5.46 5.46
Compressor Input kW 1.64 1.64
Rated load current A 8.1 8.1
Locked rotor Amp A 29.5 29.5
Thermal protector Inner Inner
Refrigerant oil ml FV50S,400 FV50S,400
Model WZDK170-38G-1 WZDK170-38G-1
Type DC Motor DC Motor
Outdoor fan Brand
motor NIDEC SHIBAURA NIDEC SHIBAURA
Input W 170 170
Speed r/min 820 820
Number of rows 2 2
Tube pitch(a)× row pitch(b) mm 22×19.05 22×19.05
Fin spacing mm 1.6 1.6
Fin type Hydrophilic aluminum foil Hydrophilic aluminum foil
Outdoor coil
Tube outside dia. and type mm φ7.94 φ7.94
Inner grooved copper tube Inner grooved copper tube
Coil length ×height mm 885×880 885×880
Number of circuits 6 6
Type RS15/6-3-WILO RS15/6-3-WILO
Water pump Input (H/M/L) W 93/67/46 93/67/46
Pumping head m 5.5 5.5
Outdoor air flow m3/h 5100 5100
Throttle EXV+capillary EXV+capillary
Outdoor noise level (sound pressure)*(3) dB(A) 58 58
Water flow m3/h 0.86 1.20
The plate heat-exchanger water pressure kPa 15 15
drop
The Max. and Min. water inlet pressure kPa 500/150 500/150
Net dimension (W×H×D) mm 990×966×354 990×966×354
Outdoor Packing dimension mm 1120×1100×435 1120×1100×435
unit (W×H×D)
Net/ Gross weight kg 81/91 81/91
Type R410A R410A
Refrigerant
Charged volume kg 2.5 2.5
Connection Power wire mm2 3×2.5 3×2.5
wiring Signal wire mm2 3×0.75 3×0.75
Pipe Water inlet/outlet inch 1’’ 1’’
diameter
Control Wired controller Wired controller
Ambient temperature ℃ Cooling: -5℃~46℃; Heating: -15-27℃(Antifreeze must be added below 5℃)
Water outlet temperature range ℃ Cooling: 4~20 ℃; Heating: 30~55 ℃

Note: Specifications are based on the following conditions:


1. Cooling: (*1) chilled water inlet/outlet temperature: 12/7°C,outdoor ambient temperature 35°C DB.
(*2) chilled water inlet/outlet temperature: 23/18°C,outdoor ambient temperature 35°C DB.
10
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

2. Heating: (*3) warm water inlet/outlet temperature: 40/45°C,outdoor ambient temperature 7°C DB/6°C WB .
(*4) warm water inlet/outlet temperature: 30/35°C,outdoor ambient temperature 7°C DB/6°C WB .
3. It is tested 1m away in front of the unit in a semi-anechoic room(sound pressure).
4. The above data may be changed without notice for future improvement on quality and performance.

Model MGC-V10W/D2N1 MGC-12W/D2RN1


Power supply V-Ph-Hz 220-240, 1, 50 380-415, 3, 50
Capacity kW 10.0(2.9~10.5) 11.2(3.1~12.0)
Cooling*(1)
Input kW 2.95 3.38
Capacity kW 10.9 14.50
Cooling*(2)
Input kW 2.49 2.80
Capacity kW 11.0(3.2~12.0) 12.3(3.3~13.2)
Heating*(3)
Input kW 3.14 3.72
Capacity kW 10.96 13.75
Heating*(4)
Input kW 2.51 2.85
EER(*1) kW/kW 3.39 3.31
EER(*2) kW/kW 4.39 5.17
Max. input consumption kW 4.8 5.2
Max. input current A 25 8.9
Model ATQ420D1UMU ATQ420D2UMU
Type Rotary Rotary
Brand GMCC GMCC
Capacity kW 13.1 13.0
Compressor Input kW 3.42 3.45
Rated load current A 6.85 6.9
Locked rotor Amp A 52 44
Thermal protector Inner Inner
Refrigerant oil ml VG74,1400 VG74,1400
Model WZDK100-38G WZDK100-38G
Type DC Motor DC Motor
Outdoor fan Brand
motor Panasonic Panasonic
Input W 100 100
Speed r/min 800 800
Number of rows 2 2
Tube pitch(a)× row pitch(b) mm 22×19.05 22×19.05
Fin spacing mm 1.6 1.6
Fin type Hydrophilic aluminum foil
Outdoor coil
Tube outside dia. and type mm φ7.94 φ7.94
Inner grooved copper tube
Coil length ×height mm 1276×870 1276×870
Number of circuits 7 7
Type RL25/8.5 RL25/8.5
Water pump Input (H/M/L) W 210/175/120 210/175/120
Pumping head m 8 8
Outdoor air flow m3/h 7000 7000
Throttle EXV EXV
Outdoor noise level (sound pressure)*(3) dB(A) 59 59
Water flow m3/h 1.72 1.92
The plate heat-exchanger water pressure kPa 18 18
drop
The Max. and Min. water inlet pressure kPa 500/150 500/150
Net dimension (W×H×D) mm 970×1327×400 970×1327×400
Outdoor Packing dimension mm 1082×1456×435 1082×1456×435
unit (W×H×D)
Net/ Gross weight kg 110/121 110/121
Type R410A R410A
Refrigerant
Charged volume kg 2.8 2.8
2
Connection Power wire mm 3×4.0 5×3.0
wiring Signal wire mm2 3×0.75 3×0.75
Pipe Water inlet/outlet inch 1-1/4” 1-1/4”
diameter
Control Wired controller Wired controller
Ambient temperature ℃ Cooling: -5℃~46℃; Heating: -15-27℃(Antifreeze must be added below 5℃)
Water outlet temperature range ℃ Cooling: 4~20 ℃; Heating: 30~55 ℃

Note: Specifications are based on the following conditions:


11
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

1. Cooling: (*1) chilled water inlet/outlet temperature: 12/7°C,outdoor ambient temperature 35°C DB.
(*2) chilled water inlet/outlet temperature: 23/18°C,outdoor ambient temperature 35°C DB.
2. Heating: (*3) warm water inlet/outlet temperature: 40/45°C,outdoor ambient temperature 7°C DB/6°C WB .
(*4) warm water inlet/outlet temperature: 30/35°C,outdoor ambient temperature 7°C DB/6°C WB .
3. It is tested 1m away in front of the unit in a semi-anechoic room(sound pressure).
4. The above data may be changed without notice for future improvement on quality and performance.

Model MGC-V14W/D2RN1 MGC-16W/D2RN1


Power supply V-Ph-Hz 380-415, 3, 50 380-415, 3, 50
Capacity kW 12.5(3.3~14.0) 14.5(3.5~15.5)
Cooling*(1)
Input kW 3.9 4.53
Capacity kW 15.17 16.70
Cooling*(2)
Input kW 3.13 3.73
Capacity kW 13.8(3.5~15.4) 16.0(3.7~17.0)
Heating*(3)
Input kW 4.25 4.85
Capacity kW 15.30 16.97
Heating*(4)
Input kW 3.15 3.86
EER(*1) kW/kW 3.2 3.2
EER(*2) kW/kW 4.84 4.48
Max. input consumption kW 5.6 5.9
Max. input current A 9.6 10.1
Model ATQ420D2UMU ATQ420D2UMU
Type Rotary Rotary
Brand GMCC GMCC
Capacity kW 13.0 13.0
Compressor Input kW 3.45 3.45
Rated load current A 6.9 6.9
Locked rotor Amp. A 44 44
Thermal protector Inner Inner
Refrigerant oil ml VG74,1400 VG74,1400
Model WZDK100-38G WZDK100-38G
Type DC Motor DC Motor
Outdoor fan Brand
motor Panasonic Panasonic
Input W 100 100
Speed r/min 800 800
Number of rows 2 2
Tube pitch(a)× row pitch(b) mm 22×19.05 22×19.05
Fin spacing mm 1.6 1.6
Fin type Hydrophilic aluminum foil
Outdoor coil
Tube outside dia. and type mm φ7.94 φ7.94
Inner grooved copper tube
Coil length ×height mm 1276×870 1276×870
Number of circuits 7 7
Type RL25/8.5 RL25/8.5
Water pump Input (H/M/L) W 210/175/120 210/175/120
Pumping head m 8 8
Outdoor air flow m3/h 7000 7000
Throttle EXV EXV
Outdoor noise level (sound pressure)*(3) dB(A) 60 60
Water flow m3/h 2.15 2.49
The plate heat-exchanger water pressure kPa 18 19
drop
The Max. and Min. water inlet pressure kPa 500/150 500/150
Net dimension (W×H×D) mm 970×1327×400 970×1327×400
Outdoor Packing dimension mm 1082×1456×435 1082×1456×435
unit (W×H×D)
Net/ Gross weight kg 111/122 111/122
Type R410A R410A
Refrigerant
Charged volume kg 2.9 3.2
Connection Power wire mm2 5×3.0 5×3.0
wiring Signal wire mm2 3×0.75 3×0.75
Pipe Water inlet/outlet inch 1-1/4’’ 1-1/4’’
diameter
Control Wired controller Wired controller
Ambient temperature ℃ Cooling: -5℃~46℃; Heating: -15-27℃(Antifreeze must be added below 5℃)
Water outlet temperature range ℃ Cooling: 4~20 ℃; Heating: 30~55 ℃

12
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

Note: Specifications are based on the following conditions:


1. Cooling: (*1) chilled water inlet/outlet temperature: 12/7°C,outdoor ambient temperature 35°C DB.
(*2) chilled water inlet/outlet temperature: 23/18°C,outdoor ambient temperature 35°C DB.
2.Heating: (*3) warm water inlet/outlet temperature: 40/45°C,outdoor ambient temperature 7°C DB/6°C WB .
(*4) warm water inlet/outlet temperature: 30/35°C,outdoor ambient temperature 7°C DB/6°C WB .
3. It is tested 1m away in front of the unit in a semi-anechoic room(sound pressure).
4. The above data may be changed without notice for future improvement on quality and performance.

13
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

6. Dimensions
MGC-V5W/D2N1,MGC-V7W/D2N1 (Unit: mm)

354

966

990

366

624

MGC-V10W/D2N1,MGC-V12W/D2RN1,MGC-V14W/D2RN1,MGC-V16W/D2RN1
(Unit : mm)
1327

900
970

600
360
400
348
320

14
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

7. Piping Diagram
MGC-V5W/D2N1,MGC-V7W/D2N1

HEAT PUMP

1 compressor 6 electronic expansive valve 11 accumulator


2 high pressure switch 7 liquid receiver 12 low pressure switch
3 4-way value(only HEAP PUMP) 8 plate heat exchanger 13 crankcase heater
4 condenser 9 frost heater
5 filter 10 water temperature sensor

MGC-V10W/D2N1,MGC-V12W/D2RN1, MGC-V14W/D2RN1, MGC-V16W/D2RN1


19 20 22 23
21
17
15
24
A
8 9

16 18

6
2 7 5 7

10 HP

13
LP 11 4
14
12

Cooling
1 3 Heating

1 Compressor 9 Differential Pressure Switch 17 Thermistor For Water Outlet


2 4-Way Valve 10 High Pressure Switch 18 Thermistor For Water Inlet
3 Accumulatior 11 Low Pressure Switch 19 Automatic Discharge Valve
4 Air Side Heat Exchanger 12 Discharge Gas thermistor 20 Expansion Tank
5 Electronic Expansion Valve 13 thermistor For Outdoor Temperature 21 Circulating Pump
6 Storage Tank 14 Thermistor For Evaporation In Heating 22 Pressure Gauge
7 Strainer (Thermistor For Condenser In Cooling) 23 Safety Valve
8 Water Side Heat Exchanger 15 Thermistor For Plate Heat Exchange 1 24 Auto-watet replenishing
(Plate Heat Exchange) 16 Thermistor For Plate Heat Exchange 2

15
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

8. Wiring Diagram
MGC-V5W/D2N1,MGC-V7W/D2N1

16
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

MGC-V10W/D2N1

17
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

MGC-V12W/D2RN1,MGC-V14W/D2RN1,
MGC-V16W/D2RN1

18
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

9. Electric Characteristics

Outdoor Unit Power Supply Compressor OFM


Model
Hz Voltage Phase Min. Max. MCA TOCA MFA MSC RLA kW FLA
MGC-V5W/D2N1 50Hz 220~240V 1Ph 198V 264V 10.1 14.6 20 29.5 8.1 0.195 1.65
MGC-V7W/D2N1 50Hz 220~240V 1Ph 198V 264V 10.1 15.6 20 29.5 8.1 0.195 1.65
MGC-V10W/D2N1 50Hz 220~240V 1Ph 198V 264V 15.1 25.0 30 52 12.1 0.20 1.8
MGC-V12W/D2RN1 50Hz 380~415V 3Ph 342V 456V 8.6 8.9 15 44 6.9 0.20 1.8
MGC-V14W/D2RN1 50Hz 380~415V 3Ph 342V 456V 8.6 9.6 15 44 6.9 0.20 1.8
MGC-V16W/D2RN1 50Hz 380~415V 3Ph 342V 456V 8.6 10.1 15 44 6.9 0.20 1.8
Remark:
MCA: Min. Current Amps. (A)
TOCA: Total Over-current Amps. (A)
MFA: Max. Fuse Amps. (A)
MSC: Max. Starting Amps. (A)
RLA: Rated Current Amps. (A)
OFM: Outdoor Fan Motor
FLA: Full Load Amps. (A)
kW: Rated Motor Output (kW)

19
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

10. Capacity Tables


MGC-V5W/D2N1
Cooling
Ambient temp.(℃)
21.00 25.00 30.00 35.00 40.00 46.00
Chilled
water
outlet
Capacity

Capacity

Capacity

Capacity

Capacity

Capacity
Power

Power

Power

Power

Power

Power
EER

EER

EER

EER

EER

EER
temp.

W/
(℃) kW kW W/W kW kW kW kW W/W kW kW W/W kW kW W/W kW kW W/W
W
5.00 5.60 1.37 4.10 5.27 1.41 3.75 4.97 1.45 3.43 4.70 1.50 3.14 4.40 1.57 2.80 4.05 1.65 2.46
6.00 5.79 1.39 4.17 5.44 1.43 3.81 5.13 1.47 3.48 4.85 1.52 3.19 4.54 1.59 2.85 4.19 1.67 2.50
7.00 5.99 1.41 4.23 5.63 1.46 3.86 5.30 1.50 3.53 5.00 1.55 3.23 4.70 1.63 2.88 4.33 1.71 2.53
8.00 6.17 1.46 4.24 5.80 1.50 3.86 5.45 1.55 3.52 5.14 1.60 3.22 4.83 1.68 2.88 4.46 1.76 2.53
9.00 6.35 1.47 4.31 5.95 1.52 3.93 5.60 1.56 3.58 5.27 1.61 3.27 4.96 1.69 2.93 4.58 1.78 2.58
10.00 6.59 1.49 4.41 6.17 1.54 4.01 5.80 1.59 3.65 5.45 1.64 3.33 5.14 1.72 2.99 4.75 1.80 2.63
11.00 6.77 1.51 4.49 6.34 1.55 4.08 5.95 1.60 3.71 5.59 1.65 3.38 5.27 1.73 3.04 4.88 1.82 2.68
12.00 6.93 1.53 4.53 6.48 1.58 4.11 6.07 1.63 3.73 5.70 1.68 3.40 5.38 1.76 3.06 4.99 1.85 2.70

13.00 7.05 1.54 4.57 6.59 1.59 4.14 6.17 1.64 3.76 5.79 1.69 3.43 5.47 1.77 3.08 5.08 1.86 2.72
14.00 7.23 1.55 4.65 6.75 1.60 4.21 6.31 1.65 3.82 5.92 1.70 3.48 5.60 1.79 3.13 5.20 1.88 2.77
15.00 7.32 1.56 4.69 6.83 1.61 4.24 6.38 1.66 3.85 5.97 1.71 3.49 5.66 1.80 3.15 5.26 1.89 2.79

16.00 7.50 1.58 4.76 6.99 1.63 4.30 6.53 1.68 3.90 6.11 1.73 3.54 5.79 1.81 3.19 5.39 1.90 2.83
17.00 7.60 1.58 4.80 7.07 1.63 4.33 6.60 1.68 3.92 6.17 1.74 3.55 5.85 1.82 3.21 5.45 1.91 2.85

Note: The inlet/outlet water temperature difference is 5°C.

Heating

Ambient temp.(℃)

-10 -6 -2 2 7 10 13
Hot
water
outlet
Capacity

Capacity

Capacity

Capacity

Capacity

Capacity

Capacity
Power

Power

Power

Power

Power

Power

Power
COP

COP

COP

COP

COP

COP

COP
temp.

(℃) kW kW W/W kW kW W/W kW kW W/W kW kW W/W kW kW W/W kW kW W/W kW kW W/W


40.00 3.41 1.06 3.21 4.26 1.21 3.53 5.02 1.34 3.74 5.58 1.46 3.82 6.06 1.54 3.94 6.79 1.63 4.17 7.81 1.76 4.44

41.00 3.30 1.09 3.04 4.13 1.23 3.35 4.87 1.37 3.55 5.42 1.49 3.64 5.89 1.57 3.76 6.59 1.66 3.97 7.57 1.80 4.21
42.00 3.21 1.11 2.90 4.02 1.26 3.19 4.74 1.40 3.39 5.28 1.52 3.47 5.75 1.60 3.59 6.42 1.70 3.78 7.36 1.83 4.02
43.00 3.13 1.13 2.77 3.93 1.28 3.06 4.64 1.43 3.25 5.17 1.55 3.33 5.64 1.63 3.45 6.28 1.73 3.63 7.19 1.87 3.84

44.00 3.07 1.15 2.66 3.86 1.31 2.94 4.56 1.46 3.13 5.09 1.58 3.21 5.56 1.67 3.33 6.18 1.77 3.50 7.05 1.91 3.70
45.00 3.03 1.18 2.57 3.81 1.34 2.85 4.50 1.49 3.03 5.03 1.62 3.12 5.50 1.70 3.24 6.11 1.80 3.39 6.96 1.95 3.58
46.00 2.97 1.19 2.50 3.74 1.35 2.77 4.43 1.50 2.95 4.95 1.63 3.04 5.42 1.72 3.16 6.00 1.82 3.30 6.83 1.97 3.48

47.00 2.88 1.21 2.37 3.63 1.38 2.64 4.31 1.53 2.81 4.82 1.66 2.90 5.28 1.75 3.02 5.84 1.86 3.15 6.64 2.00 3.31
48.00 2.77 1.25 2.21 3.49 1.42 2.46 4.15 1.58 2.63 4.65 1.71 2.71 5.10 1.80 2.83 5.63 1.91 2.94 6.38 2.07 3.09
49.00 2.61 1.30 2.01 3.31 1.48 2.24 3.93 1.64 2.40 4.41 1.78 2.48 4.84 1.88 2.58 5.34 1.99 2.68 6.04 2.15 2.81
50.00 2.45 1.36 1.79 3.10 1.55 2.00 3.69 1.72 2.14 4.14 1.87 2.21 4.55 1.97 2.31 5.01 2.09 2.40 5.66 2.26 2.51

Note: The inlet/outlet water temperature difference is 5°C.

20
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

MGC-V7W/D2N1
Cooling
Ambient temp.(℃)
21.00 25.00 30.00 35.00 40.00 46.00
Chilled
water
outlet
Capacity

Capacity

Capacity

Capacity

Capacity

Capacity
Power

Power

Power

Power

Power

Power
EER

EER

EER

EER

EER

EER
temp.

W/
(℃) kW kW W/W kW kW kW kW W/W kW kW W/W kW kW W/W kW kW W/W
W
5.00 7.84 1.98 3.95 7.38 2.04 3.61 6.96 2.11 3.31 6.58 2.17 3.03 6.17 2.28 2.70 5.67 2.39 2.37
6.00 8.10 2.01 4.03 7.62 2.07 3.67 7.18 2.14 3.36 6.78 2.21 3.08 6.36 2.32 2.75 5.86 2.43 2.41
7.00 8.38 2.05 4.08 7.88 2.12 3.72 7.42 2.18 3.40 7.00 2.25 3.11 6.57 2.36 2.78 6.06 2.48 2.44
8.00 8.64 2.12 4.09 8.12 2.18 3.72 7.63 2.25 3.40 7.20 2.32 3.11 6.76 2.43 2.78 6.24 2.56 2.44
9.00 8.89 2.14 4.16 8.34 2.20 3.79 7.84 2.27 3.45 7.38 2.34 3.15 6.94 2.46 2.83 6.42 2.58 2.49
10.00 9.22 2.17 4.26 8.64 2.23 3.87 8.12 2.30 3.52 7.64 2.38 3.22 7.19 2.49 2.88 6.65 2.62 2.54
11.00 9.48 2.19 4.33 8.88 2.26 3.93 8.33 2.33 3.58 7.83 2.40 3.26 7.38 2.52 2.93 6.83 2.64 2.58
12.00 9.70 2.22 4.37 9.07 2.29 3.96 8.50 2.36 3.60 7.98 2.43 3.28 7.54 2.56 2.95 6.99 2.68 2.60
13.00 9.87 2.24 4.41 9.23 2.31 4.00 8.64 2.38 3.63 8.10 2.45 3.30 7.66 2.58 2.97 7.11 2.70 2.63
14.00 10.12 2.25 4.49 9.45 2.32 4.06 8.84 2.40 3.69 8.28 2.47 3.35 7.83 2.59 3.02 7.28 2.72 2.67
15.00 10.25 2.27 4.52 9.56 2.34 4.09 8.93 2.41 3.71 8.36 2.48 3.37 7.92 2.61 3.04 7.37 2.74 2.69
16.00 10.50 2.29 4.59 9.79 2.36 4.15 9.14 2.43 3.76 8.55 2.51 3.41 8.10 2.63 3.08 7.54 2.76 2.73

17.00 10.64 2.30 4.63 9.90 2.37 4.18 9.24 2.44 3.78 8.63 2.52 3.43 8.19 2.65 3.10 7.64 2.78 2.75

Note: The inlet/outlet water temperature difference is 5°C.

Heating

Ambient temp.(℃)

-10 -6 -2 2 7 10 13
Hot
water
outlet
Capacity

Capacity

Capacity

Capacity

Capacity

Capacity

Capacity
Power

Power

Power

Power

Power

Power

Power
COP

COP

COP

COP

COP

COP

COP
temp.

(℃) kW kW W/W kW kW W/W kW kW W/W kW kW W/W kW kW W/W kW kW W/W kW kW W/W


40.00 4.96 1.56 3.17 6.20 1.78 3.49 7.30 1.98 3.70 8.11 2.15 3.78 8.81 2.26 3.90 9.87 2.40 4.12 11.35 2.59 4.39
41.00 4.81 1.60 3.01 6.01 1.81 3.32 7.08 2.02 3.51 7.88 2.19 3.60 8.57 2.31 3.72 9.59 2.44 3.92 11.00 2.64 4.17
42.00 4.67 1.63 2.87 5.85 1.85 3.16 6.90 2.06 3.35 7.68 2.24 3.44 8.37 2.35 3.56 9.34 2.49 3.74 10.70 2.69 3.97
43.00 4.55 1.66 2.74 5.71 1.89 3.03 6.75 2.10 3.21 7.52 2.28 3.30 8.20 2.40 3.42 9.14 2.55 3.59 10.45 2.75 3.80
44.00 4.47 1.70 2.63 5.61 1.93 2.91 6.63 2.14 3.10 7.40 2.33 3.18 8.08 2.45 3.30 8.98 2.60 3.46 10.26 2.80 3.66
45.00 4.40 1.73 2.54 5.54 1.97 2.82 6.55 2.19 3.00 7.32 2.38 3.08 8.00 2.50 3.20 8.88 2.65 3.35 10.12 2.86 3.54
46.00 4.31 1.75 2.47 5.43 1.99 2.74 6.44 2.21 2.92 7.20 2.40 3.00 7.88 2.53 3.12 8.73 2.68 3.26 9.94 2.89 3.44
47.00 4.19 1.78 2.35 5.28 2.03 2.61 6.26 2.25 2.78 7.01 2.45 2.87 7.68 2.58 2.98 8.50 2.73 3.11 9.65 2.95 3.27
48.00 4.02 1.84 2.19 5.08 2.09 2.43 6.03 2.32 2.60 6.76 2.52 2.68 7.41 2.65 2.79 8.19 2.81 2.91 9.28 3.04 3.06
49.00 3.80 1.91 1.99 4.81 2.17 2.22 5.72 2.41 2.37 6.42 2.62 2.45 7.04 2.76 2.55 7.76 2.92 2.65 8.79 3.16 2.78

50.00 3.56 2.01 1.77 4.50 2.28 1.98 5.36 2.53 2.12 6.02 2.75 2.19 6.62 2.90 2.29 7.28 3.07 2.37 8.23 3.32 2.48

Note: The inlet/outlet water temperature difference is 5°C.

21
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

MGC-V10W/D2N1
Cooling
Ambient temp.(℃)
21.00 25.00 30.00 35.00 40.00 46.00
Chilled
water
outlet
Capacity

Capacity

Capacity

Capacity

Capacity

Capacity
Power

Power

Power

Power

Power

Power
EER

EER

EER

EER

EER

EER
temp.

W/
(℃) kW kW W/W kW kW kW kW W/W kW kW W/W kW kW W/W kW kW W/W
W
5.00 11.20 2.60 4.31 10.54 2.68 3.94 9.95 2.76 3.60 9.40 2.85 3.30 8.81 2.99 2.95 8.10 3.14 2.58
6.00 11.57 2.64 4.39 10.89 2.72 4.00 10.26 2.80 3.66 9.69 2.89 3.35 9.09 3.04 2.99 8.37 3.19 2.63
7.00 11.98 2.69 4.45 11.26 2.78 4.06 10.60 2.86 3.70 10.00 2.95 3.39 9.39 3.10 3.03 8.66 3.25 2.66
8.00 12.35 2.77 4.45 11.59 2.86 4.06 10.91 2.95 3.70 10.28 3.04 3.38 9.66 3.19 3.03 8.92 3.35 2.66
9.00 12.70 2.80 4.53 11.91 2.89 4.13 11.19 2.98 3.76 10.54 3.07 3.44 9.92 3.22 3.08 9.16 3.38 2.71
10.00 13.18 2.84 4.64 12.35 2.93 4.22 11.60 3.02 3.84 10.91 3.11 3.50 10.28 3.27 3.14 9.51 3.43 2.77
11.00 13.54 2.87 4.72 12.68 2.96 4.29 11.90 3.05 3.90 11.18 3.14 3.56 10.54 3.30 3.19 9.76 3.47 2.82
12.00 13.85 2.91 4.76 12.96 3.00 4.32 12.15 3.09 3.92 11.41 3.19 3.57 10.77 3.35 3.21 9.98 3.52 2.84
13.00 14.10 2.94 4.80 13.18 3.03 4.36 12.34 3.12 3.96 11.58 3.22 3.60 10.94 3.38 3.24 10.15 3.55 2.86
14.00 14.45 2.96 4.89 13.49 3.05 4.43 12.62 3.14 4.02 11.83 3.24 3.65 11.19 3.40 3.29 10.40 3.57 2.91
15.00 14.64 2.97 4.93 13.66 3.06 4.46 12.76 3.16 4.04 11.95 3.25 3.67 11.32 3.42 3.31 10.52 3.59 2.93
16.00 15.00 3.00 5.00 13.98 3.09 4.52 13.05 3.19 4.09 12.21 3.29 3.72 11.58 3.45 3.35 10.78 3.62 2.97

17.00 15.19 3.01 5.04 14.15 3.11 4.55 13.20 3.20 4.12 12.33 3.30 3.73 11.71 3.47 3.37 10.91 3.64 3.00

Note: The inlet/outlet water temperature difference is 5°C.

Heating

Ambient temp.(℃)

-10 -6 -2 2 7 10 13
Hot
water
outlet
Capacity

Capacity

Capacity

Capacity

Capacity

Capacity

Capacity
Power

Power

Power

Power

Power

Power

Power
COP

COP

COP

COP

COP

COP

COP
temp.

(℃) kW kW W/W kW kW W/W kW kW W/W kW kW W/W kW kW W/W kW kW W/W kW kW W/W


40.00 6.82 1.96 3.47 8.53 2.23 3.82 10.04 2.48 4.05 11.15 2.70 4.14 12.12 2.84 4.27 13.57 3.01 4.51 15.61 3.25 4.80

41.00 6.61 2.00 3.30 8.27 2.28 3.63 9.74 2.53 3.85 10.83 2.75 3.94 11.79 2.90 4.07 13.18 3.07 4.29 15.13 3.32 4.56
42.00 6.42 2.05 3.14 8.04 2.32 3.46 9.48 2.58 3.67 10.56 2.81 3.76 11.50 2.96 3.89 12.84 3.13 4.10 14.71 3.38 4.35
43.00 6.26 2.09 3.00 7.86 2.37 3.31 9.28 2.64 3.52 10.34 2.86 3.61 11.28 3.02 3.74 12.56 3.20 3.93 14.37 3.45 4.16

44.00 6.14 2.13 2.88 7.71 2.42 3.19 9.12 2.69 3.39 10.18 2.92 3.48 11.11 3.08 3.61 12.35 3.26 3.79 14.11 3.52 4.00
45.00 6.05 2.17 2.78 7.61 2.47 3.08 9.01 2.74 3.28 10.07 2.98 3.37 11.00 3.14 3.50 12.21 3.33 3.67 13.92 3.59 3.87
46.00 5.93 2.20 2.70 7.47 2.49 3.00 8.85 2.77 3.19 9.90 3.01 3.29 10.84 3.17 3.42 12.01 3.36 3.57 13.66 3.63 3.76

47.00 5.76 2.24 2.57 7.26 2.54 2.85 8.61 2.83 3.05 9.65 3.07 3.14 10.56 3.23 3.27 11.68 3.43 3.41 13.27 3.70 3.58
48.00 5.53 2.31 2.40 6.98 2.62 2.66 8.29 2.91 2.85 9.30 3.17 2.94 10.19 3.33 3.06 11.25 3.53 3.19 12.76 3.81 3.35
49.00 5.23 2.40 2.18 6.61 2.73 2.43 7.86 3.03 2.60 8.82 3.29 2.68 9.68 3.47 2.79 10.67 3.67 2.91 12.08 3.97 3.05

50.00 4.89 2.52 1.94 6.19 2.86 2.16 7.37 3.18 2.32 8.28 3.46 2.40 9.10 3.64 2.50 10.01 3.86 2.60 11.32 4.17 2.72

Note: The inlet/outlet water temperature difference is 5°C.

22
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

MGC-V12W/D2RN1

Cooling
Ambient temp.(℃)
21.00 25.00 30.00 35.00 40.00 46.00
Chilled
water
outlet
Capacity

Capacity

Capacity

Capacity

Capacity

Capacity
Power

Power

Power

Power

Power

Power
EER

EER

EER

EER

EER

EER
temp.

W/
(℃) kW kW W/W kW kW kW kW W/W kW kW W/W kW kW W/W kW kW W/W
W
5.00 12.54 2.98 4.21 11.81 3.07 3.85 11.14 3.16 3.52 10.53 3.26 3.23 9.86 3.42 2.88 9.08 3.60 2.52
6.00 12.96 3.02 4.29 12.19 3.12 3.91 11.49 3.21 3.58 10.85 3.31 3.28 10.18 3.48 2.93 9.38 3.65 2.57
7.00 13.41 3.08 4.35 12.61 3.18 3.96 11.87 3.28 3.62 11.20 3.38 3.31 10.52 3.55 2.96 9.70 3.73 2.60
8.00 13.83 3.18 4.35 12.99 3.28 3.96 12.22 3.38 3.62 11.51 3.48 3.31 10.82 3.66 2.96 9.99 3.84 2.60
9.00 14.22 3.21 4.43 13.34 3.31 4.03 12.54 3.41 3.68 11.80 3.52 3.36 11.11 3.69 3.01 10.26 3.88 2.65
10.00 14.76 3.26 4.53 13.83 3.36 4.12 12.99 3.46 3.75 12.22 3.57 3.42 11.51 3.75 3.07 10.65 3.93 2.71
11.00 15.17 3.29 4.61 14.20 3.39 4.19 13.32 3.49 3.81 12.52 3.60 3.48 11.81 3.78 3.12 10.94 3.97 2.75
12.00 15.52 3.34 4.65 14.52 3.44 4.22 13.60 3.55 3.84 12.77 3.66 3.49 12.06 3.84 3.14 11.18 4.03 2.77
13.00 15.79 3.36 4.70 14.76 3.47 4.26 13.82 3.57 3.87 12.97 3.69 3.52 12.25 3.87 3.17 11.37 4.06 2.80
14.00 16.19 3.39 4.78 15.11 3.49 4.33 14.14 3.60 3.93 13.25 3.71 3.57 12.54 3.90 3.22 11.65 4.09 2.85

15.00 16.39 3.40 4.82 15.29 3.51 4.36 14.29 3.62 3.95 13.38 3.73 3.59 12.67 3.92 3.24 11.79 4.11 2.87
16.00 16.80 3.44 4.89 15.66 3.54 4.42 14.62 3.65 4.00 13.68 3.77 3.63 12.97 3.95 3.28 12.07 4.15 2.91
17.00 17.02 3.45 4.93 15.85 3.56 4.45 14.78 3.67 4.03 13.81 3.78 3.65 13.11 3.97 3.30 12.22 4.17 2.93

Note: The inlet/outlet water temperature difference is 5°C.

Heating
Ambient temp.(℃)

-10 -6 -2 2 7 10 13
Hot
water
outlet
Capacity

Capacity

Capacity

Capacity

Capacity

Capacity

Capacity
Power

Power

Power

Power

Power

Power

Power
COP

COP

COP

COP

COP

COP

COP
temp.

(℃) kW kW W/W kW kW W/W kW kW W/W kW kW W/W kW kW W/W kW kW W/W kW kW W/W


40.00 7.63 2.33 3.28 9.54 2.65 3.61 11.22 2.94 3.82 12.47 3.19 3.90 13.55 3.36 4.03 15.18 3.56 4.26 17.46 3.85 4.53
41.00 7.39 2.38 3.11 9.25 2.70 3.43 10.89 3.00 3.63 12.12 3.26 3.72 13.18 3.43 3.84 14.74 3.64 4.05 16.92 3.93 4.31

42.00 7.17 2.42 2.96 8.99 2.75 3.26 10.60 3.06 3.46 11.81 3.33 3.55 12.86 3.50 3.67 14.35 3.71 3.87 16.45 4.01 4.10
43.00 7.00 2.47 2.83 8.78 2.81 3.13 10.37 3.12 3.32 11.56 3.39 3.41 12.61 3.57 3.53 14.05 3.79 3.71 16.07 4.09 3.93
44.00 6.87 2.52 2.72 8.63 2.87 3.01 10.20 3.19 3.20 11.38 3.46 3.29 12.42 3.65 3.41 13.81 3.86 3.57 15.78 4.17 3.78
45.00 6.77 2.58 2.63 8.51 2.93 2.91 10.07 3.25 3.10 11.25 3.53 3.18 12.30 3.72 3.31 13.65 3.94 3.46 15.56 4.26 3.65
46.00 6.63 2.60 2.55 8.36 2.96 2.83 9.90 3.28 3.01 11.07 3.57 3.10 12.12 3.76 3.22 13.42 3.98 3.37 15.28 4.30 3.55
47.00 6.44 2.65 2.43 8.12 3.01 2.69 9.63 3.35 2.88 10.78 3.64 2.96 11.81 3.83 3.08 13.06 4.06 3.22 14.84 4.39 3.38
48.00 6.18 2.73 2.26 7.81 3.10 2.51 9.27 3.45 2.69 10.40 3.75 2.77 11.40 3.95 2.89 12.58 4.18 3.01 14.27 4.52 3.16
49.00 5.85 2.84 2.06 7.39 3.23 2.29 8.79 3.59 2.45 9.87 3.90 2.53 10.83 4.11 2.64 11.93 4.35 2.74 13.51 4.70 2.87
50.00 5.47 2.98 1.83 6.93 3.39 2.04 8.24 3.77 2.19 9.26 4.09 2.26 10.18 4.31 2.36 11.20 4.57 2.45 12.65 4.93 2.56

Note: The inlet/outlet water temperature difference is 5°C.

23
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

Cooling
MGC-V14W/D2RN1

Ambient temp.(℃)
21.00 25.00 30.00 35.00 40.00 46.00
Chilled
water
outlet
Capacity

Capacity

Capacity

Capacity

Capacity

Capacity
Power

Power

Power

Power

Power

Power
EER

EER

EER

EER

EER

EER
temp.

W/
(℃) kW kW W/W kW kW kW kW W/W kW kW W/W kW kW W/W kW kW W/W
W
5.00 13.99 3.43 4.07 13.18 3.54 3.72 12.43 3.65 3.41 11.75 3.76 3.12 11.01 3.95 2.79 10.13 4.15 2.44
6.00 14.47 3.49 4.15 13.61 3.60 3.78 12.83 3.71 3.46 12.11 3.82 3.17 11.36 4.01 2.83 10.46 4.21 2.48
7.00 14.97 3.56 4.21 14.07 3.67 3.83 13.25 3.78 3.50 12.50 3.90 3.21 11.74 4.10 2.87 10.82 4.30 2.52
8.00 15.43 3.67 4.21 14.49 3.78 3.83 13.63 3.90 3.50 12.85 4.02 3.20 12.08 4.22 2.86 11.15 4.43 2.52
9.00 15.87 3.70 4.29 14.89 3.82 3.90 13.99 3.93 3.56 13.18 4.06 3.25 12.40 4.26 2.91 11.46 4.47 2.56
10.00 16.47 3.76 4.38 15.44 3.87 3.99 14.50 3.99 3.63 13.64 4.12 3.31 12.85 4.32 2.97 11.88 4.54 2.62
11.00 16.93 3.79 4.46 15.85 3.91 4.05 14.87 4.03 3.69 13.98 4.16 3.36 13.18 4.37 3.02 12.20 4.58 2.66
12.00 17.32 3.85 4.50 16.20 3.97 4.08 15.18 4.09 3.71 14.26 4.22 3.38 13.46 4.43 3.04 12.48 4.65 2.68
13.00 17.63 3.88 4.54 16.47 4.00 4.12 15.43 4.12 3.74 14.47 4.25 3.40 13.67 4.46 3.06 12.69 4.69 2.71
14.00 18.07 3.91 4.62 16.87 4.03 4.19 15.78 4.15 3.80 14.79 4.28 3.45 13.99 4.50 3.11 13.00 4.72 2.75
15.00 18.30 3.93 4.66 17.07 4.05 4.22 15.95 4.17 3.82 14.94 4.30 3.47 14.15 4.52 3.13 13.15 4.74 2.77
16.00 18.75 3.97 4.73 17.48 4.09 4.27 16.32 4.22 3.87 15.27 4.35 3.51 14.47 4.56 3.17 13.47 4.79 2.81
17.00 18.99 3.99 4.77 17.68 4.11 4.30 16.50 4.24 3.89 15.42 4.37 3.53 14.63 4.59 3.19 13.64 4.81 2.83

Note: The inlet/outlet water temperature difference is 5°C.

Heating

Ambient temp.(℃)

-10 -6 -2 2 7 10 13
Hot
water
outlet
Capacity

Capacity

Capacity

Capacity

Capacity

Capacity

Capacity
Power

Power

Power

Power

Power

Power

Power
COP

COP

COP

COP

COP

COP

COP
temp.

(℃) kW kW W/W kW kW W/W kW kW W/W kW kW W/W kW kW W/W kW kW W/W kW kW W/W


40.00 8.56 2.66 3.22 10.70 3.02 3.54 12.59 3.36 3.75 13.99 3.65 3.83 15.20 3.84 3.96 17.03 4.07 4.18 19.58 4.40 4.45
41.00 8.29 2.71 3.05 10.37 3.08 3.36 12.22 3.43 3.57 13.59 3.72 3.65 14.79 3.92 3.77 16.54 4.16 3.98 18.98 4.49 4.23

42.00 8.05 2.77 2.91 10.09 3.15 3.21 11.90 3.50 3.40 13.25 3.80 3.49 14.43 4.00 3.61 16.10 4.24 3.80 18.46 4.58 4.03
43.00 7.86 2.83 2.78 9.86 3.21 3.07 11.64 3.57 3.26 12.97 3.88 3.35 14.15 4.08 3.47 15.76 4.33 3.64 18.03 4.67 3.86
44.00 7.70 2.88 2.67 9.68 3.28 2.95 11.44 3.64 3.14 12.77 3.96 3.23 13.94 4.17 3.35 15.50 4.41 3.51 17.70 4.77 3.71
45.00 7.59 2.94 2.58 9.55 3.34 2.86 11.30 3.71 3.04 12.63 4.04 3.13 13.80 4.25 3.25 15.32 4.51 3.40 17.46 4.87 3.59
46.00 7.44 2.97 2.51 9.37 3.38 2.78 11.11 3.75 2.96 12.42 4.08 3.05 13.59 4.29 3.17 15.06 4.55 3.31 17.14 4.91 3.49
47.00 7.22 3.03 2.38 9.11 3.44 2.64 10.81 3.83 2.82 12.10 4.16 2.91 13.25 4.38 3.03 14.66 4.64 3.16 16.65 5.01 3.32

48.00 6.94 3.12 2.22 8.76 3.55 2.47 10.40 3.94 2.64 11.66 4.28 2.72 12.79 4.51 2.84 14.12 4.78 2.95 16.01 5.16 3.10
49.00 6.56 3.25 2.02 8.29 3.69 2.25 9.86 4.10 2.41 11.07 4.46 2.48 12.15 4.69 2.59 13.39 4.97 2.69 15.16 5.37 2.82
50.00 6.14 3.41 1.80 7.77 3.87 2.01 9.25 4.30 2.15 10.39 4.68 2.22 11.42 4.92 2.32 12.56 5.22 2.41 14.20 5.64 2.52

Note: The inlet/outlet water temperature difference is 5°C.

24
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

MGC-V16W/D2RN1

Cooling
Ambient temp.(℃)
21.00 25.00 30.00 35.00 40.00 46.00
Chilled
water
outlet
Capacity

Capacity

Capacity

Capacity

Capacity

Capacity
Power

Power

Power

Power

Power

Power
EER

EER

EER

EER

EER

EER
temp.

W/
(℃) kW kW W/W kW kW kW kW W/W kW kW W/W kW kW W/W kW kW W/W
W
5.00 16.23 3.99 4.07 15.29 4.11 3.72 14.42 4.24 3.40 13.63 4.37 3.12 12.77 4.59 2.78 11.75 4.82 2.44
6.00 16.78 4.05 4.14 15.79 4.18 3.78 14.88 4.31 3.46 14.05 4.44 3.16 13.18 4.66 2.83 12.14 4.89 2.48
7.00 17.37 4.13 4.20 16.32 4.26 3.83 15.37 4.39 3.50 14.50 4.53 3.20 13.62 4.76 2.86 12.55 4.99 2.51
8.00 17.90 4.26 4.20 16.81 4.39 3.83 15.82 4.53 3.49 14.91 4.67 3.19 14.01 4.90 2.86 12.93 5.14 2.51
9.00 18.41 4.30 4.28 17.27 4.43 3.90 16.23 4.57 3.55 15.28 4.71 3.24 14.38 4.95 2.91 13.29 5.19 2.56
10.00 19.11 4.36 4.38 17.91 4.50 3.98 16.81 4.64 3.63 15.82 4.78 3.31 14.90 5.02 2.97 13.78 5.27 2.61
11.00 19.64 4.41 4.46 18.39 4.54 4.05 17.25 4.68 3.68 16.21 4.83 3.36 15.29 5.07 3.02 14.16 5.32 2.66
12.00 20.09 4.47 4.49 18.79 4.61 4.08 17.61 4.75 3.71 16.54 4.90 3.38 15.61 5.14 3.03 14.47 5.40 2.68
13.00 20.45 4.51 4.54 19.11 4.65 4.11 17.89 4.79 3.74 16.79 4.94 3.40 15.86 5.19 3.06 14.72 5.45 2.70
14.00 20.96 4.54 4.62 19.57 4.68 4.18 18.30 4.82 3.79 17.15 4.97 3.45 16.23 5.22 3.11 15.08 5.48 2.75

15.00 21.23 4.56 4.65 19.80 4.70 4.21 18.50 4.85 3.82 17.33 5.00 3.47 16.41 5.25 3.13 15.26 5.51 2.77
16.00 21.75 4.61 4.72 20.27 4.75 4.27 18.93 4.90 3.87 17.71 5.05 3.51 16.79 5.30 3.17 15.63 5.57 2.81
17.00 22.03 4.63 4.76 20.51 4.77 4.30 19.14 4.92 3.89 17.88 5.07 3.53 16.97 5.33 3.19 15.82 5.59 2.83

Note: The inlet/outlet water temperature difference is 5°C.

Heating
Ambient temp.(℃)

-10 -6 -2 2 7 10 13
Hot
water
outlet
Capacity

Capacity

Capacity

Capacity

Capacity

Capacity

Capacity
Power

Power

Power

Power

Power

Power

Power
COP

COP

COP

COP

COP

COP

COP
temp.

(℃) kW kW W/W kW kW W/W kW kW W/W kW kW W/W kW kW W/W kW kW W/W kW kW W/W


40.00 9.93 3.03 3.27 12.41 3.45 3.60 14.60 3.83 3.81 16.22 4.16 3.89 17.63 4.38 4.02 19.74 4.65 4.25 22.71 5.02 4.52
41.00 9.61 3.10 3.10 12.03 3.52 3.42 14.17 3.91 3.62 15.76 4.25 3.71 17.15 4.47 3.83 19.17 4.74 4.04 22.01 5.12 4.30
42.00 9.33 3.16 2.95 11.70 3.59 3.26 13.79 3.99 3.46 15.36 4.34 3.54 16.73 4.56 3.67 18.67 4.84 3.86 21.40 5.23 4.09
43.00 9.11 3.22 2.82 11.43 3.66 3.12 13.49 4.07 3.31 15.04 4.43 3.40 16.40 4.66 3.52 18.27 4.94 3.70 20.90 5.33 3.92
44.00 8.93 3.29 2.71 11.22 3.74 3.00 13.26 4.15 3.19 14.80 4.52 3.28 16.16 4.75 3.40 17.97 5.04 3.57 20.52 5.44 3.77
45.00 8.80 3.36 2.62 11.07 3.82 2.90 13.10 4.24 3.09 14.64 4.61 3.18 16.00 4.85 3.30 17.76 5.14 3.45 20.25 5.55 3.65
46.00 8.63 3.39 2.55 10.87 3.85 2.82 12.88 4.28 3.01 14.40 4.65 3.10 15.76 4.90 3.22 17.46 5.19 3.36 19.87 5.61 3.54
47.00 8.37 3.46 2.42 10.56 3.93 2.69 12.53 4.37 2.87 14.03 4.75 2.96 15.37 5.00 3.08 16.99 5.30 3.21 19.31 5.72 3.38
48.00 8.04 3.56 2.26 10.16 4.05 2.51 12.06 4.50 2.68 13.52 4.89 2.77 14.83 5.15 2.88 16.37 5.46 3.00 18.56 5.89 3.15
49.00 7.61 3.70 2.05 9.62 4.21 2.28 11.43 4.68 2.44 12.83 5.08 2.52 14.09 5.35 2.63 15.52 5.67 2.74 17.57 6.13 2.87
50.00 7.12 3.89 1.83 9.01 4.42 2.04 10.72 4.91 2.18 12.05 5.34 2.26 13.24 5.62 2.36 14.57 5.96 2.45 16.46 6.43 2.56

Note: The inlet/outlet water temperature difference is 5°C.

25
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

11. Operation Limits


COOLING
C

46
O U T SID E A IR T EM PERAT U RE

35

20

-5

-10 45 7 15 20 C
DELIVERY WATER TEMPERATURE
HEATING
C

27
O U T SID E A IR T EM PERAT U RE

20

-3

-15

30 35 45 55 C
DELIVERY WATER TEMPERATURE

a) Ethylene Glycol Solutions

Water and ethylene glycol solutions used as a thermal vector in the place of water reduce the performance
of the unit. Multiply the performance figures by the values given in the following table.

Freezing point (°C)


0 -5 -10 -15 -20 -25
Percentage of ethylene glycol in weight
0 12% 20% 28% 35% 40%
cPf 1 0.98 0.97 0.965 0.96 0.955
cQ 1 1.02 1.04 1.075 1.11 1.14
cdp 1 1.07 1.11 1.18 1.22 1.24
cPf: correction factor of heating/cooling capacity
cQ: correction factor of flow rate
cdp: correction factor of pressure drop

26
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

Note:
1. During winter leaving the unit unused, please drain water out completely from unit if no anti-freeze were
charged into pipeline, or keep power on (at standby or off status) and ensure that water is contained inside
of unit.
2. When ambient temperature lower 5℃, running cooling mode must be charged antifreeze. Refers to upper
parameters for the charged volume.

b) Fouling Factors
The performance data given refer to conditions with clean evaporator plates (fouling factor=1). For different
fouling factors, multiply the figures in the performance tables by the coefficient given in the following table.
Fouling factors Evaporator
2
(m °C/W) f1 fk1 fx1
-5
4.4×10 - - -
-4
0.86×10 0.96 0.99 0.99
-4
1.72×10 0.93 0.98 0.98
f1 correction factor of capacity
fk1 power input correction factor of compressor
fx1 correction factor of total power input

27
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

12. Water Pressure Drop


MGC-V5W/D2N1, MGC-V7W/D2N1

MGC-V10W/D2N1

Heat exchanger pressure drop (water side) 研发提供

28
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

MGC-V12W/D2RN1

MGC-V14W/D2RN1

29
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

MGC-V16W/D2RN1

30
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

13. Sound Level

O u td o o r U n it

M ic r o

1 .4 m

1 .0 m

Model Noise level (dB(A))


MGC-V5W/D2N1 58
MGC-V7W/D2N1 58
MGC-V10W/D2N1 59
MGC-V12W/D2RN1 59
MGC-V14W/D2RN1 60
MGC-V16W/D2RN1 60
Note:
1).High/low air flow of outdoor fan motor.
2). It is tested 1 meter away from the machine in a semi-anechoic room (sound pressure).

31
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

14. Exploded View

MGC-V5W/D2N1, MGC-V7W/D2N1

32
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

28.4

28.5 28.6
28.7 28.3
28.1 28.2

No. Part Name Quantity No. Part Name Quantity


1 Welded parts of fixed plate 1 19 Discharge temp sensor ass'y 1
2 Welded part of support 1 20 Liquid receiver ass'y 1
3 Bearing base 1 20.1 Accumulator cylinder 1
4 Fixed plate of inlet pipe 1 20.2 Pressure controller 1
5 Support bar of check valve 1 21 Drain-pipe ass'y of plate heat exchanger 1
6 Partition ass'y 1 22 Expansion vessel 1
7 Compressor 1 23 Clamp 1
8 Compressor electric heater 1 24 Shielded pump ass'y 1
9 Support ass'y of compressor 1 25 DC motor 1
10 Base plate parts 1 26 Display cover ass'y 1
11 Drain pipe adapter 1 27 Display box ass'y 1
12 Hydraulic meter 1 28 Outdoor unit electric box ass'y 1
13 Pipe temp. sensor ass'y 1 28.1 PFC inductance 1
14 Outlet water pipe ass'y 1 28.2 Module board ass'y 1
14.1 Water charge valve 1 28.3 Outdoor main control board ass'y 1
14.2 Valve electric heater 1 28.4 Transformer 1
14.3 Safety valve 1 28.5 Wire joint 1
14.4 Water flow switch 1 28.6 Wire joint,6p 1
15 Inlet water pipe ass'y 1 28.7 Power supply board ass'y of outdoor unit 1
15.1 Exhaust valve 1 29 Top cover parts 1
16 Plate heat exchanger ass'y 1 30 Axial fan assy 1
16.1 Heat-exchanger electric heater 1 31 Front panel 1
17 EXV ass'y 1 32 Outlet grille ass'y 1
17.1 Liquid accumulator can 1 33 Condenser parts 1
17.2 Electronic expansion valve 1 34 Room temp sensor ass'y 1
18 4-way valve ass'y 1 35 Pipe temp.sensor ass'y 1
18.1 4-way valve suite 1 36 Front clapboard ass'y 1
18.1.1 4-way valve 1 37 Left supporting board 1
18.1.2 Solenoid 1 38 Motor bracket 1
18.2 Pressure controller 1 39 Rear net frame 1
18.3 Meter connector 1 40 Baffle ass'y 1

33
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

MGC-V10W/D2N1

34
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

25.6

25.9
25.1

25.2 25.7

25.3

25.8

25.4 25.5

No. Part Name Quantity No. Part Name Quantity


1 Right-front plate ass'y 1 21 Gas-liquid separator 1
2 Four-way valve parts 1 22 Differential pressure switch 1
2.1 Four-way valve ass'y 1 23 Hydraulic meter 1
2.2 Pressure switch 1 24 Display box ass'y 1
3 Welded parts of base 1 25 Outdoor electrical control box ass'y 1
4 Suction pipe ass'y 1 25.1 Module board ass'y 1
4.1 Pressure controller 1 25.2 Radiator 1
5 Accumulator ass'y 1 25.3 Terminal block, 3P 2
6 Fixed plate ass'y of compressor 1 25.4 Radiator 1
7 Compressor 1 25.5 Three phase bridge 1
8 EXV ass'y 1 25.6 Transformer 1
8.1 Electronic expansion valve 1 25.7 Electrolytic capacitor 2
8.2 Expansion valve wire(CAM-MD12GRSZ-5) 1 25.8 Wire joints,12P 1
9 Exhaust valve ass'y 1 25.9 Outdoor control board ass'y 1
9.1 Exhaust valve 1 26 Right back plate 1
10 Connection pipe ass'y 1 27 Inductance Box Ass'y 1
11 Base 1 27.1 PFC Inductor 2
12 Fixed plate of inlet/outlet pipe 1 28 Condenser ass'y 1
13 Connection pipe parts of water pump 1 29 Coaming ass'y 1
13.1 Water charge valve 1 30 Bracket ass'y, net 1
13.2 Safety valve 1 31 Installation plate of expansion tank 1
14 Drain pipe adapter 2 32 Top cover ass'y 1
15 Water pump 1 33 Expansion vessel 1
16 Coaming I 1 34 Rear-left supporting board 1
17 Plate heat exchanger ass'y 1 35 Motor bracket assembly 1
17.1 Electrical heater of plate heat exchanger 1 36 DC Motor 2
17.2 Plate heat exchanger 1 37 Axial fan 2
18 Rubber gasket 1 38 Front Panel 1
19 Coaming II 1 39 Net 2
20 Connection pipe ass'y of differential pressure valve 1 40 Handle 3
20.1 Electrical heater of differential pressure valve 1

35
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

MGC-V12W/D2RN1, MGC-V14W/D2RN1, MGC-V16W/D2RN1

36
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

25.4

25.9
25.1

25.5
25.2

25.3
25.6

25.10 25.8
25.7
25.11

No. Part Name Quantity No. Part Name Quantity


1 Right-front plate ass'y 1 22 Differential pressure switch 1
2 Four-way valve parts 1 23 Hydraulic meter 1
2.1 Four-way valve ass'y 1 24 Display box ass'y 1
2.2 Pressure switch 1 25 Outdoor electrical control box ass'y 1
3 Welded parts of base 1 25.1 Inverter module 1
4 Suction pipe ass'y 1 25.2 Radiator 1
4.1 Pressure controller 1 25.3 Three phase bridge 1
5 Accumulator ass'y 1 25.4 Aluminum electrolytic capacitors 2
6 Fixed plate ass'y of compressor 1 25.5 outdoor unit power supply board 1
7 Compressor 1 25.6 Resistance 2
8 EXV ass'y 1 25.7 AC contactor 1
8.1 Electronic expansion valve 1 25.8 Wire joints,14P 1
8.2 Expansion valve wire(CAM-MD12GRSZ-5) 1 25.9 Outdoor main control board ass'y 1
9 Exhaust valve ass'y 1 25.10 Wire joint, 2p 1
9.1 Exhaust valve 1 25.11 Terminal block, 3P 1
10 Connection pipe ass'y 1 26 Right back plate 1
11 Base 1 27 Inductance parts ass'y 1
12 Fixed plate of inlet/outlet pipe 1 27.1 Reactance 1
13 Connection pipe parts of water pump 1 28 Condenser ass'y 1
13.1 Water charge valve 1 29 Coaming ass'y 1
13.2 Safety valve 1 30 Bracket ass'y, net 1
14 Drain pipe adapter 2 31 Installation plate of expansion tank 1
15 Water pump 1 32 Top cover ass'y 1
16 Coaming I 1 33 Expansion vessel 1
17 Plate heat exchanger ass'y 1 34 Rear-left supporting board 1
17.1 Plate heat exchanger 1 35 Motor bracket assembly 1
17.2 Electrical heater of plate heat exchanger 1 36 DC Motor 2
18 Rubber gasket 1 37 Axial fan 2
19 Coaming II 1 38 Front Panel 1
20 Connection pipe ass'y of differential pressure valve 1 39 Net 2
20.1 Electrical heater of differential pressure valve 1 40 Handle 3
21 Gas-liquid separator 1

37
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

15. Installation
a) Installation of general information
General warning
1. These units have been designed to chilled and hot water and must be used in applications compatible with
their performance characteristics; these appliances are designed for residential or similar applications.
2. Incorrect installation, regulation and maintenance or improper use absolves the manufacturer from all
liability, whether contractual or otherwise, for damage to people, animals or things. Only those
applications specifically indicated in this list are permitted.
3. Read this manual carefully. All work must be carried out by qualified personnel in conformity with
legislation in force in the country concerned.
4. The guarantee is invalidated if the above instructions are not respected and if the unit is started up for the
first time without the presence of personnel authorized by the Company (where specified in the supply
contract) who should draw up a“ start-up” report.
5. The documentation supplied with the unit must be consigned to the owner who should keep it carefully for
future consultation in the event of maintenance or service.
6. All repair or maintenance work must be carried out by the Company’s Technical Service or qualified
personnel following the instructions in this manual. The air-conditioner must under no circumstances be
modified or tampered with as this may create situations of risk. Failure to observe this condition absolves
the manufacturer of all liability for resulting damage.

Fundamental safety rules


When operating equipment involving the use of electricity and water, a number of fundamental safety rules
must be observed, namely:

Prohibition
1. This appliance is not intended for use by persons (including children) with reduced physical, sensory
or mental capabilities, or lack of experience and knowledge, unless they have been given supervision
or instruction concerning use of the appliance by a person responsible for their safety.
2. Do not touch the unit with bare feet or with wet or damp parts of the body.
3. Do not carry out cleaning operations without first disconnecting the system from the electricity supply.
4. Do not modify safety or regulation devices without authorization and instructions from the manufacturer.
5. Do not pull, detach or twist the electrical cables coming from the unit, even when disconnected from the
mains electricity supply.
6. Do not open doors or panels providing access to the internal parts of the unit without first ensuring that the
mains switch is in the off position.
7. Do not introduce pointed objects through the air intake and outlet grills.
8. Do not dispose of, abandon or leave within reach of children packaging materials (cardboard, staples,
plastic bags, etc.) as they may represent a hazard.

Important
1. The chiller appliances are supplied without the main switch. The power supply to the unit must be
disconnected using a suitable main switch that must be supplied and installed by the installer.
2. Respect safety distances between the unit and other equipment or structures. Guarantee adequate space
for access to the unit for maintenance and/or service operations.
Power supply: the cross section of the electrical cables must be adequate for the power of the unit and the
power supply voltage must correspond with the value indicated on the respective units. All units must be
earthed in conformity with legislation in force in the country concerned.
3. Hydraulic connections should be carried out as indicated in the instructions to guarantee correct operation
of the unit. Empty the water circuit or add glycol if the unit is not used during the winter.
Handle the unit with the utmost care to avoid damage.

38
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

b) Installation of outdoor unit


Choice of installation site
Before installing the unit, agree with the customer the site where it will be installed, taking the following
points into consideration:
- check that the fixing points are adequate to support the weight of the unit.
- pay scrupulous respect to safety distances between the unit and other equipment or structures to ensure
that air entering the unit and discharged by the fans is free to circulate.

Positioning
Before handling the unit, check the capacity of the lifting equipment used, respecting the instructions on the
packaging.
To move the unit in the horizontal, make appropriate use of a lift truck or similar, bearing in mind the weight
distribution of the unit. To lift the unit, insert tubes long enough to allow positioning of the lifting slings and
safety pins in the feet on the unit.
To avoid the slings damaging the unit, place protection between the slings and the unit. Position the unit in
the site indicated by the customer. Place either a layer of rubber (min. thickness 10 mm) or vibration damper
feet (optional) between the base and support surface. Fix the unit, making sure it is level and that there is
easy access to hydraulic and electrical components. If the site of installation is exposed to strong winds, fix
the unit adequately to the support surface using tie rods if necessary. If a heat pump unit is being installed,
make sure the condensate is drained using the drain hose supplied as standard. Prevent leaves, branches
or snow from accumulating around the unit. These could reduce the efficiency of the unit.

39
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

c) Installation space (units: mm)


 Since the gravity center of the unit is not at its physical center, so please be careful when lifting it with a sling.
 Never hold the inlet of the outdoor unit to prevent it from deforming.
 Do not touch the fan with hands or other objects.
 Do not lean it more than 45℃, and do not lay it sidelong.
 Make concrete foundation according to the specifications of the outdoor units.
 Fasten the feet of this unit with bolts firmly to prevent it from collapsing in case of earthquake or strong wind.

>60cm

Fix with bolt

Single unit installation


(Wall or obstacle)
>300

Air inlet
>300 Maintain
channel
Air inlet >600
>2000

Air outlet

Parallel connect two units or above

>300
>600

>2000

Parallel connect the front with rear sides

>2000 >500 >3000 >3000 >300

All the pictures in this manual are for explanation purpose only. They may be slightly different from the air conditioner you
purchased (depend on model).The actual shape shall prevail.

40
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

d) Hydraulic connection
The choice and installation of components is the responsibility of the installer who should follow good
working practice and current legislation. Before connecting the pipes, make sure they do not contain stones,
sand, rust, or others which might damage the unit. Construction of a bypass is recommended to enable the
pipes to be washed through without having to disconnect the unit (see drain valves). The connection piping
should be supported in such a way as to avoid it weighing on the unit. It is recommended that the following
devices are installed in the water circuit of the evaporator. A hydraulic safety valve shall be mounted in water
system, which should open constantly.

1). Connecting drawing of pipeline system


For MGC-V5W/D2N1 & MGC-V7W/D2N1

Factory connections Installer connections 1 Pressure gauge


2 Vibration damper joint
9 13 3 Gate valve
4 Calibrating valve
15 1
6 5 Water flow switch
2 6 Thermometer
3
10 WATER INLET
1 11 T
7 Pump
8 Safety valve
13
7 14 9 Air vent
12 10 Expansion tank
8 5 1
6
11 Mesh filter
F 16 2 4 T 12 Auto-water replenishing
13 Temperature sensor
14 14 Drain/chemical washing valve
14 WATER OUTLET
15 Plate heat exchanger
16 Additional pump

For MGC-V10W/D2N1 ,MGC-V12W/D2RN1, MGC-V14W/D2RN1 & MGC-V16W/D2RN1

Factory Connections Site Connections


3

2 1
4
7
11

10 6 13 WATER INLET
A

5
9

8 7 14
11

10 12 F WATER OUTLET

9 9

1 Plate Heat Exchange 8 Safety Valve


2 Differential Pressure Switch 9 Drain/Chemical Washing Valve
3 Automatic Discharge Valve 10 Flexible Joint
4 Expansion Tank 11 Thermometer
5 Auto-watet replenishing 12 Calibrating Valve
6 Circulating Pump 13 Y-shaped Filter
7 Pressure Gauge 14 Water Flow Switch
41
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

If the installation requires a useful head higher than that obtained by installing a pump assembly and storage
tank, it is recommended that an additional pump is installed on the unit. Provided the additional pump
installed inside of unit, the pump must connected close to plate heat exchanger. Provided the pump installed
outside of unit, the pump shall be connected at water pipe’s outlet. The pump can be easily installed on the
unit by removing the pump connection pipe. Connect to terminal PL,PN on the electric panel.

Important
1) The chillers must be provided with a filling/top-up system connected to the return line and a drain cock in
the lowest part of the installation. Installations containing anti-freeze or covered by specific legislation
must be fitted with hydraulic disconnections.
2) The manufacturer is not liable for obstruction, breakage or noise resulting from the failure to install filters
or vibration dampers. Particular types of water used for filling or topping up must be treated with
appropriate treatment systems. For reference values, see the table.

e).Design of the store tank in the system

 kW is the unit for cooling capacity, L is the unit for (G) minimum water flow volume in the formula.
Comfortable type air conditioner
G= cooling capacity×2.6L
Process type cooling
G= cooling capacity×7.4L
 In certain occasion (especially in manufacture cooling process), for conforming the system water
content requirement, it’s necessary to mount a tank equipping with a cut-off baffle at the system to avoid
water short-circuit, Please see the following schemes:

Error Recommendation

Error Recommendation

f).Chilled water flow

Minimum chilled water flow


The minimum chilled water flow is shown in the below table.
If the system flow is less than the minimum unit flow rate, the evaporator flow can be recalculated, as shown
in the diagram.

42
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

For minimum chilled water flow rate For maximum chilled water flow rate
Evaporator
Evaporator

Recirculation
Recirculation

Maximum chilled water flow


The maximum chilled water flow is limited by the permitted pressure drop in the evaporator. It is provided in
the below table.
If the system flow is more than the maximum unit flow rate, bypass the evaporator as shown in the diagram
to obtain a lower evaporator flow rate.
Minimum and maximum water flow rates
Item 3
Water flow rate(m /h)
Model Minimum Maximum
MGC-V5W/D2N1 0.77 0.95
MGC-V7W/D2N1 1.08 1.32
MGC-V10W/D2N1 1.54 1.89
MGC-V12W/D2RN1 1.72 2.11
MGC-V14W/D2RN1 1.93 2.36
MGC-V16W/D2RN1 2.24 2.73

g). Design of expansion tank

If a closed expansion tank with its filled volume of air is too small, the system pressure will easily exceed the
maximum allowable pressure and cause water to discharge from the pressure relief valve, thus wasting
water. If the closed tank is too large, when the water temperature drops, the system pressure may decrease
to a level below the minimum allowable value and cause trouble in the air vent. Therefore, accurate sizing of
a closed expansion tank is essential.

For diaphragm expansion tanks, the minimum volume of the water tank, Vt, gal(m3),can be calculated by the
following formula, recommended by ASHRAE Handbook 1996, HVAC Systems and Equipment:

Vt=Vs v2/v1-1-3α(T2-T1)
1-p1/p2
T1=lower temperature,oF (℃)
T2=higher temperature, oF (℃)
Vs=volume of water in system, gal(m3)
p1=absolute pressure at lower temperature,psia(kPa abs.)
p2=absolute pressure at higher temperature,paia(kPa abs.)
v1,v2=specific volume of water at lower and higher temperature, respectively, ft3/lb(m3/kg)
α=linear coefficient of thermal expansion; for steel, α=6.5x10-6in./in·oF(1.2x10-5per ℃); for copper,
α=9.5x10-6in./in·oF(1.7x10-5per ℃)
In a chilled water system, the higher temperature T2 is the highest anticipated ambient temperature when

43
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

the chilled water system shuts down during summer. The lower temperature in a heating system is often the
ambient temperature at fill conditions(for example, 50 oF or 10℃).

h). Water quality control


When industrial water is used as chilled water, little furring may occur; however, well water or river water,
used as chilled water, may cause much sediment, such as furring, sand, and so on. Therefore, well water or
river water must be filtered and softened in softening water equipment before flowing into chilled water
system. If sand and clay settle in the evaporator, circulation of
chilled water may be blocked, and thus leading to freezing accidents; if hardness of chilled water is too high,
furring may occur easily, and the devices may be corroded. Therefore, the quality of chilled water should be
analyzed before being used, such as PH value, conductivity, concentration of chloride ion, concentration of
sulfide ion, and so on.

PH 6-8
Total hardness less than 50 ppm
Electrical conductivity less than 200 mV/cm (25°C)
Sulfide ion none
Chlorine ions less than 50 ppm
Ammonia ions none
Sulfate ion less than 50 ppm
Silicon less than 30 ppm
Total iron less than 0.3 ppm
Sodium ion No requirement
Calcium ion less than 50 ppm

Filling the installation


- Before filling, check that the installation drain cock is closed.
- Open all installation and terminal air vents.
- Open the gate valves.
- Begin filling, slowly opening the water filling cock outside the unit.
- When water begins to leak out of the terminal air vent valves, close them and continue filling until the
pressure gauge indicates a pressure of 1.5 bars.

Emptying the installation


- Before emptying, place the mains switch in the“off” position.
- Make sure the installation fill/top-up water cock is closed.
- Open the drain cock outside the unit and all the installation and terminal air vent valves.

44
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

Size and position of connections

For MGC-V5W/D2N1 & MGC-V7W/D2N1 model


water inlet
auto-water
replenishing orifice

security discharge

water outlet
D
C
F
B
G

A
Water outlet of plate heat exchanger E
H

A B C D E F G H Water Auto-water Security


Model
(mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) inlet/outlet (Ø) replenishing (Ø) discharge (Ø)
MGC-V5W/D2N1
70 106 230 362 108 161 76 119 R1 G1/2 G1/2
MGC-V7W/D2N1

For MGC-V10W/D2N1,MGC-V12W/D2RN1, MGC-V14W/D2RN1, MGC-V16W/D2RN1 model

auto-water
replenishing orifice

water outlet
water inlet security discharge
A
B
C
D

E
F

Water
A B C D E F Auto-water Security
Model inlet/outlet
(mm) (mm) (mm) (mm) (mm) (mm) replenishing (Ø) discharge (Ø)
(Ø)
MGC-V10W/D2N1
MGC-V12W/D2RN1
300 195 155 105 68 105 R5/4 G1/2 G1/2
MGC-V14W/D2RN1
MGC-V16W/D2RN1

Important
a) The installation must be filled to a pressure of between 1 and 2 bars.
b) It is recommended that this operation be repeated after the unit has been operating for a number of hours.
The pressure of the installation should be checked regularly and if it drops below 1 bar, the water content
should be topped-up.
c) Check the hydraulic tightness of joints.
d) An all-pole disconnection device which has at least 3mm separation distance in all pole and a residual
current device (RCD) with the rating of above 10mA shall be incorporated in the fixed wiring according to
the national rule the appliance shall be installed in accordance with national wiring regulations.
e) If the fluid in the circuit contains anti-freeze, it should not be allowed to drain freely as it is pollutant. It
should be collected for possible reuse. When draining after heat pump operation, take care as the water
may be hot (up to 50°).

45
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

i). Electrical connection


The unitary mini chillers leave the factory already wired, and require the installation of an omni polar thermal
overload switch, a lockable mains disconnecting switch for the connection to the mains power supply, and
the connection of the flow switch to the corresponding terminals. All the above operations must be carried
out by qualified personnel in compliance with the legislation in force.
For all electrical work, refer to the electrical wiring diagrams in this manual. You are also recommended to
check that the characteristics of the mains electricity supply are adequate for the absorptions indicated in the
electrical characteristics table below, also bearing in mind the possible use of other equipment at the same
time.

Important
 Power to the unit must be turned on only after installation work (hydraulic and electrical) has been
completed.
 All electrical connections must be carried out by qualified personnel in accordance with legislation in
force in the country concerned.
 Respect instructions for connecting phase, neutral and earth conductors.
 The power line should be fitted upstream with a suitable device to protect against short-circuits and
leakage to earth, isolating the installation from other equipment.
 Voltage must be within a tolerance of ±10% of the rated power supply voltage for the unit (for three
phase units, the unbalance between the phases must not exceed 3%).If these parameters are not
respected, contact the electricity supply company.
 For electrical connections, use double insulation cable in conformity with current legislation in the
country concerned.
 An omnipolar thermal overload switch and a lockable mains disconnecting switch, in compliance with
the CEI-EN standards (contact opening of at least 3mm), with adequate switching and residual
current protection capacity based on the electrical data table shown below, must be installed as near
as possible to the appliance.
 The devices on the unit must be lockable. An efficient earth connection is obligatory. Failure to earth
the appliance absolves the manufacturer of all liability for damage.
 Do not use water pipes to earth the unit.
Electrical Panel
The electrical panel is located inside the unit at the top of the technical compartment where the various
components of the refrigerant circuit are also to be found.
To access the electrical panel, remove the front panel of the unit by undoing the screws.

5/7kW 10~16kW

46
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

j) Electrical Power Connection

1) MGC-V5W/D2N1, MGC-V7W/D2N1

Power Cable
Power Supply
L
N
Outdoor units GND

Residual Current
CIrcuit-breaker

For the functional connection of the unit, bring the power supply cable to the electrical panel inside the unit
and connect it to terminals L-N and respecting the (L) phase, (N) neutral and earth in the case of
single phase units (220-240V~50Hz).

2) MGC-V10W/D2N1

L N GND 1 2 3 4 5 6 7 8 9 10 11

PUMP2 Remote alarm Remote shutdownRemote cooling/heating wire controller

L N GND

Residual Current
Circuit-breaker
L N GND
AC 220-240V 50Hz

NOTE: The outdoor units must be installed with an Residual Current Circuit-breaker near the power supply
and must be effectively earthed.

47
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

3) MGC-V12W/D2RN1, MGC-V14W/D2RN1, MGC-V16W/D2RN1

A B C N GND 1 2 3 4 5 6 7 8 9 10 11

PUMP2 Remote alarm Remote shutdown Remote cooling/heating wire controller

A B C N GND

Residual Current
Circuit-breaker
A B C N GND
AC 380-415V 50Hz
Auxiliary Connection
1) MGC-V5W/D2N1, MGC-V7W/D2N1

1 2 1 2 L 1
PUMP2 BOIL ON/OFF

L
220~240 V
N
L
220~240 V
N

AC CAN TACTOR

Addtitiona l pum p Reserved Switch

1.“PUMP2”wiring terminal supplies ON/OFF signals only. Standby water pump must be controlled by the AC
contactor.
2.“ON/OFF” wiring terminal L supplies 220V voltage.
The unit must be powered off when connecting the remote control switch.
When the remote control switch is closed, the unit is forced to shut down.

48
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

2) MGC-V10W/D2N1,MGC-V12W/D2RN1, MGC-V14W/D2RN1, MGC-V16W/D2RN1

a. Additional pump
Main control board

1 2

L
220-240V
N

L
220-240V
N A1

AC contactor
A2

Additional pump

“PUMP2” terminal only provides passive switching signal.


Additional water pump must be controlled by the AC contactor.

b. Remote alarm

Main control board

3 4

Remote alarm terminal only provides passive switching signal.


Current passing through the terminal interface should less than 1.5A, otherwise please use AC contactor to
control load indirectly.

c. Remote shutdown

5 6

SWITCH

If switch is closed, the unit will be stopped forcibly.


Under this circumstance, anti-frozen protection and other protection functions are still effective.
If switch breaks, unit can run normally according settings.

49
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

d. Remote cooling/heating

7 8

SWITCH 2
If switch 2 is closed, the unit will shift to heating mode forcibly;
If switch 2 breaks, the unit will shift to cooling mode forcibly.

Note:
● Remote shutdown and Remote cooling/heating is optional function.
● Choose this function by DIP switch SW4_1(SW3_1 for 12/14/16kW) on PCB board.
Factory default has no remote cooling/heating.
● When the remote control and wired controller used at the same time, the unit will carry out the last
command of arbitrary terminal.
● Remote shutdown has the highest priority. In the status of remote shutdown, other controllers can’t start
the unit.

e. Remote controller

9 10 11

P Q E

● The wired controller is optional.


● Please use 3-core shielded wire to connect the wired controller and the shielding layer must be
grounded.
● When connecting wired controller, outdoor unit control panel is mainly used for display which can check
parameters and inquiry, can’t be used to set mode and temperature..

The Specification of Power:


Type MGC-V5W/D2N1 MGC-V7W/D2N1 MGC-V10W/D2N1 MGC-V12W/D2RN1 MGC-V14W/D2RN1 MGC-V16W/D2RN1

Power(V/Ph/Hz)) 220~240/1/50 220~240/1/50 220~240/1/50 380~415/3/50 380~415/3/50 380~415/3/50


Circuit
25/20 30/25 40/35 30/25 30/25 30/25
breaker/fuse (A)
Power wire
3×2.5 3×2.5 3×4.0 5×3.0 5×3.0 5×3.0
(mm2)
Ground wire
2.5 2.5 4.0 2.5 2.5 2.5
(mm2)

Important
The power cord type designation is H07RN-F.
Connecting cable between indoor unit and outdoor unit shall be approved poly-chloroprene sheathed flexible
cord, type designation H07RN-F or heavier cord.
The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air
gap.

50
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

16. Checking and Starting Up the Unit


Preparing for first start up
Restarting after shutting down for long periods
The chiller must be started up for the first time by the Technical Service. Before starting up the chillers, make
sure that:
- All safety conditions have been respected.
- The chiller is adequately fixed to the surface it rests on.
- Functional distances have been respected.
- Hydraulic connections have been carried out as indicated in the manual.
- The water circuit is filled and vented. When draining after heat pump operation, take care as the water
may be hot.
- The water circuit valves are open.
- Electrical connections have been carried out correctly.
- Voltage is within a tolerance of 10% of the rated voltage for the unit.
- The unit is correctly earthed.
- All electrical and hydraulic connections are tight and have been completed correctly.
- Use grommet A for the electrical power cable and grommet B for the other external wires.

To complete the electrical connections:


- Remove the inspection panel by unscrewing the five screws. For example, MGC-V5W/D2N1 model.

51
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

1
3 2

se
t

3
To access the control panel, open the door:

-remove the screw 1 and screw 2;

-lift the door 3.

52
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

17. Running and Maintenance


a) Operating characteristics
Set point in cooling mode
(factory set) = 12°C, Hysteresis = 3°C.
The compressor starts with water temperatures above 12°C.
The compressor shuts down with water temperatures of less than 9°C.
Set point in heating mode
(factory set) = 40°C, Hysteresis = 4°C.
The compressor starts with water temperatures below 38°C.
The compressor shuts down with water temperatures above 42°C.
In the event of a temporary power failure, when power returns, the mode set previously will be retained in the
memory.

Compressor start up delay


Two functions prevent the compressor from starting up too frequently
- Minimum time since last start-up 300 seconds.

Pump
The electronic board includes a pump control output. The pump starts when the assembly is powered up
and at least 285 seconds before the compressor starts up and stops 120 seconds after the assembly shuts
down. After the first 120 seconds of pump operation when the water flow is at full speed, the water flow
alarm functions are activated (differential pressure switch and flow switch). With a pump connected to
terminals PL and PN on the installer terminal board.

Fan speed control


For correct operation of the unit with different outside temperatures, the microprocessor controls the fan
speed based on the pressure reading from the pressure probe, thus enabling heat exchange to be increased
and/or decreased, maintaining the condensing or evaporation temperature practically constant.
The fan functions independently of the compressor.

Frost prevention alarm


To prevent the water freezing and damaging the plate heat exchanger, the microprocessor shuts down the
compressor if the temperature measured by the heat exchanger outlet temperature sensor is less than 3°C.
The frost prevention temperature set point can be modified by an authorized service center only and only
after verifying that the water circuit contains antifreeze. Tripping of this alarm shuts down the compressor but
not the pump, which remains active. To reset normal functions, the outlet water temperature must rise to
more than +15°C. Reset is manual.

Water flow alarm


The microprocessor provides for management of a water flow alarm controlled by a differential pressure
switch fitted as standard on the appliance to be installed on the water delivery piping.
This safety device may trip after the first 120 seconds of pump operation when the water flow is up to speed.
Tripping of this alarm shuts down the compressor but not the pump, which remains active. To reset normal
functions, the alarm contact must be deactivated for at least 15 seconds.
When electrical current exceeds to setting value and condenser temperature over than 62°C, system will
shut down, but not returns to normal operation until the condenser temperature decreased less than 52°C.

53
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

b) Routine maintenance
Never perform any cleaning operations before having disconnected the unit from the mains power supply.
If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similarly
qualified manufacturer or its service agent or a similarly qualified.
Regular maintenance is fundamental to maintain the efficiency of the unit both in terms of operation and
energy consumption. The Technical Assistance Service maintenance plan must be observed, with an
annual service which includes the following operations and checks:
- Filling of the water circuit.
- Presence of air bubbles in the water circuit.
- Efficiency of safety devices.
- Power supply voltage.
- Power input.
- Tightness of electrical and hydraulic connections.
- Condition of the compressor contactor.
- Efficiency of the plate heat exchanger heater.
- Checking of operating pressure, superheating and sub cooling.
- Efficiency of compressor heater.
- Cleaning of finned coil (*).
- Cleaning of fan grills.
- Cleaning of condensate drain pan (if installed).
(*) For “Heat pump” appliances, the checks are to be performed quarterly.
For units installed near the sea, the intervals between maintenance should be halved.

c) Extraordinary maintenance
Never perform any cleaning operations before having disconnected the unit from the mains power supply.

Chemical washing
You are recommended to chemically wash the plate heat exchanger after every 3 years of operation.

Refrigerant gas content


The chillers are filled with R410a refrigerant gas and tested in the factory. In normal conditions, there should
be no need for the Technical Assistance Service to intervene to check the refrigerant gas. However, over
time, small leaks may develop at the joints leading to loss of refrigerant and draining of the circuit, causing
the unit to function poorly. In this case, the leaks of refrigerant must be identified and repaired and the
refrigerant circuit refilled. Proceed as follows:
- Empty and dry the entire refrigerant circuit using a vacuum pump connected to the low and high pressure
tap until the vacuum meter reads about 10Pa. Wait a couple of minutes and check that this value does not
rise to more than 200Pa.
- Connect the refrigerant gas cylinder or a filling cylinder to the low pressure line pressure gauge
connection.
- Fill with the quantity of refrigerant gas indicated on the rating plate of the unit.
- Always check the superheating and sub cooling values. In the nominal operating conditions for the
appliance, these should be between 5 and 10°C and between 4 and 8°C respectively.
- After a couple of hours of operation, check that the liquid indicator indicates circuit dry (dry-green).

Important
In the event of partial leaks, the circuit must be completely emptied before being refilled
The R410a refrigerant must only be filled in the liquid state. Operating conditions other than nominal
conditions may produce considerably different values.
Seal testing or identification of leaks must only be carried out using R410a refrigerant gas, checking with a
suitable leak detector.

54
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

Prohibition
1. The refrigerant circuit must not be filled with a refrigerant other than that indicated of specification.
2. The use of a different refrigerant may cause serious damage to the compressor.
3. Oxygen, acetylene or other inflammable or poisonous gases must never be used in the refrigerant circuit
as they may cause explosion or poisoning.
4. Oils other than those indicated on manual before must not be used. The use of different oils may cause
serious damage to the compressor.

d) Shutting down for long periods


If it is previewed not to use the machine for long periods
After deactivating the chiller:
-Make sure the model is in the power off model " ", or alternatively disconnect the unit from the power
supply.
-Make sure the remote control switch is closed (if present) .
-Close the water valves.

Important
If there is a possibility that the outside temperature may drop below zero, there is the risk of freezing.
The water circuit MUST BE EMPTIED AND SHUT OFF POWER (when draining after heat pump operation
take care as the water may be hot) or antifreeze must be added in the proportion recommended by the
manufacturer.

55
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

18. Controller
18.1 Standard controller
It is built-in with the chiller at the factory.
The front panel of the device functions as the user interface and is used to perform all operations relating to
the device.

11 ① ② ③ ④ ⑤ ⑥

17
23 22
⑧ 18
19

24 21
20

7.1 7.2

12 13 14 15 16

NO. Icon Description


① Outside heat source running icon(Reserved)
② Cooling mode icon
This icon will be constantly light when customers choose cooling mode.
③ Heating mode icon
This icon will be constantly light when customers choose heating mode.
④ Water pump mode icon
This icon will be constantly light when customers choose water pump mode.
⑤ Force cooling icon
This icon will be constantly light when customers choose force cooling mode.
⑥ Power off icon
This icon will be constantly light when customers choose Power off mode.
7.1 Clock icon, “:” flash once every 1s. It will display time when customers set the timer.

The last 2 digits of the nixie tube “ ” icon. If “ ” is constantly light, it will display the current
inlet water temperature. Its’unit is ℃ .When customers do the water temperature setting, icon will
7.2
display the setting water temperature. When checking, “ ” will display the result of checking. When
water heating is broken down or in protection, “ ” display the error code and protection code.
Clock icon

It will display when finish setting the clock and be extinguished when the clock setting work is done.
Timing on function icon

will flash when setting timing on. The icon will be constantly light when finish setting.
Timing off function icon

will flash when setting timing off. The icon will be constantly light when finish setting.
Breakdown light icon
11 When the unit is broken down or under protection, this icon will flash and will be off when malfunction
and protection are eliminated.
Compressor booting indicator icon
12 When booting the compressor, this icon will be constantly light. It will be off when the compressor is
shut down
E-heater booting indicator icon(Reserved)
13 When booting the external E-heater, this icon will be constantly light. It will be off when the external
E-heater is shut down.
Fan booting indicator icon
14
When booting the fan, this icon will be constantly light. It will be off when the fan is shut down.
Water pump booting indicator icon
15 When booting the water pump, this icon will be constantly light. It will be off when the water pump is
shut down.
16 Key freezing icon

56
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

When freezing the keys, this icon will be constantly light. It will be off when unfreezing keys.
Temperature unit icon
17 When the control panel displays temperature, this icon will be constantly light.
Current unit icon
18
When the control panel displays current, this icon will be constantly light.
Time format icon
19 The unit is 12-hour format. “ ”will be constantly light when it is forenoon.
“ ” will be constantly light when it is afternoon
Frequency unit icon
20
It will be constantly light when the control panel displays frequency of the compressor.
ON/OFF and OK button
21 1.Long press “ ” for 3S will power on or off the controller.
2.Press “ ” to confirm the former operation when finishing the setting work.
Mode choice function/Function choice/Back function button
1.Mode choice function. Choose operation mode.
2.Function choice. Long press it for 3s to enter function setting in the main interface.(Clock setting,
22 Timing on and timing off setting)
3.Back to the previous menu. Long press it for 3s to back to previous menu in the function setting
interface. Top menu is the main interface.
Up
23 1.(Value increase)
2.Forward to the previous interface.
Down
24 1.(Value decrease)
2.Backward to the next interface.

18.1.1 Control panel operation description

1) ON/OFF
The first time to powered on the unit, operation panel displays “OFF”. Long press “ ” for 3s, to unlock
“OFF” status and enter into standby status.
Power on: In the standby status, press “ ” to enter mode choice function. Press “ ” circularly
to choose one kind of “power on” mode, the mode icon will flicker at the moment. Press “ ” to confirm
the power on mode. The unit will run as the chosen mode when the mode icon will be constantly light.
Power off: Press “ ” in the main interface to enter mode choice function and the icon which indicate
the current mode will flicker. Press “ ” circularly to choose power off mode,
“ ” will flicker at this moment. Press “ ” button to confirm the power off mode. By this time, “ ”
will be constantly light and the unit stops.

2) Mode choice and temperature settings


Press “ ” in the main interface to enter mode choice function. The “Mode” icon will flicker. Click
“ ” circularly to choose a mode. The circulating order is “Cooling mode”→“Heating mode”→
“Water pump mode” →“Power off mode” → “Cooling mode. The chosen mode will flicker. Press
“ ”or “ ” to increase/decrease the temperature in the chosen mode.
Press “ ” to confirm power off mode and the set temperature. Mode icon will be constantly light and
the unit will run as the chosen mode. Press “ ” or “ ” in the main interface to increase/decrease the
temperature in the chosen mode.
3) Clock setting
Long press “ ” for 3s to enter function interface. “ ” clock icon will flicker. Press “ ” to
enter clock setting function. “ ” icon will be constantly light and the first 2 digits on nixie tube will flicker.
Press “ ” or “ ” to set minute. Press “ ” when finish setting and “ ” will be extinguished.

4) Timing setting
a. Timing on setting
① Long press “ ” for 3s to enter function interface. “ ” clock icon will flicker. Press “ ”again
to enter timing on function. “ ” will flicker and press “ ” to enter timing on setting.

57
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

② At this moment, last 2 digits of the nixie tube display “01” which means the first group setting begins.
Press “ ” to the next step.
③ By this time, mode icon will flicker and press “ ”to choose timing on mode. Press “ ” to confirm
your choice and go to the next step.
④ By this time, the last 2 digits of the nixie tube will flicker and press “ ” or “ ” to adjust temperature
and set the temperature of the inlet water. Press “ ” to confirm and move to the next step.
⑤ By this time, the first 2 digits of the nixie tube will flicker and press “ ” or “ ” to adjust time of timing
on. Press “ ” to confirm and switch to minute setting automatically. The last 2 digits of the nixie
tube will flicker and press “ ” or “ ” to adjust minute setting of timing on.(minimal unit of minute
adjustment: 15 minutes) .
⑥ Press “ ” to confirm. The first group setting is finished and “ ” will be constantly light.
When processing the second timing setting, repeat the 1-2 operation above. When the nixie tube displays
“01” and flicker, press“ ” or “ ” to choose the timing on group. When the nixie tube displays “ 02 ”
which means setting timing on function of the second group.
Refers the timing on setting operation of group 1 to set that of group 2.
● Long press “ ” for 3s to return to the previous interface to reset the parameter during setting clock
timing.

b. Timing off setting


① Long press “ ” for 3s in the main interface to enter function interface. Press “ ” circularly to
enter timing off function. “ ” will flicker and press “ ” to enter timing off setting.
② At this moment, the last 2 digits of the nixie tube display “01” which means the first group setting begins.
Press “ ” to the next step.
③ By this time, the first 2 digits of the nixie tube will flicker and press “ ” or “ ” to adjust time of
timing off. Press “ ” to confirm and switch to minute setting automatically. The last 2 digits of the
nixie tube will flicker and press “ ” or “ ” to adjust minute setting of timing off. Press “ ” to
confirm. The first group setting is finished and “ ” will be constantly light.
④ When processing timing setting of group 2, repeat the 1-2 operation above. When the nixie tube
displays “01” and flicker, press “ ” or “ ” to choose the timing off group. When the nixie tube
displays “02”which means setting timing off function of the second group.
Refers the timing off setting operation of group 1 to set that of group 2.

c. Cancel all timing on/off settings


Long press “ ” for 3s to enter function interface. “ ” clock icon will flicker and press “ ”
to choose the timing function. “ ” and “ ” flicker simultaneously means choosing to cancel all
timing functions.
Press “ ” to cancel timing settings. “ ” and “ ” both will be extinguished.

18.1.2 Functions of combination key


Force cooling function
Press “ ” and “ ” simultaneously for 3s in the main interface to enter into force cooling mode.
The force cooling mode icon will be constantly light.
Press “ ” button and “ ” button simultaneously for 3s to quit force cooling mode. The unit will
enter power off mode automatically when quitting force cooling mode.

18.1.3 Auto-lock(unlock) function


If don’t operate the controller in 60s, the keyboard will lock automatically. Press “ ”and “ ”

58
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

simultaneously for 3s to unlock.

18.1.4 Factory Reset


In main interface, long press “ ” for 3s, the unit will close and recovers to factory default mode.
Display panel will display ”OFF”.

59
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

18.2 Optional wired controller (KJR-120F/BMK-E, KJR-120F1/BMK-E)

Features
a. Touch key operation;
b. LCD displays operation parameters;
c. Multiple timer;
d. Real-time clock (battery life:5~8 years).

18.2.1 Overview

5
1
6
2

7
3
8
4
9
16 MODE 10

11 FUNCTIONS 11

15 12
(Press for 3sec to (Press for 3sec to
cancel timer) unlock)

14 13

①.Operation icon
②.Code area
③.Setting temperature
④.Timing On/Off
⑤.Function Icon
⑥.Unit number
⑦.Water Level Indication(reserved)
⑧.Clock
⑨.Water temp.
⑩.ON/OFF Key
⑪.Left Right Key
⑫.Confirm Key
⑬.Function key
⑭.Add and Reduce key
⑮.Cancel key
⑯.Mode key

1. Operation icon : Indicate unit ON and OFF status; the icon displays when the unit is on and does not
display when the unit is off;

60
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

2. Mode area: Indicate the main unit operating mode; details refer to its’ manual;

3. Setting temperature: 2 status can be displayed: ;


4. Timing ON/OFF indication : Indicate the timing information; details refers to page 10 of the
manual;

5. Function icon

1) : Displays when the unit controlled by remote switch;

2) : The conflict icon.

3) : Displays when the unit is needed. Press and hold “MODE” key for 3 seconds to cancel the icon
and timing will restart until next maintenance;

4) : The reserved icon. ;

5) : The reserved icon. ;

6) : Displays when check function is on; details refers to the manual;

7) : Displays when ambient temperature is low which means the main unit need anti-freezing action;

8) : Displays when no key operation for 2 minutes and all keys are locked. Press and hold “OK” key for
3 seconds to unlock;
9) : Displays when error or protection occurs and means the unit need maintenance by professionals.

6The unit number: The user can set the number, details refer to page 16 of the manual;
7. Water level indication: The reserved icon;
8. Clock: Under normal status displays clock; Under timing setting displays the setting timing, details refer to
page 15 of the manual;
9. Water temperature: Under normal status display water temperature; Under water temperature setting
status displays the setting value; Under check status displays check parameter, details refer to Page 9, 18 of
the manual;
10. ON/OFF key: Turn on and turn off functions, details refer to page 7 of the manual.
11. Right and Left key: Press these keys to check setting water temperature; Press right key to shift to the
next step setting under timing setting status; Press these keys to turn over the unit parameter information
under check status;
12. OK key: Press this key to confirm settings. Press and hold this key for 3 seconds to unlock under
locking status;
13. Function key: Setting water temperature, timing and clock etc, details refer to Page 9-17; Press and hold
this key for 3 seconds to enter check status, details refer to page 18 of the manual;
14. Add and Reduce key: Move up or move down values of temperature, timing etc;
15. Cancel key: Press this key to cancel parameter setting under setting status; Press and hold this key for 3
seconds to cancel timing when timing is valid;
16. Mode key: Power on the cooling function, heating function or water pump function, details refer to Page 8
of the manual.

61
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

18.2.2 Operation instructions

a. Turn On and Turn Off the main unit

1) Press the On/Off key to control On and Off status of the main unit.
2) Under Off status, press the On/Off key “ ” to run the main unit, at that time the LCD of wired controller
will display the operation icon “ ”. The main unit will running as the current setting of the wired controller.
3) Under On status, press the On/Off key “ ” to turn off the main unit and the operation icon “ ” on the
LCD will disappear.

ONLINE
QUANTIT Y

RUN

WATER
TEM P.

TIMER

MODE Press one time

FUNCTIONS

(Press for 3sec to (Press for 3sec to


cancel timer) unlock)

b. Setting operating mode and function parameters


1) Setting operating mode and water temperature
Setting operating mode: Press “MODE” key to choose operation mode. The setting mode will change as
the following order each time the key is pressed:

Cooling
→ Heating → Water pump

Press “OK” key or wait for 7 seconds to confirm. During the setting process pressing the “CANCEL” key
to exit without saving.

RUN

WATER
TEMP.

TIMER

MODE

FUNCTIONS

(Press for 3sec to (Press for 3sec to


cancel timer) unlock)

62
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

2) Setting water temperature:


Method 1:Press the “▲” or “▼” to adjust the water temperature after the controller is powered on. Press
“OK” key or wait for 7 seconds to confirm.
Method 2:Setting water temperature in parameters function. Press “FUNCTIONS” key under main
interface once to enter water temperature setting interface. Press the “▲” or “▼” to adjust the water
temperature .Press “OK” key or wait for 7 seconds to confirm.

RUN

WATER
TEMP.

TIMER
ON

MODE
Press
once
FUNCTIONS

(Press for 3sec to (Press for 3sec to


cancel timer) unlock)

Water temperature setting check: To check the water temperature setting value, press the “ ” or “ ”key


under the main page(the page displayed after the controller is powered on).

c. Setting function parameters


Press “FUNCTIONS” key to choose operation parameters. The setting function parameters will change
as the following order each time the key is pressed:

Water temperature
→ Timing → Clock → Unit NO.
→ Water pump forced

1) Timing setting: 3 timing periods can be set on the wired controller: Timer 1, Timer 2, Timer 3. These 3
timers can control the main unit to be turned ON and OFF 3 times at most during a day.
2) Setting method: press “FUNCTIONS” key under main page twice to enter timing setting. Then the LCD
will display as the following:

TIMER 1
ON

63
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

RUN

WATER
TEMP.

TIMER
ON

MODE
Press
twice
FUNCTIONS

(Press for 3sec to (Press for 3sec to


cancel timer) unlock)

At this time the hour of the clock will flash, which means the current setting is the hour of Timer 1 “On”,
press the “▲” or “▼” to adjust, press “ ” key when finished, and then the minute of the clock will

flash, which means the current setting is the minute of Timer 1 “On”, press the “▲” or “ ▼ ” to adjust,
press “ ” key when finished, the LCD will display as the following:

TIMER 1
OFF

At this time the hour of the clock will flash, which means the current setting is the hour of Timer 1 “Off”,
press the “▲” or “▼” to adjust, press “ ” key when finished, and then the minute of the clock will

flash, which means the current setting is the minute of Timing 1 “Off”, press the “▲” or “▼” to adjust,
press “ ” key when finished, the LCD will display as the following:

TIMER
ON

At this time the hour of the clock will flash, it means the current setting is the hour of the Timer 2 “On”.
And the follow setting method will be the same as the Timer 1. Similarly, the setting of Timing 3 is the
same as this method. After setting is finished, press “OK” key or wait for 7 seconds to confirm the setting,
and the LCD will display the effective timing information, as the following display:

TIMER

64
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

Example of Timing setting


Main page

Press “FUNCTIONS” key twice to enter hour


setting interface of “Timer 1 On”

Press the “▲” or “▼” key to set the hour


number of “Timing 1 On” to be 07


Press “ ” key to enter minute setting interface of
“Timer 1 On”, adjust the minute number to be 10


Press “ ” key to enter hour setting interface of
“Timer 1 Off”, adjust the hour number of “Timer 1 “Timer 1” setting
Off” to be 12 failed, after 7
seconds, the
page shift to the

Press “ ” key to enter minute setting interface of


main page.
“Timer 1 Off”, adjust the minute number to be 30

No No


Whether press “OK” key Whether press “ ” key

Yes Yes
Successfully set the On time of Finish setting the On time of
“Timer 1” to be 07:10 and Off time “Timer 1” to be 07:10 and Off
of “Timer 1 Off ” to be 12:30, then time to be 12:30, then enter the
back to the main page. setting of “Timer 2”.

The setting steps of “Timer 2” and “Timer 3” are the same as “Timer 1”,
after setting all the settings then press “OK” key, the 3 timing periods will
be effective.

During any period of timing setting to press “OK” key , the timing periods which have been set will be
effective (only if the “On” and “Off” of one timing period have been set, the setting is effective).
Check timing information: to check the timing which has been set, press “ ” or “ ” key under main page,

the “ On ”and “ Off ” time of Timer1, Timer 2 and Timer3 will be displayed in turns.
Cancel timing: press and hold “CANCEL” key for 3 seconds, then all the effective timing periods will be
cancelled.
Note: Correct: To avoid timing error, each period of timing should not be crossed. E.g.:
Correct:
TIMER 1 TIMER 2 TIMER 3

5:00 8:00 10:00 12:00 18:00 22:00


Wrong:
TIMER 1 TIMER 2

5:00 7:00 8:00 12:00

65
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

d. Setting clock

RUN

WATER
TEMP.

TIMER
ON

MODE
Press 3
times

FUNCTIONS

(Press for 3sec to (Press for 3sec to


cancel timer) unlock)

Press the “FUNCTION” key 3 times to enter clock setting. The hour of the clock will flash, which means
the current setting is the hour of the clock, press the “▲” or “▼” to adjust, press “ ” key when


finished, and then the minute of the clock will flash, it means the current setting is the minute of the clock,
press the “▲” or “▼” to adjust, press “ OK ” key when finished or wait for 7 seconds to confirm.
During the setting process pressing the “CANCEL” key to exit without saving.
NOTE: To get the correct timing On and timing Off time, please correctly set the clock!

e. Setting unit number

RUN

WATER
TEMP.

TIMER
ON

MODE
Press 4
times

FUNCTIONS

(Press for 3sec to (Press for 3sec to


cancel timer) unlock)

Press the “FUNCTIONS” key 4 times to enter the unit number setting. Press “▲” or “▼” to adjust
the unit number. press “ OK ”key when finished or wait for 7 seconds to confirm. During the setting
process pressing the “CANCEL” key to exit without saving. The setting value is 0-18.

66
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

f. Force opening water pump

WATER
TEMP.

TIMER
ON

MODE

Press 5
times
FUNCTIONS

(Press for 3sec to (Press for 3sec to


cancel timer) unlock)

Press the “FUNCTIONS” key 5 times to force open the water pump. The water pump icon will flash.
Press “ OK ”key to confirm. During the setting process pressing the “CANCEL” key to exit without saving.
Note:
a. Forcing water pump function is only limited to stand-by mode, others modes not response.
b. Under forcing water pump function, other settings will not responsible, except stopping
c. When communication disconnects, it will show E2 error in 2 minutes, the wired controller will
automatically cancel the forcing water pump function; while connected, the wired controller keeps
synchronizing with the unit( If forcing water pump function is still on-going, the controller keeping showing
its status).
d. The outdoor unit does not response after activating the forcing water pump function, (eg: forcing water
pump function cannot be activated under forcing heating in stand-by mode),the function will be
automatically stopped if it is not activated within 5 minutes.

18.2.3 Checking function


1) Check function allows the user to check all the operating parameters, error and protection information of
the unit.
2) Entering method: press and hold “FUNCTIONS” key for 3 seconds to enter check interface, as the figure
display:

check CHECK
icon

Unit number
RUN

check
parameter
check sequence
number

MODE

Press
FUNCTIONS
3 seconds

(Press for 3sec to (Press for 3sec to


cancel timer) unlock)

3) Press “ ” or “ ” to check all the status information of the unit.


67
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

Check content when wired controller setting is 1:


(The checking content is the same as the PCB’s checking.)
Order Contents
1 Running mode: 0-shutdown,1-Pump mode,2-Cooling,3-Heating,4-Forced cooling, 5-Forced heating.
2 Fan speed:0-Shutdown,1~7-Fan speed.
3 Total capacity requirements.
4 The revised capacity requirements.
5 Cooling/heating temp. setting.
6 T3 temperature value
7 T4 temperature value
8 Tp temperature Value
9 Tin temp. Value (Inlet water temperature)
10 Tout temp. Value (Outlet water temperature)
11 Tb1 temp. Value (Temperature 1 of heat plate)
12 Tb2 temp. Value (Temperature 2 of heat plate)
13 T6 temp. Value(Reserved )
14 Outdoor unit current
15 Power supply voltage AD value
16 Electronic expansion valve opening steps
17 The unit model:10-10kW,12-12kW,14-14kW,16-16kW
18 The program version number
19 The last error cord
20 The second error cord
21 The first error cord
22 ---

68
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

19.Troubleshooting
19.1 PCB parts instructions
MGC-V5W/D2N1, MGC-V7W/D2N1
PFC&IPM panel

 
7  8  9 
 
 
 
 
 
 
 
 
 
 
 
6   
 
5   
 
4   
 

 
 
 
 
 
 
 
 
  10 
2  1  12  11 
 
1. Input rectifier bridge port 1
2. Input rectifier bridge port 2
3. PFC inductance port 1
4. P-OUT
5. PFC inductance por 2
6. N-OUT
7. PFC control port
8. +18V port
9. IPDU communication port
10. IPM power port N
11. Compressor connection port U/V/W
12. IPM power port P

69
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

Main control panel


 
  9  11  13  16
 
8  10  12  14  15  17 18 19
 
 
 
 
20 
 
  21 
 7  22 
 6  23 
24 
  25 
26 
 
 5  27 
 
28 
  29 
 
 
 
 
   
 
 
  4  3  2 1
1. Power L
2. Power N
3. Preliminary charging relay (rectifier bridge input port 1)
4. Input rectifier bridge line (rectifier bridge input port 2)
5. 5A fuse
6. To IPDU
7. To PFC
8. Solenoid valve (Reserve)
9. Electric heater of plate heat exchanger
10. Electric heater of compressor
11. Pump
12. Electric heater of water flow switch
13. 4-way valve
14. Additional pump/Boil (Reserve)
15. Transformer input
16. Electronic expansion valve
17. Remote control
18. DC fan power supply port
19. DC fan port
20. Tin/Tout/Tb1 temperature sensor
21. Radiator temperature sensor (Reserve)
22. Discharge temperature sensor (Tp)
23. Outlet of outdoor heat exchanger temperature sensor(T3)
24. Ambient temperature sensor(T4)
25. Low pressure switch
26. High pressure switch
27. Operation and display panel port
28. Water flow switch
29. Transformer output

70
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

DC filter panel

 
 
 

 
 

 
 
  3 
  5 

1. IPM Power supply N


2. IPM Power supply P
3. PFC output power P
4. PFC output power N
5. DC 380V (DC fan power supply port)

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

71
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

MGC-V10W/D2N1
Main control panel
  27  28 30  31 33
29  32
 
 
 

 
26   
 
  2 
25  
  3 

24  
5.1 
  5.2 
23  6 
  7.1 
22  7.2 
 
21  8 
 
20  9 
 
19    10 

18   
  11 
 
17   
16 
 
12 
 
 
 
 
 
 
15   13 
 
 
  14 
 
 

1. Transformer output port


2. Tin/Tb1/Tout/Tb2 temperature sensor port
Note: Tin: water inlet temperature Tout: water outlet temperature
Tb1: Temperature 1 of plate heat exchanger Tb2: Temperature 2 of plate heat exchanger
3. Radiator temperature sensor port(Reserved) (T6)
4. Discharge temperature sensor port
5.1 Outlet of outdoor heat exchanger temperature sensor port(T3)
5.2    Ambient temperature sensor port (T4) 
6.    Operation and display panel port 
7.1    Low pressure switch 
7.2    High pressure switch 
8.    Differential pressure valve port 
9.    Factory debug port 
10.    Wired controller port 
11.    Electric expansion valve port 
12.    Power supply input port L 
13.    Power supply input port N 
14.    Ground wire

72
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

15. Rectifier bridge input port N


16. Rectifier bridge input port L
17. 8A fuse tube
18. Solenoid valve port(Reserved)
19. Exhaust valve electric heater port
21. Plate heat exchanger electric heater
22. Differential pressure valve electric heater port
23. Built-in water pump port
24. Compressor electric heater
25. 4-way valve port
26. External pump/Remote alarm port
27. Transformer input port
38. P/N/+15V port
29. Communication port between IPDU and main PCB
30. Down DC fan port
31. Check touch switch
32. Up DC fan port
33. Force-cooling touch switch

PFC Module

12 


4

11 

10 

9  8  7 6

73
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

1. +18V output port


2. Input Port P for IPM
3. Power supply port U of the compressor
4. Power supply port V of the compressor
5. Power supply port W of the compressor
6. PFC output N
7. PFC output P
8. PFC inductance port L_1
9. PFC inductance port L_2
10. PFC input N
11. IPM input N
12. Communication port to main control board

MGC-V12W/D2RN1, MGC-V14W/D2RN1&MGC-V16W/D2RN1
Main control panel
 
230 
 
 
 
 
 
 
 
 
 
 
29 
 
 
28   

 
 
27 
26    2 
 
  3 
25  

  8 
24  9 
 
23 
 
22    5 
6.1 
21  
6.2 
20    7.1 
7.2 
19    10 
18    11 
17   
12 
16  
 
 
 
15  14  13 

74
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

1. Input port for switching power supply


2. Debugging port
3. Connection port for operation and display panel
4. Tin/Tb1/Tout/Tb2 temperature sensor port
Note: Tin: water inlet temperature
Tout: water outlet temperature
Tb1: Temperature 1 of plate heat exchanger
Tb2: Temperature 2 of plate heat exchanger
5. Discharged temperature sensor port (Tp)
6.1 T3 temperature sensor port
6.2 T4 ambient temperature sensor port
7.1. Low pressure switch
7.2 High pressure switch
8. Checking touch switch
9. Force-cooling touch switch
10. Differential pressure valve port
11. Factory debugging port
12. Wired controller port
13. AC Current transformer
14. ”Remote on/off” and “remote cooling/heating” port
15. Electronic expansion valve port
16. AC 220V power supply port
17. Solenoid valve port(Reserved)
18. Exhaust valve electric heater port
19. Electric heater port of Plate heat exchanger
20. Electric heater port of differential pressure valve
21. Built-in water pump port
22. Electric heater of the compressor
23. Precharge AC contactor port
24. 4-way valve port
25. External water pump/Remote alarm port
26. Up DC fan port
27. Down DC fan port
28. Power supply port for switching power supply of PFC board
29. Drive module port
30. P/N/+15V port

75
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

IPM
  module
 
 
 
  1
 
 

 
 
 
2
 
 
 
 
 
 
 
 
 
 
 
 
7  6  5  4  3 

1. +15V output port


2. communication port to main control board
3. IPM input port N
4. Compressor connection port W
5. Compressor connection port V
6. Compressor connection port U
7. IPM input P
8. Power supply port for switching power supply

76
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

Filter
  board
  11 
 
 
 
  1 
10  
 
9   2 
 
 

 
  3 

7  6 
5 4
1. Power supply port L3
2. Power supply port L2
3. Power input port L1
4. Power input port N
5. Ground wire
6. Loaded power supply port for main control board
7. Power supply port for main control board
8. Power output port L1 after filtering
9. Power output port L2 after filtering
10. Power output port L3 after filtering
11. Ground wire

19.2 Function setting dial switches instructions

For 5/7kW

For 10kW

77
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

For 12-16kW

19.3. Query function for the built-in controller


a. To enter parameter checking function Press “ ” and “ ” simultaneously for 3s to enter into the
interface of parameter checking function. At this moment, first 2 digits of the digital tube will display
sequence number and the last 2 digits is specific parameters.
Press “ ” or “ ” to query the relative parameters.

b.Quit parameter query function


If there’s no operation in 20s when enter the parameter query, it will quit automatically and return
to the main interface. Press “ ” and “ ” simultaneously to quit parameter query manually.

Query content table

5/7kW
No. Content Note
Show inlet water temperature when the unit is in standby mode and
water pump mode. Display operating frequency when the unit is in
1 Frequency
cooling mode and heating mode. When defrosting displays dF. Pb
displays when anti-freezing mode running.
2 Operating mode 0-Power off,1-water pump,2-cooling,3-heating,4-force cooling
3 Operating fan speed level 0—Power off (1-7)
4 The total required capacity before revised Actual value (Force cooling displays 5)
5 Capacity requirements after revised Actual value (Force cooling displays 5)
6 Temperature set Actual setting temperature under cooling or heating mode
7 T3 Actual value(Outlet temperature of outdoor heat exchanger)
8 T4 Actual value(Outdoor ambient temperature)
9 Tp Actual value(Compressor discharged temperature)
10 Tin Actual value(Water inlet temperature of plate heat exchanger)
11 Tout Actual value(Water outlet temperature of plate heat exchangers)
12 Tb1 Actual value (Temperature 1 of plate heat exchangers)
13 Tb2 Actual value (Temperature 2 of plate heat exchangers(equals to Tb1 )
14 T6 Reserved (Cooling fin surface temperature(reserved)
15 Operation current Actual value
16 Power supply voltage Actual AD value
17 EXV Opening degrees Actual value×8
18 Model 5kW:5; 7kW:7
19 Version number ----
20 Err 1 The last one malfunction code
21 Err 2 The last second malfunction code
22 Err 3 The last third malfunction code

78
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

10-16kW

No. Content Note


Clock displays when standby. Inlet water temperature displays when
running. dF displays when defrosting. Pb displays when anti-freeze
0 Normal display
running. d0 displays when oil return, d8 displays when remote control is
off.
Display operating frequency when the unit is in cooling mode and
1 Frequency
heating mode.
0-Power off,1-water pump,2-cooling,3-heating,4-force cooling, 5-force
2 Operating mode
heating
3 Operating fan speed level 0—Power off (1-7)
4 The total required capacity before revised Actual value (Force cooling displays 5)
5 Capacity requirements after revised Actual value (Force cooling displays 5)
6 Temperature set Actual setting temperature under cooling or heating mode
7 T3 Actual value(Outlet temperature of outdoor heat exchanger)
8 T4 Actual value(Outdoor ambient temperature)
9 Tp Actual value(Compressor discharged temperature)
10 Tin Actual value (Water inlet temperature of plate heat exchanger)
11 Tout Actual value (Water outlet temperature of plate heat exchangers)
12 Tb1 Actual value(Temperature 1 of plate heat exchangers)
13 Tb2 Actual value(Temperature 2 of plate heat exchangers(equals to Tb1 )
14 T6 Reserved(Cooling fin surface temperature(reserved)
15 Operation current Actual value
16 Power supply voltage Actual AD value
17 EXV Opening degrees Actual value×8
18 Err 1 The last one malfunction code
19 Err 2 The last second malfunction code
20 Err 3 The last third malfunction code

79
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

19.4 Error code table

5/7kW

Error Note
Content
Code
E9 EEPROM malfunction
H0 Communication malfunction between main chip and IPDU.
E4 T3,T4 sensor malfunction
The same as
E5 Voltage protection malfunction
10-16kW
E6 DC fan motor malfunction
EA A fan in the A region run for more than 5 minutes in heating mode
Eb There are two times E6 fault in 10 minutes (recovery after power off)
HH Inlet water temperature sensor malfunction for 5/7kW models.
EC Outlet water temperature sensor malfunction (5/7kW) 5/7kW
C0 Temperature sensor malfunction of plate heat exchanger for 5/7kW.
P1 High pressure protection
P2 Low pressure protection
P3 Current protection of the compressor
The same as
P4 Discharged temperature protection
10-16kW
P5 T3 high temperature protection of outdoor condenser
P6 IPDU module protection
P8 Typhoon protection
Protection when temperature difference between inlet & outlet water in heating mode is too
CH
large for 5/7kW
Protection when temperature difference between inlet & outlet water in cooling mode is too 5/7kW
CL
large for 5/7kW.
CP Anti-freeze protection of plate heat exchanger for 5/7kW
Pb System anti-freeze protection The same
C8 Water flow switch protection malfunction as 10-16kW
PH Protection when water temperature in heating mode is too high for 5/7kW. 5/7kW
dF Defrosting The same as
d8 Remote control 10-16kW

80
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

10-16kW

Error Code Content Note


E9 EEPROM malfunction
H0 Communication malfunction between main chip and IPDU.
E4 T3,T4 sensor malfunction
E5 Voltage protection malfunction The same as 5/7kW
E6 DC fan motor malfunction
EA A fan in the A region run for more than 5 minutes in heating mode
Eb There are two times E6 fault in 10 minutes (recovery after power off)
C0 Inlet water temperature sensor malfunction for 10~16kW models.
C1 Outlet water temperature sensor malfunction (10-16kW)
F7 Sensor temperature 1 of plate heat exchangers for 10-16kW. 10-16kW
F8 Sensor temperature 2 of plate heat exchangers for 10-16kW.
PL Reserved for 10-16kW.
P1 High pressure protection
P2 Low pressure protection
P3 Current protection of the compressor
P4 Discharged temperature protection The same as 5/7kW
P5 T3 high temperature protection of outdoor condenser
P6 IPDU module protection
P8 Typhoon protection
CH Protection when water temperature is too high in heating mode.
CL To low water temperature protection in heating mode for 10-16kW 10-16kW
CP Anti-idling protection for water pump
Pb System anti-freeze protection
The same as 5/7kW
C8 Water flow switch protection malfunction
Protection when temperature difference between inlet water & outlet water is too
PH 10-16kW
large for 10-16kW.
dF Defrosting
The same as 5/7kW
d8 Remote control

81
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

E9 malfunction: EEPROM malfunction


The malfunction may be caused by two reasons:
1) The EEPROM is not inserted well; 2) Outdoor main PCB is broken.

LED displays E9

EEPROM malfunction

NO
Check whether EEPROM is installed properly. Installed properly again.

Yes

Replace main PCB.

H0 malfunction : Communication malfunction between main chip and IPDU.

LED displays H0

Communication malfunction between main chip and IPDU

NO
Whether the signal wire is connected normally between module board . Connect wire again.

YES

NO
Replace main PCB.
Judge whether LED on the module board flash normally or not
when powered on.

YES

Replace module board.

82
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

E4 malfunction : T3,T4 sensor malfunction


HH malfunction : Inlet water temperature sensor malfunction for 5/7kW models.
C0 malfunction : Inlet water temperature sensor malfunction for 10-16kW models.
EC malfunction: Outlet water temperature sensor malfunction for 5/7kW models.
C1 malfunction: Outlet water temperature sensor malfunction for 10-16kW models.
C0 malfunction: Temperature sensor malfunction of plate heat exchanger for 5/7kW models
F7 malfunction: Sensor temperature 1 of plate heat exchangers for 10-16kW.
F8malfunction: Sensor temperature 2 of plate heat exchangers for 10-16kW.

T3: outlet temperature of outdoor heat exchanger


T4: outdoor ambient temperature

LED displays E4/HH/EC/C0/C1/F7/F8

Whether sensor fails to work.

NO

YES
Judge whether the wire body is broken and the terminal is fall off. Connect wire again.

NO
YES
Judge whether the port of temperature sensor connected wrong. Connect properly again.

NO
YES
Use a multi-meter to check the resistance value of the temperature sensor Replace temperature sensor.
is normal or not.

NO

Replace main PCB.

E5 malfunction: Voltage protection malfunction

LED displays E5

Voltage protection

Judge whether the input voltage is within 198-252V. NO


Check the power supply.

YES

Replace main PCB.

83
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

E6 malfunction: DC fan motor malfunction

LED displays E6

Outdoor unit DC fan cannot work.

Refers to the wiring diagram to check whether NO


the unit wiring is correct or not. Connect again.

YES
Check the voltage
Check whether the power and voltage of the DC between “+”,”-” port NO Replace PFC
fan motor is normal or not and whether the NO
of PFC module is within module board..
voltage between red and black terminal of DC 277-354V.
motor is from 277V to 354V in waiting state. 是

YES
YES

NO
Check whether the power and voltage of the DC fan
motor is normal or not and whether the voltage between Replace IPM module.
white and black terminal of DC motor is from 15V in
waiting state.
Check voltage
YES between yellow YES
NO and black
Whether the outdoor fan will work after the indoor fan terminal of the Replace fan.
operates for 3 minutes. fan is over 2.4V

YES
NO

Replace the main PCB.

84
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

P1 malfunction: High pressure protection

LED displays P1

High pressure protection

NO
Judge whether the wiring connection is correct. Connect again.

YES

Judge wire body is broken or not.

To confirm: short-circuit high pressure switch and check whether NO


Replace high pressure switch.
the system can operate normally or not.

YES

Check whether the cooling system is normal or not.

YES
Check whether pressure of the system is too high. Stop the system.

NO
NO
Rectify the air duct
Whether side air duct of outdoor unit meets the standard.

YES
YES
Whether the heat exchanger needs cleaning. Clean.

NO
YES
Whether the pipeline is blocked. Rectify the pipeline.

NO
YES
Judge the circulation water pump is damaged or not.
Repair or replace the water pump
NO
YES
Whether plate heat exchanger is fouling or blocked severely Clean or replace heat exchanger .

NO

Replace main PCB.

85
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

P2: Low pressure protection

LED displays P2

Low pressure protection

NO
Whether wiring connection between low pressure switch and PCB is Connect well again.
connected well or properly.

YES

Whether the low pressure switch is damaged.

NO

YES
Short-circuit low pressure switch and check whether the
Replace low pressure switch .
system can work normally.

NO

Whether the cooling system can work as normal.

YES

Check whether the outdoor ambient temperature is too low. Stop the unit.

NO Leakage detecting: add nitrogen or refrigerant


YES into the system. “si”,”si” will sound evidently if
Whether refrigerant system leaks. leaks heavily. Use soap water(the combination
of water and detergent ) or electronic detector
to detect if leaks slightly.
NO

Connect pressure gauge with the system measuring port.

NO
YES Replace the EXV, then use high
Whether EXV works properly or stuck or blocked pressure nitrogen to clean and air the
pipeline, add the refrigerant at last.
NO

Replace outdoor main PCB.

86
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

P3: Compressor current protection


It will protect when input current is more than 22A(31A for 10-16kW ). It will recover when input current is less than 22A
(31A for 10-16kW ). It will recover automatically.

LED displays P3

Compressor current protection

NO
Check whether the input current of the power wire is more than 22A.
(31A for 10-16kW ) Replace main PCB

YES

Check cooling system is normal or not.

YES
YES
Stop the unit.
Check whether the outdoor ambient temperature is too high.

NO
YES
Check whether the outdoor unit ventilates well. Make the outdoor unit
ventilates well.

NO
` YES
Whether the heat exchanger needs cleaning or not. Clean heat exchanger.

NO
YES Remove the refrigerant pipe and then use high
If the refrigerant pipe is blocked or not? pressure nitrogen or refrigerant to blow the pipe.
NO Vacuumed the pipe then add the refrigerant again.
NO
YES
Whether the circulation water pump is damaged. Repair or replace the water pump

NO
NO
YES
Whether plate heat exchanger is fouling or blocked severely Clean or replace heat exchanger.

NO

Replace main PCB.

87
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

P4: Compressor discharged temperature protection 
When the discharged temperature of the compressor is higher than 115°C, the unit will stop running. When the
discharged temperature of the compressor is lower than 83°C , the unit resumes normal operation automatically.

LED displays P4

Discharged temperature protection of the compressor

YES
Check whether the discharged temperature of the compressor is higher than 115°C.

NO

Check whether the compressor discharged NO


temperature sensor connects with PCB correctly Connect correctly again.
according to the wiring diagram.

Check refrigerant leaks or not.


YES
YES

Whether the discharged temperature sensor is damaged or not. Stop leaking and then add the refrigerant again.

NO
Check whether resistance of compressor discharged Replace compressor discharged
temperature sensor is correct or not . temperature sensor.

YES

Replace outdoor main PCB

88
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

P5: Condenser high temperature protection


When condenser temperature is higher than 62 degrees, the unit will stop operating. When pipe temperature outside is
lower than 52 degrees, the unit will resume operate.

LED displays P5

Condenser high temperature protection

YES
Check whether condenser temperature is higher than 62
degrees

NO

NO
Check whether the resistance of condenser
temperature sensor is correct. Replace the temperature sensor

YES

Replace the outdoor main PCB.

YES Whether outdoor temperature is too high(higher than 48


Stop the unit degrees)or not.

NO

YES
Clean heat exchanger Whether heat exchanger needs cleaning.

NO
Replace EXV and then use high pressure YES
nitrogen to blow the pipe. Vacuumed the Check if the EXV is blocked or not.
pipe then add the refrigerant again.

NO

Replace outdoor main PCB.

89
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

P6: IPM Module protection

LED displays P6

IPM module protection

Check whether the input power is Adjust to the right range.


Check whether P-N voltage on the IPM module NO correct. The power is 220-240V, 1N, NO Then check whether the
is OK. The DC voltage is from 277 to 356V. 50Hz. system runs normally.

NO
YES Connect firmly YES
NO again and check
Check if wiring connection NO Connect firmly again and
whether it is Check whether power
between DC filter and IPM module check whether it is
connected wiring is connected
is fasten or not. connected right.
correctly and firmly.
correctly.
NO
YES NO

Connect well again YES


Check whether wiring NO and check whether
connection of the compressor it is connected
is connected right and firmly. correctly.

Check whether the output voltage of


NO single-phase bridge rectifier is within
YES NO
277-356V Replace rectifier.

YES
Replace IPM module and Solve the problem YES
check
  whether the system
can operate normally or not..
Check if it is connected NO
normally before entering bridge Connect wire correctly..
NO rectifier . If wire body terminal is
connected firmly.

Replace main PCB and check


YES Solve the YES
whether the system can
operate normally or not. malfunction.
Check the fuse on the power
board is normal or not.
NO

YES YES
Replace compressor and check Solve the NO
whether the system can Replace the
malfunction.
operate normally or not. Replace the main PCB. same model
fuse.

90
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

P8: Typhoon protection

LED displays P8

Typhoon protection

Check if strong wind blows outdoor unit or two YES Stop the unit to prevent strong wind
outdoor units blows each other. to blow the outdoor fan.

NO
NO Replace the outdoor main PCB
Check whether the fan motor is damaged.

YES

Replace outdoor fan motor.

CH malfunction: Protection when temperature difference between inlet & outlet water in heating
mode is too large for 5/7kW
CL malfunction: Protection when temperature difference between inlet & outlet water in cooling
mode is too large for 5/7kW.
CP malfunction: Anti-freeze protection of plate heat exchanger for 5/7kW.
PH malfunction: Protection when water temperature in heating mode is too high for 5/7kW.
CH malfunction: Protection when water temperature in heating mode is too high for 10-16kW.
PH malfunction: Protection when temperature difference between inlet water & outlet water is too
large for 10-16kW.

LED displays CH/CL/CP/PH

① Protection when temperature difference between inlet & outlet water in heating/cooling mode is too large;
② Anti-freeze protection of plate heat exchanger③Protection when water temperature in heating mode is too high

YES
Whether actual measured temperature difference between outdoor outlet water
temperature minus inlet water temperature is higher than 14°C

NO

Check inlet water sensor and outlet water sensor is


fall off or damaged. Replace main PCB.

YES
Check whether the volume of water flow is
Place temperature sensor to the related position or replace it. enough or not.

YES
NO Whether gear of water pump NO
Adjust to high
level is chosen right. Whether water system is stuck.

YES
YES

Water flow pump head of external water pump choices Replace water system component.

Select the proper water pump again.

91
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

Note: when the ambient temperature is less than 8℃, inlet water temperature and temperature of plate heat exchanger is less
than 2℃, crankcase heater of plate works. CP appears. If inlet water temperature and temperature of plate heat exchanger is
more than 7℃, crankcase heater stops working and CP code disappears.

CL malfunction: To low water temperature protection in heating mode for 10-16kW.

LED displays CL

To low water temperature protection in heating mode. Determine the location again.

YES
YES
Whether the 4-way valve switch can switch normally Whether the thermometer bulb of water
outlet and inlet location are right.

NO
YES NO
Plug well
Check whether the 4-way valve coil fall off and the valve body jammed.
again Replace main
PCB
NO
NO
Check whether 4-way valve coil and body jammed. Replace main PCB

YES

Replace 4-way valve

Pb malfunction: Anti-freeze protection

LED displays Pb

Anti-freeze protection

The actual measured temperature of outdoor water outlet temperature and plate heat YES Normal system
protection
exchanger temperature is less than 3 ℃ in cooling mode. Water inlet temperature and
plate heat exchanger temperature is less than 5 ℃ in heating mode and waiting mode.

NO

Check whether water inlet sensor and plate heat NO


exchanger is fall off or damaged.(especially when the
Replace main PCB.
outdoor temperature is lower than 0℃)

YES

Place temperature sensor to the related position or replace it.

Note:
1) The actual measured temperature of outdoor water outlet temperature and plate heat exchanger temperature is less
than 3 ℃ in cooling mode, the compressor stops running. But the water pump continue operating. If the temperature is
more than 8℃, Pb code disappears.
2) The actual measured temperature of outdoor water inlet temperature and plate heat exchanger temperature is less
than 8℃ in waiting state, water pump works. The actual measured temperature of outdoor water inlet temperature and
plate heat exchanger temperature is less than 5℃, the unit enter heating mode in force. Compressor works too. This is
normal.

92
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

C8 malfunction: System water flow protection


CP malfunction: Anti-idling protection for water pump

LED displays C8/CP

System water flow protection or anti-idling protection for water pump

YES
Whether system water flow leaks. Repair the leaks and add the water again.

NO
YES
Whether the water pipe is too long and not To configure external water pump
connected to water pump.

NO
YES
Whether water system is stuck. Wash or replace the stuck components and
pipeline.
NO
YES
Whether water pump is damaged. Replace water pump.

NO

Whether water flow switch is damaged.

YES
Remove the water flow switch and close
the fin manually to check whether Replace water flow switch.
malfunction still exists

Malfunction still exists.

YES

Replace main PCB

93
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

20. Optional Accessories


No. Name Specification Remark
1 Wired controller KJR-120F/BMK-E (with Midea logo) Customized
2 Wired controller KJR-120F1/BMK-E (without Midea logo) Customized

94
MCAC-ATSM-2014-09 Aqua Mini Full DC Inverter Unitary Chiller 50Hz

Appendix
Accessories
Item Name of accessory Qty Shape

Installation and
1 1
operation manual

2 Rubber sealed ring 2

3 Outlet connection pipe 1

4 Straight screwdriver 1 -----

95
Aqua Mini Full DC Inverter Unitary Chiller 50Hz MCAC-ATSM-2014-09

Temperature-Resistance characteristic sheet for pipe temperature sensor,


ambient temperature sensor,inlet water temperature sensor and outlet
water temperature sensor.
Sensor characteristic sheet Unit:Temp:℃--K, Ratio:KΩ
Temp. Ratio Temp. Ratio Temp. Ratio Temp. Ratio
-20 115.266 20 12.6431 60 2.35774 100 0.62973
-19 108.146 21 12.0561 61 2.27249 101 0.61148
-18 101.517 22 11.5 62 2.19073 102 0.59386
-17 96.3423 23 10.9731 63 2.11241 103 0.57683
-16 89.5865 24 10.4736 64 2.03732 104 0.56038
-15 84.219 25 10 65 1.96532 105 0.54448
-14 79.311 26 9.55074 66 1.89627 106 0.52912
-13 74.536 27 9.12445 67 1.83003 107 0.51426
-12 70.1698 28 8.71983 68 1.76647 108 0.49989
-11 66.0898 29 8.33566 69 1.70547 109 0.486
-10 62.2756 30 7.97078 70 1.64691 110 0.47256
-9 58.7079 31 7.62411 71 1.59068 111 0.45957
-8 56.3694 32 7.29464 72 1.53668 112 0.44699
-7 52.2438 33 6.98142 73 1.48481 113 0.43482
-6 49.3161 34 6.68355 74 1.43498 114 0.42304
-5 46.5725 35 6.40021 75 1.38703 115 0.41164
-4 44 36 6.13059 76 1.34105 116 0.4006
-3 41.5878 37 5.87359 77 1.29078 117 0.38991
-2 39.8239 38 5.62961 78 1.25423 118 0.37956
-1 37.1988 39 5.39689 79 1.2133 119 0.36954
0 35.2024 40 5.17519 80 1.17393 120 0.35982
1 33.3269 41 4.96392 81 1.13604 121 0.35042
2 31.5635 42 4.76253 82 1.09958 122 0.3413
3 29.9058 43 4.5705 83 1.06448 123 0.33246
4 28.3459 44 4.38736 84 1.03069 124 0.3239
5 26.8778 45 4.21263 85 0.99815 125 0.31559
6 25.4954 46 4.04589 86 0.96681 126 0.30754
7 24.1932 47 3.88673 87 0.93662 127 0.29974
8 22.5662 48 3.73476 88 0.90753 128 0.29216
9 21.8094 49 3.58962 89 0.8795 129 0.28482
10 20.7184 50 3.45097 90 0.85248 130 0.2777
11 19.6891 51 3.31847 91 0.82643 131 0.27078
12 18.7177 52 3.19183 92 0.80132 132 0.26408
13 17.8005 53 3.07075 93 0.77709 133 0.25757
14 16.9341 54 2.95896 94 0.75373 134 0.25125
15 16.1156 55 2.84421 95 0.73119 135 0.24512
16 15.3418 56 2.73823 96 0.70944 136 0.23916
17 14.6181 57 2.63682 97 0.68844 137 0.23338
18 13.918 58 2.53973 98 0.66818 138 0.22776
19 13.2631 59 2.44677 99 0.64862 139 0.22231

96