Super Solution
● External structure 26
● Basic features and interrupting operation 28
● Standards and certification 31
● Types and ordering information 32
● Type of circuit breakers 42
● Ratings 46
Susol VCB is full line-up new VCB which has the high ● Accessories 60
interrupting capacity, large current(~50kA, ~5000A), and ● Control circuit diagrams 91
Dimensions 95
maximized compatibility with existing products through the
●
Suitable for use as the main circuit breaker to protect key installations in the
places such as device industry, power plants, high-rise buildings, large ships.
4I
▶S
trengthening of the high interrupting capacity and large current
models and full line-up new VCB models to high/middle/low.
Voltage Interrupting current Rated current
7.2kV 8/12.5/20/25/31.5/40/50kA 400/630/1250/2000/3150/4000A
12kV 20/25/31.5/40/50kA 630/1000/1250/2000/2500/3150/4000/5000A
17.5kV 20/25/31.5/40/50kA 630/1000/1250/2000/2500/3150/4000A
24kV 12.5/25/31.5/40kA 630/1250/2000/2500/3150A
36kV 25/31.5/40kA 1250/2000/3150A
▶C
onvenience of switchgear configuration and a variety of
accessories.
•CB compartment structure: Metal isolation structures to prevent the
accident spread and ensure safety. And the convenience of switchgear
building is extended by its module style.
•A variety of accessories: UVT, Locking Magnet, Plug Interlock, Key lock,
Temperature Sensor, MOC, TOC, Earthing S/W.
•Maximizing compatibility with existing products through the dualistic
deployment of phases and compact models.
I5
7.2kV (VL-06)
•Rated short-time (for withstand current ): 3sec.
•Rated operating sequence: O-0.3s-CO-15s-CO
•Type test level: M2, E2 (List1), C2
•100% Compatibility
- with existing fixed type breakers
- with existing drawout type breakers
•Various cradle: E, F and G type
•A variety of control power
- DC 24~30V, DC 48~60V, DC 110V, DC 125V, DC 220V
- AC 48V, AC 100~130V, AC 220~250V
•A variety of accessories
-C harge switch, UVT, Secondary trip Coil, Current trip coil,
Trip Latch Checking S/W, Position S/W
-K ey-lock, Button lock, Button cover, Padlock, UVT, Time
Delay Controller, Lifting hook, CTD
•Anti Pumping Device
•TEST/SERVICE Automatic Position Indicator
•Standards and certification
- IEC62271-100 (2012) [M2, C2, E2 (List1)]
- Tested in enclosure
- KERI type tested, V-check (KESCO) certification
Ur Isc Ir
(kV) (kA) (A)
7.2 8 400
12.5 630
E type
F type
H type I7
Main circuit structure
with high reliability
Susol
VCB
Breaker
Insulation rod
Lower terminal
Shunt
Vacuum interrupter
Upper terminal
Tulip contactor
Fixed
electrode
Fixed
Contacts
seal cup Vacuum Interrupter, VI
Arc shield
The vacuum rate within the VI is very high the contacts are made of special alloy (copper-
Bellows (approximately 5x10-5 Torr) and the spacing chromium) and the interior is completely sealed
shield
Ceramic between fixed contact and movable contact to prevent loss of vacuum.
is about 6~20mm, depending on the Therefore the wearing of the contacts can be
Bellows
voltage. minimized in the event of short-circuit and the
Movable
Movable seal cup The contacts are in a structure that arc can arc energy by overvoltage or switching can be
electrode
easily be extinguished and the surfaces of reduced effectively.
8I
< < Susol VCB Series
Convenience and
Variety
I9
Stego Tulip
Main circuit structure with high reliability
•Maximizing the durability and reliability of the main circuit contactors (Stego Tulip contactor)
•Strong structure for the temperature rise (Natural cooling system)
Tulip finger
Tulip spring
Plate understar :
Securing freedom of Tulip
Plate star: Supporting Tulip for position maintaing and torsional flow prevention
10I
< < Susol VCB Series
7.2/12/17.5/24/25.8/36kV...
(VH-06/12/17/20/25/36)
I 11
CB Compartment
Convenience in building switchgears
•CB compartment structure: H type cradle
•Metal isolation structure to prevent the accident spread and ensure safety
•Convenience of switchgear building
7.2/12/17.5/24/25.8/36kV 20/25/31.5/40/50kA
•Metal isolation structure to prevent the accident spread and ensure safety
•Convenience of operation by Truck
- Drawable in the closed position of the switchgear door
- Racking-in/out positions indicated mechanically
•Equipped with safety devices and accessories
- Control power connected Interlock
- Earthing S/W and interlock, MOC/TOC (ANSI)
•Convenience in building switchgears
- Module assembly with CB compartment
12I
< < Susol VCB Series
LV
Compartment
CB
Compartment
Accessories of CB compartment
(H type cradle)
PT
OC (Mechanism Operated Cell S/W)
■M
Compartment
OC (Truck Operated Cell S/W)
■T
hutter Padlock
■S
emperature Sensor
■T
oor Emergency ON/OFF Button
■D
arthing switch & Accessaries
■E
Key lock for Earthing S/W
Locking Magnet for Earthing S/W
Position S/W for Earthing S/W
M (Temperature Monitoring Unit)
■T
I 13
Cradles
E, F, G, K and H type... Variety of the Cradles
F type
E type
E type F type
•Economic style cradle with the •Safety shutter has been added
basic structure to the cradle of type E
•No safety shutter and bushing •No bushing
•For MESG •For MESG
•Applies VL type VCB •Applies VL type VCB
14I
< < Susol VCB Series
H type
K type
G type
H type
•Metal isolation structure to prevent the
accident spread and ensure safety
K type •Convenience of operation by Truck
•Premium style cradle with -D rawable in the closed position of
metal safety shutter and the switchgear door
bushings -R acking-in/out positions indicated
•Metal isolated structure: To mechanically
prevent spreading accident - Control power connected Interlock
and secure safety •Convenience in building switchgears
G type •More convenient by -M odule assembly with CB
•Premium style cradle with withdrawable Truck compartment
safety shutter and bushings •For MCSG -A ssembly with CT/PT integrated
•For MESG •Applied to medium capacity/ compartment
•Applies VL type VCB high capacity VCB •Applies VL/VH type VCB
I 15
Convenience
Convenience in building switchgears
- Maximizing compatibility with existing products through the dualistic deployment of phases and compact models.
150 210
150 210
VCB rating
Ur (kV) Isc (kA) Ir (A)
12 20/25 630
31.5 1000
1250
17.5 20/25 630
31.5 1250
P150 P210
(distance between phases: 150mm) (distance between phases: 210mm)
150 210
150 210
VCB rating
Ur (kV) Isc (kA) Ir (A)
12 20/25 2000
17.5 20/25 2000
P150 P210
(distance between phases: 150mm) (distance between phases: 210mm)
275
275
VCB rating
Ur (kV) Isc (kA) Ir (A)
17.5 31.5 2500
P275
(distance between phases: 275mm)
16I
< < Susol VCB Series
210 275
VCB rating 210 275
VCB rating
Ur (kV) Isc (kA) Ir (A)
24 31.5/40 2000
25.8 31.5/40 2000
P210 P275
(distance between phases: 210mm) (distance between phases: 275mm)
I 17
Accessories
Breaker
Motor Current trip coil
Closing coil Key lock
Trip coil Button padlock
Counter Button cover
Auxiliary contacts Position switch
UVT coil Lead wire
18I
< < Susol VCB Series
Cradle
Handle for Racking-in and out
UVT time delay controller
Condenser trip device
I 19
Accessories
Breaker
M otor Position switch
Closing coil Handle for Racking-in/out
Trip coil UVT time delay controller
Counter CTD (Condenser trip device)
Auxiliary contacts MOC (Mechanism operated cell switch)
UVT coil Padlock (H type Door Interlock)
Key lock Locking magnet
B utton padlock Plug Interlock
Button cover
20I
< < Susol VCB Series
Cradle (H type)
TOC (Truck operated cell s/w) Emergency ON/OFF button
MOC (Mechanical operated cell s/w) Earthing switch & Accessary
T emperature sensor Key lock for Earthing switch
Door Locking Magnet for Earthing switch
Door interlock Position s/w for Earthing switch
Shutter padlock TM (Temperature monitoring unit)
I 21
Accessories
Breaker
Motor Auxiliary contact wire D oor Interlock for withdrawable type
AC/DC coil rectifier Key lock Lifting hook
T rip coil/Closing coil B utton cover/Push bar Charge handle
Secondary trip coil Button padlock Racking in/out handle
AC/DC UVT coil rectifier Position switch UVT Time delay controller
UVT coil Locking magnet CTD (Condenser trip device)
Latch checking switch Plug interlock Wireless Temp. monitoring sensor
22I
< < Susol VCB Series
Cradle (H type)
MOC (Mechanism operated cell switch) Earthing switch & Accessaries
TOC (Truck operated cell switch) Key lock for Earthing switch
Shutter padlock Locking magnet for Earthing switch
Temperature sensor Position switch for Earthing switch
Door TM (Temperature monitoring unit)
Emergency ON/OFF button
I 23
Standards and certifications
E2 (List 1 or List3)
E2 (List3) is first proposed in the IEC 62271-100(2008) to improve the efficiency of the interrupting test.
According to it the number of interrupting test T60 is increased instead of fewer number of T10 and T30
compared to the existing List1. List3 compared with the List1 maintains the equivalent of the test but has
severe test conditions because 34% higher arc energy applied to the breaker. List3 is applied to Susol VCB
series.
Arc Energy: List 1 (100%) < List 2 (125%) < List 3 (134%)
134%
125%
100%
E2 List1 E2 List2
E2 List3 E1
24I
< < Susol VCB Series
M2, C2
IEC standards to verify the relibilty of the product allows to select the quality level for the product to be tested
according to its real performance and practical usage. The highest quality level of M2, C2 has been applied to
Susol VCB.
C - O
2000 operation test
Sequence Control Voltage Number of operations
85% 500
M2 M2
C - O 100% 500
C - O 110% 500
O - CO - C 100% 250
M1 M110,000 10,000
operations operations
2,000 2,000
operations operations
•Pre-test (characteristics, isolation, and temperature) •Pre-test (characteristics, isolation, and temperature)
•Confirmative tests after the completion of 2000 operations •Confirmative tests after every 2000 operation
(Characteristics, isolation, temperature) •Confirmative tests after the completion of 10,000
operations (Characteristics, isolation, temperature)
C1, C2: Capacitive current breaking test is to verify the probability of restriking and C2 class is secured for all Susol VCB.
C1 C1
2 restrikes are allowed
during “O” 24 operations C2 C2 Restrike is not allowed
during “O” 24 operations
and “CO” 24 operations and “CO” 24 operations
I 25
External structure of VCB
❸C
harge/Discharge Indicator
❹ ON/OFF Indicator
❻
❺M
anual Charging Handle
❺ ❻ Key Lock
❶
❸ ❼ Operation Counter
❷ ❽ TEST/SERVICE
❹ Position Indicator
Back side
26
Breaker ... VH type
❸C
harge/Discharge Indicator
❶ ❹ ON/OFF Indicator
❻
❸ ❺M
anual Charging Handle
❻ Key Lock
❺ ❼ Operation Counter
❷
❽ TEST/SERVICE
❹ Position Indicator
Back side
27
Basic functions and interrupting operation
Basic functions
Manual operation
① Manual Charge
a) VL type: operate the charge handle 7-8 times as a fully stroke.
b) VH type: Insert the charge handle into the handle slot first. Rotate the handle clockwise 40 times more and then
charge will be complete with a click sound.
- When the closing spring is charged fully "CHARGED" is displayed at the charge indicator.
② Manual closing
a) Pressing the ON button the breaker is closed.
b) With the closing of the breaker "ON" is displayed at Close/Trip indicator and "DISCHARGED" at the charge
indicator.
③ Manual trip
a) Pressing the OFF button the breaker is opened.
b) "OFF" is displayed at Close/Trip indicator.
Electric operation
① Electric charge
The breaker is remotely closing with charging of closing spring.
If the breaker closing the closing spring is automatically charged by gear motors.
② Electric closing
Remote closing is operated by the closing coil.
③ Electric trip
Remote trip can be operated by the trip coil or UVT coil.
Main contacts are operated by the energy of the spring mechanism and closing spring is charged by the motor in the
mechanism.
Breaker is closed by closing coil and tripped by trip coil.
These operations are repeated in VCB as shown in the below sequence chart.
Motor
Closing spring
Opening spring
Closing coil
Opening coil
Main contact
Closing time Opening time
28
Basic functions and interrupting operation
Fixed electrode
Fixed shield
Ceramic
Bellows shield
Bellows
An example of oscillogram obtained through the interrupting test using LC resonant circuit
29
Basic functions and interrupting operation
Arc voltage waveforms and arc image captured during arcing time
30
Standards and certification
Susol VCB has been type tested and obtained certifications according to the latest IEC standard at international testing
laboratory and can be installed and applied at the environment and conditions in accordance with the standard.
Standard
- IEC 62271-1 (2007.10)
High-voltage switchgear and controlgear - Part 1: Common specifications.
- IEC 62271-100 (2008.04)
High-voltage switchgear and controlgear - Part 2: Alternating-current circuit breakers.
31
Types and ordering information
7.2kV (VL-06)
Breaker
VL 06 P 08 A 04
Basic model name Rated voltage (kV) Version Rated short time current (kA) Phase distance/Compatibility Rated current (A)
VL Susol VCB 06 7.2 P Fixed 08 8 A Standard 04 400
E E type drawout 13 12.5 Compatible with 06 630
B
F F type drawout existing breaker Note6)
G G type drawout
VL-06E08A04 M1 C1 T1 SA1 U1 A 14 7
32
Cradle
VCL 06 E 08 A 06
Basic model name Rated voltage (kV) Version Rated short time current (kA) Phase distance/Compatibility Rated current (A)
Susol VCB 06 7.2 E E type drawout 08 8 A Standard 04 400
VCL
Cradle F F type drawout 13 12.5 Compatible with 06 630
B
G G type drawout existing cradle Note)
Note) In case of replacing the existing old type VCB with Susol VCB please order type B for cradle and A for breaker.
33
Types and ordering information
7.2/12/17.5kV (VL-06/12/17)
Breaker
VL 06 H 20 A 06
Basic model name Rated voltage (kV) Version Rated short time current (kA) Phase distance/Compatibility Rated current (A)
VL Susol VCB 06 7.2 P Fixed 20 20 A 150mm 06 630
12 12 E E type drawout (for MESG) 25 25 B 210mm 13 1250
17 17.5 F F type drawout (for MESG) 32 31.5 D 275mm 20 2000
G G type drawout (for MESG) Compatible with 25 2500
K type drawout (for MCSG F existing products
K compatible with K
compatible with Pro-MEC type)
H H type drawout (for MCSG) K Pro-MEC G/T(T)
Note) 1. In case of 7.2kV
Note) 1. B
reaking current 31.5kA: E/F/G type 1) Phase distance 150mm only
can be used only with 7.2kV 2) 20/25kA: only 630/1250/2000A available (E/F/G)
2. K
type: Usable only 7.2/12kV 3) 31.5kA: only 1250/2000A available (E/F/G)
Compatible with Pro-MEC G/T(T) 2. K type: phase distance 150mm only
(for withdrawable type for MCSG) 3. In case of 12/17.5kV
1) H type: phase distance 150/210/275 all available
2) P type 630/1250A: phase distance 150/210 all available
3) In case of 20/25kA: 12/17.5kV E/F type phase distance 210 available
4) K type: compatible with Pro-MEC G/T(T) (phase distance 150mm)
5) F type (compatible with existing products): Available only to 20/25kA and
630/1250A (phase distance 210mm)
4. Rated current 2500A: only available 31.5kA P/H type (phase distance 210/275mm)
VL-06H20A06 M1 C1 T1 SB1 U1 A 14 7
VCL 06 H 20 A 06 A 14 7
Basic model name Rated voltage (kV) Rated short time current (kA) Rated current (A)
Susol VCB 06 7.2 20 20 06 630
VCL
Cradle 12 12 25 25 13 1250
17 17.5 32 31.5 20 2000
25 2500
Optional
TM Temperature Monitoring
Note) A is written only once in case of more
than one.
* AX: Must be selected at E, F, G-type
1250A, 2000A of 7.2kV 31.5kA VCB
35
Types and ordering information
24/25.8/36kV (VL-20/25/36)
Breaker
VL 20 H 13 B 06
Basic model name Rated voltage (kV) Version Rated short time current (kA) Phase distance/Compatibility Rated current (A)
VL Susol VCB 20 24 P Fixed 13 12.5 B 210mm 06 630
25 25.8 E E type drawout (for MESG) 16 16 F 265mm 13 1250
36 36 F F type drawout (for MESG) 25 25 D 275mm 20 2000
G G type drawout (for MESG) Enclosed type, 25 2500
G
K type drawout (for MCSG Tulip Contact
K Note) - P, E, F, G type : phase distance 265mm only
compatible with Pro-MEC type)
- K-type: 630A and 1250A - , 210mm and 265mm
H H type drawout (for MCSG) 2000A - phase distance 265mm only
- H-type: All ratings - dual phase distance,
210mm and 275mm dual
(2500A - phase distance 275mm only)
-E , F-type: phase distance and appearance are
distinguished with F and G
VL-20H13B06 M1 C1 T1 SB1 U1 A 14 7
36
Cradle
VCL 20 H 13 B 06 A 14 7
Basic model name Rated voltage (kV) Rated short time current (kA) Rated current (A)
Susol VCB 20 24 13 12.5 06 630
VCL
Cradle 25 25.8 16 16 13 1250
36 36 25 25 20 2000
25 2500
Optional
TM Temperature Monitoring
Note) A is written only once in case of more
than one.
37
Types and ordering information
7.2/12kV (LVB-06/12)
Breaker
LVB 06 G 40 L / 12 1A 2B BB6GT2
Basic model name Rated voltage (kV) Rated short time current (kA) Rated current (A) Connector and wire
LVB Susol VCB 06 7.2 32 31.5 12 1250A 2B A type connector, 4a4b
38
Cradle
LCL 06 G 40 D / 12 BCDT2
Basic model name Rated voltage (kV) Rated short time current (kA) Rated current (A)
Pro-MEC 06 7.2 32 31.5 12 1250A
LCL
Cradle 12 12 40 40 20 2000A
Note) 1. One out of T, T2 and T3 should be selected for G/T type(MCSG drawable type).
T2 is the standard and T (Product before Earthing S/W interlock change)
is suitable for compatibility with existing products.
T3 is available only for 1250/2000A.
2. U1(Reduced height type) and B(Earthing S/W) can not be selected simultaneously.
39
Types and ordering information
7.2/12/17.5/24/25.8/36kV (VH-06/12/17/20/25/36)
Breaker
VH 06 H 25 B 13
Rated voltage (kV) Version Rated short time current (kA) Phase distance/Compatibility Rated current (A)
Basic model name
06 7.2 P Fixed 25 25 A 150mm 12 1200A
VH Susol VCB
12 12 E E type drawout (for MESG) 32 31.5 B 210mm 13 1250A
17 17.5 F F type drawout (for MESG) 40 40 D 275mm 20 2000A
20 24 G G type drawout (for MESG) 50 50 E 300mm 25 2500A
25 25.8 K type drawout (for MCSG Note) K Compatible with K 30 3000A
K 1. 25kA is for 24/36kV Pro-MEC G/T(T)
36 36 compatible with Pro-MEC type) 2. 31.5/40kA is for 32 3150A
7.2/12/17.5/24/36kV
L 320mm
H H type drawout (for MCSG) 3. 50kA is for 7.2/12/17.5kV Note) K 40 4000A
can be selected for
Pro-MEC G/T(T)
compatible models 50 5000A
ONLY and the phase
distance is 150mm. Note) Refer to the rating
table for selecting
rated current.
VH-06H25B13 M1 C1 T1 SB2 U1 A 14 7
VCH 06 H 25 B 13 A 14 7
Basic model name Rated voltage (kV) Rated short time current (kA) Rated current (A)
Susol VCB 06 7.2 25 25 12 1200A
VCL
Cradle 12 12 32 31.5 13 1250A
17 17.5 40 40 20 2000A
20 24 50 50 25 2500A
25 25.8 30 3000A
36 36 32 3150A
40 4000A
50 5000A
Optional
TM Temperature Monitoring
Note) A is written only once in case of
more than one.
41
Type of circuit breakers
7.2/12/17.5/24/25.8/36kV (VL-06/12/17/20/25/36)
Ur Isc Ir[A] VCB CRADLE
Connector
[kV] [kA] p=130 p=150 p=210 p=265 p=275 Type Version Type Version
VCL-0608A04 E,F,G A
VL-0608A04 P,E,F,G
8 400 VCL-0608B04 E,F,G A
VL-0608B04 P,E,F,G A
VCL-0613A06 E,F,G A
VL-0613A06 P,E,F,G
12.5 630 VCL-0613B06 E,F,G A
VL-0613B06 P,E,F,G A
630 VL-0620A(K)06 P,E,F,G,K,H VCL-0620A(K)06 E,F,G,K,H P,E,F,G,K:A/B, H:B
7.2 20 1250 VL-0620A(K)13 P,E,F,G,K,H VCL-0620A(K)13 E,F,G,K,H P,E,F,G,K:A/B, H:B
2000 VL-0620A20 P,E,F,G,H VCL-0620A20 E,F,G,H P,E,F,G:A/B, H:B
630 VL-0625A(K)06 P,E,F,G,K,H VCL-0625A06 E,F,G,K,H P,E,F,G,K:A/B, H:B
25 1250 VL-0625A(K)13 P,E,F,G,K,H VCL-0625A13 E,F,G,K,H P,E,F,G,K:A/B, H:B
2000 VL-0625A(K)20 P,E,F,G,K,H VCL-0625A20 E,F,G,K,H P,E,F,G,K:A/B, H:B
630 VL-0632A06 P,H VCL-06H32A06 H B
31.5 1250 VL-0632A(K)13 P,E,F,G,K,H VCL-0632A13 E,F,G,K,H P,E,F,G,K:A/B, H:B
2000 VL-0632A(K)20 P,E,F,G,K,H VCL-0632A20 E,F,G,K,H P,E,F,G,K:A/B, H:B
630 VL-1220A(K)06 P,K,H VCL-1220A06 K,H K:A/B, H:B
1250 VL-1220A(K)13 P,K,H VCL-1220A13 K,H K:A/B, H:B
2000 VL-12H20A20 H VCL-12H20A20 H B
630 VL-1220B06 P,E,F,H VCL-1220B06 E,F,H P,E,F:A/B, H:B
20
1250 VL-1220B13 P,E,F,H VCL-1220B13 E,F,H P,E,F:A/B, H:B
2000 VL-1220B20 P,E,F,H VCL-1220B20 E,F,H P,E,F:A/B, H:B
630 VL-1220F06 E,F VCL-1220F06 E,F A/B
1250 VL-1220F13 E,F VCL-1220F13 E,F A/B
630 VL-1225A(K)06 P,K,H VCL-1225A06 K,H K:A/B, H:B
1250 VL-1225A(K)13 P,K,H VCL-1225A13 K,H K:A/B, H:B
2000 VL-1225A(K)20 K,H VCL-1225A20 K,H K:A/B, H:B
630 VL-1225B06 P,E,F,H VCL-1225B06 E,F,H P,E,F:A/B, H:B
12 25
1250 VL-1225B13 P,E,F,H VCL-1225B13 E,F,H P,E,F:A/B, H:B
2000 VL-1225B20 P,E,F,H VCL-1225B20 E,F,H P,E,F:A/B, H:B
630 VL-1225F06 E,F VCL-1225F06 E,F A/B
1250 VL-1225F13 E,F VCL-1225F13 E,F A/B
630 VL-1232A06 P,H VCL-12H32A06 H B
1250 VL-1232A(K)13 P,K,H VCL-1232A13 K,H K:A/B, H:B
2000 VL-1232A(K)20 K,H VCL-1232A20 K,H K:A/B, H:B
630 VL-1232B06 P,H VCL-12H32B06 H B
31.5
1250 VL-1232B13 P,H VCL-12H32B13 H B
2000 VL-1232B20 P,H VCL-12H32B20 H B
2500 VL-1232B25 P,H VCL-12H32B25 H B
2500 VL-1232D25 P,H VCL-12H32D25 H B
630 VL-17H20A06 H VCL-17H20A06 H B
1250 VL-17H20A13 H VCL-17H20A13 H B
2000 VL-17H20A20 H VCL-17H20A20 H B
630 VL-1720B06 P,E,F,H VCL-1720B06 E,F,H P,E,F:A/B, H:B
20
1250 VL-1720B13 P,E,F,H VCL-1720B13 E,F,H P,E,F:A/B, H:B
2000 VL-1720B20 P,E,F,H VCL-1720B20 E,F,H P,E,F:A/B, H:B
630 VL-1720F06 E,F VCL-1720F06 E,F A/B
1250 VL-1720F13 E,F VCL-1720F13 E,F A/B
630 VL-17H25A06 H VCL-17H25A06 H B
1250 VL-17H25A13 H VCL-17H25A13 H B
2000 VL-17H25A20 H VCL-17H25A20 H B
630 VL-1725B06 P,E,F,H VCL-1725B06 E,F,H P,E,F:A/B, H:B
17.5 25
1250 VL-1725B13 P,E,F,H VCL-1725B13 E,F,H P,E,F:A/B, H:B
2000 VL-1725B20 P,E,F,H VCL-1725B20 E,F,H P,E,F:A/B, H:B
630 VL-1725F06 E,F VCL-1725F06 E,F A/B
1250 VL-1725F13 E,F VCL-1725F13 E,F A/B
630 VL-1732A06 P,H VCL-17H32A06 H B
1250 VL-1732A13 P,H VCL-17H32A13 H B
2000 VL-1732A20 H VCL-17H32A20 H B
630 VL-1732B06 P,H VCL-17H32B06 H B
31.5
1250 VL-1732B13 P,H VCL-17H32B13 H B
2000 VL-1732B20 P,H VCL-17H32B20 H B
2500 VL-1732B25 P,H VCL-17H32B25 H B
2500 VL-1732D25 P,H VCL-17H32D25 H B
42
Ur Isc Ir[A] VCB CRADLE
Connector
[kV] [kA] p=130 p=150 p=210 p=265 p=275 Type Version Type Version
630 VL-2013B06 K,H VCL-2013B06 K,H K:A/B, H:B
1250 VL-2013B13 K,H VCL-2013B13 K,H K:A/B, H:B
630 VL-2013F06 P,E,F,G,K VCL-2013F06 E,F,G,K A/B
630 VL-2013G06 E,F VCL-2013G06 E,F A/B
12.5
1250 VL-2013F13 P,E,F,G,K VCL-2013F13 E,F,G,K A/B
1250 VL-2013G13 E,F VCL-2013G13 E,F A/B
630 VL-20H13D06 H VCL-20H13D06 H B
1250 VL-20H13D13 H VCL-20H13D13 H B
630 VL-2016B06 K,H VCL-2016B06 K,H K:A/B, H:B
1250 VL-2016B13 K,H VCL-2016B13 K,H K:A/B, H:B
630 VL-2016F06 P,E,F,G,K VCL-2016F06 E,F,G,K A/B
630 VL-2016G06 E,F VCL-2016G06 E,F A/B
16
1250 VL-2016F13 P,E,F,G,K VCL-2016F13 E,F,G,K A/B
1250 VL-2016G13 E,F VCL-2016G13 E,F A/B
24 630 VL-20H16D06 H VCL-20H16D06 H B
1250 VL-20H16D13 H VCL-20H16D13 H B
630 VL-2025B06 K,H VCL-2025B06 K,H K:A/B, H:B
1250 VL-2025B13 K,H VCL-2025B13 K,H K:A/B, H:B
2000 VL-20H25B20 H VCL-20H25B20 H B
630 VL-2025F06 P,E,F,G,K VCL-2025F06 E,F,G,K A/B
630 VL-2025G06 E,F VCL-2025G06 E,F A/B
1250 VL-2025F13 P,E,F,G,K VCL-2025F13 E,F,G,K A/B
25 1250 VL-2025G13 E,F VCL-2025G13 E,F A/B
2000 VL-2025F20 P,E,F,K VCL-2025F20 E,F,K A/B
2000 VL-2025G20 E,F VCL-2025G20 E,F A/B
630 VL-20H25D06 H VCL-20H25D06 H B
1250 VL-20H25D13 H VCL-20H25D13 H B
2000 VL-20H25D20 H VCL-20H25D20 H B
2500 VL-20H25D25 H VCL-20H25D25-AS H B
630 VL-2513B06 K,H VCL-2513B06 K,H K:A/B, H:B
1250 VL-2513B13 K,H VCL-2513B13 K,H K:A/B, H:B
630 VL-2513F06 P,E,F,G,K VCL-2513F06 E,F,G,K A/B
630 VL-2513G06 E,F VCL-2513G06 E,F A/B
12.5
1250 VL-2513F13 P,E,F,G,K VCL-2513F13 E,F,G,K A/B
1250 VL-2513G13 E,F VCL-2513G13 E,F A/B
630 VL-25H13D06 H VCL-25H13D06 H B
1250 VL-25H13D13 H VCL-25H13D13 H B
630 VL-2516B06 K,H VCL-2516B06 K,H K:A/B, H:B
1250 VL-2516B13 K,H VCL-2516B13 K,H K:A/B, H:B
630 VL-2516F06 P,E,F,G,K VCL-2516F06 E,F,G,K A/B
630 VL-2516G06 E,F VCL-2516G06 E,F A/B
16
1250 VL-2516F13 P,E,F,G,K VCL-2516F13 E,F,G,K A/B
1250 VL-2516G13 E,F VCL-2516G13 E,F A/B
25.8 630 VL-25H16D06 H VCL-25H16D06 H B
1250 VL-25H16D13 H VCL-25H16D13 H B
630 VL-2525B06 K,H VCL-2525B06 K,H K:A/B, H:B
1250 VL-2525B13 K,H VCL-2525B13 K,H K:A/B, H:B
2000 VL-25H25B20 H VCL-25H25B20 H B
630 VL-2525F06 P,E,F,G,K VCL-2525F06 E,F,G,K A/B
630 VL-2525G06 E,F VCL-2525G06 E,F A/B
1250 VL-2525F13 P,E,F,G,K VCL-2525F13 E,F,G,K A/B
25 1250 VL-2525G13 E,F VCL-2525G13 E,F A/B
2000 VL-2525F20 P,E,F,K VCL-2525F20 E,F,K A/B
2000 VL-2525G20 E,F VCL-2025G20 E,F A/B
630 VL-25H25D06 H VCL-25H25D06 H B
1250 VL-25H25D13 H VCL-25H25D13 H B
2000 VL-25H25D20 H VCL-25H25D20 H B
2500 VL-25H25D25 H VCL-25H25D25-AS H B
630 VL-3625D06 P,H VCL-3625D06 H P:A/B, H:B
1250 VL-3625D13 P,H VCL-3625D13 H P:A/B, H:B
36 25
2000 VL-3625D20 P,H VCL-3625D20 H P:A/B, H:B
2500 VL-3625D25 P,H VCL-3625D25 H P:A/B, H:B
Note) 1. Ur = Rated voltage 2. Isc = Rated short-circuit current
3. Ir = Rated normal current 4. p = Phase distance
5. E,F and G types are cradles for MESG(Metal Enclosed Switchgear) and H type for MCSG(Metal Clad Switchgear)
6. For the partial replacement of 7.2kV 8/12.5kA VCB, in case of using the existing old type cradle and replacing breaker only,
please order type B (Compatible with existing breaker). Compatibille busbars are required for fixed version.
To replace VCB fully(breaker and cradle) please order type A for breaker and compatible cradle B.
43
Type of circuit breakers
7.2/12/17.5/24/25.8/36kV (VH-06/12/17/20/25/36)
Ur Isc Ir[A] VCB CRADLE
Connector
[kV] [kA] p=150 p=210 p=254 p=275 p=320 Type Version Type Version
VH-0632A13 P,E,F,G VCL-0632A13 E,F,G
1250 A/B
LVB-06-32L/12 P,E,F,G,G/T LCL-06G-32D/12-T2 G/T
VH-0632A20 P,E,F,G VCL-0632A20 E,F,G
31.5 2000 A/B
LVB-06-32L/20 P,E,F,G,G/T LCL-06G-32D/20-T2 G/T
VH-0632B32 P,E,F,K,H VCL-0632B32 E,F,G,K,H
3150 P,E,F,G,K: A/B,H:B
LVB-06-32L/30 P,E,F,G/T LCL-06G-32D/30-T2 G/T
VH-0640A13 P,E,F,G,K,H VCL-0640A13 E,F,G,K,H
1250 P,E,F,G,K: A/B,H:B
LVB-06-40L/12 P,E,F,G,G/T LCL-06G-40D/12-T2 G/T
VH-0640A20 P,E,F,G,K,H VCL-0640A20 E,F,G,K,H
2000 P,E,F,G,K: A/B,H:B
LVB-06-40L/20 P,E,F,G,G/T LCL-06G-40D/20-T2 G/T
7.2 40
VH-0640B32 P,E,F,K,H VCL-0640B32 E,F,G,K,H
3150 P,E,F,G,K: A/B,H:B
LVB-06-40L/30 P,E,F,G/T LCL-06G-40D/30-T2 G/T
4000 VH-0640D40 P,K,H VCL-06K40D40 K,Ha,Hb B
5000 VH-06H40L50 H VCL-06Ha40L50 Ha B
1250 VH-0650B13 P,H VCL-06H50B13 H B
2000 VH-0650B20 P,H VCL-06H50B20 H B
2500 VH-0650D25 P,H VCL-06H50D25 H B
50
3150 VH-0650D32 P,H VCL-06H50D32 H B
4000 VH-0650D40 P,K,H VCL-06K50D40 K,Ha,Hb B
5000 VH-06H50L50 H VCL-06Ha50L50 Ha B
1250 LVB-12G-32L/12-T2 G/T LCL-12G-32D/12-T2 G/T A/B
2000 LVB-12G-32L/20-T2 G/T LCL-12G-32D/20-T2 G/T A/B, H:B
31.5
VH-1232B32 K,H VCL-1232B32 K,H A/B
3150
LVB-12G-32L/30-T2 G/T LCL-12G-32D/30-T2 G/T A/B
VH-1240A(K)13 K,H VCL-1240A(K)13 K,H K:A/B, H:B
1250
LVB-12G-40L/12-T2 G/T LCL-12G-40D/12-T2 G/T A/B
VH-1240A(K)20 K,H VCL-1240A(K)20 K,H K:A/B, H:B
2000
LVB-12G-40L/20-T2 G/T LCL-12G-40D/20-T2 G/T A/B
40
VH-1240B32 K,H VCL-1240B32 K,H K:A/B, H:B
12 3150
LVB-12G-40L/30-T2 G/T LCL-12G-40D/30-T2 G/T A/B
4000 VH-1240D40 P,K,H VCL-12K40D40 K,Ha,Hb B
5000 VH-12H40L50 H VCL-12Ha40L50 Ha B
1250 VH-1250B13 P,H VCL-12H50B13 H B
2000 VH-1250B20 P,H VCL-12H50B20 H B
2500 VH-1250D25 P,H VCL-12H50D25 H B
50
3150 VH-1250D32 P,H VCL-12H50D32 H B
4000 VH-1250D40 P,K,H VCL-12K50D40 K,Ha,Hb B
5000 VH-12H50L50 H VCL-12Ha50L50 Ha B
3150 VH-1732B32 H VCL-1732B32 H B
31.5
3150 VH-1732D32 H VCL-1732D32 H B
1250 VH-1740B13 K,H VCL-1740B13 K,H K:A/B, H:B
2000 VH-1740B20 K,H VCL-1740B20 K,H K:A/B, H:B
40 3150 VH-1740C32 K VCL-1740C32 H H:B
3150 VH-1740D32 H VCL-1740D32 K A/B
17.5
4000 VH-1740D40 P,H VCL-1740D40 Ha,Hb B
1250 VH-1750B13 P,H VCL-17H50B13 H B
2000 VH-1750B20 P,H VCL-17H50B20 H B
50 2500 VH-1750D25 P,H VCL-17H50D25 H B
3150 VH-1750D32 P,H VCL-17H50D32 H B
4000 VH-1750D40 P,H VCL-1750D40 Ha,Hb B
44
Ur Isc Ir[A] VCB CRADLE
Connector
[kV] [kA] p=150 p=210 p=275 p=300 Type Version Type Version
25 2500 VH-2025D25 P,H VCL-20H25D25 H B
VCL-20H32B13 H B
1250 VH-2032B13 P,H
VCL-20H32F13 H B
VCL-20H32B20 H B
2000 VH-2032B20 P,H
31.5 VCL-20H32F20 H B
1250 VH-2032D13 P,H VCL-20H32D13 H B
2000 VH-2032D20 P,H VCL-20H32D20 H B
24 3150 VH-2032D32 P,H VCL-20H32D32 H B
VCL-20H40B13 H B
1250 VH-2040B13 P,H
VCL-20H40F13 H B
VCL-20H40B20 H B
2000 VH-2040B20 P,H
40 VCL-20H40F20 H B
1250 VH-2040D13 P,H VCL-20H40D13 H B
2000 VH-2040D20 P,H VCL-20H40D20 H B
3150 VH-2040D32 P,H VCL-20H40D32 H B
25 2500 VH-2525D25 P,H VCL-25H25D25 H B
VCL-25H32B13 H B
1250 VH-2532B13 P,H
VCL-25H32F13 H B
VCL-25H32B20 H B
2000 VH-2532B20 P,H
31.5 VCL-25H32F20 H B
1250 VH-2532D13 P,H VCL-25H32D13 H B
2000 VH-2532D20 P,H VCL-25H32D20 H B
25.8 3150 VH-2532D32 P,H VCL-25H32D32 H B
VCL-25H40B13 H B
1250 VH-2540B13 P,H
VCL-25H40F13 H B
VCL-25H40B20 H B
2000 VH-2540B20 P,H
40 VCL-25H40F20 H B
1250 VH-2540D13 P,H VCL-25H40D13 H B
2000 VH-2540D20 P,H VCL-25H40D20 H B
3150 VH-2540D32 P,H VCL-25H40D32 H B
1200 VH-2725E12 P,H VCL-27H25E12 H B
27 25
2000 VH-2725E20 P,H VCL-27H25E20 H B
1250 VH-3625E13 P,H VCL-36H25E13 H B
25 2000 VH-3625E20 P,H VCL-36H25E20 H B
3150 VH-3625E32 P,H VCL-36H25E32 H B
1250 VH-3632E13 P,H VCL-36H32E13 H B
36 31.5 2000 VH-3632E20 P,H VCL-36H32E20 H B
3150 VH-3632E32 P,H VCL-36H32E32 H B
1250 VH-3640E13 P,H VCL-36H40E13 H B
40 2000 VH-3640E20 P,H VCL-36H40E20 H B
3150 VH-3640E32 P,H VCL-36H40E32 H B
Note) 1. Ur = Rated voltage
2. Isc = Rated short-circuit current
3. Ir = Rated normal current
4. p = Phase distance
5. H type is MCSG style drawable type with a box type cradle for CB compartment construction.
6. G/T types are MCSG style drawable types with a cradle for builting in the switchgear , not a box type. (K of VCL type name indicates 4000A)
Example of G/T type : LVB-06G-32L/12-T2, LCL-06G-32D/12-T2
7. G/T types use LVB and LCL names.
8. E, F and G types provide cradles for MESG(Metal Enclosed Switchgear) and H, G/T types for MCSG(Metal Clad Switchgear).
9. In case of 7.2/12kV, 31.5kA/40kA H type: Please contact us.
45
Ratings - 7.2kV 8/12.5kA 400/630A
VL-06
Control voltage Closing coil (V) AC/DC 100~130V, AC/DC 200~250V, DC 125V, DC 24~30V, DC 48~60V, AC 48V
Trip coil (V) AC/DC 100~130V, AC/DC 200~250V, DC 125V, DC 24~30V, DC 48~60V, AC 48V
Electrical E2 (List1)
46
Ratings - 7.2/12/17.5kV 20/25kA 630/1250/2000A
VL-06/12/17
Rated normal current Ir (A) 630 1250 2000 630 1250 2000 630 1250 2000
Trip coil (V) DC 24~30V, DC 48~60V, DC 110V, DC 125V, DC 220~250V, AC 48V, AC 100~130V, AC 220~250V
Electrical E2 (List3)
Drawout E, F, G type (for MESG), H type (for MCSG) E, F type (for MESG), H type (for MCSG)
Weight Breaker (E, F, G, K type) (kg) 100 100 130 115 (120) 115 (120) 130 (140) 115 (120) 115 (120) 130 (140)
Cradle (E, F, G, K type) (kg) 170 170 180 170 (200) 170 (200) 180 (200) 170 (200) 170 (200) 180 (200)
Dimensions Breaker (P, E, F, G, K, H type) Page 98~109 Page 98~109 Page 98~109
47
Ratings - 7.2/12/17.5kV 31.5kA 630/1250/2000/2500A
VL-06/12/17
Rated normal current Ir (A) 630 1250 2000 630 1250 2000 2500 630 1250 2000 2500
Control voltage Closing coil (V) DC 24~30V, DC 48~60V, DC 110V, DC 125V, DC 220~250V, AC 48V, AC 100~130V, AC 220~250V
Phase distance ** (mm) 150 150 (210) 210 (275) 150 (210) 210 (275)
Weight Breaker (H type) (kg) 100 100 130 115/120 115/120 130/140 160/175 115/120 115/120 130/140 165/175
Cradle (H type) (kg) 170 170 200 170/200 170/200 170/200 260/290 170/200 170/200 170/200 260/290
Breaker (P, E, F, G, K type) (kg) 85 85 100 85/100 85/100 100/115 120/135 85/100 85/100 100/115 120/135
48
Ratings - 24/25.8kV 12.5/16/25kA 630/1250/2000/2500A
VL-20/25
Rated normal current Ir (A) 630 1250 630 1250 630 1250 2000 2500
Note1)
Rated frequency fr (Hz) 50/60
Control voltage Closing coil (V) DC 24~30V, DC 48~60V, DC 110V, DC 125V, DC 220~250V, AC 48V, AC 100~130V, AC 220~250V
Trip coil (V) DC 24~30V, DC 48~60V, DC 110V, DC 125V, DC 220~250V, AC 48V, AC 100~130V, AC 220~250V
Drawout E,F,G type (for MESG) / K, H type (for MCSG) H type (for MCSG)
Weight Breaker (H type) (kg) 120 (130) 130 (140) 150 (160)
Dimensions Breaker (P, E, F, G, K, H type) Page 158~167 Page 168~174 Page 174~178
49
Ratings - 36kV 25kA 630/1250/2000/2500A
VL-36
Control voltage Closing coil (V) DC 24~30V, DC 48~60V, DC 110V, DC 125V, DC 220, AC 48V, AC 100~130V, AC 220~250V
Trip coil (V) DC 24~30V, DC 48~60V, DC 110V, DC 125V, DC 220, AC 48V, AC 100~130V, AC 220~250V
Electrical E2 (List 3)
50
Ratings - 7.2/12kV 31.5/40kA 1250/2000/3150A
LVB-06/12
Item
LVB-06-3232 LVB-06-4012, 20, 32 LVB-12-3232 LVB-12-4012, 20, 32
Rated voltage Ur (kV) 7.2 7.2 12 12
Rated normal current Ir (A) 3150 * 1250 2000 3150 * 3150 * 1250 2000 3150 *
Rated short-time withstand current Ik/tk (kA/s) 31.5/3 40/3 31.5/3 40/3
Electrical E2 (List1)
Weight Breaker (MESG, MCSG) (kg) 210, 220 135, 160 135, 160 210, 220 220 164 165 220
Cradle (MESG, MCSG) (kg) 135, 155 55, 110 63, 117 135, 155 155 110 117 155
Dimensions Breaker (MESG, MCSG) Page 197~198 Page 193~194 Page 197~198 Page 197~198 Page 193~194 Page 197~198
Cradle (MESG, MCSG) Page 199~201 Page 195~196 Page 199~201 Page 199~201 Page 195~196 Page 199~201
51
Ratings - 7.2/12/17.5kV 40kA 1250/2000A
VH-06/12/17
Rated normal current Ir (A) 1250 2000 1250 2000 1250 2000 1250 2000 1250 2000
Rated short-circuit breaking capacity (MVA) 499 831 499 831 1212
Control voltage Closing coil (V) DC 48V, DC 110V, DC 125V, DC 220~250V, AC 48V, AC 110V, AC 220V
Trip coil (V) DC 48V, DC 110V, DC 125V, DC 220~250V, AC 48V, AC 110V, AC 220V
Auxiliary contacts
4a4b, 10a10b
Electrical E2 (List 3)
52
Ratings - 7.2/12/17.5kV 31.5/40kA 3150A
VH-06/12/17
Item VH-06/12/1732/4032
Rated voltage Ur (kV) 7.2 12 17.5
Control voltage Closing coil (V) DC 48V, DC 110V, DC 125V, DC 220~250V, AC 48V, AC 110V, AC 220V
Trip coil (V) DC 48V, DC 110V, DC 125V, DC 220~250V, AC 48V, AC 110V, AC 220V
Electrical E2 (List 3)
53
Ratings - 7.2/12/17.5kV 50kA 1250/2000/2500/3150A
VH-06/12/17
Rated normal current Ir (A) 1250 2000 2500 3150 1250 2000 2500 3150 1250 2000 2500 3150
Control voltage Closing coil (V) DC 48V, DC 110V, DC 125V, DC 220~250V, AC 48V, AC 110V, AC 220V
Trip coil (V) DC 48V, DC 110V, DC 125V, DC 220~250V, AC 48V, AC 110V, AC 220V
Electrical E2 (List3)
Drawout H
type (for MCSG)
Weight Breaker (H type) (kg) 230 287 290 230 287 290 230 287 290
Cradle (H, type) (kg) 175 320 320 175 320 320 175 320 320
Dimensions Breaker (H type) Page 214 Page 216 Page 214 Page 216 Page 214 Page 216
Cradle (H, type) Page 215 Page 217 Page 215 Page 217 Page 215 Page 217
54
Ratings - 7.2/12/17kV 40/50kA 4000A
VH-06/12/17
Rated short-circuit breaking capacity (MVA) 499 831 1212 624 1040 1515
Control voltage Closing coil (V) DC 48V, DC 110V, DC 125V, DC 220~250V, AC 48V, AC 110V, AC 220V
Trip coil (V) DC 48V, DC 110V, DC 125V, DC 220~250V, AC 48V, AC 110V, AC 220V
55
Ratings - 7.2/12kV 40/50kA 4000A
VH-06/12
Control voltage Closing coil (V) DC 48V, DC 110V, DC 125V, DC 220~250V, AC 48V, AC 110V, AC 220~250V
Trip coil (V) DC 48V, DC 110V, DC 125V, DC 220~250V, AC 48V, AC 110V, AC 220~250V
Electrical E2 (List 3)
56
Ratings - 7.2/12kV 40/50kA 5000A
VH-06/12
Control voltage Closing coil (V) DC 48V, DC 110V, DC 125V, DC 220~250V, AC 48V, AC 110V, AC 220V
Electrical E2 (List1)
Drawout * K type
57
Ratings - 24/25.8kV 25/31.5/40kA 1250/2000/2500/3150A
VH-20/25
Rated normal current Ir (A) 2500 1250 2000 3150 1250 2000 3150
Rated short-circuit making current Ip (kA) 2.5×Isc (50Hz)/2.6×Isc (60Hz) 2.6×Isc (60Hz) 2.5×Isc (50Hz)/2.6×Isc (60Hz)
Control voltage Closing coil (V) DC 48V, DC 110V, DC 125V, DC 220~250V, AC 48V, AC 110V, AC 220V
Trip coil (V) DC 48V, DC 110V, DC 125V, DC 220~250V, AC 48V, AC 110V, AC 220V
Electrical E2 (List3)
Phase distance ** (mm) 275 210 (275) 210 (275) 275 210 (275) 210 (275) 275
Weight Breaker (H type) (kg) 295 256 (273) 256 (273) 318 256 (273) 256 (273) 318
Cradle (H type) (kg) 316 257 (284) 257 (284) 316 257 (284) 257 (284) 316
Dimensions Breaker (H type) Page 224 Page 226~229 Page 231 Page 226~229 Page 231
Cradle (H type) Page 225 Page 227, 230 Page 232 Page 227, 230 Page 232
58
Ratings - 36kV 25/31.5/40kA 1250/2000/3150A
VH-36
Rated normal current Ir (A) 1250 2000 3150 1250 2000 3150 1250 2000 3150
Control voltage Closing coil (V) DC 48V, DC 110V, DC 125V, DC 220~250V, AC 48V, AC 110V, AC 220V
Trip coil (V) DC 48V, DC 110V, DC 125V, DC 220~250V, AC 48V, AC 110V, AC 220V
Electrical E2 (List3)
Weight Breaker (H type) (kg) 400 490 400 490 400 490
Dimensions Breaker (H type) Page 233 Page 235 Page 233 Page 235 Page 233 Page 235
Cradle (H type) Page 234 Page 236 Page 234 Page 236 Page 234 Page 236
59
Accessory
Supplied as
Mounting
Type Accessory VL: 7.2kV Remarks page
Position VL: 20/25kA VH
8/12.5kA
U Under Voltage Trip Coil Option Option Option Attached at the factory 68
A3 Position S/W(Test: 1a1b, Service: 2b) Option Option Option Attached at the factory 69
A4 Position S/W(Test: 2a, Service: 2a) Option Option Option Attached at the factory 69
A5 Position S/W(Test: 1a1b, Service: 1a1b) Option Option Option Attached at the factory 69
Breaker A6 Latch Checking Switch - - Option Attached at the factory 70
(Internal)
C Counter ● ● ● Attached at the factory 70
AA Lead Wire: A/B type connector Option Option Option Attached at the factory 74
AB Plug/Terminal for Lead Wire Option Option Option Attached at the factory 74
* : Basic Installation
60
Supplied as
Mounting
Type Accessory VL: 7.2kV Remarks page
Position VL: 20/25kA VH
8/12.5kA
ES(Earthing Switch)
A2 - Option Option Attached at the factory 83
with Position Switch(2a2b)
ES(Earthing Switch)
A4 - Option Option Attached at the factory 83
with Position Switch(6a6b)
ES(Earthing Switch)
A5 - Option Option Attached at the factory 83
with Keylock
ES(Earthing Switch)
A6 - Option Option Attached at the factory 84
with Locking magnet: DC110V
ES(Earthing Switch)
A7 - Option Option Attached at the factory 84
with Locking magnet: DC220V
ES(Earthing Switch)
A8 - Option Option Attached at the factory 84
with Locking magnet: DC125V
ES(Earthing Switch)
A9 - Option Option Attached at the factory 84
with Locking magnet: DC24V
ES(Earthing Switch)
AA - Option Option Attached at the factory 84
with Locking magnet: DC48V
ES(Earthing Switch)
AB - Option Option Attached at the factory 84
Cradle with Locking magnet: AC48V
ES(Earthing Switch)
AC - Option Option Attached at the factory 84
with Locking magnet: AC110V
ES(Earthing Switch)
AD - Option Option Attached at the factory 84
with Locking magnet: AC220V
AM Type H Lead Wire 4a4b (Normal cable) - Option Option Attached at the factory 89
61
Accessory
VL type
Motor •Charge the closing spring of a circuit breaker by
the external power source. When the charging is
complete, control power of the motor will be
"OFF" by the built-in Limit S/W. Without the
external power source, charge manually.
Main
shaft
Charge completion
contact
Motor
VL type
DC 24~
DC 48~ AC 100~ AC 200~
Input voltage (Vn) DC 110V DC 125V DC 220V AC 48V
30V 60V 130 250V
Load current (A) ≤5 ≤3 ≤1 ≤ 1 ≤ 0.5 ≤ 3 ≤ 1 ≤ 0.5
Starting current (A) 5 times of load current
Charge time Within 5 sec.
Note) Rated operation and control voltage range, see page 66.
VH type
Motor
VH Type
Input voltage (Vn) DC 48V DC 110V DC 125V DC 220V AC 48V AC 110V AC 220V
Load current (A) ≤6 ≤3 ≤3 ≤ 2.6 ≤6 ≤3 ≤ 2.6
Starting current (A) ≤ 30 ≤ 20 ≤ 20 ≤ 17 ≤ 30 ≤ 20 ≤ 17
Charge time Within 12 sec.
Note) Rated operation and control voltage range, see page 66.
62
Closing Coil: C Installed inside of a breaker as standard
VL type
•It is a control device which closes a circuit
breaker, when applying voltage continuously or
instantaneously over 200ms to the coil control
terminals.
Closing coil
VL type
DC 24~ DC 48~ AC 100~ AC 200~
Input voltage (Vn) DC 110V DC 125V DC 220V AC 48V
30V 60V 130 250V
Power consumption (inrush, W) 200
Power consumption (steady, W) ≤5
Note) Rated operation and control voltage range, see page 66.
VH type
•It is a control device which closes a circuit
breaker, when applying voltage continuously
about 45ms to the coil control terminals.
Electrical pumping preventing circuit is built in.
Closing coil
VH Type
Input voltage (Vn) DC 48V DC 110V DC 125V DC 220V AC 48V AC 110V AC 220V
Rated current (A) ≤8 ≤ 3 ≤ 3 ≤ 2.5 ≤8 ≤ 3 ≤ 2.5
Note) Rated operation and control voltage range, see page 66.
63
Accessory
VL type
•It is a control device which trips a circuit breaker
from remote place, when applying voltage
continuously or instantaneously over 35ms to
coil control terminals.
•When UVT coil is installed, its location is
changed.
Trip coil
VL type
DC 24~ DC 48~ AC 100~ AC 200~
Input voltage (Vn) DC 110V DC 125V DC 220V AC 48V
30V 60V 130 250V
Power consumption (inrush, W) 200
Power consumption (steady, W) ≤5
Note) Rated operation and control voltage range, see page 66.
VH type
•It is a control device which trips a circuit
breaker, when applying voltage continuously or
instantaneausly over 35ms to the coil control
terminals.
Trip coil
VH Type
Input voltage (Vn) DC 48V DC 110V DC 125V DC 220V AC 48V AC 110V AC 220V
Rated current (A) ≤8 ≤3 ≤3 ≤ 2.5 ≤8 ≤3 ≤ 2.5
Note) Rated operation and control voltage range, see page 66.
64
Secondary Trip Coil: A1 Installed inside of a breaker as an option
VL type
•It is a control device which trips a circuit breaker
doubly from the outside. If the trip coil (T ) fails,
it can trip a circuit breaker safely.
•Trip coil: Install it at existing location.
•Secondary trip coil: Install it on the right side of
the trip coil.
•It is not available with UVT coil when installing
secondary trip coil.
Secondary
Trip coil
VL type
DC 24~ DC 48~ AC 100~ AC 200~
Input voltage (Vn) DC 110V DC 125V DC 220V AC 48V
30V 60V 130 250V
Power consumption (inrush, W) 200
Power consumption (steady, W) ≤5
VH type
•It is a control device which trips a circuit breaker
doubly from the outside. If the trip coil (T) fails, it
can trip a circuit breaker safely.
•It is not available with UVT coil when installing
secondary trip coil.
Secondary
Trip coil
VH Type
Input voltage (Vn) DC 48V DC 110V DC 125V DC 220V AC 48V AC 110V AC 220V
Rated current (A) ≤8 ≤ 3 ≤ 3 ≤ 2.5 ≤8 ≤ 3 ≤ 2.5
65
Accessory
Susol VCB
Item Remarks
VL: 7.2kV 8/12.5kA VL: 20/25kA VH
AC 85~110% 85~110% 85~110%
Motor
DC 75~110% 85~110% 85~110%
AC 85~110% 85~110% 85~110%
Closing
DC 75~125% 85~110% 85~110%
AC 60~125% 85~110% 85~110%
Trip
DC 60~125% 70~110% 70~110%
IEC62271-100 (2008)
Applied standards IEC62271-100 (2008) IEC62271-100 (2008)
KSC4611
VL type : T9
•This trip coil uses the output of the CT as its
Current Trip Coil control power source and is used with over
current relay in combination. Two current trip
coils are supplied.
•Coil burden is 90VA.(T9)
•Coil impedance(Z) is like below
- 3A: 10Ω or less, Operating current AC 3A (T9)
- 1A: 160Ω or less, Operating current AC 1A (AV)
- 5A: 6Ω or less, Operating current is AC 5A (AW)
•CT must be installed at load side.
If it is installed at bus side there is the danger of
malfunction or damage to CT.
•Don’t disconnect the control power connector on
main power is live condition at service position.
Otherwise there is the danger of malfunction or
damage to CT.
VL type : AV, AW
66
Auxiliary Contact: SA Installed inside of a breaker as an option
VL type
•It is a contact used to monitor ON/OFF status of
Auxiliary contact a breaker from remote place.
•The auxiliary contacts supplied as standard
configuration is 4a4b. 10a10b is also available
on request.
ᆞFor 7.2kV 8/12.5kA VCB standard configuration
is 2a2b. 4a4b and 6a6b are optional.
VL: 7.2kV VL: 20/25kA,
Item
8/12.5kA VH
Standard 2a2b 4a4b
Optional 4a4b, 6a6b 10a10b
VH type
Auxiliary contact
VL/VH Type
Item Resistive load (A) Inductive load (A) Remarks
250V 10 5
AC
125V 10 5
Contact
250V 10 5 For all models
configuration
DC 125V 10 5
30V 10 5
67
Accessory
VL type VH type
VL type
•It is installed inside of a breaker to trip when the main power or control power voltage drops below certain value.
Instantaneous type is only available with UVT coil and Time delay type is available by connecting UVT coil and UVT
time delay controller.
•The closing of a circuit breaker is impossible mechanically or electrically if control power is not supplied to UVT.
To close the circuit breaker, 65~85% of rated voltage should be applied.
•UVT and secondary trip coil will not be selected together.
VL type
DC 24~ DC 48~ AC 100~ AC 200~
Input voltage (Vn) DC 110V DC 125V DC 220V AC 48V
30V 60V 130 250V
VH Type
Input voltage (Vn) DC 48V DC 110V DC 125V DC 220V AC 48V AC 110V AC 220V
68
Position Switch: A3, A4, A5 Installed inside of a breaker as an option
•This switch is used to indicate the breaker position (SERVICE, TEST), and contact configuration is 2a2a or 2a2b.
VL: 20/25kA VH
Position
switch
Position
switch
Contact configuration
1 3 5 7 1 3 5 7 1 3 5 7
2 4 6 8 2 4 6 8 2 4 6 8
1a1b(TEST) 2b(SERVICE) 2a(TEST) 2a(SERVICE) 1a1b(TEST) 1a1b(SERVICE)
69
Accessory
VH type
•This switch works in conjunction with the
mechanism of the breaker. It checks if the
breaker is ready to be closed.
•When the mechanism is OFF and the closing
spring is at charged status the switch becomes
"ON", which means the mechanism is ready to
be closed.
•If the latch is not in a proper position the switch
prevents the breaker from closing.
In case of VH type it is connected internally in
series with the closing coil.
Latch checking
switch
VL/VH type
•It displays the total number of ON/OFF
operations of a breaker.
70
Keylock: A7 Installed inside of a breaker as an option
VL type
•The key is to unlock the locking device first to
close the breaker electrically and mechanically.
*How to operate
- It is not possible to pull out the key in the
unlocked position, possible only in locked status.
- Pushing "OFF" switch of a breaker turn the key
counter-clockwise to the locked position and pull
it out.
- It is not possible to close the breaker electrically
and mechanically in the locked position.
- Insert the key and turn clockwise and then the
breaker can be closed electrically and
mechanically.
Keylock
VH type
*How to operate
- It is not possible to pull out the key in the
unlocked position, possible only in locked status.
- Trip the breaker first and then turn the key
counter-clockwise to the locked position and pull
it out.
- It is not possible to close the breaker electrically
and mechanically in the locked position.
Keylock
71
Accessory
VL type
•It is to prevent manual operation of ON/OFF
button due to user’s wrong handling.
•It is not possible to handle ON/OFF operation
under the “Button lock” status.
Button Padlock
VH type
Button Padlock
72
Button Cover: A9 Installed outside of a breaker as an option
VL type
•It is a protection cover to prevent an accident
due to unintended operation of ON/OFF button.
•Use the push-bar to operate the ON/OFF
button.
Push Bar
Button Cover
VH type
Push Bar
Button Cover
73
Accessory
VL/VH type
•It is to connect with the control circuit of a
Lead wire breaker from outside. (supply wire length: 2m)
•A type connector is supplied for P/E/F/G type of
VL VCB.
•B type connector is supplied for P type of VH
VCB.
A type connector
•In case of H type breaker of VL and VH models
the Lead wire is installed in the cradle when
supplied.
B type connector
Cradle type P E F G H
VCB model
Enclosed in the breaker
VL Enclosed in the breaker
Installed in the cradle (option)
VL/VH type
•It is connector to connect with the connector installed in the breaker. (supply connectors and terminal only for lead wire)
•Type of connector is depends on the type of connector installed in the breaker- A or B.
74
Plug interlock: AC Installed inside of a breaker as an option
Door interlock
75
Accessory
MOC
VH type
MOC
76
Locking magnet: AF Installed inside of a breaker as an option
VL type
•It allows the drawing-in of the breaker in the
TEST position under the condition that the
control power connector on the cradle (H type)
is connected with the connecting terminal of the
breaker and the power is supplied.
•During the drawing-in or in the SERVICE
position draw-in/out is allowed without supplying
power.
* Control power rating is the same as that of a motor.
Locking
magnet
VH type
Locking magnet
77
Accessory
VL type
•Device for monitoring the functions of the trip
coils.
•Supplied as standard for VL model and optional
for VH model.
•To monitor the trip coils connect its terminals
with the trip coil monitoring relay as shown on
the circuit diagram.
- If the trip coil is normal: closed-circuit
consisting
- If the trip coil is damaged: open circuit
1) Terminals A5 and A6 monitor the trip coils in
closed position of the breaker.
2) Terminal A6 and aux. contact terminal 34
monitor the trip coils in trip position of the
breaker.
•Coil Test Unit is opional, which enable
monitoring the coils by connecting in parallel
with the trip coil operation switch.
•In case Secondary Trip Coil Monitoring contact,
Trip Coil T1,T2,T3 are available.
VH type
78
Coil Test Unit: CTU Installed outside of a breaker as an option
•When no current flows through the coil it gives the test current which does not cause the coil to operate to check
whether the coil is disconnected or not.
- If the test current flows normally: coil normal
- If the test current does not flow through: coil disconnected
※ As it is connected in parallel with the control part of the coil the normal operation of the coil is not affected.
※ Monitoring of the running coils is not possible.
※ One test unit can monitor up to two coils.
Input voltage
AC/DC 75~264V
Fail 1
24~250V
(AC/DC) Alarm 1
Shunt 1
Coil
Test
Fail 2
Unit
24~250V
(AC/DC) Alarm 2
Shunt 2
CTU CTU
Input voltage Input voltage
Coil drive power(+) (+) (+)
1 2
Coil drive power
5 Fail (LED)
Fail (RELAY)
7
Coil Alarm (LED)
Coil test current Alarm (RELAY)
Coil Test Unit
Coil drive power(-)
79
Accessory
Ratings
Ratings Specification •It gets a circuit breaker tripped electrically within
regular time when control power supply is
Model CB - T1 CB - T2 broken down and is used with Shunt coil, SHT.
Rated input voltage (V) AC 100/110 AC 200/220 In case there is no DC power, It can be used as
the rectifier which supplies DC power to a circuit
Frequency (Hz) 50/60 50/60
breaker by rectifying AC power.
Rated charge voltage (V) 140/155 280/310
•Tripping within 30 seconds on the power failure
Charging time Within 10sec. Within 10sec. is possible. However after that automatic trip
Trip possible time Within 30sec. Within 30sec. circuit must be configured separately in the
switchgear.
Range of Input voltage 85%~110% 85%~110%
Condenser capacity (μF) 1,000 560
(Mounting hole)
Circuit diagram
80
UVT Time delay: UDC Installed outside of a breaker as an option
•UVT time delay, UDC is to delay the trip signal from UVT.
•Without UDC the breaker will be tripped instantaneously by the trip signal from UVT installed inside of the breaker
even in the the momentary power failure.
•UDC can delay the trip time to avoid this unintended instantaneous trip in the event of such power failure.
•It can be installed on the cradle or inside of the switchgear.
•UDC provides output contacts for indication of trip status due to the UVT coil inside of the breaker.
b contact is closed at normal state and a contact is closed at trip.
1. Characteristics
48~60 48
100~130 100~130 0.65~0.85 Vn 0.4~0.65 Vn 200 ≤ 5 0.5, 1, 1.5, 3
200~250 200~250
- Operating voltage ranges are based on the minimum value of each rated voltage (Vn)
Rated voltage (V) Rated current (A), Resistive load Max. switching voltage (A) Max. switching current (A)
24V DC ≤ 12
110V DC
120V AC ≤ 12 15
250V AC
250V AC ≤ 10
3. Wiring diagram
Delayed
trip signal
5 7
14 16
18(a)
Operating UVT Delay
UVT output 19(c)
18 19 20 contact 20(b) Controllor
a c b
0.5
1
Signal for 1.5
tripping 14 16
3
DC48~60V
AC48
[sec]
Instantaneous
5 7 trip signal
Time Delay for UVT
D1
D2
UVT
81
Accessory
monitoring unit: TM
82
Earthing Switch: A1 Built-in a cradle as an option
*R
egarding the operations of earthing switch and
related accessories see the instruction manual.
*A
pplicable Standards: IEC 62271-102
Earthing
Switch
: A2, A4
•In case of using earthing switch it can be added to indicate the ON / OFF
status of the earthing switch.
83
Accessory
•In case of using earthing switch it can be added for two types
of interlocking.
1) Interlock to keep opening
2) Interlock to keep earthing
: A6~AD
•In case of using earthing switch it can be added to prevent the earthing
switch from opening or earthing before it is energized.
•Verify if the locking magnet is energized before opening or earthing the
earthing switch.
•Control voltage
- DC 24V / DC 48V / DC 110V / DC 125V / DC 220V
- AC 48V / AC 110V / AC 220V
84
Shutter padlock: AE Built-in a cradle as an option
Shutter
padlock
Circuit diagram
121 122 124 125 127 128 130 131
VH Type
TOC
85
Accessory
(MOC: AG)
VL type
Circuit diagram
102 101 105 104 108 107 111 110
MOC
VH Type
a Contact: 101-103, 104-106, 107-109, 110-112,
b Contact: 102-103, 105-106, 108-109, 111-112
Door
86
Door Interlock: AJ Built-in a cradle as an option
Door
Emergency
Push button
87
Accessory
A B
C D
88 88
Type H Cradle Lead Wire: AM~AO Built-in a cradle as an option
Lead
Wire
Door
Padlock
89
Accessory
B If dimension A in Fig. 1 is
less than 120mm B type
pallet can be used.
Width :≤ 550mm In case of more than 120mm
550
Bottom
<Fig 1>
90
VL-06
Trip coil monitoring contact
Note1)
Note2) Note3)
M: Spring charging motor LS4, LS5: Position S/W (close in TEST position)
TC: Trip coil LS6, LS7: Position S/W (close in SERVICE position)
TC1: Secondary trip coil TEST : 1a1b TEST : 2a TEST : 1a1b
S/W
C: Close coil SERVICE : 2b SERVICE : 2a SERVICE : 1a1b
No.
UVT: Under voltage trip A3 A4 A5
52a: Auxiliary switch (a) LS4 Close at TEST position Close at TEST position Close at TEST position
52b: Auxiliary switch (b) LS5 OPEN at TEST position Close at TEST position OPEN at TEST position
CTC : Current trip coil LS6 OPEN at SERVICE position Close at SERVICE position Close at SERVICE position
CTC1 : Secondary Current trip coil LS7 OPEN at SERVICE position Close at SERVICE position OPEN at SERVICE position
CS : Closing spring charged Limit Switch
Y : Anti-Pumping Device
Anti-Pumping Device is installed inside
as standard IEC62271-100 3.6.128
91
92
Trip coil monitoring contact
Secondary trip coil with TCM Contact
Note2)
VL-06/12/17/20/25/36
Note1)
Note3) Note4)
Note4) Note4)
Current Trip Coil(1A,5A) indicating contact
(Charge completion indicating contact)
<Connecting terminal arrangement>
Ø: External terminal of VCB Y : Anti-Pumping Device
52 : Vacuum circuit breaker Anti-Pumping Device is installed inside as standard IEC62271-100 3.6.128 A type connector
M : Spring charging motor
LS4, LS5 : Position S/W (TEST position)
TC : Trip coil(SHT)
LS6, LS7 : Position S/W (SERVICE position)
TC1 : Secondary Trip coil(SHT1)
C : Closing coil(CC) TEST : 1a1b TEST : 2a TEST : 1a1b
S/W
UVT : Under Voltage Trip SERVICE : 2b SERVICE : 2a SERVICE : 1a1b
52a : Auxiliary switch (NO) No.
A3 A4 A5
52b : Auxiliary switch (NC) LS4 Close at TEST position Close at TEST position Close at TEST position
LS2 : Motor stop limit switch
LS5 OPEN at TEST position Close at TEST position OPEN at TEST position
CTC : Current Trip coil(3A)
CTC1 : Secondary Current Trip coil(3A) LS6 OPEN at SERVICE position Close at SERVICE position Close at SERVICE position
CTC2 : Current Trip coil(1A,5A) LS7 OPEN at SERVICE position Close at SERVICE position OPEN at SERVICE position
CTC3 : Current Trip coil(1A,5A) LM : Locking magnet(only withdrawable type)
LET : Low Energy Trip Device(25mJ,100mJ)
CS : Closing spring charged indication limit switch
11. Above circuit diagram is based on "OFF" state of VCB and closing spring is charged.
12. Please, keep the direction of P,N on this circuit diagram.
*Y : Anti-pumping device
Anti-pumping device Y supply anti-pumping function to VCB as below. It is composed with circuit in close coil and mechanism.
In case the closing coil(C) becomes permanently energized, the circuit breaker remains in the open position after it has been opened,
either by manual or electrical operation. The circuit breaker can be closed only if the closing coil(C) is momentarily de-energized.
Closing coil monitoring contact Trip coil monitoring contact
Note 2)
Note 5)
VH-06/12/17/20/25/36
Note 1)
Note 3) Note 4)
93
94
Earthing S/W Auxiliary switch
6a 6b P
Compartment
2a 2b
MOC Note2) TOC Note3) TM Note4)
E1 E5 E9 E13 E17 E21 E3 E7 E11 E15 E19 E23 17 102 101 105 104 108 107 111 110 121 122 124 125 127 128 130 131 8(R+) 9(S+) 10(T+)
LM TM TM TM
Note) 1. LM - If it is energized with the rated power the earthing switch can be closed or opened (for H type cradle)
2. MOC - This auxiliary switch is used to indicate the Close/Open of VCB (for H type cradle)
It is composed of 4 cell switches with 4 changeover contacts.
Option
3. TOC - This auxiliary switch is used to indicate the 'SERVICE' position of VCB (for H type cradle)
It is composed of 4 cell switches with 4 changeover contacts.
4. TM - Temperature Alarm Unit displays the input temperature detected through the temperature sensor installed
in H-type cradle. Temperature sensor can be installed in each phase and can be connected with the
temperature module.
5. Please make sure that keep the direction of P, N on this circuit diagram.
* Above circuit diagram is based on the status that the earthing S/W is Open and the breaker is at Test or between
Test and Service position. MOC indicates the Open of the breaker. If the breaker is Closed from Service, the
contacts configuration is displayed on the contrary.
Dimensions - VL type VL-06
(Mounting hole)
95
Dimensions - VL type
Racking in/out
Stroke:150 Main circuit terminal
96
VL-06
Racking in/out
Main circuit terminal
Stroke:150
Racking in/out
Stroke:150 Main circuit terminal
97
Dimensions - VL type
M12
(Earthing hole)
91.5
281
96.5
6(10)
99
Dimensions - VL type
616
669
350
295
29
692.5
672.5
332.5
230.5
104.5
13 288 32
522
12.5
351
53 383
436
672.5
332.5
230.5
104.5
288
13 351 32
522
32.5
53 383
436
100
VL-06/12/17/20/25/36
101
Dimensions - VL type
273.5
194
112
110
Racking in/out
Stroke:200
102
VL-06/12/17/20/25/36
150 150
(Mounting hole)
725 183.7
1017.7
(Mounting hole)
(Mounting hole)
8- 11
550
(Mounting hole)
TUBE TUBE
30
30
Detail A Detail A
87.3
20
2-M8 (DP:18)
43.4
103
Dimensions - VL type
M12(Earthing hole)
96.5
46.8
104
VL-06/12/17/20/25/36
105
Dimensions - VL type
273.5
106
VL-06/12/17/20/25/36
110
125
(Mounting hole)
(Mounting hole) (Earthing hole)
110
125
273.5
107
Dimensions - VL type
194
112
110
A
Racking in/out
Stroke:220
108
VL-06/12/17/20/25/36
150 150
550.4
(Mounting hole)
725 202.7
1017.7
310 465
65 285 150 150 277.7
550
(Mounting hole)
TUBE
30
25
Detail A
68.3
20
2-M8 (DP:18)
43.4
109
Dimensions - VL type
40
4- 13
178
212
152
10
M12
(Earthing hole)
509
281
46.8
96.5
450 212
295
670
650
10
320
470 315 156
589 523.5
A
440
7.2kV,31.5kA,630,상간150, P Type
310
35
688
623.5
280
154
76
320 25
21.5
19.5
13
4
503 358
53 383
469
110
VL-06/12/17/20/25/36
(For assembly of
lifting hook and LV (Mounting hole)
compartment
mounting hole)
(Mounting hole)
(Mounting hole)
(Mounting hole)
(Mounting hole)
111
Dimensions - VL type
40
4- 13
178
212
10
152
M12
509
(Earthing hole)
281
46.8
96.5
450 212
295
670
650
10
320
470 315 156
589 523.5
7.2kV,31.5kA,1250A,상간150, P Type
112
VL-06/12/17/20/25/36
113
Dimensions - VL type
Racking in/out
166 Stroke: 175 40
20
180
525
210
491
180
2-Ø14
260 410 6-Ø12
(Mounting hole)
150 150
10
295
720.2
326.2
139 790 150
600
114
VL-06/12/17/20/25/36
616
669
350
328 Stroke:225
450
295
692.5
676
48
332.5
230.5
288 32 104.5
12.5
13 351
522 53 383
436
676
332.5
230.5
104.5
288 32
32.5
13 351
522 53 383
436
115
Dimensions - VL type
26
(Mounting
hole)
560
83
295
(Mounting hole)
100 660
S ST: 225
ST: 225
48
VIEW
295
"C"
1235
345
1250A: 12t
2000A: 25t
285
S
600 12 100 660 156
731.5
946
150
600
560
83
150
100 662
1250A:12t
2000A:25t
295
1235
630
731.5
946
116
VL-06/12/17/20/25/36
110
607
660
440
A
310
35
688
623.5
280
154
76
320 25
21.5
19.5
13
4
503 358
53 383
469
7.2/12/17.5kV,31.5kA,630/1250A,상간150, H Type
117
Dimensions - VL type
(For assembly of
lifting hook and LV (Mounting hole)
compartment
mounting hole)
(Mounting hole)
(Mounting hole)
(Mounting hole)
(Mounting hole)
118
VL-06/12/17/20/25/36
M12(Earthing hole)
96.5
46.8
119
Dimensions - VL type
120
VL-06/12/17/20/25/36
121
Dimensions - VL type
616
669
350
328 Stroke:225
450
295
692.5
676
48
332.5
230.5
288 32 104.5
12.5
13 351
522 53 383
436
676
332.5
230.5
104.5
288 32
32.5
13 351
522 53 383
436
122
VL-06/12/17/20/25/36
26
(Mounting
hole)
560
83
295
(Mounting hole)
100 660
S ST: 225
ST: 225
48
VIEW
295
"C"
1235
345
1250A: 12t
2000A: 25t
285
S
600 12 100 660 156
731.5
946
150
600
560
83
150
100 662
1250A:12t
2000A:25t
295
1235
630
731.5
946
123
Dimensions - VL type
194
112
110
A
Racking in/out
Stroke:220
124
VL-06/12/17/20/25/36
150 150
550.4
(Mounting hole)
725 202.7
1017.7
310 465
65 285 150 150 277.7
550
(Mounting hole)
TUBE
30
25
Detail A
68.3
20
2-M8 (DP:18)
43.4
125
Dimensions - VL type
M12(Earthing hole)
46.8
96.5
M12(Earthing hole)
46.8
96.5
126
VL-06/12/17/20/25/36
613.5
311.5
670
302
295
670
650
310
103 286
670 78 483
715 94.5 315
655.5
670
302
295
670
650
310
169.5
103 286
670 78 483
715 94.5 315
655.5
127
Dimensions - VL type
128
VL-06/12/17/20/25/36
616
669
350
328 Stroke:225
450
295
Ø29
692.5
676
332.5
230.5
13 288 32 104.5
12.5
351
522 53 383
436
328 Stroke:225
450
295
Ø29
692.5
676
332.5
230.5
104.5
288
13 351 32
32.5
522 53 383
436
129
Dimensions - VL type
11.8
210
139
766.4
690
725
210
50
270 440 340
295
720.2
6
87.2
326
278.5
800 860 40
1050
(Earthing hole)
11.8
210
139
766.4
725
690
210
60
10
326
278.5
800 860 40
1050
130
VL-06/12/17/20/25/36
11.8
(Earthing hole)
210
766.4
690
725
210
50
270 440 340
295
720.2
6
87.2
326.2
278.5
800 860 55
1050
(Earthing hole)
11.8
210
139
766.4
690
725
210
60
720.2
87.2
326.2
278.5
800
860 40
1050
131
Dimensions - VL type
(Earthing hole)
(Mounting hole)
278.5
(Earthing hole)
(Mounting hole)
278.5
132
VL-06/12/17/20/25/36
194
112
110
A
Racking in/out
Stroke:200
194
112
110
Racking in/out
Stroke: 220
133
Dimensions - VL type
150 150
550
(Mounting hole)
725 183.7
1017.7
(Mounting hole)
(Mounting hole)
400
400
1120
205
400
400
445
212.5
212.5
(Mounting hole)
550
TUBE TUBE
30
30
Detail A Detail A
87.3
20
2-M8 (DP:18)
43.4
134
VL-06/12/17/20/25/36
210
mounting hole) 700
210
(Mounting hole)
725 183.7
1017.7
(Mounting hole)
(Mounting hole)
(Mounting hole)
700
TUBE TUBE
30
30
Detail A Detail A
87.3
20
2-M8(DP:18)
63.4
135
Dimensions - VL type
M12(Earthing hole)
46.8
96.5
136
VL-06/12/17/20/25/36
(Earthing hole)
(Mounting hole)
137
Dimensions - VL typ
(Earthing hole)
(Mounting hole)
138
VL-06/12/17/20/25/36
194
112
110
A
Racking in/out
Stroke:220
Racking in/out
Stroke:220
139
Dimensions - VL type
150 150
mounting hole) 550 2-M12 (DP:25)
(Mounting hole)
725 202.7
1017.7
(Mounting hole)
TUBE
30
25
Detail A
68.3
20
2-M8 (DP:18)
43.4
140
VL-06/12/17/20/25/36
210 210
25
mounting hole)
700
(Mounting hole)
725 183.7
1017.7
(Mounting hole)
700
TUBE
30
25
Detail A
87.3
20
2-M8(DP:18)
63.4
141
Dimensions - VL type
M12(Earthing hole)
46.8
96.5
M12(Earthing hole)
46.8
96.5
142
VL-06/12/17/20/25/36
616
669
350
328 Stroke:225
450
295
692.5
676
48
332.5
230.5
288 32 104.5
12.5
13 351
522 53 383
436
676
332.5
230.5
104.5
288 32
32.5
13 351
522 53 383
436
143
Dimensions - VL type
26
(Mounting
hole)
560
83
295
(Mounting hole)
100 660
S ST: 225
ST: 225
48
VIEW
295
"C"
1235
345
1250A: 12t
2000A: 25t
285
S
600 12 100 660 156
731.5
946
150
600
560
83
150
100 662
1250A:12t
2000A:25t
295
1235
630
731.5
946
144
VL-06/12/17/20/25/36
616
669
350
328 Stroke:225
450
295
692.5
676
48
332.5
230.5
288 32 104.5
12.5
13 351
522 53 383
436
676
332.5
230.5
104.5
288 32
32.5
13 351
522 53 383
436
145
Dimensions - VL type
26
(Mounting
hole)
560
83
295
(Mounting hole)
100 660
S ST: 225
ST: 225
48
VIEW
295
"C"
1235
345
1250A: 12t
2000A: 25t
285
S
600 12 100 660 156
731.5
946
150
600
560
83
150
100 662
1250A:12t
2000A:25t
295
1235
630
731.5
946
146
VL-06/12/17/20/25/36
110
607
660
A
440
310
35
688
623.5
280
154
76
320 25
21.5
19.5
13
4
503 358
53 383
469
194
112
110
7.2/12/17.5kV,31.5kA,630/1250A,상간150,A H Type
Racking in/out
Stroke: 220
147
Dimensions - VL type
(For assembly of
lifting hook and LV (Mounting hole)
compartment
mounting hole)
(Mounting hole)
(Mounting hole)
(Mounting hole)
(Mounting hole)
148
VL-06/12/17/20/25/36
210
210
(Mounting hole)
725 183.7
1112.7
400
400
310
1120
400
400
465
212.5
212.5
(Mounting hole)
700
30
30
87.3
20
2-M8(DP:18)
63.4
DETAIL A
SCALE 2/15
SEE DETAIL A
149
Dimensions - VL type
M12(Earthing hole)
46.8
96.5
194
112
110
Racking in/out
Stroke:220
150
VL-06/12/17/20/25/36
194
112
110
A
Racking in/out
Stroke:220
151
Dimensions - VL type
150 150
mounting hole)
550.4
14(Mounting hole)
725 202.7
1112.7
(Mounting hole)
(Mounting hole)
400
400
310
1120
400
400
465
212.5
212.5
(Mounting hole)
550
30
25
DETAIL A
68.3
20
2-M8(DP:18)
43.4
DETAIL B
SCALE 2/15
152
VL-06/12/17/20/25/36
210
25
210
14(Mounting hole)
725 183.7
1112.7
400
400
310
1120
400
400
465
212.5
212.5
(Mounting hole)
700
30
DETAIL A
87.3
20
2-M8(DP:18)
63.4
DETAIL A
SCALE 1/6
SEE DETAIL A
153
Dimensions - VL type
60
4- 13
178
212
152
523.5
10
M12(Earthing hole)
281
46.8
96.5
455
600 212
295
20
690
670
650
320
315 156
670
523.5
789
606.5
4- 13
178
212
152
523.5
M12
10
(Earthing hole)
281
46.8
96.5
800 212
295
20
670
650
320
154
VL-06/12/17/20/25/36
110
589
642
A
359.5
Note) Please be informed that When B-type connecter is
used to design switchgears, the height can be
110mm higher based on “A”
310
79
688
280
165
76
19.5
320 25 21.5
4
13 358
653
53 383
469
A
359.5
646.5
280
165
76
320 25
21.5
19.5
4
13 358
853 53 383
469
155
Dimensions - VL type
35
210
210
14(Mounting hole)
725 197.2
1017.2
400
400
310
1120
400
400
465
212.5
212.5
(Mounting hole)
700
35
35
73.8
20
2-M8(DP:18)
63.4
DETAIL A
SCALE 2/15
SEE DETAIL A
156
VL-06/12/17/20/25/36
35
275
950.4
275
(Mounting hole)
725 197.2
1017.2
400
400
310
1120
400
400
465
212.5
212.5
(Mounting hole)
950
35
35
73.8
20
2-M8(DP:18)
63.4
157
Dimensions - VL type
(Earthing hole)
158
VL-06/12/17/20/25/36
617.5
311.5
700 306
340
10
805
805
400
126.5
103 312
700 72 493
94.5 335
745
659.5
700 264.5
120
340
805
805
29
400
312
103
443
700 72 451.5
745 94.5 335
618
159
Dimensions - VL type
576
311.5
700 264.5
120
340
805
805
29
400
126.5
312
103
443
700 72 451.5
745 94.5 335
618
700 360
340
29
805
805
400
126.5
103 312
72 547
700
94.5 335
745
713.5
160
VL-06/12/17/20/25/36
767
820
437
340
29
827.5
827.5
422.5
301.5
13 350 50 185.5
12.5
653 53 437
463
827.5
827.5
422.5
301.5
185.5
13 350 50
53 437
12.5
886
463
161
Dimensions - VL type
110
746
799
458 A
310
35
770
756
325
198
4
72
13 365 35 19.5
21.5
653
403
53 438
524
A
458
756
325
198
4
72
13 365 35
19.5
21.5
853 403
53 438
524
162
VL-06/12/17/20/25/36
(Earthing hole)
163
Dimensions - VL type
617.5
311.5
700 306
340
10
805
805
400
126.5
103 312
72 493
700
94.5 335
745
659.5
265 265
576
311.5
700 264.5
120
340
805
805
29
400
312
103 443
700 72 451.5
745 94.5 335
618
164
VL-06/12/17/20/25/36
576
311.5
700 264.5
120
340
805
805
29
400
126.5
312
103
443
700 72 451.5
745 94.5 335
618
830
265 265
671.5
311.5
700 360
340
29
805
805
400
126.5
103 312
700 72 547
745 94.5 335
713.5
165
Dimensions - VL type
767
820
437
340
29
827.5
827.5
422.5
301.5
13 350 50 185.5
12.5
653 53 437
463
840
422.5
301.5
185.5
350 50
12.5
437
53 463
166
VL-06/12/17/20/25/36
110
746
799
458 A
310
35
770
756
325
198
72
4
13 365 35 19.5
21.5
653 438
53 471
524
840
275 275
194
112
110
746
799
A
458
756
325
198
4
72
13 365 35
19.5
21.5
853 403
53 438
524
167
Dimensions - VL type
(Earthing hole)
700 306
340
10
805
805
400
103 312
72 493
700
94.5 335
745 659.5
168
VL-06/12/17/20/25/36
617.5
311.5
700 306
340
10
805
805
400
126.5
103 312
700 72 493
745 335
659.5
(Earthing hole)
169
Dimensions - VL type
700 306
340
10
805
805
400
126.5
103 312
72 493
700
94.5 335
745
659.5
170
VL-06/12/17/20/25/36
576
311.5
700 264.5
120
340
805
805
29
400
312
103 443
700 72 451.5
745 94.5 335
618
830
265 265
576
311.5
700 264.5
120
340
805
805
29
400
126.5
312
103
443
700 72 451.5
745 94.5 335
618
171
Dimensions - VL type
671.5
311.5
700 360
340
29
805
805
400
126.5
103 312
700 72 547
745 94.5 335
713.5
827.5
827.5
422.5
301.5
185.5
13 350 50
12.5
653 53 437
463
172
VL-06/12/17/20/25/36
340
29
840
422.5
301.5
185.5
350 50
12.5
437
53 463
A
458
756
325
198
72
4
13 365 35
19.5
21.5
653 438
53 471
524
173
Dimensions - VL type
110
746
799
A
458
Note) Please be informed that When B-type connecter is
used to design switchgears, the height can be
110mm higher based on “A”
310
35
770
756
325
198
4
72
13 365 35
19.5
21.5
853 403
53 438
524
(Earthing hole)
174
VL-06/12/17/20/25/36
617.5
311.5
700 306
340
10
805
805
400
103 312
700 72 493
745 94.5 335
659.5
830
265 265
78
617.5
311.5
700 306
340
20
805
805
400
126.5
103 312
700 72 493
745 94.5 335
659.5
175
Dimensions - VL type
576
311.5
700 264.5
120
340
805
805
48
400
103 312
700 443
745 72 451.5
94.5 335
618
830
265 265
576
311.5
700 264.5
120
340
805
805
48
400
126.5
103 312
443
700 72 451.5
745 94.5 335
618
176
VL-06/12/17/20/25/36
767
820
437
340
48
827.5
827.5
422.5
301.5
185.5
350 50
12.5
886 13 437
53 463
516
640
210 210
194
112
110
746
799
A
447.5
756
345
181
4
89
13 365 35
19.5
21.5
653 403
53 438
524
177
Dimensions - VL type
110
746
799
A
447.5
Note) Please be informed that When B-type connecter is
used to design switchgears, the height can be
110mm higher based on “A”
310
48
770
756
345
181
89
4
13 365 35
19.5
21.5
853
403
53 438
524
A
447.5
756
345
181
89
4
13 365 35
21.5
19.5
853 403
53 438
524
178
VL-06/12/17/20/25/36
Rating A B T
630, 1250A 768 190.5 10
2000A 778 185.5 20
(Earthing hole)
(Mounting hole)
179
Dimensions - VL type
Insulation
Barrier
Rating A B T
630, 1250A 768 190.5 10
2000A 778 185.5 20
(Earthing hole)
252.5 45
(Mounting hole)
45
180
VL-06/12/17/20/25/36
Note) In case of phase distance 210mm ( ) means dimensions and 630A, 1250A areavailable only
Items : VCL-20K13B06, VCL-20K13B13, (G-type closed Tulip way, 630A, 1250A)
181
Dimensions - VL type
(For assembly of
lifting hook and LV (Mounting hole)
compartment
mounting hole)
(Mounting hole)
(Mounting hole)
(Mounting hole)
(Mounting hole)
DETAIL A
DETAIL A
SEE DETAIL A
DETAIL A
182
VL-06/12/17/20/25/36
275
275
35
(Mounting hole)
865 275.5
1239.5
455
455
310
1230
455
455
510
212.5
212.5
(Mounting hole)
950
30
30
DETAIL A DETAIL A
87.3
20
2-M8(DP: 18)
63.4
183
Dimensions - VL type
210 210
25
750.4
49
(Mounting hole)
865 275.5
1239.5
455
455
310
1230
455
455
530
212.5
212.5
(Mounting hole)
750
2- 12
10.0
30
25
DETAIL A
87.3
20
2-M8(DP: 18)
63.4
184
VL-06/12/17/20/25/36
275
950.4
25
275
49
(Mounting hole)
865 275.5
1239.5
455
455
310
1230
455
455
530
212.5
212.5
(Mounting hole)
950
2- 12
10.0
30
25
DETAIL A
87.3
20
2-M8(DP: 18)
63.4
185
Dimensions - VL type
50
275
950.4
50
275
79
(Mounting hole)
865 275.5
1239.5
455
455
310
1230
455
455
530
212.5
212.5
(Mounting hole)
950
30
25
25
DETAIL A
87.3
20
2-M8(DP: 18)
63.1
186
VL-06/12/17/20/25/36
895
275 275 2-Ø14
60
40
4-Ø13
M12
243
315.5
255.5
10
(Earthing hole)
705.5
43
369
97
760
802 315.5
380
1043.5
1003.5
15
970.5
492.5
403 221
811
705.2
931
857.7
848.4
275 275
1048.5
995
600
380
Ø32
1004.5
983
462
244.3
134.3
12.8 516
19.5
21.5
21.5
187
Dimensions - VL type
275 275
950.4
Ø35
1194 335
1624
565
530
1700
380
565
530
665
212.5
212.5
30
128.5
128.5
Ø12 Ø12
TUBE TUBE
2-Ø 2-Ø
12 12
20
20
87.3 56
M8(DP:18)
25
73.6
20
Detail A
Scale 2/15
188
VL-06/12/17/20/25/36
895
275 275 2-Ø14
80
40
40
4-Ø13 M12
315.5
(Earthing hole)
243
10
255.5
43
705.5
369
97
760
802 315.5
380
1043.5
1003.5
970.5
20
492.5
403 221
811
705.5
931 858
848.4
275 275
1048.3
995
600
380
Ø48
1004.5
983
462
244.3
134.3
12.8 516
21.5
19.5
21.5
189
Dimensions - VL type
275 275
950.4
SCALE 3/10
Ø49
1194 335
1624
565
530
1700
380
565
530
665
212.5
212.5
141
Ø12
2-
Ø1
20
TUBE
87.3 56
M8(DP:18)
25
73.6
20
Detail A
Scale 2/15
190
VL-06/12/17/20/25/36
895
275 275 6-Ø14
100
40
60
M12
315.5
243
255.5
10
(Earthing hole)
43
705.5
369
97
760
802 315.5
380
20
1043.5
1003.5
970.5
492.5
403 221
811
705.5
931
858
848.4
275 275
1048.3
995
600
380
Ø79
1004.5
983
462
244.3
134.3
12.8 516
19.5
21.5
21.5
191
36kV,25kA,2500A,P275,H Type
Dimensions - VL type VL-06/12/17/20/25/36
275 275
950.4
SCALE 3/10
Ø79
1194 335
1624
565
530
1700
380
565
530
665
212.5
212.5
87.3
151.2
12
35.4
Ø12
2-
Ø1
20
TUBE
87.3 56
M8(DP:18)
35.4
25
73.6
20
Detail A
Scale 2/15
192
Dimensions - LVB type LVB-06/12
20
20
2-M12(Earthing hole)
40
40
118
271
1250A(E, F type) 2000A(E, F type)
125.5 4- 13
553
478
20
295
130
670
670
20
286.6
320
115.5 400.6 117
515 547
589
B type connector
A type connector
60 80 60 80
468.5
125.5
478
295
130
670
670
286.6
310
169.5
193
Dimensions - LVB type
689
528 15
516
478
295
130
702.5
705.5
702.5
342.5
319.1
114.5 126
115.5 350.7 47
3
501 388.5
618
A type connector B type connector
668
528 15
516
478
295
130
715.5
715.5
725.5
355.5
127.5 126
332.1
115.5 350.7 60
10
496 388.5
618
A type connector B type connector 668
194
LVB-06/12
87.5 90 80 90 87.5
70 105 70 105 70
180
180
139
50
525
180
180
2- 14 4- 14
7- 12
1250A 2000A 260 410 210
(Mounting hole)
A
295
720.2
23.2 A
326.2
600 790 15
820
940
180
180
139
50
525
180
180
4- 14 2- 14
2- 14
1250A 2000A 7- 12 260 410 210
(Mounting hole)
600 790 15
820
940
195
Dimensions - LVB type
(Mounting hole)
196
LVB-06/12
20
69 4040
330
125.5 4- 13
703 (Mounting hole)
620
40
350
750.5
750.5
130
40
328.5
286.6
125.5
620
360
750.5
750.5
130
303.5
286.6
129
197
Dimensions - LVB type
693
714 16.5
690
620
360
795.5
805.5
795.5
130
140.2 135.6
331.6
348.5
115.5 321.7 60
450.6
10
687
624.7
A type connector B type connector 674.4
714 16.5
690
620
360
795.5
805.5
130
795.5
140.2 135.6
331.6
348.5
115.5 321.7 60
10
687 450.6
624.7
A type connector B type connector 674.4
198
LVB-06/12
139
50
675
4-M12 DP25
940.2
309.7360
23.4
750 825 15
877
930
Withdrawable (F cradle)
Only for 50 Racking in/out Stroke:175
3 position type
50
80 (Earthing hole)
50
139
4-M12 DP25
750 825 15
877
930
199
Dimensions - LVB type
200
LVB-06/12
(Mounting hole)
201
Dimensions -VH type
687.5
150 150 330.5 Stroke: 225
295
Ø48
137.5 126
355.5
53.5 350.7
528 11.8 Ø60
388.5
10
618
478
130
716
726
332.1
496
A type connector B type connector
355.5
53.5 350.7
528 11.8 Ø60
388.5
10
618
478
130
716
726
332.1
496
A type connector B type connector
202
VH-06/12/17/20/25/36
1250/2000A G class
Section S-S
VIEW "C"
(Mounting hole)
4-Ø14
(Mounting hole)
VIEW "A"
2-Ø13 60
12 25
26
26
660
83
290
(1250A) (2000A)
100
560 260
Section S-S
S 225 38 12
(stroke)
150 150
46
A
295
295
203
1235
10
46
205.5
630
17
S
537 946
600
203
Dimensions -VH type
360
Ø48
180.7 120
358.2
10
670 11.8
54 328.2
Ø80
443
636.2
620
799.2
809.2
130
336.2
644
B type connector
A type connector
(Earthing hole)
(Mounting hole)
204
VH-06/12/17/20/25/36
360
Ø79
181 120
358.5
714 11.8
10
Ø80
53.5 328.2
441
626.5
620
799.5
809.5
130
336.5
737.6
B type connector
A type connector
1300
639
61
800 1013.8
210 210
230 230
24
70
35
145
724
360
RUN
293
100
715
6-Ø14 (Mounting hole) 230 230
760
205
Dimensions -VH type
360
Ø79
180.7 120
358.2
11.8
10
814
54 328.2 Ø80
443
634.2
774
799.2
809.2
130
340.2
788
B type connector
A type connector
(Earthing hole)
(Mounting hole)
206
VH-06/12/17/20/25/36
522 11.8
714
538 357 Stroke: 220
295
Ø48
130
750.3
753.9
363.5
336
123.5 89
53.5 386.2 Ø79
495
3.5
442.5
644.5
522 11.8
714
538
357 Stroke: 220
295
Ø48
130
750.3
753.8
363.5
336
123.5 89
3.5
780
720
150 150
A
73
292.7
2-M12(DP:25mm)
61.5 61.5
8-Ø13
780
680
25 2-Ø 8.4
50 <Earthing S/W stator
mounting hole>
37.5
Detail A
Scale 3/10
650
565
295
1230
73
545
350
185
284.6 459
81.8
524 780
364
105
59
459 See Detail A
Section A-A
Around assembling hole of earthing
switch stator, cut the heat-shrinkable
tube to both upper and lower direction.
Ø8
Connecting busbar method
(with earthing switch)
Busbar : 10t×80 (2 sheet) <1250/2000A>
56.8
Ø8 Ø12
27
208
VH-06/12/17/20/25/36
210 210
673 11.8
714
692 335 Stroke: 220
360
Ø48
806.5
130
803
357.5
336
124 89
3.5
645 53.5 414 Ø79
442.5
644.5
210 210
673 11.8
714
692 335 Stroke: 220
360
A
Ø79
806.5
130
803
357.5
336
124 89
3.5
53.5 475.5
673 Ø79
442.5
644.5
209
Dimensions -VH type
292.7
37.5
71.5
8-Ø13
81.5
680
780
2-Ø 8.4
37.5
360
1230
73
539
350
185
A 484
81.8
362.1
803.4
674
105
354
181
59
484 See Detail A
210
VH-06/12/17/20/25/36
930
100
870
210 210 40 5-M12 (DP : 25mm)
20
291.7
85
8-Ø13
40
75
81.5
20
780
680
2-Ø 8.2
<Earthing S/W stator
37.5
50 mounting hole>
Detail A
Scale 1/5
800
715.6
360
1230
73
539
350
185
A
81.8
361.9 484
803.4
674
105
358
59
484
See Detail A
Section A-A
Around assembling hole of earthing
switch stator, cut the heat-shrinkable
tube to both upper and lower direction.
Ø8
Connecting busbar method
(with earthing switch)
Busbar : 10t×120 (2 sheet) <3150A>
57.3
Ø8
35
211
Dimensions -VH type
853 11.8
714
890 335 Stroke: 220
360
Ø79
808.5
130
805
357.5
332
124 89
3.5
54 414 Ø79
826
442.5
644.5
212
VH-06/12/17/20/25/36
291.7
20
85
8-Ø13
40
75
81.5
780
680
37.5 2-Ø 8.2
<Earthing S/W stator
mounting hole>
50
Detail A
Scale 1/5
1000
915.6
A
360
1230
73
539
350
185
A
484
81.8
461.9
803.4
855
358
105
181
Ø8
35
213
Dimensions -VH type
2-M12 (DP:25)
25
610
862.5
816
130
M12
(Earthing hole)
285
108
115.5 94 137
360 144
602
695
Racking in/out
12 725 Stroke:220
653
353
644
340
48
130
380
335
89
193.5
412
72
3.5
42
447
53 656
214
VH-06/12/17/20/25/36
(For assembly of
25
210
lifting hook and LV
compartment
210
mounting hole)
49
780 187
1073
450
450
340
1325
450
450
565
212.5
212.5
65 285 200 200 217
(Mounting hole)
60
30
30
TUBE TUBE
84.3
20
2-M8 (DP:18)
63.3
215
Dimensions -VH type
4-M12 (DP:25)
50
79
50
750
862.5
130
M12
(Earthing hole)
285
108
115.5 94
786 360 114 142
864 602
695
12
Racking in/out
725 Stroke:220
844 353
340
869.5
130
380
335
89
193.5
400
42
3.5
447
53 656
216
VH-06/12/17/20/25/36
4-M12
50
(For assembly of
lifting hook and LV
compartment
mounting hole) 50
(Mounting hole)
825 239.5
1167
450
450
340
1325
450
450
565
212.5
212.5
(Mounting hole)
12
30
30
TUBE TUBE
25
25
90.8
20
2-M8 (DP:18)
49.4
217
Dimensions -VH type
980
157 275 275
614.6
65
400
290
819
949
27
421
864
980
819
999
738.5
27
474.5
864 410
568.6
3.5
906
708.6
218
VH-06/12/17/20/25/36
1000
68
387
1294
479
81
908
275 275
400
400
1294
561.5
561.5
210
1030.8 11.3
1150.8
1183.5
327 270
309 220
210 50
M12
5
40
40
228
240
340
50
50
40
424.7
단면 A-A
219
Dimensions -VH type
77
908
1083.5
389
400
2015
1226
1050
210 315
220
VH-06/12/17/20/25/36
320 320
1.6
Stroke: 300
410
340
929.5
929.5
6.3
926
389.5
350
1009 27 410
1031 700.5
1033
41
1013.3 1038
162.5
1133.3 1130
1149
320 320
M16 90
90
410
476.5
529.5
221
Dimensions -VH type
179.5
44
330
4- 13
923 Mounting Hole
286.5
906
65
4-M12
Busbar TAP
65
120
400
Terminal Diameter
876
212.6 136.5 107
130
147
341
286.6
134
to have enough Insulation distance.
113.5
859 615.1
959
222
VH-06/12/17/20/25/36
(Earthing hole)
(Mounting hole)
223
Dimensions -VH type
4-M12 (DP:25)
214
320
834
750
130
M12
(Earthing hole)
287.5
110.5
115.5 118 142
786 174
864
12
853
Racking in/out
857 Stroke:310
850 445
340
130
440
80
335
225
497
3.5
41.5
535
53 788
224
VH-06/12/17/20/25/36
50
275
compartment
mounting hole)
275
50
(Mounting hole)
970 240
1312
500
500
340
1380
500
500
625
212.5
212.5
(Mounting hole)
30
TUBE
25
90.3
20
2-M8 (DP:18)
49.4
225
Dimensions -VH type
2-M12 (DP:25)
610
130
M12
(Earthing hole)
287.5
110.5
115.5 118 137
174
12
653
Racking in/out
857 Stroke:310
652 445
340
130
440
80
335
225
497
41.5
3.5
535
53 788
226
VH-06/12/17/20/25/36
4-M12
(For assembly of
25
210 210
lifting hook and LV
compartment
mounting hole) 2-M12 (DP:25)
(Mounting hole)
970 239.5
1302
500
500
340
1380
500
500
625
212.5
212.5
(Mounting hole)
60
30
30
TUBE TUBE
85.8
20
2-M8 (DP:16)
49.4
227
Dimensions -VH type
210 210
25
2-M12 (DP:25)
970 239.5
1302
(Mounting hole)
(Mounting hole)
500
500
340
1380
500
500
625
212.5
212.5
60 300 280 300 269.5
(Mounting hole)
228
VH-06/12/17/20/25/36
2-M12 (DP:25)
750
130
M12
(Earthing hole)
287.5
110.5
115.5 118 142
174
12
853
Racking in/out
857 Stroke:310
850 445
340
130
440
80
335
225
497
41.5
3.5
535
53 788
229
Dimensions -VH type
25
(For assembly of
lifting hook and LV
275
compartment 2-M12 (DP:25)
mounting hole)
275
(Mounting hole)
970 239.5
1302
500
500
340
1380
500
500
625
212.5
212.5
(Mounting hole)
30
TUBE
85.8
20
2-M8 (DP:18)
49.4
230
VH-06/12/17/20/25/36
4-M12 (DP:25)
(Mounting hole)
750
130
M12
(Earthing hole)
287.5
110.5
115.5 118 142
786 174
864
12
853
Racking in/out
857 Stroke:310
850 445
340
130
440
335
80
225
497
41.5
535
3.5
53 788
231
Dimensions -VH type
50
275
compartment
mounting hole)
275
50
(Mounting hole)
970 240
1312
500
500
340
1380
500
500
625
212.5
212.5
(Mounting hole)
30
TUBE
25
90.3
20
2-M8 (DP:18)
49.4
232
VH-06/12/17/20/25/36
M12
(Mounting hole)
1042.5
220.1
115.5
Withdrawable (H type unit, phase distance 300mm)
(Relative connection conductor)
Racking in/out
Stroke:440
233
Dimensions -VH type
11-M8
43
Mounting TAP Mounting hole
300
300
221.5 221.5
402
1150
1100
900
300
570
300
300
24
300
20 Duct hole for wiring
6-M5
Mounting TAP
6-M8 45
Mounting TAP
Mounting hole 65 270 270
1200
1100
300 300
A (symmetrically)
23.5
60
Mounting hole
288
9-M8
Mounting TAP 7
14
480
40
288
216.5
480
2165
2150
2200
400
See Detail A
216.5
600
53.5
480
15
901
600
480
604
104
140
140
A
485 649 360.5 25 1194 608 66
740
846
488
290
285
268 268 268
Mounting hole
285
assembled in pannel
300 300 300 Duct hole for wiring
40
52
563
234
VH-06/12/17/20/25/36
M12
(Mounting hole)
1042.5
220.1
115.5
Withdrawable (H type unit, phase distance 300mm) (Relative connection conductor)
Racking in/out
Stroke:440
8.5
8.5
235
Dimensions -VH type VH-06/12/17/20/25/36
40
14
300
296.5 40
201.5
300
12
10
221.5
1200 505
A
400
1520
855
203.8
50.5
290
A 61 563 463
56.12
46
1226.7
120
740 140.5
846
873.4
Ø25
30 40 127.5 30 Remove both side of shrink tube
for bolting busbar when using Cu PIPE
110
40
14
7 Ø10
STS HEX M8X70 BOLT
Ø19
Using Cu PIPE(2ea) as right figure
Detail A or Bending BUSBAR(28.5mm)
Ø8.5
See Detail A
28.5
assembled in pannel
104
236
Side-Mount type VCB
Item VL-2516B 06
Rated voltage Ur (kV) 25.8
Control voltage Closing coil (V) DC 24~30V, DC 48~60V, DC 110V, DC 125V, DC 220V, AC 48V, AC 100~130V, AC 200~250V
Trip coil (V) DC 24~30V, DC 48~60V, DC 110V, DC 125V, DC 220V, AC 48V, AC 100~130V, AC 200~250V
Electrical E1
Left L type
Weight CB (kg) 95
237
Side-Mount type VCB
A1 9 A3 D1 A5 22 24 26 28 40 36 38 50 52 54
LS2 CS
MOTOR POWER SOURCE
52a
23 25 27 29 41
M 37 39 51 53 55
C ote1)
UVT TC
A2 10 A4 A6 23 25 27 29 41 37 39 51 53 55
N N D2
N
Closing Spring Contact (Charge switch) <Connecting terminal arrangement>
Ø: External terminal of VCB C : Closing coil(CC) LS2 : Motor stop limit switch A
A2 A4 A6 10 D2
B
23 25 27 29 41 37 39 51 53 55
M : Spring charging motor 52a : Auxiliary switch (a) indication limit switch (5a5b)
TC : Trip coil(SHT) 52b : Auxiliary switch (b)
145
210 210
M10-DP 25
212.5
120
600
605
818
355.5
38.5
100
169 873
300 1000
M10-DP 20
Note) This external shape is based on “R” Type (Installation type)
Ordering information
VL 25 R 16 B 06
Basic model name Rated voltage (kV) Installation type Breaking Phase distance/Compatibility Rated current (A)
e-VCB 25 25.8 R On the right (Fixed type) 16 16 B 210mm 06 680
L On the left (Fixed type)
Motor control voltage Closing coil voltage Trip coil voltage Aux. contact & wire ass'y UVT Other accessories
M0 Without Motor C0 Without Closing coil T0 Without Trip coil A type connector, U0 Without UVT AA Lead Wire
SA5
M1 DC 110V C1 DC 110V T1 DC 110V 5a5b U1 DC 110V AB User Plug(Part)
M2 DC 220V C2 DC 220V T2 DC 220V U2 DC 220V
M3 DC 125V C3 DC 125V T3 DC 125V U3 DC 125V
M4 DC 24V~30V C4 DC 24V~30V T4 DC 24V~30V U4 DC 24V~30V
M5 DC 48V~60V C5 DC 48V~60V T5 DC 48V~60V U5 DC 48V~60V
M6 AC 48V C6 AC 48V T6 AC 48V U6 AC 48V
M7 AC 100V~130V C7 AC 100V~130V T7 AC 100V~130V U7 AC 100V~130V
M8 AC 200V~250V C8 AC 200V~250V T8 AC 200V~250V U8 AC 200V~250V
238
Technical data
Number[ops.]
Number[ops.]
239 239
Technical data
Number[ops.]
Number[ops.]
240
Standard Use Environment for Susol VCB
The operation characteristic of Vacuum Circuit Breaker such as insulation and endurance is often influenced
largely by external environment and thus should be applied appropriately with conditions of the place where
it is used taken into consideration.
The following values are the limits have been set in accordance with IEC 62271-100 (IEC 62271-1)
Ambient Temperature
- maximum temperature: +40℃
- 24-hour average maximum temperature: +35℃
- minimum temperature: -5℃
Altitude
- 1000m or less above sea level
Relative Humidity
- 24 hours average value: 95% or less
- One month average: 90% or less
241
Technical data
The circuit breaker is designed for use in standard use environment specified in Section 2.1 of IEC62271-1.
Concerning the special use environments as below the special use conditions are
required to be considered, thus please contact us in advance.
- where altitude and ambient temperature are out of standard use environment.(-40℃)
- where a strong sea breeze blows
- when usually used in a humid place
- where a lot of steam or oil steam exists
- where explosive, flammable and other harmful gases might permeate the breaker
- In a dusty place
- where abnormal vibration or shock exists
- where a lot of ice and snow exist
- other special conditions
70 36 170
50(65) 24 125
38 17.5 95
28(42) 12 75(82)
20 7.2 60
Ud [kV/1min] Ur[kV] Up [kV/1.2 50 ]
Power Frequency Impulse Withstand Voltage
Withstand Voltage
242
Special Use Environment
1.45
1.4
1.35
1.3
1.25
1.2
1.15
1.1
1.05
1
1000 1500 2000 2500 3000 3500 4000
Altitude (m)
<Fig.1 > withstand voltage correction parameter 1 by altitude (based on a required withstand voltage)
1
Correction parameter 2
0.95
0.9
0.85
0.8
0.75
0.7
0.65
0.6
0.55
0.5
1000 1500 2000 2500 3000 3500 4000
Altitude (m)
<Fig.2 > withstand voltage correction parameter 2 by altitude (based on a applicable withstand voltage)
Ex) Selecting a breaker to be used in a place of 2500m above sea level with a rated voltage 7.2kV
(correction parameter 1 applied)
- correction parameter at 2500m is 1.2
- criteria of withstand voltage by rated voltage:
Power Frequency Withstand Voltage (Ud) = 20kV, Impulse Withstand Voltage (Up) = 60kV
- requirements withstand voltage criteria:
Power Frequency Withstand Voltage (Ud) = 20×1.2 = 24kV, Impulse Withstand Voltage (Up) = 72kV
Therefore rated voltage 12kV breaker shall apply to satisfy the required withstand voltage.
Ex) To apply a breaker with a rated voltage 12kV to the place of 2,500m above sea level
(correction parameter 2 applied)
- correction parameter at 2500m is 0.825
- dielectric strength of VCB : Power Frequency Withstand Voltage (Ud) = 28×0.825 = 23.1kV,
Impulse Withstand Voltage (Up) = 75×0.825 = 62kV/1.2×50 ㎲
Therefore above breaker with rated voltage 12kV shall apply to rated voltage system 7.2kV at the altitude.
243
Technical data
Ex) The calculation of the applicable load current value when a breaker with rated current
2000A is used at 55 ℃ ambient temperature
Ia = 2000×((105-55)/65)1/2 = 2000×0.87 = 1754A
244
Comparison of GCB & VCB
In the system of medium voltage lines VCB uses a vacuum which is an eco friendly medium for arc extinguishing.
It also offers excellent interrupting properties and ease of maintenance and has expanded the area to the scope of the
GCB as the overlap increases.
Comparison
Items GCB VCB Remarks
results
Images
VI
245
246
•For your safety, please read user's manual thoroughly before operating.
•Contact the nearest authorized service facility for examination, repair, or adjustment.
•Please contact qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!
Safety Instructions •Any maintenance and inspection shall be performed by the personnel having expertise concerned.
Overseas Branches
•LSIS Co.,Ltd. Rep.Office, Vietnam
Gema Dept Tower 18F,6 Le Thanh Ton,District 1,HCM,Vietnam
Tel: 84-8-3823-7890 / E-mail: hwyim@lsis.com
•LSIS Moscow Office, Russia
Specifications in this catalog are subject to change without notice due to 123610,Krasnopresnenskaya,nab,12,building1,office No.1005,Moscow,Russia
continuous product development and improvement. Tel: 7-495-258-1466,1467 / Fax: 7-495-258-1466,1467 / E-mail: jdpark1@lsis.com
2016. 11 Vacuum Circuit Breakers(E) 2011. 01/(14) 2016. 11 Printed in Korea Staffcom