Safety and Standard PPE is required that includes protection against H2S Gas.
Environmental
Requirements
References ILD, P&ID, Operation/maintenance manual, and instrument datasheet
AD204-651-G-51074
Job Prerequisites 1. Obtain work permits
2. Ensure that work permit / JSA is read and understood in toolbox talk with all involved personal
3. Ensure all PPE requirements are met as listed in work permit / JSA before conducting the work.
4. Ensure required system overrides were properly implemented, online equipments/instruments
are isolated / removed from the system, as per P&ID given by operations and as per C&E Matrices.
NOTE: There could be a database mismatch changes made with 475 may not be recorded in
the host system database. Ensure all safety precautions and work procedures have been
followed.
Auto TVL calibrate will cause sudden changes in valve and loss of process control.
Select YES and Click NEXT
A Message appears: The transducer block is Auto; continue for the prompt to set the
transducer block mode to manual. Click NEXT
The valve will not track input if transducer block mode is MANUAL
Click NEXT
Wait till the process of finding end points is completed and click NEXT
Valve will start to move; take precaution. Watch for pinch point.
Click NEXT
The valve will move now to adjust HI and LO set pressure range
Wait till the process complete and observe TRAVEL % & PRESSURE.
A Warning appears on communicator: Valve may move when Transducer Block is set
to AUTO. Select YES & Click NEXT.
Click FINISH
3. From the display list click Transducer block mode and check the following-
o TARGET-AUTO
o ACTUAL-AUTO
o NORMAL-AUTO
**End of Procedure**
Remarks