We offer a wide range of protection devices, such as miniature circuit breakers, auxiliaries and
accessories, RCCB add-on blocks, single pole and switched neutral devices, 2 and 4 pole RCCB’s,
RCCB auxiliaries, RCBO’s, HRC fuse carriers, motor starters, earth fault relays, surge protection
devices and the new range of moulded case circuit breakers.
Miniature Circuit Breakers
6kA Type B 4.2
Protection
Devices
Single Pole & Switched Neutral Devices
Fuse Carriers 4.14
Torroids 4.27
MCCBs 4.30
Miniature Circuit Breakers
6kA Type B Single Pole
Description Technical data Connection capacity
Protection and control of circuits Type B tripping characteristics Rigid conductor 25mm2
against overloads and short complies with BS EN 60898. Flexible conductor 16mm2
circuits. Calibration temperature 30°C
Breaking capacity: 6kA
r*OEPNFTUJDJOTUBMMBUJPOT Voltage rating: 230 - 400V
Current rating: 6 - 63A
Electrical operations: 20,000
MTN163
4.2 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFT
Miniature Circuit Breakers
10kA & 15kA B, C & D Curve
In 0.5 to 63A Description Isolation Connection capacity
Un : 230V-400V These MCBs allow you to ensure The state of isolation is clearly rNN2 flexible conductor
r 1SPUFDUJPOPGDJSDVJUTBHBJOTU indicated by the “OFF” rNN2 rigid conductor
Will accept accessories short circuits mechanical position on the
see page 4.5 r 1SPUFDUJPOPGDJSDVJUTBHBJOTU toggle with the green colour. Complies with:
overload current r#4&/ L"
r *TPMBUJPO
Protection
Devices
3A 1 Mod - NCN103A NDN103A
4A 1 Mod - NCN104A NDN104A
6A 1 Mod NBN106A NCN106A NDN106A
10A 1 Mod NBN110A NCN110A NDN110A
16A 1 Mod NBN116A NCN116A NDN116A
20A 1 Mod NBN120A NCN120A NDN120A
25A 1 Mod NBN125A NCN125A NDN125A
32A 1 Mod NBN132A NCN132A NDN132A
NCN116A 40A 1 Mod NBN140A NCN140A NDN140A
50A 1 Mod NBN150A NCN150A NDN150A
63A 1 Mod NBN163A NCN163A NDN163A
r *TPMBUJPO
4.4 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFT
Auxiliaries & Accessories for Devices
NBN, NCN, NDN 10kA MCBs
All auxiliaries are common to
both single and multi-pole 10kA
circuit breakers and RCCBs.
Connection capacity
4mm2 flexible
6mm2 rigid
Protection
of main contact status
Devices
MZ201
Shunt Trip
Allows remote tripping of the associated device. Operation of the coil is indicated by a flag on the product
fascia.
Allows MCB to be closed only when voltage is above 85% of Un. MCB will automatically trip when voltage
falls to between 70-35% of Un. Operation of the coil is indicated by a flag on the product facia.
Locking Kit
MZN175
1 3
2 4 6 8
BD264
4.6 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFT
Miniature Circuit Breakers
80 - 125A C & D Curve
Thermal Magnetic Circuit HMC C Curve HMF C Curve
Breakers Curves C & D 15 kA 10 kA
In 80 to 125 A (BS EN 60898 Part 1) (BS EN 60898 Part 1)
15 kA for 80 - 100 - 125 A: 10 kA for 80 - 100 - 125 A:
These circuit breakers are BS EN 60947-2 BS EN 60947-2
intended for the protection of the Width 1.5 mod/pole width 1.5 mod/pole
circuits against overloads and
short circuits. HMD D Curve
15 kA
(BS EN 60898 Part 1)
15 kA for 80 - 100 - 125 A:
BS EN 60947-2
Width 1.5 mod/pole
These circuit breakers are Nominal Voltage Series HMC, HMD Lockable Toggle
equipped with reinforced screw 230/415 V~ r .PVOUJOHDBQBCJMJUZ MCB can be locked in “Off”
Protection
cages. Calibration setting : 30 °C bistable DIN-rail latches (2 position by the integrated
Devices
(BS EN 60898 Part 1) positions) upstream and locking facility on the toggle.
A label holder is integrated under Insulation voltage : 500 V downstream facilitate the This lock allows to insert a
the toggle to ensure the location mounting of the circuit 2.5-3.5mm plastic cable tie
of the product. Options breakers on the DIN-rail. where you can fit a warning card
Auxiliary if necessary and allows a safer
The “OFF” position is clearly r 5PWJTVBMJTFUIFTUBUF0/PS r 5FSNJOBMTXJUIUJHIUFOJOH working environment for all
shown by a green indicator OFF of the circuit breaker, compensation. These circuit personnel.
below the toggle. r 5P0/0''SFNPUFMZUIF breakers are equipped with
circuit breaker screw cages with tightening RCD Add-On Blocks
Suitable for isolation (according compensation, Simple, quick, adjustable and
to BS EN 60947-2) the r -PDLJOHNFDIBOJTN (reinforcement cage cable fixed
isolation of the circuit breakers is holding jaws). These elements 1. Assembly
indicated by a green indicator on r 5FSNJOBMDPWFSTBOEQIBTF contribute to an effective 2. Connection
the toggle. separators cable tightening over time. -PDLJOH
The assembly of the add-on
These circuit breakers have r 3$%BEEPOCMPDLT r 5IFTFDJSDVJUCSFBLFSTBSF block is carried out very quickly
quick closing : fast and equipped with cable terminals and easily. Simple and fast : it
simultaneous closing of the of type “fast on” upstream is a Hager innovation. add-on
contacts, independent of the and downstream to feed an blocks 125A are available in
handling speed. auxiliary low voltage circuit fixed version and adjustable
(indicating lights, auxiliary version.
This increases the life of the control...)
circuit breaker whatever the type Max. current 6A
of load. Max. cable csa - 6 mm2
Model Icc / Curve Accessories Fast-on Connection Tightening Comp. System Lockable Front Product Labelling
HMF 10kA / C Yes No No Yes Yes
HMC, HMD 15kA / C, D Yes Yes Yes Yes Yes
HMF199T
HMF299T
HMF399T
HMF499T
4.8 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFT
Miniature Circuit Breakers
80 - 125A 15kA C Curve
Curves C Use KEMA
15 kA BS EN 60898-1 Commercial and industrial Approved according to
15 kA BS EN 60947-2 applications. BS EN 60898-1.
Protection
Devices
HMC199T
HMC299T
HMC399T
HMC499T
HMD199T
HMD299T
HMD399T
HMD499T
4.10 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFT
Auxiliaries & Accessories for Devices
HMF, HMC, HMD 10kA & 15kA MCBs
Terminal Covers Screw Cap
MZN130
Phase Separator
Protection
Devices
Description Cat ref.
1 Set of 3 Phase Separators MZN131
MZN131
BTC280E
BDC480E
4.12 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFT
Single Pole & Switched Neutral (SPSN) Devices
MCB
Description Technical Data Connection Capacity
Protection and control of circuits Type C tripping characteristics Rigid 16mm2
against overloads and short Complies with BS EN 60-898 Flexible 10mm2
circuits. Calibration temperature 30ºC
Breaking capacity - 6kA
Voltage rating - 230VAC
Protection
Devices
Single Pole and Switched Neutral MCB
.-/"
JK01B
Locking Kit
MZN175
-
Locking Kit
MZN175
4.14 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFT
2 & 4 Pole RCCBs
AC Sensitive
To open a circuit automatically in Sensitivities (Fixed) All RCCBs have trip free
the event an earth fault between 10, 30, 100, 300mA & 100 and mechanisms and can be
phase and earth, and/or neutral 300mA time delayed. padlocked either on or off.
and earth. A wide range of
current ratings and sensitivities Terminal capacities Operating Temperature Range
are available. 16-63A Rigid 25mm2 r UP$DMBTT"$
Suitable for domestic, Flexible 16mm2 r UP$DMBTT"
commercial and industrial 80&100A Rigid 50mm2
applications. Flexible 35mm2 Operating Voltage
2P 110-230Vac
Technical Data Features 4P 230 - 400Vac
Complies with BS EN 61008, Positive contact indication is
IEC1008 provided by the rectangular flag Width
indicator 2P - 35mm
Red = Closed 4P - 70mm
Green = Open
Indication of trip is provided by
the oval flag indicator
Yellow = Tripped
Protection
Devices
2 Pole RCCB Sensitivity 10mA
CDC225U
CFC425U
CP284U
Type A DC Sensitive
CDA425U
Terminal Covers
4.16 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFT
RCCB Auxiliaries
Time Delayed
Indicates the position of the associated RCCB on, off or tripped. Also acts as RCCB interface with
standard MCB auxiliaries MZ203-MZ206.
Protection
Devices
Description Width (17.5mm) Cat ref.
2 NO / 2NC 6A AC1 230V 1 Mod CZ001
CZ001
Shunt Trip
Allows remote tripping of the associated device. Operation of the coil is indicated by a flag on the product
fascia.
Allows RCCB to be closed, only when voltage is above 85% of Un. RCCB will automatically trip when
voltage falls to between 70-35% of Un (230V). Operation of the release is indicated by a flag on the
product facia.
MZ206
Locking Kit
MZN175
ADN120
Locking Kit
MZN175
4.18 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFT
RCBO (Commercial / Industrial)
Single Pole 10kA
Compact protection devices Technical Data Terminal Capacities These devices are single pole &
which combine the overcurrent Insulated DIN clip 16mm2 rigid, solid neutral.
functions of an MCB with the Complies with BS EN 61009, 10mm2 flexible
earth fault functions of an RCCB IEC1009 Operating Voltage
in a single unit. A range of Sensitivities (fixed) Application 127-230V AC
sensitivity and current ratings are 10mA, 30mA & 100mA 1 module devices provide a
available for use in Breaking capacity: 10kA compact solution for installation
commercial and industrial Flying neutral lead: 700mm in consumer units and Invicta 3
applications. distribution boards.
Protection
Devices
25A 1 Mod ACB125 ACC125
32A 1 Mod ACB132 ACC132
ACB125
Locking Kit
MZN175
RCBO tripping current (30mA) with flying 700mm lead for neutral connection.
ADA990U
4.20 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFT
RCBO
Single Pole & Switched Neutral Type C 4.5kA
Compact protection devices Technical Data Breaking capacity:4.5kA
which provide MCB overcurrent The units are available with Voltage rating: 110-230V.
protection and RCCB earth current ratings of 6A, 10A, 16A, Current rating: 6-40A.
fault protection in a single unit. 20A, 25A, 32A and 40A. Operations
Complies with BS EN 61009 The device switches both the Mechanical life:
phase and neutral conductors. 20,000 operations
All ratings have 30mA earth fault
protection. The units feature Connection Capacity
indicators which show whether Rigid conductor 25mm2
tripping is due to an overcurrent Flexible conductor 16mm2
or earth fault.
Protection
Devices
RCBO Single Pole and Switched Neutral Type C 4.5kA
All terminal version for cable in cable out applications e.g. local protection, caravan pitches,
festive illuminations, street lighting.
Note: Not for use in fixed busbar consumer units or distribution boards.
ADC816F
-#
4.22 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFT
HRC Fuse Carriers
BS 88
58 Fuse carrier 32A max. Rating voltage:
37 Protection and control of circuits 415 V a.c.
against overloads and short 250 V d.c.
circuits in three phase circuits. r 'VTJOHGBDUPSDMBTT2
r 3BUFECSFBLJOHDBQBDJUJFT
Suitable for fuses which comply 80 kA at 415 V a.c.
with BS 88-1-1975 and with 40 kA at 250 V d.c.
45 the standardised performance
requirements for industrial fuse
links specified in BS 88 Part 2.
BS 88 Fuse Carriers
Protection
Supplied without BS 88 fuses
Devices
Characteristics Width (17.5mm) Cat ref.
32A max. 1 Mod LS201
-4
Motor Starters
Auxiliary Contacts
MZ520N
Alarm Contact
4.24 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFT
Motor Starters cont.
83 To ensure localised control and Options Note: Please consult us for
protection of single and three Undervoltage release: MZ528N, enclosure selection
38 phase motors. MZ529N
Auxiliary contacts: MZ520N,
Technical Data MZ527N
r "EKVTUBCMFUIFSNBMSFMBZ Alarm contact: MZ527N
r "$VUJMJTBUJPODBUFHPSZ
r $POOFDUJPODBQBDJUZ Complies With
45 2 conductors IEC 947-1, IEC 947-2
max size: Flexible 1 to 4mm2 (appropriate parts of)
Rigid 1.5 to 6mm2
Protection
Under Voltage Release
Devices
To prevent automatic restarting of the controlled device
MZ521N
4.26 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFT
Earth Fault Relays with Integral Torroids
Earth Fault Relays with Integral Torroids
Protection
Devices
Torroids
HR830
HR820
OK
OK
Auxiliary contact for remote
signalling (R versions only)
SPN415R
AI1_SP115P_T1_02
AI1_SP115P_T1_02
4.28 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFT
Surge Protection Devices
with Low Voltage Protection Level
SPDs with Low Let Through Connection Capacity Replacement Cartridges
Voltage Levels 5FSNJOBMCMPDLT-
/& For Phase:
To protect very sensitive r 3JHJEDPOEVDUPSNN2 SPN140D = SPN040D
electronic equipment. r 'MFYJCMFDPOEVDUPSNN2 SPN215D = SPN015D
This fine protection SPN415D = SPN015D
complements the main Replacement Cartridges SPN215R = SPN015R
protection and can protect 1 or These cartridges replace the SPN415R = SPN015R
many electronic devices. cartridge in the main SPD For Neutral / Earth
(page 3.24). SPN215D = SPN040N
Optimal coordination is obtained SPN415D = SPN040N
when cascaded with a main They allow simple replacement SPN215R = SPN040N
protection device. without the need to cut-off the SPN415R = SPN040N
power supply.
Discharge current:
Imax. 8kA (8/20 wave) Cartridges are available for all
BHSFFO-&%POUIFGSPOUGBDF discharge currents (40kA and
indicates the status of the SPD 15kA) with and without condition
SPN208S, connected in series indication.
with the equipment that needs to
be protected (with a A keying system exists to
Protection
Devices
maximum line current of 25A). prevent a line cartridge being
Protection is assured in both interchanged by mistake with a
common and differential modes neutral one and visa versa
neutral cartridges have a
discharge current of 65kA
Ip Up Up
-
/& -/
15kA 900V 800V
40kA 900V 800V
SPN208S 65kA 850V 750V
The new range of MCCBs provides safe and easy solutions for low voltage electrical circuit
protection. The state of the art circuit breakers offer both designers and installers a wide range of
features and beneftis.
Protection
Devices
MCCBs
Special attention has been given to ergonomics, especially with the integration of these
devices in the TP&N and panelboard range.
r$BMJCSBUFEBUDFOUJHSBEF r5IFSNBMNBHOFUJDBOEFMFDUSPOJDUSJQVOJUT
r4XJUDIEJTDPOOFDUPSWBSJBOUT rQPMFUPQPMFT
r$VSSFOUMJNJUJOHUZQF
r$PNQMFUFSBOHFPGBDDFTTPSJFT
2VJDL
tips
Hager design Visibility of auxiliaries
1 5
Suites with Hager enclosures and fitted
modular products. Indicates type of auxiliary mounted
in breaker.
2 6
Permits total selectivity and facility
generator protection. Effective solution for maintenance.
3 7
18 to 70kA, Icu 415V AC. accessories
Rotary handles, padlocks, motors,
terminal covers, auxiliaries, shunts,
UVR’s, shields etc.
4 8
auxiliaries Collar terminals, front and rear
Easy opening of secondary cover, connections, extended
clip-on type auxiliaries. connections, and spreaders.
MCCBs and Switch Disconnectors
x160
Moulded Case Circuit Thermal magnetic trip, Connection Capacity
Breakers x160 2 versions: 95mm2 rigid cables
1P, 3P and 4P r ;WFSTJPOàYFEUIFSNBMBOE 70mm2 flexible cables
Mechanical test button, lockable fixed magnetic Complies with IEC 60947-2
settings, integrated padlocking r 6WFSTJPOBEKVTUBCMFUIFSNBM
handle ø 4mm. and fixed magnetic Switch Disconnectors
r L" Allows tripping at distance using
a shunt trip unit (optional)
Complies with BS EN 60947-3
AC22A / AC23A
In Cat ref.
16A HDA014Z
20A HDA018Z
25A HDA023Z
32A HDA030Z
40A HDA038Z
50A HDA048Z
63A HDA061Z
HDA123Z
80A HDA078Z
100A HDA098Z
125A HDA123Z
In Cat ref.
25A HDA025U
40A HDA040U
63A HDA063U
80A HDA080U
100A HDA100U
125A HDA125U
HDA025U
In Cat ref.
25A HDA026U
40A HDA041U
63A HDA064U
100A HDA101U
125A HDA126U
HDA101U
4.34 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFT
MCCB x160 25kA (400/415V AC) - Single Pole
In Cat ref.
16A HHA014Z
20A HHA018Z
25A HHA023Z
32A HHA030Z
40A HHA038Z
50A HHA048Z
63A HHA061Z
HHA123Z
80A HHA078Z
100A HHA098Z
125A HHA123Z
Protection
Devices
MCCB x160 25kA (400/415V AC) - Three Pole
In Cat ref.
25A HHA025U
40A HHA040U
63A HHA063U
80A HHA080U
100A HHA100U
125A HHA125U
160A HHA160U
HHA125U
In Cat ref.
125A 3 Pole HCA125Z
125A 4 Pole HCA126Z
HCA125Z
Description 3P 4P
Cat ref. Cat ref.
Sensitivity - Adjustability 0.03A, 0.1A, 0.3A, 1A, 3A, 10A HBA125H HBA126H
Time Delay Settings - Instantaneous, 60ms, 150ms, 300ms, 500ms, 1s
HBA125H
HXA021H
HXA014H
4.36 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFT
Rotary Handles
HXA030H
Protection
Multi Padlock Adapter
Devices
Description Cat ref.
To mount on MCCB for handle locking 3 padlocks, max ø 8mm HXA039H
HXA039H
Extended Connections
Description 3P 4P
Cat ref. Cat ref.
Set of 4 extended connections for lug connection outgoing HYA013H * HYA013H *
Set of 3 or 4 spreaders HYA014H HYA015H
Interphase Barriers
Description 3P & 4P
Cat ref.
Set of 3, height: 50mm HYA019H
Set of 3, height: 97mm HYB019H
Description 3P 4P
Cat ref. Cat ref.
For extended connections HYA021H HYA022H
For spreaders HYA023H HYA024H
For rear connections (shorts) HYA025H HYA026H
HYA023H
Description 3P 4P
Cat ref. Cat ref.
DIN Rail Adaptor HYA033H HYA034H
In 3P 4P
Cat ref. Cat ref.
100A HNB100H -
125A HNB125H -
160A HNB160H HNB161H
200A HNB200H HNB201H
250A HNB250H HNB251H
HNB250H
HNB161H
In 3P 4P
Cat ref. Cat ref.
250A HCB250H HCB251H
4.38 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFT
Accessories for MCCBs and Switch Disconnectors
x250
Indication Contacts Shunt Trip Direct Rotary Handle
r DIBOHFPWFSTXJUDI 0/ Remote tripping of MCCBs or r 1BEMPDLBCMF
OFF): indicates the position of switch disconnectors. r &RVJQQFEXJUIGSPOUDPWFSBOE
the MCCB is “open” or Operating voltage: 0.7 to 1.1x Un handle
“closed” r 'JUUJOHXJUIPVUBOZBEEJUJPOBM
r DIBOHFPWFSBMBSNDPOUBDU Under Voltage Release fixings
indicates MCCB tripping Allows the tripping of MCCBs
or switch disconnectors when Extended Rotary Handle
Coil Connection voltage level drops between 35 r *1
Connection capacity: and 70% of Un. Pick up voltage r 4VQQMJFEDPNQMFUFXJUITIBGU
0.75mm2 flexible cables. 0.85x Un. and handle
Optional connection cables. The
cable capacity of the terminals is For technical details see pages
0.5 to 1.25mm2. 4.64-4.72.
Protection
Devices
Description Cat ref.
Sensitivity - Adjustability 0.03A, 0.1A, 0.3A, 1A, 3A, 10A HBB251H
Time Delay Settings - Instantaneous 60ms, 150ms, 300ms, 500ms & 1s
HXA024H
HXA014H
Rotary Handles
HXA039H
Extended Connections
Description 3P 4P
Cat ref. Cat ref.
Extended Connections (set of 4 pieces) HYB010H HYB010H
Spreaders HYB011H HYB012H
HYB012H
Interphase Barriers
Description 3P & 4P
Cat ref.
Set of 3, height: 97mm HYB019H
Description 3P 4P
Cat ref. Cat ref.
For extended covers HYB021H HYB022H
For spreaders HYB023H HYB024H
For rear connections short HYB025H HYB026H
HYB024H
Rear Connection
Description 3P 4P
Cat ref. Cat ref.
Rear connection HYB031H HYB032H
HYB031H
Conductor Size
'MFYJCMFTRNN 4UVENN J # . / - E #BHRUZ $BUSFG
4.40 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFT
MCCBs and Switch Disconnectors
H400 - H630
Moulded Case Circuit r 4IPSUEFMBZ NBHOFUJD Connection Capacity
Breakers H400, H630 equivalent) adjustable: Directly on copper cable
2 versions of trip unit: 2.5 to 10x Ir (400A) terminal, with end lug max.
Thermal magnetic trip unit TM: 2.5 to 8x Ir (630A) width: 25mm.
r 5IFSNBMBEKVTUNFOU r 5JNFEFMBZT Connection capacity: 185mm2
from 0.63 to 1x In rigid cables.
r .BHOFUJDBEKVTUNFOU 3P & 4P (adjustable neutral Complies with IEC 60947-2.
from 6 to 12x In 0 - 50 - 100%).
Mechanical test button, lockable Switch Disconnectors
&MFDUSPOJDUSJQVOJU-4* settings. Allows tripping at distance using
r -POHEFMBZ UIFSNBM a shunt trip unit (optional).
equivalent) adjustable:
Ir = 0.4 to 1x In Complies with BS EN 60947-3
AC 23A / DC 22A.
Protection
Devices
MCCBs H400 50kA TM - Three Pole & Four Pole
Breaking capacity
Icu: 50kA (400/415V AC)
Ics: 50kA
Adjustable thermal 0.63 to 1x In
Adjustable magnetic 6 to 12x In
In 3P 4P
Cat ref. Cat ref.
250A HND250H HND251H
400A HND400H HND401H
HND401H
Breaking capacity
Icu: 50kA (400/415V AC)
Ics: 50kA
Overload protection = 0.4 to 1x In
Adjustable magnetic 2.5 to 8x Ir
Time delay: 0.1 - 0.2s
In 3P 4P
Cat ref. Cat ref.
630A HND630H HND631H
HND631H
Switch Disconnectors
In 3P 4P
Cat ref. Cat ref.
400A HCD400H HCD401H
630A HCD630H HCD631H
HCD400H
HXC021H HXC024H
HXC004H
HXC014H
4.42 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFT
Rotary Handles
HXD030H
Protection
Padlock
Devices
Description Cat ref.
To mount on MCCB for handle locking 3 padlocks, ø 5-8mm2 max HXD039H
HXD039H
Extended Connections
Description 3P 4P
Cat ref. Cat ref.
400A set of 4 pieces - HYD010H
630A set of 4 pieces - HYD013H
400A spreaders HYD011H HYD012H
630A spreaders HYD014H HYD015H
HXD015H
Description 3P 4P
Cat ref. Cat ref.
For extended connections HYD021H HYD022H
For spreaders HYD023H HYD024H
For rear connections short HYD025H HYD026H
HYD022H
Rear Connections
Description 3P 4P
Cat ref. Cat ref.
400A HYD031H HYD032H
630A HYD033H HYD034H
HYD033H
Breaking capacity
Icu: 50kA (400/415V AC)
Ics: 50kA
Adjustable thermal Ir = 0.4 to 1x In
Adjustable magnetic 2.5 to 10x Ir
Time delay: 0.1 - 0.2s
Neutral setting from 0 - 50 - 100%
In 3P 4P
Cat ref. Cat ref.
800A HNE800H HNE801H
HNE800H
Switch Disconnectors
In 3P 4P
Cat ref. Cat ref.
800A HCE800H HCE801H
HCE800H
4.44 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFT
Accessories for MCCBs and Switch Disconnectors
H800
Indication Contacts Shunt Trip Direct Rotary Handle
r DIBOHFPWFSTXJUDI 0/ Remote tripping of MCCBs or r 1BEMPDLBCMF
OFF): indicates the position of switch disconnectors. r &RVJQQFEXJUIGSPOUDPWFSBOE
the MCCB is “open” or Operating voltage: 0.7 to 1.1x Un handle
“closed”. r 'JUUJOHXJUIPVUBOZBEEJUJPOBM
r DIBOHFPWFSBMBSNDPOUBDU Under Voltage Release fixings
indicates MCCB tripping. Allows the tripping of MCCBs
or switch disconnectors when Extended Rotary Handle
Coil Connection voltage level drops between 35 r *1
Connection capacity: and 70% of Un. Pick up voltage r 4VQQMJFEDPNQMFUFXJUITIBGU
0.75mm2 flexible cables. 0.85x Un. and handle
Optional connection cables. The
cable capacity of the terminals is For technical details see pages
0.5 to 1.25mm2. 4.83-4.90.
Protection
Devices
Description Cat ref.
1 Changeover Contact, 250V AC/3A, 125V DC/0.4A, 1 NO + 1 NC AX HXC021H
$IBOHFPWFS"MBSN$POUBDU
7"$"
7%$"
/0/$"- HXC024H
HXC021H HXC024H
HXC004H
HXC014H
Rotary Handles
HXD039H
Description 3P 4P
Cat ref. Cat ref.
For extended connections HYE021H HYE022H
For rear connections short HYE025H HYE026H
HYE021H
Rear Connection
Description 3P 4P
Cat ref. Cat ref.
800A HYE031H HYE032H
4.46 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFT
MCCBs
Reference Guide
Switches and Accessories
Version Poles In A / Ue V x160 x250 h400-h630 h800 / h1000
125 HCA125Z
160 HCA160Z
250 HCB250Z
3P 400 HCD400U
630 HCD630U
800 HCE800U
Switches
1000 HCE970U
125 HCA126Z
160 HCA161Z
250 HCB521Z
4P 400 HCD401U
630
800 HCE801U
1000 HCE971U
Protection
Devices
24V DC HXA001H HXC001H
48V DC HXA002H HXC002H
Shunt Trip Release 3/4P 110V AC HXA003H HXC003H
230V AC HXA004H HXC004H
400V AC HXA005H HXC005H
24V DC HXA011H HXC011H HXE011H
110V AC HXA013H HXC013H HXE013H
Undervoltage Release 3/4P
230V AC HXA014H HXC014H HXE014H
Auxiliaries
Short delay - - - -
Time delay - - - -
4.48 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFTr5FDIOJDBM
h400 h630 h800 / h1000
MCCB Switch MCCB Switch MCCB
HND HCD HND HCE HNE
3-4 3-4 3-4
85 - 85 - 85
Protection
Devices
50 - 50 - 50
30 - 30 - 30
20 - 20 - 20
40 - - - -
85 - 85 - 85
50 - 50 - 50
30 - 30 - 30
15 - 15 - 15
40 - - - -
- 9 - 20 -
- 5 (0.3) - 10kA (0.3s) -
A - B (400A - A (630A) - B (800A)
50ºC - 50ºC - 50ºC
100% - 100% - 100%
100% - 100% - 100%
95% - 95% - 95%
92% - 90% - 90%
89% - 80% - 80%
OK OK OK
4,500 4,500 4,500
15,000 15,000 15,000
-25 to +70ºC -25 to +70ºC -25 to +70ºC
-35 to +70ºC -35 to +70ºC -35 to +70ºC
75 150 150
IEC 60947-2 IEC 60947-3 IEC 60947-3 IEC 60947-3 IEC 60947-3
- OK - OK -
OK - -
- - -
- - -
OK - -
0.63 to 1x In - -
6-8-10-12 x In - -
- - OK - OK
- - 0.4 to 1x Ir - 0.4 to 1 x Ir
2.5 to 10x Ir (400A) 2.5 to 10x Ir (800A)
- - -
2.5 to 8x Ir (630A) 2.5 to 8x Ir (1000A)
- - 0.1-0.2s - 0.1-0.2s
4.50 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFTr5FDIOJDBM
h400 h630 h800 / h1000
MCCB Switch MCCB Switch MCCB
HND HCD HND HCE HNE
3-4 3-4 3-4
2 2 2
2 2 2
2 2 2
2 2 3
OK OK OK
OK OK OK
OK OK OK
Integrated Integrated Integrated
Protection
Devices
- - -
Breaking capacity according to BS EN 974-2. Network: 3 phases + neutral 220 / 380 ~ 240 / 380 V AC
Notes: “T” = total discrimination (up to the breaking capacity of the downstream device)
= no discrimination
UPSTREAM
Limits (kA) x160 TM
18 / 25 kA
In 16A 20A 25A 32A 40A 50A 63A 80A 100A
1A 1.5 1.6 1.8 2.3 2.9 4 T T T
DOWNSTREAM
4.52 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFTr5FDIOJDBM
x250 TM h630 LSI h800 / h1000 LSI
40 kA 50 kA 50 kA
125A 160A 100A 125A 160A 200A 250A 250A 400A 630A 630A 800A 1000A
T T T T T T T T T T T T T
T T T T T T T T T T T T T
T T T T T T T T T T T T T
4.9 T 4.6 T T T T T T T T T T
3.6 4.6 3.6 4.6 T T T T T T T T T
3.6 4.6 3.6 4.6 T T T T T T T T T
2.9 3.6 2.9 3.6 4.8 T T T T T T T T
2.9 3.6 2.9 3.6 4.8 T T T T T T T T
2.2 2.8 2.2 2.8 3.7 5.5 T T T T T T T
Protection
Devices
8.6 12 7.8 11 16 T T T T T T T T
4.9 6.4 4.7 6.2 8.6 14 23 T T T T T T
3.7 4.6 3.8 4.7 6.2 9.9 17 T T T T T T
3.7 4.6 3.8 4.7 6.2 9.9 17 T T T T T T
3.7 4.6 3.8 4.7 6.2 9.9 17 T T T T T T
2.9 3.6 3 3.7 4.9 7.4 1 T T T T T T
2.9 3.6 3 3.7 4.9 7.4 13 T T T T T T
2.2 2.8 2.3 2.8 3.8 5.9 9.9 T T T T T T
1.8 2.3 1.8 2.3 3.2 4.9 8.6 T T T T T T
1.5 1.8 1.4 1.8 2.4 4.2 7.7 T T T T T T
16 23 14 20 T T T T T T T T T
16 23 14 20 T T T T T T T T T
16 23 14 20 T T T T T T T T T
6.8 8.5 6.8 8.6 12 17 T T T T T T T
6.8 8.5 6.8 8.6 12 17 T T T T T T T
6.8 8.5 6.8 8.6 12 17 T T T T T T T
4.3 5.6 4.1 5.4 7.6 12 20 T T T T T T
3.2 4.1 3.2 4.1 5.6 8.3 14 T T T T T T
3.2 4.1 3.2 4.1 5.6 8.3 14 T T T T T T
3.2 4.1 3.2 4.1 5.6 8.3 14 T T T T T T
2.6 3.2 2.6 3.2 4.3 6.3 11 T T T T T T
2.6 3.2 2.6 3.2 4.3 6.3 11 T T T T T T
2 2.5 2 2.5 3.4 5 8.5 T T T T T T
1.5 2 1.5 1.9 2.7 4.2 7.3 T T T T T T
1.5 1.6 1.3 1.625 2.2 3.8 6.7 T T T T T T
13 18 12 16 24 T T T T T T T T
13 18 12 16 24 T T T T T T T T
13 18 12 16 24 T T T T T T T T
5.7 7.3 5.5 7.2 9.9 14 23 T T T T T T
5.7 7.3 5.5 7.2 9.9 14 23 T T T T T T
5.7 7.3 5.5 7.2 9.9 14 23 T T T T T T
3.4 4.4 3.3 4.3 5.9 8.6 14 T T T T T T
2.6 3.3 2.6 3.2 4.5 6.8 11 T T T T T T
2.6 3.3 2.6 3.2 4.5 6.8 11 T T T T T T
2.6 3.3 2.6 3.2 4.5 6.8 11 T T T T T T
2 2.5 2.1 2.5 3.4 5.3 8.6 T T T T T T
2 2.5 2.1 2.5 3.4 5.3 8.6 T T T T T T
1.5 1.8 1.5 1.9 2.4 4.1 6.8 T T T T T T
1.5 1.6 1.9 2.4 4.1 6.8 T T T T T T
1.5 1.6 2.08 3.1 5.3 T T T T T T
7.4 8.2 6.6 7.3 8.6 11 T T T T T T
8.2 7.3 8.6 11 T T T T T T
8.6 11 T T T T T T
8.9 12 T T T T T T
10 T T T T T T
T T T T T T
4.54
= no discrimination
UPSTREAM
Icc (kA) x160 TM x250 TM h400 TM h630 LSI h800 / h1000 LSI
(A) 16 20 25 32 40 50 63 80 100 125 160 100 125 160 200 250 250 400 250 400 630 630 800 1000
MCCBs
DOWNSTREAM
x160 TM
50 1.6 1.6 2.35 2.35 2.4 1.8 2.35 3.15 4.23 4.15 4.8 8.8 T T T T T T
40kA
63 2.15 2.15 2.2 1.7 2.15 3 4.05 3.9 4.6 8.3 T T T T T T
80 2.15 2.15 2.2 1.7 2.15 2.9 3.9 3.8 4.35 7.9 T T T T T T
100 2.1 1.95 2.75 3.7 3.6 4.15 7.5 T T T T T T
125 2.1 1.95 2.65 3.5 3.4 4 7 T T T T T T
160 1.95 2.6 3.45 3.35 3.9 6.6 T T T T T T
100 1.95 2.5 3.15 3.3 3.6 5.75 T T T T T T
125 2.5 3.15 3.3 3.6 5.75 T T T T T T
x250 TM
160 3.15 3.3 3.6 5.75 T T T T T T
40kA
200 3.3 3.6 5.75 T T T T T T
250 3.6 5.75 T T T T T T
h400 TM 250 5.75 T T T T T T
50kA 400 T T T T T
250 5.75 5.2 6.3 T T T
h630 LSI 400 6.3 T T T
630 T T T
630 9.6 10
h800 LSI
800 10
(FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFTr5FDIOJDBM
All values are given with MCCB at the maximum setting
Ipf prospective fault current
Selectivity Chart 380V ~ 415V AC according to BS EN 60947-2
Fault level to which discrimination is achieved (A)
Fuses upstream / circuit breakers downstream
BS88 Fuses
Notes: “T” = represents maximum discrimination to kA rating level of the downstream device
= no discrimination
UPSTREAM
Fuse Rating 20 25 32 40 50 63 80 100 125 160 200 250 315 355 400 450 500 560 630 710 800
MCCBs
Breaker Rating
16 48 65 88 143 220 316 T T T T T T T T T T T T T T T
20 46 62 83 140 207 300 T T T T T T T T T T T T T T T
25 60 79 125 190 280 T T T T T T T T T T T T T T T
32 75 122 200 320 T T T T T T T T T T T T T T T
x160 Frame 40 116 150 250 T T T T T T T T T T T T T T T
DOWNSTREAM
MCCB
50 122 200 T T T T T T T T T T T T T T T
18 & 25kA
Versions 63 170 450 630 T T T T T T T T T T T T T
80 440 630 T T T T T T T T T T T T T
100 515 770 1200 T T T T T T T T T T T
125 820 1200 T T T T T T T T T T T
160 1140 T T T T T T T T T T T
100 427 580 T T T T T T T T T T T T
x250 Frame 125 547 985 T T T T T T T T T T T
MCCB 160 755 1226 T T T T T T T T T T
40kA 200 909 1642 T T T T T T T T T
250 1402 2300 T T T T T T T T
h400 Frame 250 1200 T T T T T T T T T
MCCB 400 T T T T T T T
h630 Frame MCCB 630 T T T T T T T T T T
h800 / h1000 Frame
800 T T T
MCCB
Overload & Short Circuit Discrimination (Selectivity)
$VTUPNFS4FSWJDFT)PUMJOFr 5FDIOJDBM4VQQPSU)FMQMJOFr
4.55
Protection
Devices
x160
MCCBs, Switch Disconnectors
220/240V AC 380/415 AC
IEC 60 947-2 IEC 60 947-2
Icu 25 kA 18 kA
HDA
Ics 25 kA 18 kA
Icu 35 kA 25 kA
HHA
Ics 25 kA 20 kA
Icm - 2.8 kA
HCA
Icw - 2 kA - 1s
PUSH TO TRIP
1. 2.
5,5
TRIP
3.
4.56 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFTr5FDIOJDBM
x160 MCCBs, Switch Disconnectors
Tripping Curve
Tripping Curve
MCCB x160
10000
1000
Protection
Devices
100
100A, 40A
80A
75A
63A
(rated current)
30A
1
25A
20A
16A
15A
0.1
0.01
1 10 1
xIn
10000
160A
125A
HDA...up to 18kA 100A
1000 75-80A
HHA...up to 25kA 60-63A
50A
HNA...up to 40kA 40A
I²t (kA²s)
30-32A
15-16-20-25A
100
10
0,1 1 10 100
Prospective Current (kA)
100
0,25
0,3 160A
125A
100A
80A
75A
60-63A
0,5 50A
40A
10 30-32A
0,7 15-16-20-25A
0,8
Ip (kA)
0,9
HDA...up to 18kA
HHA...up to 25kA
HNA...up to 40kA
0.1
0,1 1 10 100
Prospective Current (kA)
4.58 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFTr5FDIOJDBM
x160 MCCBs, Switch Disconnectors
Dimensions
Dimensions
MCCB x160
A 11 96,1 A (mm) B (mm) C (mm)
B 1P 24.8 25 111
2P 49.5 25 111
3P 74.5 25 111
4P 99.5 25 111
130
114
45
C
25 25 15
Protection
Devices
68
Interphase Barriers
55
L
L (mm)
HYA019H 50
HYB019H 97
4.60 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFTr5FDIOJDBM
x160 MCCBs, Switch Disconnectors
Extended Connections
Extended Connection: Straight Bars and Spreaders
Protection
Devices
4 4
3P 3P
Ø8 Ø8
28
28
67 87
203 mm
203 mm
92 122
4P 4P
25 25 25 35 35 35
Conductor Size
Flexible mm2 4UVENN J # . / - E #BHRUZ $BUSFG
74.5 127
48.5
101.8
45
53.7
Extended Rotary Handle
12
74.5 112
200
101.8
45
74.5
10
4.62 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFTr5FDIOJDBM
x160 MCCBs, Switch Disconnectors
Auxiliaries
Auxiliaries
Auxiliaries for MCCBs and Tripping Switches
5.5
TRIP
Protection
PUSH TO TRIP
Devices
Mounting Combination for Auxiliaries and Releases
4P
3P
Auxiliary AX Shunt
contact trip
AX AL SH / UV
Alarm AL
contact Undervoltage
release
220/240V AC 380/415 AC
IEC 60 947-2 IEC 60 947-2
Icu 85 kA 40 kA
HNB
Ics 40 kA 20 kA
Icu - 9 kA
HCB
Ics - 3.6 kA - 1s
PUSH TO TRIP
1. 2.
TRIP
0,63
0,8 8 10
PUSH TO TRIP
1 5 13
l r (xIn) l i (xIn)
4.64 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFTr5FDIOJDBM
x250 MCCBs, Switch Disconnectors
Tripping Curve
2
hour
40
30
20
10
minute
2
Cold start
Protection
Devices
1
40
30
20
Tripping Time
10
1
second
0.6
0.4
0.2
0.1
0.06
0.04
0.02
0.01
0.005
80
100
125
200
300
400
500
600
1000
1500
2000
3000
4000
5000
8000
100A
108
Max. Let-through Energy (I2t) Characteristics
107
I2t (x106A2sec)
106
HHB...up to 25kA
HNB...up to 40kA
105
104
103
101 102 103 104 105
100
10
Peak Current (kA)
HHB...up to 25kA
HNB...up to 40kA
1
0.1
2 3 5 10 20 30 50 100 200 300
4.66 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFTr5FDIOJDBM
x250 MCCBs, Switch Disconnectors
Dimensions
Dimensions
MCCB x160
A A (mm) B (mm) C (mm)
96 mm 3P 104.5 35 126
35 35
4P 139.5 35 126
165 mm
144 mm
45
C
PUSH TO TRIP
Protection
Devices
B 22
68
PUSH TO TRIP
PUSH TO TRIP
A C
A (mm) B (mm) C (mm)
3P 104.8 28.5 64
4P 139.8 28.5 64
B
PUSH TO TRIP
4.68 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFTr5FDIOJDBM
x250 MCCBs, Switch Disconnectors
Connections
Extended Connection with Spreaders
M10
M10
6
6
Protection
Devices
PUSH TO TRIP
3P 3P
Ø 11
Ø 11
29.5
29.5
93 120
226
226
128 168
4P 4P
35 35 35 50 50 50
4P
3P
35 35 35 16 57
11
144 mm
6
11
PUSH TO TRIP
92
9 mm
Max.
Ø8
25 mm
Max.
5 12.7 Nm
Interphase Barriers
1. 2.
Conductor Size
Flexible mm2 4UVENN J # . / - E #BHRUZ $BUSFG
4.70 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFTr5FDIOJDBM
x250 MCCBs, Switch Disconnectors
Accessories
Rotary Handle
116
48.5
101.8
45
53.7
PUSH TO TRIP
Protection
Devices
104.5
12
Extended Rotary Handle
A 107.5
200
101.8
45
PUSH TO TRIP
10
TRIP
PUSH TO TRIP
4P
Auxiliary 3P
contact AX SH Shunt Trip
AX AL SH / UV
Alarm AL UV Undervoltage
contact release
4.72 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFTr5FDIOJDBM
h400 - h630
MCCBs, Switch Disconnectors
Protection
Devices
Settings
B
A
0,8
TM 0,63 8 10
1
400 A
6 12
Ir (x In) Ii (x In)
Neutral Settings:
1 B
2 -POHEFMBZDVSSFOU*STFUUJOH
2. Other curve characteristics setting (tr, Isd, tsd)
Ir (A) Characteristics 3. Neutral protection against overloads setting
0,85 5
0,8 0,9 4 6
0,63 0,95 3 7
0,5 1 2
0,4 1
ON
50 % 100 %
3
OFF
PICK UP TEST IN
Adjustable IR In A
250A / 400A 630A
T
4.74 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFTr5FDIOJDBM
h400 - h630 MCCBs, Switch Disconnector
Tripping Curve, Electronic Trip Unit Setting
MCCB h630 LSI (250A and 400A)
3
2 T
hour
Ir
1 Ip
40 tr
30 tp
20 Isd
tsd
10
minute
Ii
6
I
4
2
Overlapped
1
characteristics
40
Protection
30
Devices
20
Tripping Time
10
1
second
0.6
0.4
0.2
0.1
0.06
0.04
0.02
0.01
0.005
80
100
125
200
300
400
500
600
1000
1500
2000
3000
4000
5000
8000
IR (A)
LTD Pick-up Current IR x/n 0.4 0.5 0.63 0.8 0.9 0.95 1
Characteristics No. 1 2 3 4 5 6 7
rR (s) 11 21 21 5 10 19 29
LTD
200% x Ir 600% x Ir
Standard Isd x/R 2.5 5 10
STD
tsd (s) 0.1 0.2
INST Ii x/R 14 (max : 13 x In
In x/n 0 - 0.5 - 1
Optional N
tN (s) tN = tR
IR
1
Ip
40 tR
30 tp
Ig
20 Isd
tsd
10
minute
tg Ii
6
I
4
2
Overlapped
1
characteristics
40
30
20
Tripping Time
10
1
second
0.6
0.4
0.2
0.1
0.06
0.04
0.02
0.01
0.005
80
100
125
200
300
400
500
600
1000
1500
2000
3000
4000
5000
8000
IR (A)
LTD Pick-up Current IR x/n 0.4 0.5 0.63 0.8 0.85 0.9 0.95 1
Characteristics No. 1 2 3 4 5 6
rR (s) 11 21 21 5 10 16
LTD
200% x I R 600% x I R
Standard Isd x/R 2.5 5 8
STD
tsd (s) 0.1 0.2
INST Ii x/R 14 (max : 13 x In)
In x/n 0 - 0.5 - 1
Optional N
tN (s) tN=tR
4.76 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFTr5FDIOJDBM
h400 - h630 MCCBs, Switch Disconnectors
Thermal Constraint and Current Limiting Curves
Thermal Constraint Curve
30 30
20 20
10 10
5 5
3 3
2 2
I2t (x106A2sec)
I2t (x106A2sec)
1 1
Protection
Devices
0.5 0.5
0.3 0.3
0.2 0.2
HND...up to 50kA HND...up to 50kA
HED...up to 70kA HED...up to 70kA
0.1 0.1
0.05 0.05
0.03 0.03
0.02 0.02
30 30
20 20
10 10
2
Ip (kA)
Ip (kA)
0.5 0.5
0.3 0.3
0.2 0.2
HND...up to 50kA HND...up to 50kA
HED...up to 70kA HED...up to 70kA
0.1 0.1
0.05 0.05
0.03 0.03
0.02 0.02
A 145
45 45
102
C
B 32
97
4.78 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFTr5FDIOJDBM
h400 - h630 MCCBs, Switch Disconnectors
Accessories
Terminal Covers for Extended Connections (spreaders)
4P 185 114 99 98
Protection
Devices
Terminal Covers for Rear Connections and Collar Terminal
A C
D
3P 140 3 4.5 97 93
4P 185 3 4.5 97 93
30
30
8
Ø14 Ø14
349 mm
30
4P
60 60 60
208
Rear Connections
4P
3P
15 56
15
45 45 45
228 mm
6/8
15
96
12
Max.
M 10
30 mm
Max.
4.80 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFTr5FDIOJDBM
h400 - h630 MCCBs, Switch Disconnectors
Accessories
Direct Rotary Handle
139.5 200
103
241.5
127
Protection
Devices
Extended Rotary Handle
139.5 180.5
23.8
200
127
241.5
27
6
6
TRIP
AX
AL SH / UV
Undervoltage
release
Alarm UV
contact
AL
4.82 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFTr5FDIOJDBM
h800
MCCBs, Switch Disconnectors
Protection
Devices
LSI 1 B
2
800/1000 A Ir (A) Characteristics
0,85 5
0,8 0,9 4 6
0,63 0,95 3 7
0,5 1 2
0,4 1
ON
60 % 100 %
3
OFF
PICK UP TEST IN
--POHEFMBZQSPUFDUJPOBHBJOTUPWFSMPBET*SBOEUSTFUUJOHT
S - Short delay - protection against short circuits: Isd and tsd settings
Adjustable IR 1
}
In A
T
250A / 400A
7 LSI
6 Long Time Delay Short Time Delay Inst
5 Ir (x In) tr (s) isd (xlr) tsd (s) Ii (xlr)
4
1
0.4 OK
2 0.5 OK
2
5,6,7 0.63 OK
0.2S
3 1. 0.8 OK
0.1S Ir (x In) 0.85 -
1,2 3 4 0.9 OK
2.5 5 10 14 xIR I
0.95 OK
1 OK
1 11s at 2 xlr 2.5 0.1 14 (max 12
2 21s at 2 xlr x In)
3 5
2.
1. Ir(A) 2. Im 3. N 4 5s at 6 xlr 10
Characteristics
-4* 0.4 - 1 In 2 - 10 Ir 0% 5 10s at 6 xlr 0.2
50% 6 19s at 6 xlr
100%
7 29s at 6 xlr
3. 0%
Neutral 50%
protection 100%
4
3
2
hour
1
50
40
30
20
10
minute
8
6
5
4
3 5
2
6
7
1
50
40
30
Tripping Time
20
10 1
8
6
5 2
4
3
2
3
1
second
0.8
0.6 4
0.5
0.4
0.3 5,6,7
0.2
0.1
0.08
0.06
0.05 1,2,3,4
0.04
0.03
0.02
0.01
0.005
80
90
100
125
150
200
250
500
600
700
800
900
1000
1500
2000
2500
3000
4000
5000
6000
7000
8000
Ir (%)
IR (A)
LTD Pick-up Current IR x/n 0.4 0.5 0.63 0.8 0.9 0.95 1
Characteristics No. 1 2 3 4 5 6
rR (s) 11 21 21 5 10 16
LTD
200% x Ir 600% x Ir
Standard Isd x/R 2.5 5 8
STD
tsd (s) 0.1 0.2
INST Ii x/R 14 (max : 10 x In)
In x/n 0.8
Optional NP
tN (s) In = tR
4.84 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFTr5FDIOJDBM
h800 MCCBs, Switch Disconnectors
Thermal Constraint and Current Limiting Curve
Thermal Constraint Curve
MCCB h800
30
20
10
Protection
0.5
Devices
0.3
0.2
HNE...up to 50kA
HEE...up to 70kA
0.1
0.05
0.03
0.02
MCCB h800
30
20
10
2
Ip (kA)
0.5
0.3
0.2
HNE...up to 50kA
HEE...up to 70kA
0.1
0.05
0.03
0.02
A
B
145
331
403
90
D
35
70 70 99,5
B
534
534
A C
3P 206 18 102
4P 280 18 102
4.86 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFTr5FDIOJDBM
h800 MCCBs, Switch Disconnectors
Connection
Extended Connection
1. 2.
36
Ø 13
40
Protection
Devices
19
Rear Connections
90°
12 12 12
58 58
122 mm
20 36
243,5 mm
288,5 mm
Ø 13
19
4.88 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFTr5FDIOJDBM
h800 MCCBs, Switch Disconnector
Accessories
Direct Rotary Handle
115 200
103
127
Protection
Devices
Extended Rotary Handle
130 188
92 23,8
200
127
27
139,5 215
118
160
2
1
TRIP
Auxiliary
contact
AX SH Shunt
trip
AX
AL SH / UV
Alarm AL UV Undervoltage
contact release
4.90 (FOFSBM$BUBMPHVFr1SPUFDUJPO%FWJDFTr5FDIOJDBM
Downlighter
junction box
With the J501 downlighter junction box, all of these obstacles can be
overcome.