SELECTION CHART : FUSE PROTECTED DOL STARTER FEEDERS

TYPE '2' Co-ordination, Iq=50 kA at 415V, 3Ø, 50 Hz.


as per Standards: IEC 60947-4-1, IS 13947 (Part 4/Sec 1), EN 60947-4-1
Sr. Motor Rating: 3Ø, 415V, 50 Hz Contactor Overload Relay Nominal Backup fuse S-D-F
No. hp kW In (A) Type Type Range (A) Type Rating (A)
1 0.125 0.09 0.4 MNX 9 MNX-R3 0.3 - 0.5 HF 2 FN 32 / FNX 32
2 0.16 0.12 0.45 MNX 9 MNX-R3 0.3 - 0.5 HF 2 FN 32 / FNX 32
3 0.2 0.15 0.57 MNX 9 MNX-R3 0.45 - 0.75 HF 2 FN 32 / FNX 32
4 0.25 0.19 0.75 MNX 9 MNX-R3 0.6 - 1.0 HF 4 FN 32 / FNX 32
5 0.33 0.25 0.9 MNX 9 MNX-R3 0.6 - 1.0 HF 4 FN 32 / FNX 32
6 0.5 0.37 1.2 MNX 9 MNX-R3 0.9 - 1.5 HF 6 FN 32 / FNX 32
7 0.75 0.55 1.6 MNX 9 MNX-R3 1.4 - 2.3 HF 6 FN 32 / FNX 32
8 1 0.75 2.1 MNX 9 MNX-R3 1.4 - 2.3 HF 8 FN 32 / FNX 32
9 1.5 1.1 2.7 MNX 9 MNX-R3 2.0 - 3.3 HF 10 FN 32 / FNX 32
10 1.75 1.3 3 MNX 9 MNX-R3 2.0 - 3.3 HF 10 FN 32 / FNX 32
11 2 1.5 3.5 MNX 9 MNX-R3 3-5 HF 16 FN 32 / FNX 32
12 2.5 1.8 4.8 MNX 9 MNX-R3 4.5 - 7.5 HF 16 FN 32 / FNX 32
13 3 2.25 5 MNX 9 MNX-R3 4.5 - 7.5 HF 16 FN 32 / FNX 32
14 4 3 6.4 MNX 9 MNX-R3 4.5 - 7.5 HF 20 FN 32 / FNX 32
15 5 3.7 7.9 MNX 9 MNX-R3 6 - 10 HF 20 FN 32 / FNX 32
16 5.5 4 8.5 MNX 9 MNX-R3 6 - 10 HF 20 FN 32 / FNX 32
17 6 4.5 9 MNX 12 MNX-R3 6 - 10 HF 25 FN 32 / FNX 32
18 7.5 5.5 11.2 MNX 12 MNX-R3 9 - 15 HF 32 FN 32 / FNX 32
19 10 7.5 14.8 MNX 18 MNX-R3 9 - 15 HF 32 FN 32 / FNX 32
20 12.5 9.3 19 MNX 25 MNX-R3 14 - 23 HF 50 FN 63 / FNX 63
21 15 11 22 MNX 25 MNX-R3 14 - 23 HF 63 FN 63 / FNX 63
22 17.5 13 24 MNX 32 MNX-R3 20 - 33 HF 63 FN 63 / FNX 63
23 20 15 29 MNX 32 MNX-R3 20 - 33 HF 63 FN 63 / FNX 63
24 25 18.6 35 MNX 40 MNX-R3 30 - 50 HN, 000* 80 FN 100 / FNX 100 *
25 30 22.5 40 MNX 45 MNX-R4 24-40 HN, 000* 80 FN 100 / FNX 100 *
26 35 26 47 MNX 70 MNX-R4 30 - 50 HN, 000* 100 FN 100 / FNX 100 *
27 40 30 55 MNX 70 MNX-R4 45 - 75 HN, 000* 100 FN 100 / FNX 100 *
28 45 33.5 60 MNX 70 MNX-R4 45 - 75 HN, 000* 100 FN 100 / FNX 100 *
29 50 37 66 MNX 80 MNX-R4 45 - 75 HN, 00 125 FN 125 / FNX 125
30 60 45 80 MNX 95 MNX-R4 66 - 110 HN, 00 125 FN 125 / FNX 125
31 75 55 100 MNX 110 MNX-R4 66 - 110 HN, 00 # 160 FN 160 / FNX 160 #
32 90 67.5 120 MNX 140 MNX-R5 90 - 150 HN, 0 200 FN 200 / FNX 200
33 100 75 135 MNX 140 MNX-R5 90 - 150 HN, 0 200 FN 200 / FNX 200
sheet 1 of 2
ubs \ R1: 21.10.05

SELECTION CHART : FUSE PROTECTED DOL STARTER FEEDERS


TYPE '2' Co-ordination, Iq=50 kA at 415V, 3Ø, 50 Hz.
as per Standards: IEC 60947-4-1, IS 13947 (Part 4/Sec 1), EN 60947-4-1
Motor Rating: 3Ø, 415V, 50 Hz Contactor Overload Relay Nominal Backup fuse S-D-F
hp kW In (A) Type Type Range (A) Type Rating (A)
34 110 80 139 MNX 185 MNX-R5 90 - 150 HN, 0 200 FN 200 / FNX 200
35 125 90 165 MNX 185 MNX-R5 135 - 225 HN, 1 250 FN 250 / FNX 250
36 150 110 200 MNX 225 MNX-R5 135 - 225 HN, 1 250 FN 250 / FNX 250
37 175 130 230 MNX 265 MNX-R5 180 - 300 HN, 1 315 FN 315 / FNX 315
38 197 147 260 MNX 265 MNX-R5 180 - 300 HN, 2 400 FN 400 / FNX 400
39 200 150 275 MNX 325 MNX-R5 180 - 300 HN, 2 400 FN 400 / FNX 400
40 215 160 280 MNX 325 MNX-R5 180 - 300 HN, 2 400 FN 400 / FNX 400
41 225 168 300 MNX 325 MNX-R5 270 - 450 HN, 2 400 FN 400 / FNX 400
42 245 180 320 MNX 325 MNX-R5 270 - 450 HN, 2 400 FN 400 / FNX 400
43 270 200 340 MNX 400 MNX-R5 270 - 450 HN, 3 500 FN 630 / FNX 630
44 300 225 385 MNX 550 MNX-R5 270 - 450 HN, 3 500 FN 630 / FNX 630
45 335 250 425 MNX 550 MNX-R5 270 - 450 HN, 3 500 FN 630 / FNX 630
46 400 300 500 MNX 550 MNX-R5L 340 - 570 HN, 3 630 FN 630 / FNX 630
47 430 315 535 MNX 550 MNX-R5L 340 - 570 HN, 3 630 FN 630 / FNX 630

30-125 hp - 500 rpm


125-300 hp - 375 rpm

sheet 2 of 2
ubs \ R0 : 15.02.05
ubs \ R1: 21.10.05
SELECTION CHART : FUSE PROTECTED STAR-DELTA STARTER FEEDERS
TYPE '2' Co-ordination, Iq=50 kA at 415V, 3Ø, 50 Hz.
as per Standards: IEC 60947-4-1, IS 13947 (Part 4/Sec 1), EN 60947-4-1
Ratings at 3Ø, 415V, 50 Hz
Contactor Overload Relay Nominal Back up fuse
Sr. MOTOR Current, In (A) S-D-F
No. hp kW Line Phase STAR LINE DELTA Type Range (A) Type Rating (A)
1 1 0.75 2.1 1.2 MNX 9 MNX 9 MNX 9 MNX-R3 0.9 - 1.5 HF 4 FN 32 / FNX 32
2 1.5 1.1 2.7 1.6 MNX 9 MNX 9 MNX 9 MNX-R3 1.4 - 2.3 HF 6 FN 32 / FNX 32
3 2 1.5 3.5 2.0 MNX 9 MNX 9 MNX 9 MNX-R3 1.4 - 2.3 HF 6 FN 32 / FNX 32
4 3 2.25 5 2.9 MNX 9 MNX 9 MNX 9 MNX-R3 2 - 3.3 HF 8 FN 32 / FNX 32
5 4 3 6.4 3.7 MNX 9 MNX 9 MNX 9 MNX-R3 3-5 HF 10 FN 32 / FNX 32
6 5 3.75 7.9 4.6 MNX 9 MNX 9 MNX 9 MNX-R3 3-5 HF 16 FN 32 / FNX 32
7 6 4.5 9 5.2 MNX 9 MNX 9 MNX 9 MNX-R3 4.5 - 7.5 HF 16 FN 32 / FNX 32
8 7.5 5.5 11.2 6.5 MNX 9 MNX 9 MNX 9 MNX-R3 4.5 - 7.5 HF 20 FN 32 / FNX 32
9 10 7.5 14.8 8.5 MNX 9 MNX 9 MNX 9 MNX-R3 6 - 10 HF 20 FN 32 / FNX 32
10 12.5 9.3 19 11.0 MNX 9 MNX 12 MNX 12 MNX-R3 9 - 15 HF 32 FN 32 / FNX 32
11 15 11 22 12.7 MNX 12 MNX 18 MNX 18 MNX-R3 9 - 15 HF 32 FN 32 / FNX 32
12 20 15 29 16.7 MNX 12 MNX 25 MNX 25 MNX-R3 14 - 23 HF 40 FN 63 / FNX 63
13 25 18.6 35 20.2 MNX 18 MNX 25 MNX 25 MNX-R3 14 - 23 HF 50 FN 63 / FNX 63
14 30 22.5 40 23.1 MNX 18 MNX 25 MNX 25 MNX-R3 20 - 33 HF 63 FN 63 / FNX 63
15 35 26 47 27.1 MNX 25 MNX 32 MNX 32 MNX-R3 20 - 33 HN, 000 * 63 FN 100 / FNX 100 *
16 40 30 55 31.8 MNX 32 MNX 32 MNX 32 MNX-R3 24 - 40 HN, 000 * 63 FN 100 / FNX 100 *
17 45 33.5 60 34.6 MNX 32 MNX 40 MNX 40 MNX-R3 24 - 40 HN, 000 * 80 FN 100 / FNX 100 *
18 50 37 66 38.1 MNX 32 MNX 45 MNX 45 MNX-R3 24 - 40 HN, 000 * 80 FN 100 / FNX 100 *
19 60 45 80 46.2 MNX 45 MNX 70 MNX 70 MNX-R4 30 - 50 HN, 000 * 100 FN 100 / FNX 100 *
20 65 48.5 87 50.2 MNX 45 MNX 70 MNX 70 MNX-R4 45 - 75 HN, 000 * 100 FN 100 / FNX 100 *
21 70 52 94 54.3 MNX 45 MNX 70 MNX 70 MNX-R4 45 - 75 HN, 00 125 FN 125 / FNX 125
22 75 55 100 57.7 MNX 45 MNX 70 MNX 70 MNX-R4 45 - 75 HN, 00 125 FN 125 / FNX 125
23 90 67.5 120 69.3 MNX 80 MNX 80 MNX 80 MNX-R4 45 - 75 HN, 00 #
160 FN 160 / FNX 160 #

24 100 75 135 77.9 MNX 80 MNX 95 MNX 95 MNX-R4 66 - 110 HN, 0 160 FN 200 / FNX 200

sheet 1 of 2
ubs \ R0: 15.02.05
ubs \ R1: 21.10.05

SELECTION CHART : FUSE PROTECTED STAR-DELTA STARTER FEEDERS


TYPE '2' Co-ordination, Iq=50 kA at 415V, 3Ø, 50 Hz.
as per Standards: IEC 60947-4-1, IS 13947 (Part 4/Sec 1), EN 60947-4-1
Ratings at 3Ø, 415V, 50 Hz
Contactor Overload Relay Nominal Back up fuse
Sr. MOTOR Current, In (A) S-D-F
No. hp kW Line Phase STAR LINE DELTA Type Range (A) Type Rating (A)
25 125 90 165 95.0 MNX 80 MNX 95 MNX 95 MNX-R4 66 - 110 HN, 0 200 FN 200 / FNX 200
26 150 110 200 115.5 MNX 95 MNX 140 MNX 140 MNX-R5 90 - 150 HN, 1 250 FN 250 / FNX 250
27 175 130 230 132.8 MNX 110 MNX 140 MNX 140 MNX-R5 90 - 150 HN, 1 250 FN 250 / FNX 250
28 200 150 275 158.8 MNX 140 MNX 185 MNX 185 MNX-R5 135 - 225 HN, 1 315 FN 315 / FNX 315
29 240 175 310 179.0 MNX 140 MNX 265 MNX 265 MNX-R5 135 - 225 HN, 2 400 FN 400 / FNX 400
30 250 185 325 187.6 MNX 140 MNX 265 MNX 265 MNX-R5 135 - 225 HN, 2 400 FN 400 / FNX 400
31 275 204 360 207.8 MNX 265 MNX 265 MNX 265 MNX-R5 135 - 225 HN, 3 400 FN 400 / FNX 400
32 300 225 385 222.3 MNX 265 MNX 265 MNX 265 MNX-R5 180 - 300 HN, 3 500 FN 630 / FNX 630
33 400 300 500 288.7 MNX 265 MNX 325 MNX 325 MNX-R5 180 - 300 HN, 3 500 FN 630 / FNX 630
34 450 335 550 317.5 MNX 400 MNX 550 MNX 550 MNX-R5 270 - 450 HN, 3 630 FN 630 / FNX 630
35 500 375 615 355.1 MNX 400 MNX 550 MNX 550 MNX-R5 270 - 450 HN, 3 630 FN 630 / FNX 630

NOTES:
1) Contactors / S-D-Fs indicated are of the minimum ratings. Higher rating of Contactors and S-D-Fs can be used.
2) For applications above 35 HP, suitable scheme should be used to
ensure change-over delay of 40-70 ms. between Star & Delta contactors.
3) Normal Motor starting time, Power factor and Efficiency is assumed in all cases.
4) * : Only size 000 fuses to be used with FNX 100 S-D-F.
5) # : Only size 00 fuses to be used with FNX 160 S-D-F.
6) Selection is valid only for complete L&T combinations ie. "S-D-F + Fuse + Contactors + O/L. Relay".
Compliance to Type '2' co-ordination is not assured in case these combinations are changed
to accommodate another brand / rating of products like S-D-F / Fuse etc.
7) All S-D-F ratings are AC-23A as per IS 13947 (Part 3), IEC 60947-3 & EN 60947-3
8) Switchgear selection for motors with longer starting times can be made available on request.

sheet 2 of 2
ubs \ R0: 15.02.05
ubs \ R1: 21.10.05
SELECTION CHART : FUSELESS PROTECTION FOR DOL STARTER FEEDERS WITH MCCB / MPCB
TYPE '2' Co-ordination, Iq=50 kA at 415V, 3Ø, 50 Hz.
as per Standards : IEC 60947-4-1, IS 13947 (Part 4/Sec 1), EN 60947-4-1
Sr. Motor Rating: 3Ø, 415V, 50 Hz Overload Relay MPCB / MCCB
Contactor
No. hp kW FLC, In (A) Type Range (A) Type Rating
1 0.125 0.09 0.4 - - MNX 9 MNX-G0 / G1 0.25 - 0.4
2 0.16 0.12 0.45 - - MNX 9 MNX-G0 / G1 0.4 - 0.63
3 0.2 0.15 0.57 - - MNX 9 MNX-G0 / G1 0.4 - 0.63
4 0.25 0.19 0.75 - - MNX 9 MNX-G0 / G1 0.63 - 1
5 0.33 0.25 0.9 - - MNX 9 MNX-G0 / G1 0.63 - 1
6 0.5 0.37 1.2 - - MNX 9 MNX-G0 / G1 1 - 1.6
7 0.75 0.55 1.6 - - MNX 9 MNX-G0 / G1 1 - 1.6
8 1 0.75 2.1 - - MNX 9 MNX-G0 / G1 1.6 - 2.5
9 1.5 1.1 2.7 - - MNX 12 MNX-G0 / G1 2.5 - 4
10 1.75 1.3 3 - - MNX 12 MNX-G0 / G1 2.5 - 4
11 2 1.5 3.5 - - MNX 12 MNX-G0 / G1 2.5 - 4
12 2.5 1.8 4.8 - - MNX 12 MNX-G0 / G1 4 - 6.3
13 3 2.25 5 - - MNX 12 MNX-G0 / G1 4 - 6.3
14 4 3 6.4 - - MNX 12 MNX-G0 / G1 6.3 - 10
15 5 3.7 7.9 - - MNX 12 MNX-G0 / G1 6.3 - 10
16 6 4.5 9 - - MNX 12 MNX-G0 / G1 6.3 - 10
17 7.5 5.5 11.2 - - MNX 12 MNX-G0 / G1 10 - 16
18 10 7.5 14.8 - - MNX 18 MNX-G0 / G1 10 - 16
19 12.5 9.3 19 - - MNX 25 MNX-G1 16 - 20
20 15 11 22 - - MNX 25 MNX-G1 20 - 25
21 17.5 13 24 - - MNX 32 MNX-G1 20 - 25
22 20 15 29 - - MNX 32 MNX-G1 24 - 32
23 25 18.6 35 - - MNX 40 MNX-G3 32 - 40
24 30 22.5 40 - - MNX 45 MNX-G3 32 - 40
25 35 26 47 - - MNX 50 MNX-G3 40 - 50
26 40 30 55 - - MNX 70 MNX-G3 50 - 58
27 45 33.5 60 - - MNX 80 MNX-G3 55 - 63
28 50 37 66 MNX-R5 42 - 69 MNX 140 DN 160H 100
29 60 45 80 MNX-R5 60 - 100 MNX 140 DN 160H 125
30 75 55 100 MNX-R5 60 - 100 MNX 140 DN 160H 160
31 90 67.5 120 MNX-R5 90 - 150 MNX 140 DN 160H 160
32 100 75 135 MNX-R5 90 - 150 MNX 185 DN 250H 200
33 110 80 139 MNX-R5 90 - 150 MNX 185 DN 250H 200
34 125 90 165 MNX-R5 135 - 225 MNX 225 DN 250H 250
35 150 110 200 MNX-R5 135 - 225 MNX 265 DN 400H 320
36 175 130 230 MNX-R5 180 - 300 MNX 265 DN 400H 400
37 197 147 260 MNX-R5 180 - 300 MNX 265 DN 400H 400
38 200 150 275 MNX-R5 180 - 300 MNX 325 DN 400H 400
39 215 160 280 MNX-R5 180 - 300 MNX 325 DN 400H 400
40 225 168 300 MNX-R5 270 - 450 MNX 400 DN 630H 500
41 245 180 320 MNX-R5 270 - 450 MNX 400 DN 630H 500
42 270 200 340 MNX-R5 270 - 450 MNX 400 DN 630H 500

NOTES :
1 Selection Chart is for Standard 3-phase, Squirrel cage Motor with Average Power Factor,
and Efficiency.
2 Motor ratings at 415 V, 50 Hz.
3 Contactor ratings indicated are the Minimum ratings suitable for the application.
Higher Sizes / Ratings can be used.
4 Normal Motor Starting time (£ 5 sec.) is assumed.
For higher Starting time, refer back to L&T.
5 All the MCCBs are Instantaneous type only.
6 Selection is valid only for complete L&T combinations ie. "Contactor, Relay, MCCB & MPCB".
Compliance to Type '2' co-ordination is not assured in case these combinations are changed
to accommodate another brand / rating of products. compiled:
ubs \ R0 : 15.02.05
ubs \ R1: 21.10.05
SELECTION CHART : FUSELESS PROTECTION FOR DOL STARTER FEEDERS WITH MCCBs, type 'DM'
TYPE '2' Co-ordination, Iq=50 kA at 415V, 3Ø, 50 Hz.
as per Standards : IEC 60947-4-1, IS 13947 (Part 4/Sec 1), EN 60947-4-1

Sr. Motor Rating: 3Ø, 415V, 50 Hz Overload Relay MCCB


Contactor
No. hp kW FLC, In (A) Type Range (A) Type Rating
1 0.125 0.09 0.4 MNX-R3 0.3 - 0.5 MNX 9 DM 16 0.63
2 0.16 0.12 0.45 MNX-R3 0.45 - 0.75 MNX 9 DM 16 0.63
3 0.2 0.15 0.57 MNX-R3 0.45 - 0.75 MNX 9 DM 16 1
4 0.25 0.19 0.75 MNX-R3 0.6 - 1 MNX 9 DM 16 1
5 0.33 0.25 0.9 MNX-R3 0.6 - 1 MNX 9 DM 16 1
6 0.5 0.37 1.2 MNX-R3 0.9 - 1.5 MNX 9 DM 16 1.6
7 0.75 0.55 1.6 MNX-R3 1.4 - 2.3 MNX 9 DM 16 1.6
8 1 0.75 2.1 MNX-R3 1.4 - 2.3 MNX 9 DM 16 2.5
9 1.5 1.1 2.7 MNX-R3 2.0 - 3.3 MNX 9 DM 16 2.5
10 1.75 1.3 3 MNX-R3 2.0 - 3.3 MNX 9 DM 16 4
11 2 1.5 3.5 MNX-R3 3.0 - 5.0 MNX 9 DM 16 4
12 2.5 1.8 4.8 MNX-R3 4.5 - 7.5 MNX 9 DM 16 5
13 3 2.25 5 MNX-R3 4.5 - 7.5 MNX 9 DM 16 5
14 4 3 6.4 MNX-R3 4.5 - 7.5 MNX 9 DM 16 7.5
15 5 3.7 7.9 MNX-R3 6 - 10 MNX 9 DM 16 7.5
16 6 4.5 9 MNX-R4 9 - 15 MNX 32 DM 16 10
17 7.5 5.5 11.2 MNX-R4 9 - 15 MNX 32 DM 16 12
18 10 7.5 14.8 MNX-R4 14 - 23 MNX 80 DM 16 16
19 12.5 9.3 19 MNX-R4 14 - 23 MNX 80 DM100 25
20 15 11 22 MNX-R4 20 - 33 MNX 80 DM 100 25
21 17.5 13 24 MNX-R4 20 - 33 MNX 80 DM 100 30
22 20 15 29 MNX-R4 20 - 33 MNX 80 DM 100 35
23 25 18.6 35 MNX-R4 30 - 50 MNX 80 DM 100 50
24 30 22.5 40 MNX-R4 30 - 50 MNX 80 DM 100 50
25 35 26 47 MNX-R4 45 - 75 MNX 80 DM 100 60
26 40 30 55 MNX-R4 45 - 75 MNX 80 DM 100 70
27 45 33.5 60 MNX-R4 45 - 75 MNX 80 DM 100 70
28 50 37 66 MNX-R4 45 - 75 MNX 80 DM 100 80
29 60 45 80 MNX-R4 66 - 110 MNX 95 DM 160 100
30 75 55 100 MNX-R4 66 - 110 MNX 110 DM 160 120
31 90 67.5 120 MNX-R5 90 - 150 MNX 140 DM 160 160
32 100 75 135 MNX-R5 90 - 150 MNX 140 DM 160 160
33 110 80 139 MNX-R5 90 - 150 MNX 185 DM 250 200
34 125 90 165 MNX-R5 135 - 225 MNX 225 DM 250 200
35 150 110 200 MNX-R5 135 - 225 MNX 265 DM 400 275
36 175 130 230 MNX-R5 180 - 300 MNX 265 DM 400 325
37 197 147 260 MNX-R5 180 - 300 MNX 265 DM 400 325
38 200 150 275 MNX-R5 180 - 300 MNX 325 DM 400 325
39 215 160 280 MNX-R5 180 - 300 MNX 325 DM 400 350
40 225 168 300 MNX-R5 270 - 450 MNX 325 DM 400 350
41 245 180 320 MNX-R5 270 - 450 MNX 325 DM 400 400
42 270 200 340 MNX-R5 270 - 450 MNX 400 DM 400 400

NOTES :
1 Selection Chart is for Standard 3-phase, Squirrel cage Motor with Average Power Factor,
and Efficiency.
2 Motor ratings at 415 V, 50 Hz.
3 Contactor ratings indicated are the minimum ratings suitable for the application.
Higher Sizes / Ratings can be used.
4 Normal Motor Starting time (£ 5 sec.) is assumed.
For higher Starting time, refer back to L&T.
5 All the MCCBs are Instantaneous type only.
6 Selection is valid only for complete L&T combinations ie. "Contactor, Relay & MCCB".
Compliance to Type '2' co-ordination is not assured in case these combinations are changed
to accommodate another brand / rating of products. compiled:
ubs \ R0 : 15.02.05
ubs \ R1: 21.10.05
SELECTION CHART : FUSELESS PROTECTION FOR DOL STARTER FEEDERS WITH MNX-G2 MPCB
TYPE '2' Co-ordination, Iq=50 kA at 415V, 3Ø, 50 Hz.
as per Standards : IEC 60947-4-1, IS 13947 (Part 4/Sec 1), EN 60947-4-1
Sr. Motor Rating: 3Ø, 415V, 50 Hz Overload Relay MPCB
Contactor
No. hp kW FLC, In (A) Type Range (A) Type Rating
1 0.25 0.19 0.75 MNX-R3 0.6 - 1 MNX 9 MNX-G2 1
2 0.33 0.25 0.9 MNX-R3 0.6 - 1 MNX 9 MNX-G2 1
3 0.5 0.37 1.2 MNX-R3 0.9 - 1.5 MNX 9 MNX-G2 1.6
4 0.75 0.55 1.6 MNX-R3 1.4 - 2.3 MNX 9 MNX-G2 1.6
5 1 0.75 2.1 MNX-R3 1.4 - 2.3 MNX 9 MNX-G2 2.5
6 1.5 1.1 2.7 MNX-R3 2 - 3.3 MNX 12 MNX-G2 4
7 1.75 1.3 3 MNX-R3 2 - 3.3 MNX 12 MNX-G2 4
8 2 1.5 3.5 MNX-R3 3-5 MNX 12 MNX-G2 4
9 2.5 1.8 4.8 MNX-R3 4.5 - 7.5 MNX 25 MNX-G2 6.3
10 3 2.25 5 MNX-R3 4.5 - 7.5 MNX 25 MNX-G2 6.3
11 4 3 6.4 MNX-R3 6 - 10 MNX 25 MNX-G2 10
12 5 3.7 7.9 MNX-R3 6 - 10 MNX 25 MNX-G2 10
13 6 4.5 9 MNX-R3 6 - 10 MNX 25 MNX-G2 10
14 7.5 5.5 11.2 MNX-R3 9 - 15 MNX 25 MNX-G2 12
15 10 7.5 14.8 MNX-R3 9 - 15 MNX 25 MNX-G2 16
16 12.5 9.3 19 MNX-R3 14 - 23 MNX 32 MNX-G2 20
17 15 11 22 MNX-R3 14 - 23 MNX 32 MNX-G2 25
18 17.5 13 24 MNX-R3 20 - 33 MNX 32 MNX-G2 25
19 20 15 29 MNX-R3 20 - 33 MNX 32 MNX-G2 32
SELECTION CHART : FUSELESS PROTECTION FOR STAR-DELTA STARTER FEEDERS WITH MCCBs, type 'DM'
TYPE '2' Co-ordination, Iq=50 kA at 415V, 3Ø, 50 Hz.
as per Standards : IEC 60947-4-1, IS 13947 (Part 4/Sec 1), EN 60947-4-1

Motor Rating: 3Ø, 415V, 50 Hz MCCB CONTACTOR Overload Relay


hp kW I line I phase Rating (In) Type I mag Star Delta Main Range Type
(A) (A) (A) (A) (A)
12.5 9.3 19 11 30 DM 100 360 MNX 80 MNX 80 MNX 80 9 - 15 MNX-R4
15 11 22 12.7 35 DM 100 420 MNX 80 MNX 80 MNX 80 9 - 15 MNX-R4
20 15 29 16.7 50 DM 100 600 MNX 80 MNX 80 MNX 80 14 - 23 MNX-R4
25 18.6 35 20.2 50 DM 100 600 MNX 80 MNX 80 MNX 80 14 - 23 MNX-R4
30 22.5 40 23.1 60 DM 100 720 MNX 80 MNX 80 MNX 80 20 - 33 MNX-R4
40 30 55 31.8 100 DM 160 1200 MNX 95 MNX 95 MNX 95 30 - 50 MNX-R4
50 37 66 38.1 100 DM 160 1200 MNX 95 MNX 95 MNX 95 30 - 50 MNX-R4
75 55 100 57.7 160 DM 160 1920 MNX 95 MNX 95 MNX 95 45 - 75 MNX-R4
100 75 135 78 200 DM 250 2400 MNX 140 MNX 140 MNX 140 60 - 100 MNX-R5
125 90 165 95.3 250 DM 250 3000 MNX 140 MNX 140 MNX 140 90 - 150 MNX-R5
150 110 200 115.5 325 DM 400 3900 MNX 225 MNX 225 MNX 225 90 - 150 MNX-R5
175 130 230 133 325 DM 400 3900 MNX 225 MNX 225 MNX 225 90 - 150 MNX-R5
200 150 275 159 400 DM 400 4800 MNX 265 MNX 265 MNX 265 135 - 225 MNX-R5

NOTES :
1 Selection Chart is for Standard 3-phase, Squirrel cage Motor with Average Power Factor,
and Efficiency.
2 Motor ratings at 415 V, 50 Hz.
3 Contactor ratings indicated are the minimum ratings suitable for the application.
Higher Sizes / Ratings can be used.
4 Normal Motor Starting time (£ 5 sec.) is assumed.
For higher Starting time, refer back to L&T.
5 All the MCCBs are Instantaneous type only.
6 Selection is valid only for complete L&T combinations ie. "Contactor, Relay & MCCB".
Compliance to Type '2' co-ordination is not assured in case these combinations are changed
to accommodate another brand / rating of products. compiled:
ubs \ R0 : 15.02.05
ubs \ R1: 21.10.05