Académique Documents
Professionnel Documents
Culture Documents
PART I
PART II
TABLE OF CONTENTS
ARTICLE
Scope 1
Pole Guying
When to Use Guys 50
Straight Line Guying 51
Terminal Poles 52
Long Spans 53
Corner Poles 54
Curved Lines 55
Poles on Hills 56-57
Guy Wire 58 to 60
Guy Fittings 61
Guy Attachments 62-63
Stub Guying 64
Anchor Guys 65
PatentedGuy Anchors 66
Guy Anchor Protection , 67
Locating Foot of Anchor Guv 68
Tree Guying ! 69 to 71
Method of Fastening Guys
" 72-73
Two Guys 74 to 76
Cross-arm Guys 77
Guy Before Running Wires 78
Clearance 79
Iron Poles 80
Guy Insulation 81
[ 679 ]
SPECIFICATIONS FOR METHODS OF AERIAL
CONSTRUCTION
1. Scope. These specifications cover construction methods for
distributing systems as follows: Mechanically, for spans up to and
including 130 feet; electrically, for street lighting circuits and for
constant potential circuits up to and including 6600 volts between
adjacent wires on the same cross-arm Higher voltages and longer
spans may be used, provided the spacing between the wires, the type
of insulators, sags, etc. are made consistent with such work. Rail-
road and wire crossing shall be made in accordance with the joint
crossing specifications.
8. Cross-arm gains, bolt holes and pole tops shall be painted with
at least one coat of preservative paint before the pole is set.
9. Poles that are to be painted in order to improve
Painting.
their appearance, shall be given a priming coat of standard green
pole paint before being taken from the yard. After the pole is set
and construction line work thereon has been completed, the poles
[ 681 1
Sec. 10 LINE CONSTRUCTION
[ 682 ]
LINE CONSTRUCTION Sec. 10
v/)
_
Db.
11!
11
"e3
ill
LINE CONSTRUCTION Sec. 10
20. Curb Line. Poles set along a curb line shall be located so
that there is a clear space of about 6 inches between the nearest
surface of the pole and the outside edge of the curb. Poles on
country roads where the curb line is not laid out should be set as
nearly as possible 6 inches inside of the line which the curb will
follow, so that when the street is afterwards laid out and curbed,
the poles need not be shifted.
Crib Braces
from 4' to 6*
length
26. After the hole is completely filled, soil shall be piled up and
packed firmly around the pole, and any sod which has been removed
to set the pole shall be neatly replaced. New pole settings shall be
inspected after they have been subjected to a heavy rainstorm, to
make sure that the filling has not sunk and left around the pole a
cavity dangerous to the public safety.
27. Crib Bracing. Poles which cannot be strongly guyed, and
which must be set in soft ground, may be given additional stability
[ 686]
LINE CONSTRUCTION Sec. 10
30. Poles Located in Rock. When poles are set in rock, the depth
of setting may be decreased, depending upon the character of the
rock.
SOCKET
SOCKET
iiK
:O
STEP
[ 689 ]
Sec. 10 LINE CONSTRUCTION
can insert small iron bolts or other form of portable pole steps when
climbing the pole. These holes shall be equipped with pole-step
sockets, as shown in Fig. 370.
35. Pole steps shall always be placed on a line with the street in
which the pole is located.
CROSS-ARMS
36. Cross-arms. Owing to the variations in dimensions and pin
spacings of cross-arms now in use, it is difficult to specify crossarrns
that will suitably conform to, or completely cover, present practice.
Whatever arm is used the spacing between the pole pins shall not
be less than 20 inches, nor should the spacing between the side
pins be less than 10^ inches. The arms covered by specification
contained in Sec. 4, Art. 2, are recommended as satisfactory standards.
Cross-arm bolts of a proper length for the thickness of the pole shall
be used. The back of the pole shall never be cut out to allow the
use of a shorter bolt, and projecting ends are not to be left on.
[ 690 ]
LINE CONSTRUCTION Sec. 10
f Through Bolt
--Vertical Brace
[ 691]
Sec. 10 LINE CONSTRUCTION
44. Double Arms. At line terminals, corners, curves, where the
line crosses over from one side of the street to the other and at
points where there is an excessive or unbalanced strain on the cross-
arms, pins and insulators, the pole should be doubled armed as
illustrated in Fig. 372. Two blocks equal in length to the thick-
ness of the pole between gains shall be placed between the arms,
one at each end between the two outside pins. An y^-inch hole
shall be bored at this point through the cross-arms and the inter-
vening block. The two cross-arms shall then be bolted together
by two 5^-inch bolts of proper length, passing through the cross-arms
and the blocks, a washer being placed at both ends of each bolt.
[692]
LINE CONSTRUCTION Sec. 10
faced toward the latter. All poles on which two or more wires are
dead ended shall be double-armed.
45. Reverse or Buck Arms. At corners, and where more than
two wires branch from the main line, buck arms shall be used.
A buck arm is a regulation cross-arm with fittings complete, set at
[ 693 J
Sec. 10 LINE CONSTRUCTION
right angles to the line cross-arm, and 12 inches below it on centers,
as previously specified for buck-arm gains. Judgment must be
exercised in the use of buck arms, and ample room must be left for
n. B
Guy
LINE CONSTRUCTION Sec. 10
47. Pins.Before being taken from the yard, each cross-arm shall
be fitted complete with pins. Pins shall fit tight into the holes in
a cross-ai m, and shall stand perpendicular to the cross-arm when
fitted. Wooden pins shall be nailed to the cross-arm with one six-
penny nail driven straight from the middle of the side of the cross-
arm.
INSULATORS
48. Equipping. Insulators shall be placed upon the cross-arrn
pins only when the wire is to be immediately attached thereto, and
shall be screwed up 'tightly in every case.
POLE GUYING
50. When to Use Guys.
Guys shall be used whenever they can
be located, so as to counteract the strain of the wires attached to
the pole and so prevent the same from being pulled from its proper
position in the line. The following general instructions cover some
of the special cases where guying is required.
three arms or more, the two poles next to the terminal pole shall be
head-guyed in the same direction to assist the latter in taking the
terminal strain.
[ 696]
LINE CONSTRUCTION Sec. 10
54. Corner Poles. All corner poles, whether the turn is made
on one pole or on two poles, shall be head- and side-guyed, as shown
in Fig. 376.
[ G98]
LINE CONSTRUCTION Sec, 10
v \' \\
[ 699 ]
Sec. 10 LINE CONSTRUCTION
[700]
LINE CONSTRUCTION Sec. 10
the angle of deviation which the line makes at the pole, the amount
of the pull being the distance from the pole to the straight line
joining points on the line located 100 feet each side of the pole.
All poles carrying two crossarms shall be side-guyed where the pull
exceeds five feet. All poles carrying one crossarm shall be side-
guyed where the pull exceeds ten feet.
56. Poles on Hills. Poles on steep hills shall be head-guyed to
take the down-hill strain of the line on the poles.
57. Details of head- and side-guying are shown in Figs. 377, 378
and 379.
58. The material used for guying shall be stranded
Guy Wire.
cable, of galvanized steel wire in accordance with National
composed
Electric Light Association standard specifications. (Sec. 3.)
59. 2300-pound cable may be used for guying light lines; that
is, for pole Lines having not more than one crossarm and for guying
crossarms
60. 5000-pound cable shall be used for all regular pole guying.
61. Guy In connection with stranded guy cable, gal-
Fitting.
vanized iron guy clamps and thimbles shall be used.
[701]
Sec. 10 LINE CONSTRUCTION
[702]
LINE CONSTRUCTION Sec. 10
703 ]
Sec. 10 LINE CONSTRUCTION
65. Anchor Guys. An anchor guy may be employed to guy
poles, but must not be installed where it might interfere with surface
traffic. It shall be constructed as shown in Fig. 382 and 383. This
anchor shall be set in the ground so that the eye of the guy rod will
3"S<juareWflsher
stand about one foot above the ground, the guy rod being in line
with the guy wire attached thereto.
66. Patented Guy Anchors. As another method of attaching
^
[705]
Sec. 10 LINE CONSTRUCTION
desirable in many places, particularly where the soil is of a sandy
or loamy character.
67. Guy-Anchor Protection. Anchor guy wires that are so close
to the street as to offer in any way an obstruction to traffic, should
be protected with an anchor shield. This shield may consist of a
2^-inch or 3-inch pipe, installed as shown in Fig. 381. The anchor
shield shall extend from the ground to a height of about eight feet.
75. When two or more guy wires run to a pole or guy stub in
close proximity to each other, the attachment of one guy shall
never over lap that of another, but shall be entirely independent
thereof.
[ 706 ]
LINE CONSTRUCTION Sec. 10
[707]
Sec. 10 LINE CONSTRUCTION
\,
[ 708 ]
LINE CONSTRUCTION Sec. 10
76. When a pole is guyed with two or more guys pulling in approx-
imately the same direction, a turnbuckle shall be installed in each
guy to enable the strain to be equalized.
77. Cross-arm Guys. Wires must sometimes be attached to a
cross-arm so that there is an unbalanced strain on one side of the
arm, tending to twist it out of position on the pole. In such cases,
the cross-arm shall be held in position by attaching the guy wire
thereto, but it is advisable to limit, so far as possible, the use of
cross-arm guys. Cross-arm guys shall, as a rule, extend back to
the guy post independently of each other or of pole guys, as shown
in Fig. 387. On light lines, however, it is sometimes advisable to
combine two guys into one "Y" or bridle guy.
78. Guy Before Running Wires. In new construction work and
in rebuilding old lines, guy wires shall be placed at points of excessive
strain and the poles held in proper position before the lines are
strung.
79. Clearance. Guys shall be attached to poles so as to interfere
as littleas possible with workmen climbing or working thereon.
Every guy which passes either over or under any electric wires other
than those attached to the guyed pole, shall be so placed and main-
tained as to provide a clearance of not less than three feet between
the guy and such electric wires. As changes in temperature will
effect the sag of the wires more than that of the guy, the latter being
under strain, allowance must be made therefore at the time the guy
is installed. For clearance of guys above ground, see Arts. 62 and 64.
80. Iron Poles. When
it is necessary to attach a guy to an iron
pole, tree blocks shallalways be used between the iron pole and the
guy wire to insulate the latter from the grounded iron pole, as shown
in Fig. 384.
81. Guy Insulation. All guy wires attached to poles carrying
electric light or power wires shall be insulated by the insertion of
two strain insulators, the upper of these insulators being inserted
in the guy so as to be at least six feet, in a horizontal direction,
from the pole itself, or at least six feet below the lowest line wire,
and the second strain insulator shall be inserted in the guy so as to
be between six feet and eight feet from the lower end of the guy
and at least eight feet from the ground. In short guys in which
the two insulators here required would be located at the same
point or near each other, the two insulators may be coupled in series
and put into the guy together.
[ 710 ]
LINE CONSTRUCTION Sec. 10
[711]
Sec. 10 LINE CONSTRUCTION
90. The perpendicular distance between wires crossing in the
span shall be four feet.
91. Line wires shall clear all roofs so that they cannot be reached
from the same, and they shall be so run that they cannot be readily
reached from any portion of any other building or structure. If
conditions require that they be attached to structures, as for example,
in running under railroad or highway bridges, they shall be protected
with sufficient insulation for the voltage carried, for the entire distance,
96. Sections of this approved tree wire shall be cut into the line,
when running through trees. Weatherproof wire shall be used in
those portions of the line clear of trees.
TABLE 111
PI6-TAIL Of ffOLO/N6~DOIVN
FOR ALUMINUM CONDUCTOR USE
STRANDS or 2I400QCJ1. ALUM-
INUM CABLE FOK HOLDING-DOWN Tie.
Foe COPPCR CONDUCTOR USE *JO
N.B.3. ANNEALED TELEPHONE
Wl*E OK ANNEALED STRANDS OF *00
COWER CABLE. ABOUT 4$rr or
WIRE NECESSARY.
Tie Wiee
Solid wire joints shall be made as shown in Fig. 392. The two ends
to be spliced shall be scraped perfectly clean and free from insulation
for the length necessary, then give one complete long wrap, followed
by four complete close wraps about each other. The ends of the
wrap shall then be cut close to the line wire and the entire joint
thoroughly cleansed and well soldered with pure and ^
solder. ^
Wipe off soldered burrs from lower ends of joint and cover the
[716]
LINE CONSTRUCTION Sec. 10
entire joint with standard tape. Give the same amount of insulation
as that on the line wire. Tape wrappings will stick better to the joint
if made while the latter is still hot from the application of solder.
LINE W/i?
Tl WlK
T/W/K
FIG. 391. Ties.
Take the strand of each cable in groups of two wires each and alter-
nately interweave them, laying all the ends closely along the cable.
Then taking each group of two strands in turn, wrap them about
the interwoven cables until all the ends have been wrapped. When
completed, the joint should be about 9 inches long. Solder and tape
as specified above.
[717]
Sec. 10 LINE CONSTRUCTION
[718]
LINE CONSTRUCTION Sec. 10
108. Branch Lines. When only one or two wires branch from a
pole, the tap may be made by the use of spreader brackets, as shown
in Fig. 394. If the branch line carries more than two wires, a buck
arm shall be used.
109. Spreader Brackets. Spreader brackets shall be fastened
to the crossarms with four ^-inch carriage bolts.
110. Pole Wiring. All taps and connecting wires passing from
one level to another on a pole shall, so far as possible, be made
vertical. All taps, branch wires and loops crossing from one side
of a pole to the other shall cross the same horizontally. They shall
also be made on one side of the pole only, namely, the cross-arm side,
in order to keep the back of the pole free for climbing.
LOCATION OF WIRES
121. Series Circuits. Every series circuit shall start from station,
substation, or other point of distribution, on a given pin and cross-
arm, and shall follow this same relative pin and cross-arm throughout
its course. Circuits shall not jump from one location on a cross-
arm to another location on the same cross-arm, nor to a different
cross-arm, but shall always be placed on their proper pin. Such a
system of confining each circuit to a given pin throughout its course
makes trouble hunting and repair work much simpler than they
[722]
LINE CONSTRUCTION Sec. 10
[723]
SECTION 10
PART II
PART II
TABLE OF CONTENTS
AKTICLE
Stringing of Secondary Wires ,
1 to 7
Lightning Arresters 30 to 33
Consumers' Services 34 to 39
Pole Wiring for Street Arc Lamps 40-41
Pole Wiring for Street Incandescent Lamps 42-43
SPECIFICATIONS COVERING METHODS OF OVER-
HEAD LINE CONSTRUCTION FOR SECONDARY
VOLTAGES, INCLUDING POLE WIRING
FOR STREET-LIGHTING WORK
METHODS OF SECONDARY SYSTEM WORK
STRINGING OF SECONDARY WIRES
1. Secondary wires in all systems shall be located below the
lowest arm carrying primary wires or series lighting wires.
2. Secondary wires of the same circuit, if carried on cross-arms
shall be attached to adjacent pins. If secondary racks are used,
Figs. 409 to 411, they shall be located below the lowest arm on
the pole. The secondary wires shall be so located that the crossing
of the pole will be avoided as much as possible; viz., on the side of
the pole from which the greater number of consumers will be cut in.
3. When running single-phase, two-wire secondary mains,
attached to cross-arms, the wires shall be placed on the two end
pins on the side nearer the greater number of consumers.
4. When running single phase three wire secondary mains attached
to cross-arms, the wires shall be placed on the three end pins with
the neutral wire in the center.
When running single phase three wire secondary mains, on se-
condary racks, the neutral wire shall be in the top position.
5. When running two-phase, three- wire or four- wire, or three-
phase, three-wire, secondary mains, the wires shall be placed in the
same relative position as described for three-wire, single-phase work.
6. When running secondary mains where there is a probability
of change to a system requiring additional wires, it is desirable to
so locate the wires that vacant pins will be left, which will permit
the running of the additional wires without disturbing existing wires.
7. 220-volt secondary mains shall not extend more than 600
feet in any direction from a transformer, although the secondary
mains may be extended to a greater distance by banking trans-
formers, when load conditions make it desirable.
[731]
Sec. 10 LINE CONSTRUCTION
[732]
LINE CONSTRUCTION Sec. 10
[ 734 ]
LINE CONSTRUCTION Sec. 10
[ 735 ] i ,
Sec. 10 LINE CONSTRUCTION
Fuse Blocks
22. To protect both the primary wire and the transformer, a
single-pole fuse block, preferably of the porcelain variety, shall be
inserted in each leg of the primary circuit when connection is made
to transformer.
23. Fuse blocks may be placed at the head of all branch circuits,
thus confining trouble on a branch circuit to the branch developing it.
24. Fuse blocks shall be located on the arm or on rear double
arm from which the transformer is supported, and shall always be
bolted to the crossarm by means of galvanized iron bolts not less
than }/^-inch in diameter and usually approximately 4H inches long.
25. Fuse blocks protecting transformers of three kilowatts capacity
and over, shall be of a capacity equal to one ampere per kilowatt of
IL HI
FIG. 403. Special transformer rack.
[737]
LINE CONSTRCUTION
*it mm
[ 738 ]
LINE CONSTRUCTION Sec. 10
I 739 ]
Sec. 10 LINE CONSTRUCTION
[740]
LINE CONSTRUCTION Sec. 10
1 1,
[741]
Sec. 10 LINE CONSTRUCTION
[742]
LINE CONSTRUCTION Sec. 10
[743-]
Sec. 10 LINE CONSTRUCTION
[744]
LINE CONSTRUCTION Sec. 10
[747]
Sec. 10 LINE CONSTRUCTION
the ground to the cross-arm, shall be of a suitable insulating conduit,
in order to afford all possible protection to linemen working on the
pole.
[749]