RAMAGUNDAM SS
Members Present:
M/s.GE representative reported to the site on 11thDEC 2017 and completed the following works,
BAY Panel Serial No. Installation Relay Ref. Relay SL. No. Status
REF/NAME panel
LINE DIFFERENTIAL AA2C17001437 Scheme Check, Relay
B1737!/GA17027 PROTECTION (L90) Configuration &Testing
220 KV - Completed including all functional checks
Feeder 1 CRP 201/EV0153/201 BCU & BACKUP 34205986 and Trips logics were
RP PROTECTION (C264) Completed, Panel
Commissioned.
B1737!/GA17027 LINE DIFFERENTIAL AA2C17001439 Scheme Check, Relay
- PROTECTION (L90) Configuration &Testing
220 KV 201/EV0154/202 Completed including all functional checks
Feeder 2 CRP RP BCU & BACKUP 34205984 and Trips logics were
PROTECTION (C264) Completed, Panel
Commissioned.
BACKUP_C264 34205978
DIFFERENTIAL Scheme Check, Relay
220 KV BI612!/GA15008- PROTECTION (T60) ABHC17000971 Configuration &Testing
Trafo 2 CRP 203/EVO107/203 REF 34205980 including all functional checks
RP Completed PROTECTION(P141) and Trips logics were
BI612!/GA15008- Completed , Panel
203/EVO106/206 Commissioned.
CP BACKUP 34205983
PROTECTION (C264)
B1737!/GA17027 Scheme Check, Relay
- Configuration &Testing
220 KV BCRP 205/EV0152/205 Completed BCU 34205982 including all functional checks
RP PROTECTION(C264) and Trips logics were
Completed, Panel
BACKUP 34205979 Commissioned.
PROTECTION(P141)
L90 L90T03HKHFBLH6DLXXN67567UXXW7H 2
T60 T60T03HKHFBLH6DM8NP67U67W5F 2
P141 P141916A6M0510J 6
C264 C264MB1M6910023504000030111N10 5
The Above mentioned relays (Annexure: 1) are configured and Logics Checked as per
scheme.
Numerical Relays protection functions are successfully tested with relay test kit and the
same was witnessed by M/s. L&T,M/s RFCL &M/s EIL.
All protection relay settings installed in the relays are provided by M/s. L&T and its Test
reports hardcopies are submitted to M/s. L&T.
All Auxiliary relays functions are tested and Tripping circuits are healthy and found ok.
Scheme check of 220 kV Panels found OK.
All Backup relays were tested for Directional and Non Directional Protection and tested
with TOC and IOC.
All relays were tested with the protections like Overfrequency,Under Frequency
Overvoltage and Over current protections.
All wiring issues in Panel have been rectified and Put Relay on service.
Settings has been changed in C264 as per customer requirement.
LED’s are configured in C264 as per the Customer requirement.
Synchrocheck is configured in BCU because of customer need.
Logics are changed as per scheme and customer need.
CT and VT ratios has been put as per customer requirement .
UR setup, C264 Software’s, MICOM S1 Agile installed in customer laptop.
Relay project backups has been submitted to M/s. L&T.
M/s GE representative left from site on 28thDEC 2017.
PENDING POINTS: