TECHNICAL SPECIFICATION FOR 110KV/11KV 10MVA POWER TRANSFORMER

Accessories – 1 No

1. Rated Capacity : 10000MVA


2. Rated Voltage
Primary : 110000V
Secondary : 11000V
3. Voltage variation : + / - 10%
4. Rated frequency : 50Hz
5. Frequency variation : + / - 5%
6. Number of phases :3

TECHNICAL PARTICULARS :-
1. Vector group : Dyn11
2. Tapping range : + / - 5% - 10%
3. Tap-changer : OLTC
(Bidirectional )/RTCC/AVR
4. Steps : 1.25%
5. Number of steps : 16 0R 19
6. Ambient temperature : 500C
7. Temp-rise (OIL/Wdg) : 50/550C
8. No-load loss (Max) : 8%
9. Full-load loss (Max) : 30%
0
10. Impedance at 75 C : 8%
11. Insulation level (Kvp/KVrms)
HV : 550KV-peak /230kv rms
HV NEUTRAL : Appilicable
LV : 40KV-peak /10kv rms
12. Control voltage : 220 Volts DC

13. Neutral earthing : Resistively Earthed - THRU NGR


14. Cooling : ONAN
15. TERMINAL DETAILS
HV : Bare Bushings
LV : Bushing cable box with disconnecting chamber
LV Neutral
: 1) 600/1A CL PS
: 2) 600/1A 30VA 5P10

HV/LV orientation : at 1800


Cable box suitable for 3 runs of core 400 SQMM XLPE 11KV Unearthed cable

16. Test to be done on Transformer AT FACTORY BEFORE DELIVERY


1) Pressure and vaccum test
2) Impulse test
3) Tan delta test
4) Heat run test
5) AND ALL ROUTINE TESTS