Vous êtes sur la page 1sur 2

FireBus Systems, Inc.

Model 8913-PS-AC & 8914-PS-AC


System & Field Power Supplies
Wide range AC to DC Power Supplies
For use with FB-8800 Safety Logic Solver

Overview Mounting
Designed for use with FireBus FB-8000 Process Control A rugged snap-fit device allows easy and reliable fixing
Systems and FB-8800 Safety Systems the 8913-PS-AC onto various types of 35 mm DIN rail. A heavy duty DIN
and the 8914-PS-AC are members of a family of DIN-rail rail mounting kit is available for larger amplitude vibration
mountable system and field power supplies. environments (8413-FN-DN).
The power supplies are primary controlled AC-DC and A pair of mounting brackets are also available for screw
DC-DC flyback converters with a constant switching fixing the unit to a flat panel (8414-FK-SU). The units
frequency of 130 kHz. The single step conversion of the have pluggable screw terminals providing easy access
line input voltage to a low output voltage and the power from the front panel.
factor correction, results in an extremely high efficiency. Key Features
These power supplies have been designed to the latest • Certified for use in SIL 2 applications (IEC 61508)
industry requirements and standards and are ideal for
use in demanding applications such as Fire & Gas Safety • Power factor correction with low harmonic distor-
equipment in harsh environments, including in Zone 2 tion; negligibly low inrush current
and Division 2 hazardous areas.
• High immunity to transients and surges; and low
Safety Standards
electromagnetic emissions.
The 8913-PS-AC and 8914-PS-AC power supplies cor-
respond to class I equipment according to IEC/EN60950 • Input over- and undervoltage lock-out and thermal
They also comply with EN61010-1 and EN 50178 stan- protection
dards and have been designed in accordance with these
standards for: • Output overvoltage protection by a second control
loop to ensure safe operation of the final system.
• Building in on DIN-Rails or on a wall/panel
• All outputs are electrically isolated SELV1 circuits
• Basic insulation between input and case, based on with low output noise.
250 VAC/350 VDC
• Proof against no-load, overload and short-circuits.
• Double insulation between input and output, based
on 250 VAC/350 V DC • Can operate at full load up to an ambient tempera-
ture of 70ºC in free air.
• Operational insulation between the outputs

• The use in a pollution degree 2 environment (AC-


input).

• Connecting the input to a primary circuit with a


maximum transient rating of 2500 V (overvoltage
class II based on a 110V primary circuit, overvolt-
age class II based on a 230 V primary circuit).
Power Supplies 8913-PS-AC: 8914-PS-AC: 8913-PS-AC & 8914-PS-AC
8913-PS-AC System & Field PS ELECTRICAL ELECTRICAL MECHANICAL
8914-PS-AC Field PS EMC Compliance: EMC Compliance: Mounting Methods:
EN 61000-2,3,4,5,6,11 EN 61000-2,3,4,5,6,11 35 mm x 7.5 mm
EN 55011/22, EN 55014 EN 55011/22,EN 55014 T Section DIN rail
Environmental Classifications:
Electrical Safety: Electrical Safety:
Class I, Division 2, Groups A,
EN 60950 EN 60950 Dimensions:
B, C & D T4
INPUT INPUT 4.05 in (103.0 mm) width
Rated (nominal) input voltage Rated (nominal) input voltage 5.43 in (138.0 mm) high
Certificate:
93 / 240 VAC; 47-65 Hz 93 / 240 VAC; 47-65 Hz 4.47 in (113.6 mm) deep
TÜV 01 ATEX 1774X
100 / 240 VDC 100 / 240 VDC
Approved for:
Operating input voltage: Operating input voltage: Weight:
II 3 G EEx n A II T4
85 / 264 VAC; 47-65 Hz 85 / 264 VAC; 47-65 Hz Net 26.45 oz (750 g)
Certificate:
90 / 250 VDC 90 / 250 VDC
FM 3011821
Efficiency: Efficiency:
Approved for:
up to 87% up to 87%
Class I, Div. 2, Groups
Connections: Connections:
A, B, C, D, T4
2-part pluggable con- 2-part pluggable con-
nector nector
Temperature ranges: Input protection: Input protection:
-40°F (-40°C) to 158°F (+70°C) 6.3A slow blow fuse and 6.3A slow blow fuse and
(Max. Amb.) voltage dependent voltage dependent
resistor resistor
Relative humidity: OUTPUTS OUTPUTS
93%, 104°F (40°C) Output 1 Voltage: Output Voltage:
for 56 days 24.7 VDC ±10% 24.7 VDC ±10%
Output 1 Current: Output Current:
5 A (nominal) 10 A (nominal)
Output 2 Voltage: Connections:
11.95 VDC ±5% 2-part pluggable con-
Output 2 Current: nector
5 A (nominal) Input-Output Isolation:
Connections: 2800 VDC
2-part pluggable con- Holdup time (full rated load)
nector 15 ms (typical)
Input-Output Isolation: Thermal Protection:
2800 VDC Reduced output power
Holdup time (full rated load) Supply health indicator:
15 ms (typical) LED
Thermal Protection:
Reduced output power NOTE: Output supports load
Supply health indicator: sharing for redundancy.
LED

NOTE: Output 2 supports load


sharing for redundancy. An
external diode should be used
with Output 1 if load sharing for
redundancy is required.

Ordering information:
8913-PS-AC System and Field Power Supply
8914-PS-AC Field Power Supply

Copyright ©2009 FireBus Systems, Inc. Note: The information in this data sheet is given in good faith and consid-
P. O. BOX 460269, ered accurate at the time of printing, however, the company reserves the
Houston, TX 77056-8269 right to change specifications of products at any time without prior notice.
http://www.FireBusSystems.com.

09FCS084-A09