4310 SUBSTATION MAIN GENERATOR LOAD TEST

( 775kVA, 620kW )
Oil Oil Engine Duration Load
Freq. Pressure
Date Time Current (A) Voltage (V ) Temp. Temp. (min.) Remarks
(Hz) (bar) (%)
(°C) (°C)
L1 L2 L3 L1L2 L2L3 L1L3
6/29/2015 10:15 161.5 162.9 163 416 415 415.5 50 5.3 71 7 15

6/29/2015 10:22 378 378 379 415 415 414.7 50 5 73 10 35

6/29/2015 10:33 595 596 596 415 415 414.8 50 5 75 10 55

6/29/2015 10:43 593 595 597 415 414.5 414.6 50 4.9 75 10 55

6/29/2015 10:52 808 812 812 415 415 414.8 50 4.9 80 10 75

6/29/2015 11:02 810 811 811.5 415 415 415 50 4.7 80 12 75

NOTE:
1 ) The full load current = 1079.5 A
Prepared By June
2 ) Engine temperature alarm setting = 100°C
Reviewed By Afsal