The approved updated final settings should be applied and printed out from the relay
by using the software of the relay.
The following test format contains minimum required tests and some of settings are
mentioned as an example and not as limitation.
3. ELECTRICAL TESTS
Burden =7 VA
MEASUREMENTS
Open Degsi 4 Measurement primary value operational value primary after connecting to the relay
& observe the reading, in primary values.
Input CT Applied Value (A) CT Ratio Applied (A) Displayed Secondary Value (A) Displayed Primary Value (A)
R 50 50/5 5 50
S 50 50/5 5 50
T 50 50/5 5 50
N 0
Input CT Applied Value (A) CT Ratio Applied (A) Displayed Secondary Value(A) Displayed Primary Value(A)
N 1 50/5 1 10
Input PT Applied Value PT Ratio Applied Displayed Secondary Value (V) Displayed Primary Value (KV)
R-S 110 33000/110 110 33K
S-T 110 33000/110 110 33K
R-T 110 33000/110 110 33K
R-N 63.51 33000/110 63.51 19.05K
S-N 63.51 33000/110 63.51 19.05K
T-N 63.51 33000/110 63.51 19.05K
1.05X
PHASE Pickup TMS CURVE Injected A 1.05X Relay
Theory
R 15.5 A 0.35 D.T 16.275 A 0.35 sec 0.366 sec
50-1 S 15.5 A 0.35 D.T 16.275 A 0.35 sec 0.366 sec
T 15.5 A 0.35 D.T 16.275 A 0.35 sec 0.366 sec
1.05X
PHASE Pickup TMS CURVE Injected A 1.05X Relay
Theory
R 37 A 0.02 D.T 38.85 A 0.02 sec 0.032 sec
50-2 S 37 A 0.02 D.T 38.85 A 0.02 sec 0.032 sec
T 37 A 0.02 D.T 38.85 A 0.02 sec 0.032 sec
1.05X
PHASE Pickup TMS CURVE Injected A 1.05X Relay
Theory
50N-1 N 1A 0.1 sec D.T 1.05 0.1 0.106
50N-2 N 0.5 A 2 D.T 0.525 2 2.018
K factor Time constant Thermal alarm stage Current alarm set point
0.56 2 90% 2.8 A
49
Trip time Trip time
Injected current
Theory Relay
5.6 A 34.52 sec 35.24 sec