BUSBAR PROTECTION SYSTEMS

Busbars Are a Vital, Yet Often Overlooked, Part of the Power System

By Paul Marot, P.Eng.

Busbars are a vital, often overlooked, part of the power system. Busbar faults are rare. However, when
one occurs damage is widespread and plant downtime is substantial. This soon reminds users of
busbars' importance and, in particular, the importance of good protection.

Busbar Protection and Requirements

The high fault levels associated with busbar require that protection be fast. Typical fault clearing time
should be less than 100ms; with fast breakers this means measuring time should be about 20 to 30 ms.

In order to minimize the interruption to the plant the protection system must correctly identify the area
of the fault and open only the necessary and minimum number, of breakers. To achieve this, it must
discriminate properly -- but because of speed requirements, discrimination based on time delays is not
acceptable. It is therefore preferable to have a clearly defined zone of protection or unit scheme.

Busbars, the connection nodes of multiple power circuits, must have very secure protection since
tripping of a busbar usually has widespread power interruptions. The risk of an unnecessary trip must be
kept to a minimum. This immediately brings stability into consideration as it is usually a fault just beyond
the zone of busbar protection -- commonly known as through faults -- which has similar fault levels to
the bus that causes a mistrip of the busbar protection. The protection must be stable for these though
fault.

It should be pointed out that the above requirements can, depending on the application and relay
principles involved, be competing -- an improvement of one means a deterioration of the other. For
example, an increase in security would probably be achieved at the expense of tripping time.

Relaying Principles Impact on CT Requirements

To understand the current transformer (CT) requirements of different busbar protection systems, it is
worth looking at the various relaying principles or measuring devices available for use with busbar
protection systems. The most common types are basic circulating current differential, biased differential,
and overcurrent and direction overcurrent relaying.

The relaying principle of basic circulating current differential uses the well known Mertz Price circulating
current principle. It compares current signals and requires them to be matched, thus requiring very
accurate current signals from the CT's as well as matched CT ratios. Errors in the current matching or
transient CT errors can cause relay operation, so that some time will be spent examining CT's and
sources of errors.

Biased differential uses the Mertz Price principle but compares the difference between current signals
and the average of the current signals and requires the result to be above a certain percentage before
operating.

It basically has an operate winding which looks at the difference current and restrain windings which
looks at the average current.

Obviously this relaying principal can accommodate greater sources of error in CT's. It is a more secure
principle but not as fast as the circulating current principle.
Most modern overcurrent relays use a principle of peak or RMS measurement of the current. The
measured signal is obtained by passing the CT secondary current through an input CT on the relay. The
relay measurement requires very little energy from the measured signal, so by design, these relay input
CT's impose very little burden on the main CT's. Consequently CT's for use with overcurrent relays have
no stringent requirements besides those of standard relaying accuracy.

Directional overcurrent relaying would be used in a direction comparison type scheme described later
but the measuring element is usually an overcurrent relay that is directionalised. Such relays do not pose
any more limitations on the CT's than overcurrent relays.

CT Performance And Requirements

The simplified CT equivalent circuit given in Figure 1 is first examined to establish a device's limitations
when applied to relaying.

The CT takes magnetizing current from the primary circuit and since this current does not flow into the
relay branch, there is an error between the primary and relay currents. This is a major source of ratio
error.

Winding resistance is part of the CT burden and needs to be taken into account when establishing the CT
kneepoint voltage (Vk) requirement for a particular application. This should be known and the smaller it
is the better.

The kneepoint of the CT gives an indication of the burden the CT can accommodate. Recall that we are
trying to get accurate signals up to current values in excess of 20 times rated and this is especially likely
with busbar CT's where fault levels are high. The kneepoint is the point on the magnetization curve
where a large increase in magnetizing current produces a minimal increase in the output voltage needed
to drive current through the secondary burden. This value is given directly in the CT specification:
10L200 where the 200 figure means the CT can produce 200 volts on the output with the current being
within the stated accuracy. It must be remembered that the ratio of a CT greatly influences the
maximum kneepoint that can be obtained by a CT. The kneepoint is basically the maximum secondary
output voltage the CT can develop. The physical size of the CT and how much core iron is used
determines the volt per turn on the secondary winding. This typically varies from 1.5 to 2.5V per turn, so
given the number of turns which is the CT ratio, one can estimate the maximum obtainable kneepoint.
Don't try and expect a 400V kneepoint out of a 400/5 ratio CT!

If the CT becomes saturated because of high flux in the core, it will not produce any secondary output
current. In fact, the secondary will appear as load to the other parallel connected CT¹s. This is illustrated
by the short across the magnetizing branch in Figure 2 and the load is simply the CT winding resistance.

Busbar Protection Schemes

In order to examine different relay principles, and some basic CT performance characteristics, various
forms of busbar protection will be reviewed. The busbar protection scheme, namely the blocking
scheme, will also be reviewed in light of all the features found in modern over current relays.

For the purposes of simplicity only single busbar systems will be considered. These are common in HV
sub-transmission level power systems. The variety of busbar configurations such as breaker and a half,
double busbar and ring bus arrangements found on EHV and HV transmission systems utilize the same
principles but only in more complicated systems.

High Impedance Differential


This is a simple yet fast scheme with a low relaying cost, but it requires good CT inputs with well
matched ratios with high CT kneepoints. This is most easily obtained by utilizing CT's from one
manufacturer only which is usually possible with a new installation.

All incoming busbar CT's are paralleled and connected in opposite polarity to the paralleled outgoing
busbar CT's. The differential relay is then connected across the paralleled CT's.

The relays used most often in this scheme are simple attracted armature relays which have fast
operating times. This scheme can thus easily provide 20ms operating times including the trip relay time.

The main application consideration with this scheme is stability for heavy through faults. The stability is
determined by the CT's and relay settings which in turn affect the sensitivity of the scheme.

Consider a simple two CT differential circuit shown in Figure 3. If the right hand side CT saturates, which
means it appears as a load as previously described, then it will cause a voltage to develop across the
relay which will be If(2Rl + Rct). If this voltage is greater than the setting voltage, the relay will operate.
This is undesirable. Therefore, this becomes the setting criterion; the relay should be set to a voltage >
If(2Rl + Rct).

Once the setting is determined, the scheme sensitivity can be calculated by considering the relay
operating current reflected to the primary plus the magnetizing current of the CT¹s connected in parallel.
Recall that the CT primary provides the magnetizing current not reflected in the secondary. The primary
operating current for the scheme can be found from the formula:

Ip= N (Ir + nIu) where N= CT ratio

Ir= relay operating current at setting

Iu= magnetizing current at setting

voltage (obtained off CT magnetizing curve)

n= number of CT set connected

in parallel

If the relay setting voltage is high, the CT magnetizing current at the setting voltage totaled up for all the
CT's can be significant.

For an internal fault, the CT's will attempt to force all the secondary current through the relay. With a
high impedance differential relay, this would require very high secondary voltages, beyond the CT's
capabilities, again causing saturation. However, reliable operation of the relay does take place if there is
a significant time before saturation occurs. This is because, if the kneepoint is well above the setting
voltage, the relay will receive sufficient voltage to operate before saturation occurs. Manufacturers thus
recommend a voltage of at >