Académique Documents
Professionnel Documents
Culture Documents
DSC-001(B1).docx
CLIENT: CONSULTANT:
DSC-001(B1).docx
CLIENT: CONSULTANT:
Table of Contents
1. INTRODUCTION 6
1.1 Terms and Definitions ........................................................................................................... 6
2. ABBREVIATION 7
3. REFERENCES 7
3.1 ANSI(AMERICAN NATIONAL STANDARDS INSTITUTE) ......................................... 8
3.2 API (AMERICAN PETROLEUM INSTITUTE) ................................................................. 8
3.3 ASME(AMERICAN SOCIETY OF MECHANICAL ENGINEERS) ................................. 8
3.4 IEC(INTERNATIONAL ELECTRO-TECHNICAL COMMISSION) ................................ 8
3.5 ISA(INSTRUMENTATION, SYSTEM, AUTOMATION SOCIETY OF AMERICA) ..... 9
3.6 ISO (INTERNATIONAL STANDARD ORGANISATION) .............................................. 9
3.7 NACE (NATIONAL ASSOCIATION OF CORROSION ENGINEERS)........................... 9
3.8 IPS(IRANIAN PETROCHEMICAL STANDARD) ............................................................ 9
DSC-001(B1).docx
CLIENT: CONSULTANT:
DSC-001(B1).docx
CLIENT: CONSULTANT:
DSC-001(B1).docx
CLIENT: CONSULTANT:
1. INTRODUCTION
Arvandan Oil and Gas company intends to construct an 8" N.B. buried flowline
from Sohrab WH1 to South Azadegan North Cluster.
Sohrab Field is located at North of Azadegan Field, and 115 Km North West of
Ahwaz right along the international border with Iraq.
DSC-001(B1).docx
CLIENT: CONSULTANT:
2. ABBREVIATION
3. REFERENCES
Throughout this specification the following dated and undated standards and
codes are referred to. These referenced documents shall, to the extent specified
herein, form a part of this specification.
For undated references, the latest edition of the referenced document
(including any supplements and amendments) applies. For dated references, the
edition cited applies.
The applicability of changes in the dated references that occur after the cited date
shall be mutually agreed upon by Owner/Client and the Vendor / Contractor.
DSC-001(B1).docx
CLIENT: CONSULTANT:
IEC 60073 Basic & Safety Principles for Man-Machine Interfaces Marking and
Identification - Coding Principles for Indicators
IEC 60079 Electrical Apparatus for Explosive Gas Atmosphere
IEC 60446 Basic & Safety Principles for Man-Machine Interfaces Marking and
Identification - Identification of Conductors by Colors or Numerals
IEC 60331 Tests for Electric Cables Under Fire Conditions
IEC 60332 Tests on Electric Cables Under Fire Conditions
IEC 60529 Degree of Protection Provided by Enclosures (IP code)
IEC 60584 Thermocouples
IEC 60751 Industrial Platinum Resistance Thermometer Sensors
DSC-001(B1).docx
CLIENT: CONSULTANT:
DSC-001(B1).docx
CLIENT: CONSULTANT:
4. UNITS
DSC-001(B1).docx
CLIENT: CONSULTANT:
6. GENERAL
DSC-001(B1).docx
CLIENT: CONSULTANT:
DSC-001(B1).docx
CLIENT: CONSULTANT:
DSC-001(B1).docx
CLIENT: CONSULTANT:
DSC-001(B1).docx
CLIENT: CONSULTANT:
DSC-001(B1).docx
CLIENT: CONSULTANT:
7.2.2 CONTROLLERS
Controllers shall provide extensive standard algorithms as follow:
DSC-001(B1).docx
CLIENT: CONSULTANT:
Sets alarms.
Be unaffected by failure of the devices connected to the
communication system.
Retain all control configuration memory in the event of power failure.
7.2.4 ALARMS
All the alarms will be configured on DCS and shown on operator’s
monitor; any signal force shall be treated as alarm.
Important ESD alarms shall be hardwired to the auxiliary console as per
process requirements. The system shall be combined audio-visual (either
integral with logic or remote).
Acknowledge, reset, lamp test etc pushbuttons shall be provided in the
Aux. Console (Matrix Panel or External Gate for ESD).
The audio system shall comprise a dual variable pitch horn system with
combined sound power of about 85 dBA.
DSC-001(B1).docx
CLIENT: CONSULTANT:
Interface module
DCS Data Highway, control system communication network including
cabling, modems (if required), fiber optic cabling and interfaces, and
related hardware devices
Input/output Module (For trip & Control Application).
Power supply
CPUs
PLC Redundancy:
ESD PLC shall be fully redundant as per QMR or TMR (CPU, bus,
communication modules, power supply, I/O cards, etc).
F&G PLC shall be fully redundant as per QMR or TMR (CPU, bus,
communication modules, power supply, I/O cards, etc).
PLC of ESD and also F&G system should be SIL 3 unless otherwise
specified by SIL Study or Client Request.
DSC-001(B1).docx
CLIENT: CONSULTANT:
DSC-001(B1).docx
CLIENT: CONSULTANT:
Key lock system with the same key for all cabinets.
Internal door pocket for drawings.
IP42 for indoor cabinets.
Standard type with eyelet’s.
Painted sheet steel, according to RAL-7035 shall be Grey.
Modular structure accessible from two sides.
System and marshaling cabinets shall be separated.
General earth for metallic parts.
Separated and isolated earth for electronic circuits.
Fans as required (with failure detection), or natural draft and thermal
control.
Florescent lights controlled by door limit switches.
Cable entry from bottom, with supporting bar and sealing plate.
All cabinets and wires installed in cable duct or on cable tray, Facilities
on top for lifting with crane.
The Supplier/Vendor for approval shall submit general panel
organization and dimensions.
7.3.5 CABLING
This includes wiring of all links internal to the equipment and inter-
connections:
DSC-001(B1).docx
CLIENT: CONSULTANT:
7.3.6 MARKING
Each cabinet, rack, terminal block, plug, socket etc., shall be clearly
identified with a label or cable marker bearing a unique number. All cable
shall be identified using slip on, heat shrink type ferrule markers.
7.3.7 GROUNDING
The control system 24V DC signal power supply shall be floating from
ground. The following subjects shall be considered:
Noise immunity
Isolated signal reference
Galvanic Isolation
Separated grounding should be considered for IS signals, Non-IS signals
and also dirty earth as required.
8. INSTRUMENTATION DESIGN
8.1 GENERAL
8.1.1 TRANSMITTERS
Transmitters shall be smart type (for ESD transmitters should be Write
protected or conventional type), with 4-20mA signal and HART
protocol. Integral digital indicators shall be supplied for each
transmitter.
All transmitters (pressure, flow, temperature etc.) shall be provided
with burnt-out protection.
Electrical and electronic instruments shall meet the hazardous area
requirements.
DSC-001(B1).docx
CLIENT: CONSULTANT:
8.1.2 SWITCHES
Field mounted transmitters shall be used in alarming, interlock or
shutdown services instead of field mounted switches as far as
possible.
Field mounted switches, if any, shall operate on 24 VDC, volt free
contacts.
8.1.6 MATERIAL
All instrument wetted parts in connection with the process shall
generally be AISI 316, unless higher grades are required by the
process conditions. Instruments wetted part material in sour services
shall comply with NACE standard MR-01-75.
Unless otherwise specified in this document, material of Control valve
bodies, ESD valve bodies, Orifice flanges, and in-line flow
instruments flanges, displacer type level instrument flanges shall
conform to the piping flange/valve materials in accordance with the
related Piping Specification.
DSC-001(B1).docx
CLIENT: CONSULTANT:
DSC-001(B1).docx
CLIENT: CONSULTANT:
DSC-001(B1).docx
CLIENT: CONSULTANT:
accumulation of material is less likely and the sizing data for these
plates is more reliable.
Because of the minimum Reynolds number consideration, square-
edged orifices should not be used on viscous fluids. Quadrant-edged
and conical orifice plates are recommended when the Reynolds
number is under 10,000.
Flange taps can be used with quadrant-edged orifices, but only corner
taps should be used with a conical orifice.
Concentric orifices are still preferred for multi-phase flows in
vertical lines because accumulation of material is less likely and the
sizing data for these plates is more reliable.
Orifice flanges will normally house the orifice plates unless the process
requires a senior
(retractable) type orifice changer.
Senior (retractable) type orifice changers shall be used in custody
transfer applications or when the process flow rate is expected to vary
on a regular basis and a different orifice size would be required.
Orifice plates shall be 316 stainless steel in material as a minimum,
with 1/8" thickness in sizes 6" and smaller, 1/4" thickness in sizes 8" to
16", and 3/8" inch thickness in sizes 18" and larger.
Sizing and installation of orifice plates including minimum up and
downstream lengths shall be based on the latest AGA criteria and ISO
5167 and 5168 and shall conform to the latest ASME Flow
Measurement Supplement to the ASME Power test Codes. IPS-E-IN-
130 shall be considered.
Orifice shall be sized so that the maximum flow rate falls at
approximately 75% of maximum meter range and the minimum flow
does not be less than 25% of maximum meter range.
The preferred differential pressure range is 250 mbar (100" water
column).
The d/D Ratio of the orifice plate shall normally be between 0.25 and
0.70, with orifice bores of less than 0.125 inches to be avoided.
Wherever possible meter runs shall be provided on the basis of d/D
ration not less than 0.70.
Each plate shall be provided with a tab with projects data beyond the
flange. The symbol number, plate material, the actual measured bore
and the I.D. of the pipe shall be stamped on this tab. The tab shall be
in line with the drain or weep hole.
F:\d\PROJECT\ARVANDAN\SOHRAB\93-06-29\ﻣﺪارﮎ ﺟﺪﻳﺪﯼ ﮐﻪ ﻣﻴﺒﺎﺳﺖ ﺑﺮاﯼ ﮐﺎرﻓﺮﻣﺎ ارﺳﺎل ﺷﻮدINSTRUMENT\AOGC-036-IN-
DSC-001(B1).docx
CLIENT: CONSULTANT:
Drain or Vent valves shall be 3/4". For gas line, drain valve should be
considered and for liquid line, vent valve should be considered. For
mixed medium, both should be considered.
Minimum pipe size for orifice flow measurement shall be 2”. Where
required, integral orifices could be used for lines smaller than 2”.
Orifice flanges shall be consistent with ASME B16.36 and shall be of
the welding neck type.
In flammable gas service and steam, pressure taps shall be provided
with reinforced butt- welded nipples. For other services screwed
nipples may be used if permitted by the applicable piping specification.
8.2.2 CORIOLIS
Coriolis flow meter shall be used only when flow measurement
cannot be obtained by measuring differential pressure, for large
rangeability, in applications where accurate measurement of mass flow or
density is required or corrosive services.
Coriolis meters are not suitable on liquid services containing significant
gas content, or on gas services with low in-line pressure.
Coriolis flow meters should be installed on line size 1/4" up to 8".
Preferred installation of coriolis flow meters is vertical with the flow
upwards thru the meter. If horizontal installation is the only available
method, the manufacturers’ recommendations shall prevail.
Coriolis meters on high temperature services shall have remote mounted
transmitters. The temperature limit shall be checked with the meter
vendors.
8.2.3 TURBINE
Turbine meters may be used for process flow measurement where highly
accurate, wide range measurement of very small flow rates is required or
on clean low viscosity liquids with high range-ability requirements.
Turbine meters require bypass lines, to avoid filling of subsequent piping
systems and filters in upstream direction if the fluid may be polluted.
Strainers shall be installed upstream of all turbine meters to protect it
from debris.
The minimum up and downstream pipe lengths shall follow
the manufacturers’ recommendation.
Turbine meters shall not be installed on lines prone to vibration or close
to equipment that emits electromagnetic fields.
F:\d\PROJECT\ARVANDAN\SOHRAB\93-06-29\ﻣﺪارﮎ ﺟﺪﻳﺪﯼ ﮐﻪ ﻣﻴﺒﺎﺳﺖ ﺑﺮاﯼ ﮐﺎرﻓﺮﻣﺎ ارﺳﺎل ﺷﻮدINSTRUMENT\AOGC-036-IN-
DSC-001(B1).docx
CLIENT: CONSULTANT:
DSC-001(B1).docx
CLIENT: CONSULTANT:
Meter bodies shall be constructed for minimum pressure drop and have
calibration controls and integrated automatic temperature compensation.
The accuracy of the meters shall be ±0.2% or better.
Positive Displacement Meters shall meet the requirements of API
Manual of Petroleum Measurement Standards-chapter 5.2 "Measurement
of Liquid Hydrocarbons by Displacement Meters".
The Supplier in accordance with API MPMS 21.2 shall calibrate liquid
positive displacement meters.
PD flow meters shall be used only in Custody Transfer service.
DSC-001(B1).docx
CLIENT: CONSULTANT:
DSC-001(B1).docx
CLIENT: CONSULTANT:
DSC-001(B1).docx
CLIENT: CONSULTANT:
DSC-001(B1).docx
CLIENT: CONSULTANT:
instruments with the exception of tank gauges. Reflex gauge glasses shall
be used only for all clean, non-viscous liquids except the following where
transparent gauge glasses shall be used:
Interface between two liquids
When the liquid temperature is below 0 ºC gauge glass shall be
provided with frost extensions
Liquids requiring protecting shields (mica or other)
Mica shields shall be used on steam and corrosive services
The following centre to centre of nozzles shall be selected:
The actual range is formed by the total visible glass length of all sections
per gauge.
Each level gauge shall meet the design pressure and temperature of
the vessel on which it will be installed.
Gauge body and cover shall generally be constructed of carbon
steel unless the process requires a more suitable material.
If illuminators are required, they shall be a minimum of 40 watts
and suitable for use in hazardous areas.
Level gauges shall be installed so that the visible length covers the full
operating range of the vessel including transmitter spans and level alarm or
shutdown points.
Level gauges shall be limited to 5 sections maximum. If multiple gauges
are required, they shall be overlapped such that the entire range is visible.
Frost shields shall be provided on gauge glass columns in service
where the operating temperature is below 0°C.
DSC-001(B1).docx
CLIENT: CONSULTANT:
8.4.2 THERMOWELLS
DSC-001(B1).docx
CLIENT: CONSULTANT:
DSC-001(B1).docx
CLIENT: CONSULTANT:
DSC-001(B1).docx
CLIENT: CONSULTANT:
The instrument shall within the middle third of the adjustable range
cover the set point of the temperature switch.
DSC-001(B1).docx
CLIENT: CONSULTANT:
DSC-001(B1).docx
CLIENT: CONSULTANT:
DSC-001(B1).docx
CLIENT: CONSULTANT:
Special body types such as angle, split body, ‘Y” etc., may be considered
when the process fluid may be erosive, viscous or carrying suspended
solids.
The leakage class for all control valves shall be in accordance with
ANSI-FCI-70-2.
The maximum allowed A-weighted sound pressure (noise) level
of control valve on continuous duty, measured at 1 meter downstream of
the control valve at a distance of 1 meter from the pipe, shall not exceed 85
dB (A) under any of the operating conditions (min./norm./max. flow).
The stroking time of a control valve is defined as the time required
stroking the valve from 2% opening to 98% opening and vice versa
while it is at operating (min. to max.) differential pressure.
DSC-001(B1).docx
CLIENT: CONSULTANT:
Tag Number
Valve action on air failure
Body size, flange rating, type, material and Cv
Trim size , type and material
Control Characteristics
Actuator size, model and serial number
Maximum actuator supply pressure and bench set
Valve body shall be made of carbon steel unless the pipe specification
requires other materials,
Depending on the characteristics of the process medium .Minimum
material for trim is hardened stainless steel. Stellited or higher grade
Hastelloy shall be used depending on if they are more suitable for the
particular process conditions.
Teflon shall be the preferred packing material for fluids under 200°C. For
fluids over 230°C, special packing using grafoil or equivalent materials may
be used.
DSC-001(B1).docx
CLIENT: CONSULTANT:
9.5 ACTUATORS
DSC-001(B1).docx
CLIENT: CONSULTANT:
9.6 POSITIONERS
DSC-001(B1).docx
CLIENT: CONSULTANT:
accessories shall be leak tested API fire safe and certified by the
manufacturer.
Shutdown valves shall be installed with accessories that enable them to
be tested regularly. Shutdown valves shall be fail-closed unless ESD
conditions dictate otherwise.
Shutdown valve stroking time shall encourage stability and safety. The
following guides shall be adhered to:
For tripping, one second per inch of nominal valve bore;
For resetting, three seconds per inch of nominal valve bore.
Speed control and quick exhaust valves may be used to facilitate the
appropriate stroking time.
Also for better safety and performance, Tight Shut-off "V" and Partial
Stroking facility (for larger than 10") shall be considered. ESD valves should
have local reset.
All shutdown valves shall be supplied with two proximity type limit
switches (One for open position and one to show closed position).
Limit switches shall be explosion proof EEXD or intrinsically safe EEx-ia
IIB T3 suitable for Zone 1, and shall be housed in an IP65 weatherproofs
enclosure.
Limit switches shall be hermetically sealed “REED” type having 2 SPDT
contact with 1Amp, 24VDC rating.
DSC-001(B1).docx
CLIENT: CONSULTANT:
Air Lock-up valves shall be provided when the control valve shall remain
in the last position in case of failure of the instrument air supply.
The lock-up valve shall have a bolt adjustment provided with a locking
facility, for example a locking nut to prevent tampering.
A separate nameplate shall be provided to indicate the set values.
The lockup valves shall be set at 0.5 bar above the required control
valve air supply pressure, unless some other set value is required for a
particular actuator. The lock up valves shall be properly adjusted by the
Vendor.
For Control valves with a valve positioner, the lockup valve shall be
installed between the positioner output and the actuator.
Where lockup valves are applied on valves operated by a solenoid valve,
this solenoid valve shall be installed between the lockup valve and the
actuator.
F:\d\PROJECT\ARVANDAN\SOHRAB\93-06-29\ﻣﺪارﮎ ﺟﺪﻳﺪﯼ ﮐﻪ ﻣﻴﺒﺎﺳﺖ ﺑﺮاﯼ ﮐﺎرﻓﺮﻣﺎ ارﺳﺎل ﺷﻮدINSTRUMENT\AOGC-036-IN-
DSC-001(B1).docx
CLIENT: CONSULTANT:
DSC-001(B1).docx
CLIENT: CONSULTANT:
DSC-001(B1).docx
CLIENT: CONSULTANT:
½ “ for up to 5 users
¾” for up to 10 users
F:\d\PROJECT\ARVANDAN\SOHRAB\93-06-29\ﻣﺪارﮎ ﺟﺪﻳﺪﯼ ﮐﻪ ﻣﻴﺒﺎﺳﺖ ﺑﺮاﯼ ﮐﺎرﻓﺮﻣﺎ ارﺳﺎل ﺷﻮدINSTRUMENT\AOGC-036-IN-
DSC-001(B1).docx
CLIENT: CONSULTANT:
1” for up to 15 users
1 1/2” for up to 20 users
Each Pneumatic user shall be provided with ¼” stainless steel valve and
one air filter regulator with pressure gauge (pressure gauge in case of
control valves shall be installed on the positioner). On/off ball valves will
be equipped with filter only.
All tubing for field-mounted pneumatic equipment shall be ½ inch
OD, 316 Stainless Steel seamless tubing with wall thickness of 0.035
inch, and 316 Stainless Steel, bar stock double- ferrule compression type
fittings.
When the fluid on the process line can frost in ambient conditions;
To prevent plugging of impulse line or instruments bodies due to the
high fluid viscosity;
To avoid a critical condensation on the impulse line due to the ambient
temperature.
Control systems
Shutdown and alarm systems
Fire and Gas detection systems
Field electrical systems
Analyzer systems
DSC-001(B1).docx
CLIENT: CONSULTANT:
Power supply inside DCS, F&G and ESD systems shall be designed with
backup redundancy i.e. in case of one power failure; the associated
consumers shall automatically be fed from another stand-by power supply.
Using self-regulated DC-power supplies fed at 230V 50Hz for
supply to field electronic transmitters and implement the logic of the alarm
and shut down system, shall generate 24VDC.
20% of installed spare breakers and fuses shall be provided for future
expansion.
As a minimum, all piping and flange connections shall meet the design
requirements of the piping class or vessel design limits to which it is
connected.
Instrument cable entry size shall be ISO M20 X1.5 for single pair cable
connection with the appropriate cable gland. For instruments with other
than single pair cable connection, appropriate ISO size with the cable gland
shall be specified.
Earthing connection for instrument case and panel shall be done based
on earthing philosophy.
DSC-001(B1).docx
CLIENT: CONSULTANT:
10.10 PAINTING
DSC-001(B1).docx
CLIENT: CONSULTANT:
11. DOCUMENTATION
DSC-001(B1).docx
CLIENT: CONSULTANT:
DSC-001(B1).docx