Project 1/6

Project number Version 1.2.0.16


Contact D.Gajic 7/10/2017

Anchor Calculation AnchorFix-2 - Carbon 10.9 M12

The selected Anchor is applicable.

Product information

AnchorFix-2 - Carbon 10.9


Material Carbon 10.9
Type Adhesive anchor
Approval Sika - AnchorFix-2 Anchor ETA
Drill hole depth 105.0 mm
Nominal drill bit diameter 14 mm

Effective anchor depth 105.0 mm

Material
Concrete (Normal Weight)
Concrete Compressive Strength C25/30
Zone Uncracked Concrete

Concrete Reinforcement
Concrete reinforcement Normal
Edge reinforcement Without
Reinforcement to control splitting No

Conditions
Maximum short term temperature 50 °C
Maximum long term temperature 50 °C
Installation Condition Dry

Geometry
Anchor
Anchor arrangement Group of four without slotted holes
Rotation 0 °

Eccentricity
Displacements y 0.0 mm
Displacements z 0.0 mm

Anchor spacings

Sika Services AG

(P) +41 58 436 6800 (F) +41 58 436 6850


www.sika.com info@sika.com
Project 2/6
Project number Version 1.2.0.16
Contact D.Gajic 7/10/2017

Anchor Calculation AnchorFix-2 - Carbon 10.9 M12


Anchor spacings
Anchor spacing y1 350.0 mm
Anchor spacing z1 350.0 mm

Edge Distances / Concrete Thickness


Concrete thickness h 500.0 mm

Anchor plate dimensions


Anchor plate width y 500.0 mm
Anchor plate length z 500.0 mm
Anchor plate thickness 10.0 mm

Connected profile - Eccentricity


Displacements y 0.0 mm
Displacements z 0.0 mm

Stand-off
Stand-off Without

Load
Load
Tension Nd 15.65 kN
Shear Vyd 1.93 kN
Shear Vzd 0.00 kN
Bending moment Mxd 0.00 kNm
Bending moment Myd 12.73 kNm
Bending moment Mzd 0.00 kNm

Seismic
Seismic No

Section forces
Anchor Nr. Tension [kN] Shear [kN]

1 19.58 kN 0.48 kN
2 19.58 kN 0.48 kN
3 2.06 kN 0.48 kN
4 2.06 kN 0.48 kN

Sika Services AG

(P) +41 58 436 6800 (F) +41 58 436 6850


www.sika.com info@sika.com
Project 3/6
Project number Version 1.2.0.16
Contact D.Gajic 7/10/2017

Anchor Calculation AnchorFix-2 - Carbon 10.9 M12

Verifications EOTA TR 029

Steel failure - Tension


h
NSd
βN,s = N = 19.58 kN
Rk,s /γMs 60.00 kN

h NRk,s [kN] γMs NRd,s [kN] βN,s [%]


NSd [kN]
19.58 84.00 1.40 60.00 32.63

Sika Services AG

(P) +41 58 436 6800 (F) +41 58 436 6850


www.sika.com info@sika.com
Project 4/6
Project number Version 1.2.0.16
Contact D.Gajic 7/10/2017

Anchor Calculation AnchorFix-2 - Carbon 10.9 M12


Pullout and concrete cone failure - Tension
0
NRk,p = π∙d ∙hef ∙τRk

hef [mm] τRk [N/mm²] 0


NRk,p [kN]
105.0 10.00 39.58

0
Ap,N
NRk,p = NRk,p ∙ ∙ψs,Np ∙ψg,Np ∙ψec,Np ∙ψre,Np
A0p,N
0 Ap,N [mm²] ψs,Np ψg,Np ψec,Np
NRk,p [kN] A0p,N [mm²]
39.58 307200 76800 1.00 1.00 0.49
ψre,Np NRk,p [kN]
1.00 78.30
g
NSd
βN,p = N = 43.29 kN
Rk,p /γMp 43.50 kN

g NRk,p [kN] γMp NRd,p [kN] βN,p [%]


NSd [kN]
43.29 78.30 1.80 43.50 99.51

Concrete cone failure - Tension (Controlling anchors: 1, 2, 3, 4)


0
NRk,c = k 1 ∙ fck,cube ∙hef1.5

k1 hef [mm] 0
NRk,c [kN]
10.10 105.0 59.52

0
Ac,N
NRk,c = NRk,c ∙ ∙ψs,N ∙ψre,N ∙ψec,N
A0c,N
0 Ac,N [mm²] ψs,N ψre,N ψec,N
NRk,c [kN] A0c,N [mm²]
59.52 396900 99225 1.00 1.00 0.53

NRk,c [kN]
125.35
g
NSd
βN,c = N /γ = 43.29
69.64
kN
kN
Rk,c Mc
g NRk,c [kN] γMc NRd,c [kN] βN,c [%]
NSd [kN]
43.29 125.35 1.80 69.64 62.16

Sika Services AG

(P) +41 58 436 6800 (F) +41 58 436 6850


www.sika.com info@sika.com
Project 5/6
Project number Version 1.2.0.16
Contact D.Gajic 7/10/2017

Anchor Calculation AnchorFix-2 - Carbon 10.9 M12


Steel failure - Shear
h
VSd
βV,s = V = 0.48 kN
Rk,s /γMs 28.00 kN

h VRk,s [kN] γMs VRd,s [kN] βV,s [%]


VSd [kN]
0.48 42.00 1.50 28.00 1.72

Concrete pryout failure - Shear (Controlling anchors: 1, 2, 3, 4)

0
Ap,N
NRk,p = NRk,p ∙ ∙ψs,Np ∙ψg,Np ∙ψec,Np ∙ψre,Np
A0p,N
0 Ap,N [mm²] ψs,Np ψg,Np ψec,Np
NRk,p [kN] A0p,N [mm²]
39.58 307200 76800 1.00 1.00 0.49
ψre,Np NRk,p [kN]
1.00 78.30

VRk,cp = k ∙NRk,p

k NRk,p [kN] VRk,cp [kN]


2.00 78.30 156.60
g
VSd 1.93 kN
βV,cp = V = 104.40
Rk,cp /γMcp kN
g VRk,cp [kN] γMcp VRd,cp [kN] βV,cp [%]
VSd [kN]
1.93 156.60 1.50 104.40 1.85

Interaction

βN,m ax + βV,m ax
βNV = 1.2
βN,m ax [%] βV,m ax [%] βNV [%]
99.51 1.85 84.46

Sika Services AG

(P) +41 58 436 6800 (F) +41 58 436 6850


www.sika.com info@sika.com
Project 6/6
Project number Version 1.2.0.16
Contact D.Gajic 7/10/2017

Anchor Calculation AnchorFix-2 - Carbon 10.9 M12

The selected Anchor is applicable.

Hints
Notes about the calculations:
The following documents are referenced for the verification of the anchor load-bearing capacity:
- Anchor approval
The following assumptions are made for the calculations:
- The selected building material class has been verified
- all of the anchors in a group are of the same type and size
- The anchor plate remains plane during loading
The verification of the local transfer of loads into the anchorage material has been performed. The transfer of these loads to the rest of
the structure must be shown.
The design is based on numerous anchor-specific values. If the selected anchor is substituted for another or if the input values are
changed, the design must be repeated. Additional requirements of the anchor approvals have to be taken into account, especially if the
anchors are loaded dynamically.

THIS SOFTWARE APPLICATION AND THE RESULTS DERIVED FROM ITS UTILIZATION ARE
INTENDED ONLY FOR USE BY PROFESSIONAL USERS WITH EXPERT KNOWLEDGE IN
THE AREA OF THE INTENDED APPLICATION. USERS MUST INDEPENDENTLY VERIFY THE
RESULTS BEFORE ANY USE AND TAKE INTO ACCOUNT THE SITE AND APPLICATION
CONDITIONS, PRODUCT INFORMATION AND LITERATURE, TECHNICAL STATE OF THE
ART AS WELL AS LOCAL APPLICABLE STANDARDS AND REGULATIONS.

With respect to the software application and results derived from its use, SIKA MAKES NO
WARRANTIES OF ACCURACY, RELIABILITY, COMPLETENESS, MERCHANTABILITY OR
FITNESS FOR ANY PURPOSE. THE SOFTWARE APPLICATION IS PROVIDED ON AN “AS -IS”
BASIS AND SIKA EXPRESSLY DISCLAIMS ANY WARRANTIES WITH RESPECT TO THE
SOFTWARE APPLICATION AND RESULTS DERIVED FROM ITS USE.

Sika shall not be liable for any consequential, punitive, incidental, exemplary, or special damages
(including but not limited to loss of business opportunity or loss of profit) arising out of the
evaluation or use of the software application and results derived from its use.

The information, and, in particular, the recommendations relating to the application and end-use of
Sika products, are given in good faith based on Sika's current knowledge and experience of the
products when properly stored, handled and applied under normal conditions in accordance with

Sika Services AG

(P) +41 58 436 6800 (F) +41 58 436 6850


www.sika.com info@sika.com