Académique Documents
Professionnel Documents
Culture Documents
Uo
Ex (kV/mm)
r
rx ln a
ri ri rx ra
with
Uo = Operating voltage (kV) x
rx = Radius at position x (mm)
ra = External radius above the insulation (mm)
ri = Radius of the internal field delimiter (mm)
4 a'
Lm 2 10 ln (H/km)
a a 0,779 rL
with
2r
a aÿ= 3 2 a Mean geometric distance (mm)
The operating inductance for all three phases a = Phase axis distance (mm)
calculates as: rL = Diameter of conductor over inner
a semiconducting layer (mm)
4
L 2 10 ln (H/km)
0,779 rL
The inductive reactance of the cable system
with calculates for both cases as:
a = Phase axis distance (mm) X L [ /km]
rL = Diameter of conductor over inner with
semiconducting layer (mm) = Angular frequency (1/s)
Dielectric power loss factors tan for typical cable R = Ro [1 + ( - 20°C )] [ /km]
insulations are:
XLPE (1,5 to 3,5) 10þ4 with
þ4
EPR (10 to 30) 10 = 0.0393 for Copper
þ4
Oil cable (18 to 30) 10 = 0.0403 for Aluminium
High voltage cables have a metallic sheath, along sufficiently to the earthing system. The following
which a voltage is induced as a function of the table gives an overview of the possible methods
operating current. In order to handle this induced and their characteristics:
voltage, both cable ends have to be bonded
Both-end bonding
Both ends of the cable sheath are connected to
the system earth. With this method no standing
voltages occur at the cable ends, which makes it
the most secure regarding safety aspects. On the
other hand, circulating currents may flow in the
sheath as the loop between the two earthing U
points is closed through the ground. These
circulating currents are proportional to the
conductor currents and therefore reduce the cable
ampacity significantly making it the most
disadvantegous method regarding economic
aspects.
x
Induced voltage distribution at both-end bonding
Single-ended Bonding
One end of the cable sheath is connected to the
system earth, so that at the other end (ýopen
endü) the standing voltage appears, which is earth continuity
induced linearily along the cable length. In order
to ensure the relevant safety requirements, the
ýopen endü of the cable sheath has to be U
protected with a surge arrester. In order to avoid
potential lifting in case of a failure, both earth
points have to be connected additionally with an
earth continuity wire. The surge arrester (sheath
voltage limiter) is designed to deflect switching
and atmospheric surges but must not trigger in x
case of a short-circuit.
Induced voltage distribution at single-end bonding
Cross-bonding
This earthing method shall be applied for longer sheath crossing after each section. The
route lengths where joints are required due to the termination points shall be solidly bonded to earth.
limited cable delivery length. A cross-bonding
system consists of three equal sections with cyclic
L2
L3
Along each section, a standing voltage is induced. Very long route lengths can consist of several
In ideal cross-bonding systems the three section cross-bonding systems in a row. In this case, it is
lengths are equal, so that no residual voltage recommended to maintain solid bonding of the
occurrs and thus no sheath current flows. The system ends in order to prevent travelling surges
sheath losses can be kept very low with this in case of a fault.
method without impairing the safety as in the two- In addition to cross-linking the sheaths, the
sided sheath earthing. conductor phases can be transposed cyclicly. This
solution is especially suited for very long cable
engths or parallel circuits.
with
XM = Mutual inductance between core and sheath For installation in trefoil formation:
( /km) 2a
7
I = Conductor current per phase (A) LM 2 10 ln (H/km)
L = Cable length dM
Based on these reference values, the short-circuit transfer from the current carrying componen to its
currents for other durations can be converted with adjacent components is allowed.
the following formula:
1 Short-Circuit current capacity of metallic sheaths
I k ,x I k ,1s In addition to the above mentioned, the short-
tc circuit current capacity of metallic sheaths
depends on their layout. The short-circuit current
with capacity is different for tubular sheats and wire
Ikx = Short-circuit current during x seconds [kA] screens, but generally the total short-circuit
tc = Duration of short-circuit [s] current capacity of a metallic sheath is the sum of
Ik,1s = Short-circuit current during 1 second [kA] the capacity of its components.
The above stated values were calculated on a Typical metallic sheath layouts with their
non-adiabatic basis, which means that heat constructional details are listed in a separate
section.
wherein
ls = Impulse short-circuit current [kA]
= surge factor (usually defined as 1.8)
lc = Short-circuit current [kA]