HCI634V
SPECIFICATIONS & OPTIONS
Newage Stamford industrial generators meet the Standard generators feature a main stator with 6 ends
requirements of BS EN 60034 and the relevant section brought out to the terminals, which are mounted on the
of other international standards such as BS5000, VDE frame at the non-drive end of the generator. A sheet
0530, NEMA MG1-32, IEC34, CSA C22.2-100, steel terminal box contains the AVR and provides
AS1359. ample space for the customers' wiring and gland
Other standards and certifications can be considered arrangements. It has removable panels for easy
on request. access.
MX321 AVR - STANDARD All generator rotors are dynamically balanced to better
than BS6861:Part 1 Grade 2.5 for minimum vibration in
This sophisticated Automatic Voltage Regulator (AVR) operation. Two bearing generators are balanced with
is incorporated into the Stamford Permanent Magnet a half key.
Generator (PMG) system and is fitted as standard to
generators of this type.
The PMG provides power via the AVR to the main INSULATION/IMPREGNATION
exciter, giving a source of constant excitation power
independent of generator output. The main exciter The insulation system is class 'H'.
output is then fed to the main rotor, through a full wave All wound components are impregnated with materials
bridge, protected by a surge suppressor. The AVR and processes designed specifically to provide the
has in-built protection against sustained over- high build required for static windings and the high
excitation, caused by internal or external faults. This mechanical strength required for rotating components.
de-excites the machine after a minimum of 5 seconds.
Over voltage protection is built-in and short circuit
current level adjustments is an optional facility. QUALITY ASSURANCE
2
HCI634V
WINDING 312
STATOR Wdg RESIS (L-L) @ 22 Deg C 0.003 Ohms (L-L) at 22 deg c, Star Connected
ROTOR WINDING RESIS AT 22 DEG C 1.9208 Ohms at 22 deg c
R.F.I SUPPRESSION BS EN 61000-6-2 & BS EN 61000-6-4, VDE 0875N, Refer to factory for others.
WAVE FORM DISTORTION NO LOAD <1.8 % NON DISTORTING BALANCED LINEAR LOAD < 5 %
MAXIMUM OVER SPEED 2250 Rev / min
OVER LOAD 10% OVER LOAD FOR 1 HOUR ONCE EVERY 12 HOURS
BEARING DRIVE END BALL 6224 -2RS ( ISO)
BEARING NON-DRIVE END BALL 6317 -2RS ( ISO)
1 BEARING
WEIGHT COMP.GENERATOR 2274
WEIGHT WOUND ROTOR 883
WEIGHT WOUND STATOR 1082
WR2 INERTIA. 20.45
50 HZ 60 HZ
TELEPHONE INTEFERENCE THF < 2 % TIF < 50
COOLING AIR M3/ SEC 1.614 1.961
VOLTAGE SERIES STAR(Y) 380/220 400/231 415/240 440/254 416/240 440/254 460/266 480/277
VOLTAGE DELTA 220 230 240 254 240 254 266 277
KVA BASE RATING FOR REACTANCE
VALUES 800 810 800 800 875 925 963 1000
Xd DIR AXIS SYNCHRONOUS 2.934 2.68 2.460 2.19 3.22 3.04 2.90 2.764
X'd DIR AXIS TRANSIENT 0.117 0.11 0.098 0.09 0.13 0.12 0.12 0.111
X"d DIR AXIS SUB TRANSIENT 0.095 0.09 0.080 0.07 0.11 0.10 0.09 0.090
Xq QUAD AXIS REACTANCE 1.896 1.73 1.590 1.41 2.07 1.96 1.86 1.777
X"q QUAD AXIS SUBTRANSIENT 0.213 0.20 0.179 0.16 0.23 0.22 0.21 0.201
XL LEAKAGE REACTANCE 0.012 0.01 0.010 0.01 0.06 0.06 0.05 0.052
X2 NEGATIVE SEQUENCE 0.143 0.13 0.120 0.11 0.16 0.15 0.14 0.135
X0 ZERO SEQUENCE 0.012 0.01 0.010 0.01 0.01 0.01 0.01 0.011
REACTANCES ARE SATURATED VALUES ARE PER UNIT AT RATINGS AND VOLTAGE INDICATED
380 V
97
96
1
95
0.9
94 0.8
93
92
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1
800 KVA
400 V
97
96
1
95
0.9
94
0.8
93
92
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1
810 KVA
415 V
97
96
1
95
0.9
94 0.8
93
92
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1
800 KVA
440 V
97
96 1
95 0.9
94 0.8
93
92
91
0 0.2 0.4 0.6 0.8 1 1.2
800 KVA
60 HCI634V
Winding 311/ 312
Hz
THREE PHASE EFFICIENCY CURVES
416 V
97
96
95 1
0.9
94
0.8
93
92
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1
875 KVA
440 V
97
96
1
95
0.9
94
0.8
93
92
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1
925 KVA
460 V 1
97
0.9
96
0.8
95
94
93
92
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1
963 KVA
480 V 1
97
0.9
96
0.8
95
94
93
92
91
0 0.2 0.4 0.6 0.8 1 1.2
1000 KVA
HCI634V
Winding 311/312
50
Locked Rotor Motor Starting Curve
Hz
30 380 400 415 440
PERCENTAGE TRANSIENT VOLTAGE DIP
25
20
15
10
0
0 500 1000 1500 2000 2500
LOCKED ROTOR kVA
60
Hz
30 416 440 460 480
PERCENTAGE TRANSIENT VOLTAGE DIP
25
20
15
10
0
0 500 1000 1500 2000 2500 3000 3500
LOCKED ROTOR kVA
HCI634V
Hz
SYMMETRICAL
CURRENT (Amps)
ASYMMETRICAL
10000
1000
0.001 0.01 0.1 1 10
TIME (secs)
60 100000
Hz
SYMMETRICAL
CURRENT (Amps)
ASYMMETRICAL
10000
1000
0.001 0.01 0.1 1 10
TIME (secs)
7
HCI634V
Winding 311 /312 0.8 Power Factor
RATINGS
Class - Temp Rise Cont. F - 105/40°C Cont. H - 125/40°C Standby - 150/40°C Standby - 163/27°C
Star (V) 380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440
50Hz
Delta (V) 220 230 240 254 220 230 240 254 220 230 240 254 220 230 240 254
kVA 750 760 750 750 800 810 800 800 820 830 820 820 850 860 850 850
kW 600 608 600 600 640 648 640 640 656 664 656 656 680 688 680 680
Efficiency (%) 94.5 94.6 94.8 95.0 94.3 94.3 94.6 94.9 94.2 94.3 94.7 94.9 94.2 94.3 94.7 94.9
kW Input 635 643 633 632 679 687 677 675 696 704 693 691 722 730 718 717
Star (V) 416 440 460 480 416 440 460 480 416 440 460 480 416 440 460 480
60Hz
Delta (V) 240 254 266 277 240 254 266 277 240 254 266 277 240 254 266 277
kVA 813 844 888 913 875 925 963 1000 913 1050 1050 1050 1000 1100 1100 1100
kW 650 675 710 730 700 740 770 800 730 840 840 840 800 880 880 880
Efficiency (%) 94.3 94.4 94.7 94.8 94.0 94.1 94.3 94.6 94.0 93.9 94.0 94.5 94.0 93.9 94.0 94.5
kW Input 690 715 750 770 745 787 817 846 777 895 894 889 852 937 936 931
DIMENSIONS
SAE 14 18
AN 25.4 15.87
© TD_HCI634V.IND_17.4.07_01