The Philosophy Of Breaker Failure Protection

The Philosophy Of Breaker Failure Protection (photo credit: enerquestservices.com)

High speed protection scheme


The separation of equipment into zones will only work successfully if the outputs of the protections can be
guaranteed to do their job. This makes logical sense.

For the bus protection in Figure 1 for example, the breakers X and Y must trip on a fault, otherwise the
adjacent zone providing power to the fault must be tripped.

Similarly, for breaker X in Figure 2, the adjacent zone H2 would have to be tripped if breaker X did not open.
However, to maintain the speed and security in protection zones the use of timed backup protections is
minimized.
Figure 1 – Protection Zone for a Bus

Figure 2 – Overlapping Zones

The addition of a timed backup decreases the speed and also the larger backup zone reduces security. The
solution is to add a separate protection on the breaker itself, to guarantee that it will either open correctly or
removed adjacent elements from service.
Breaker failure protection is a high speed protection scheme that will trip surrounding breakers in the event that
a circuit breaker fails to clear a fault.

If, for example in Figure 3, breaker X fails to clear a fault, all of the equipment on bus H2 as well as bus H1 would
be given a trip signal via the breaker failure protection scheme.

A breaker will be considered to have failed if, after the trip signal has been generated, the breaker has:

1. Not started opening within a preset time frame (determined by switches internal to the breaker),
2. The breaker has not fully opened within a preset time frame (determined by switches internal to the
breaker), or
3. If the current has not been broken by the breaker within a preset time (determined by current measurement
devices).

Breaker failure protections are used on breakers at any voltage level, but are predominant on 13.8kV systems
and above. The more impact a failed breaker will have on electrical system stability, the more necessary to use
this high speed breaker failure protection.

Lower voltage levels 13.8kV and below may use timed backup protections if the fault clearing time is not
crucial.

Duplicate A and B Protections

Invariably each one of discrete high-speed protection zones utilize two high-speed duplicate protections. They
are often called A and B, but could be named anything (i.e., C&D, R&S, Even & Odd, etc.). The alternative to
using duplicate protections would be the use of a main high-speed protection and a timed backup.

However, because of slower operating time, the alternative is generally only used on equipment of less
electrical system impact. Duplicate protections are functionally identical, but not physically the same.

They will have the following 6 common features:

1. Functionally identical //

The duplicate protections both fulfil the same purpose and either one could be removed from service without
affecting the protection of the equipment.

2. Not physically identical //

They use different types of protection design or different relay types. Ifone of the protections were to fail due to a
system problem (i.e., harmonics in the current waveform), there would be less chance of the other
protection failing also.

Often one protection will utilize electromechanical relaying and the other solid state relaying.

3. Separate Battery Supplies //

To maintain redundancy, separate battery supplies must be provided for each protection.

4. Separate routing of wiring //

Equipment and wiring are physically separated to reduce possibilities of common faults.
5. Separate Inputs //

The protections utilize signals from completely separate current and voltage transformers. Other equipment data
that is input tothe protections (i.e., pallet positions, temperature sensors, mechanical interlocks, etc.) are also
duplicated.

6. Separate Outputs //

The protections have separate output signals to the circuit breakersor other electrical devices. Quite often the
devices will have duplicate trip coils installed to facilitate complete separation.

Figure 3 below illustrates the philosophy of duplicate (A and B) protections.

Figure 3 – A and B Protection