CORRECTIVE MAINTENANCE FAHU

Non-routine maintenance cannot be foreseen, since this is usually due to the effects of wear or fatigue
due to incorrect functioning of the unit.

Replacement of parts
 Parts must be replaced by skilled personnel:

Qualifications required:
 Qualified maintenance mechanic
 Qualified maintenance electrician
 Manufacturer’s technician

The unit is designed to allow for the execution of all operations necessary to maintain the same in a perfectly
efficient state.
However, it may happen that a component breaks down due to malfunctioning or wear; for replacement, please
consult the executive drawing.

The components which may need replacement are listed


below:
 Filters
 Belts
 Pulley motor
 Pulley fan
 Fan
 Motor
 Recovery/heating/cooling coil
 Humidification pump

For some of these operations, of a general character, a specific description is not given, since they are operations
which are included within the professional competence of the personnel appointed to carry out the same.

Cleaning
It must be remembered that it is strictly forbidden to carry out cleaning operations while the unit is functioning. The
operators appointed to maintain the unit must be informed of this ban

Before carrying out any general cleaning operations, the unit must be switched off and voltage must be disconnected
from the electrical panel by means of the main switch.
For general cleaning operations, the use of vacuum cleaners and air blowers is allowed to remove impurities from the
UNIT.

Cleaning operations m ust not involve lubricated parts, such as rotating shafts, since this could cause functioning
problems and could shorten duration.
For switching off the unit for more or less lengthy periods, it is sufficient to cut off voltage from the unit by means of the
main switch.
For the resumption of the activity, after a more or less lengthy period of idleness, general cleaning and starting up
procedures are necessary.

Components subject to wear and consumption – Spare parts


When the unit is functioning, certain mechanical and electrical parts are subject to wear and consumption; these
parts must be kept under control in order to replace or restore them before correct functioning is compromised
with the consequent stop of the unit.

E X A M P L E OF P A R T S S U B J E C T T O W E A R

CELL/POCKET/ ABSOLUTE/ ACTIVE CARBON FILTERS

EVAPORATING PACK

TRANSMISSION BELTS

HUMIDIFICATION ACCESSORIES

GERM-KILLING LAMPS

IN THE APPENDICES THERE IS A TABLE SHOWING THE PARTS SUBJECT WEAR, RELATIVE TO THE SPECIFIC UNIT ORDERED.
For particular components, such as bearings, motor shafts, etc., please consult the specific appendices
giving the technical features.

To buy the spare parts necessary for routine and/or non-routine maintenance, please contact McQuay quoting
the serial number of reference of the unit indicated in the documentation and on the plate of the unit.

Breakdown table

TYPE OF FAULT COMPONENT POSSIBLE CAUSE/SOLUTION


The rotator is deformed, unbalanced or loose
Fan rotator The nozzle is damaged
Foreign bodies have entered the fan
Pulley loose on the shaft
Pulley not aligned
Transmission Loose, too tight, worn, greasy, dirty or wrongly sized
belts
Motor or fan not well anchored
EXCESSIVE NOISE
No lubrication
Bearings Loose bearing supports
Worn or deformed bearings
Incorrect supply voltage
Motor Worn bearings
Contact between rotor and stator
Excessive speed in the channels
In the channels
Too tight anti-vibration joint
Fan Wrong rotation direction
Greater than requested load loss
INSUFFICIENT AIR Channels Closed shutters
FLOW Obstructions in the channels
Filters Too dirty
Coils Too dirty
Less than requested load loss
Channels Oversized channels
EXCESSIVE AIR Terminals not installed
FLOW Filters not inserted
Unit Access doors open
Uncalibrated shutters
Incorrect input/output pipe connection
Dirty coil
Coil
Air in the pipes
Excessive air flow
INSUFFICIENT HEAT
Insufficient water flow
YIELD
Electrical pump Insufficient pressure
Wrong rotation direction
Temperature different from that of the design
Fluid
Wrong adjustment organs
Lime deposits
Blocked nozzles
Clogged filter
Wrong rotation direction
Electrical pump Lack of water in tank
INSUFFICIENT
Dirty filter pump
HUMIDIFICATION
Coil Insufficient pre-heating
Dirty, clogged or ruined pack
Evaporating pack
Clogged distributor holes
Non-return valve Broken or clogged
Coil Leakage from the coil due to corrosion
LEAKAGE OF
Drips drawn due to the high speed of the air
WATER Fan section
The overflow pipe is clogged