Académique Documents
Professionnel Documents
Culture Documents
A. Application
· Redundant tripping schemes (RED 1))
· Repeated tripping attempts (BFP 2))
· Backup tripping (BFP)
· End fault protection (EFP 3))
· Unconditional tripping (UT 4))
· External trip initiation.
B. Features
· insensitive to DC component
· insensitive to harmonics
· single or three-phase operation
· blocking
· two independent timers (t1, t2)
· transfer tripping
· provision for disabling features (RED, BFP, EFP, UT)
· unique ID for each binary input and output.
I. C.t./v.t. inputs
· current.
1) Redundant
2) Breaker failure protection
3) End fault protection
4) Unconditional trip
3-277
ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. F
IV. Measurements
· Current amplitude L1
· Current amplitude L2
· Current amplitude L3
3-278
REG 316*4 1MRB520049-Uen / Rev. F ABB Switzerland Ltd
CB commands
TRIP t1 B00000000
TRIP t1 L1 B00000000
TRIP t1 L2 B00000000
TRIP t1 L3 B00000000
TRIP t2 B00000000
REMOTE TRIP B00000000
RED TRIP L1 B00000000
RED TRIP L2 B00000000
RED TRIP L3 B00000000
EFP REM TRIP B00000000
EFP BUS TRIP B00000000
General parameters
ParSet4..1 P1 (Select)
I Setting IN 1.20 0.20 5.00 0.01
Delay t1 s 0.15 0.02 60.00 0.01
Delay t2 s 0.15 0.02 60.00 0.01
Delay tEFP s 0.04 0.02 60.00 0.01
t Drop Retrip s 0.05 0.02 60.00 0.01
t Drop BuTrip s 0.05 0.02 60.00 0.01
t Puls RemTrip s 0.05 0.02 60.00 0.01
t1 active on (Select)
t2 active on (Select)
RemTrip active on (Select)
EFP active on (Select)
Red active on (Select)
Start Ext act. on (Select)
RemTrip after t1 (Select)
NrOfPhases 3 1 3 2
CurrentInp CT/VT-Addr 0
3-279
ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. F
Start L1 BinaryAddr F
Start L2 BinaryAddr F
Start L3 BinaryAddr F
Start L1L2L3 BinaryAddr F
External Start BinaryAddr F
CB Off BinaryAddr F
CB On BinaryAddr F
Ext Trip t2 BinaryAddr F
Ext Trip EFP BinaryAddr F
Trip t1 SignalAddr ER
Trip t1 L1 SignalAddr ER
Trip t1 L2 SignalAddr ER
Trip t1 L3 SignalAddr ER
Trip t2 SignalAddr ER
Remote Trip SignalAddr ER
Red Trip L1 SignalAddr ER
Red Trip L2 SignalAddr ER
Red Trip L3 SignalAddr ER
EFP Rem Trip SignalAddr ER
EFP Bus Trip SignalAddr ER
Retrip t1 SignalAddr ER
Uncon Trip t1 SignalAddr ER
Ext Trip t1 SignalAddr ER
Backup Trip t2 SignalAddr ER
Uncon Trip t2 SignalAddr ER
Explanation of parameters:
TRIP t1
defines the tripping channel activated by the function’s trip-
ping output TRIP t1 (matrix tripping logic). This output is acti-
vated for a ‘Retrip’, ‘External Trip Initiate’ or ‘Unconditional
Trip’.
3-280
REG 316*4 1MRB520049-Uen / Rev. F ABB Switzerland Ltd
TRIP t1 L1, L2 or L3
defines the tripping channel activated by the function’s trip-
ping outputs TRIP t1 L1, L2 or L3 (matrix tripping logic). This
output is activated for a phase segregated ‘Retrip’.
TRIP t2
defines the tripping channel activated by the function’s trip-
ping output TRIP t2 (matrix tripping logic). This output is acti-
vated for a ‘Backup Trip’ or ‘Unconditional Trip’ the after sec-
ond time step t2.
REMOTE TRIP
defines the tripping channel activated by the function’s trip-
ping output REMOTE TRIP (matrix tripping logic).
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active (see Section 5.11.).
I Setting
Pick-up of the current criterion for the breaker failure protec-
tion (BFP), end fault protection (EFP) and the redundant trip-
ping logic (RED).
Delay t1
‘Retrip’ tripping delay
Delay t2
Backup tripping delay.
Delay tEFP
End fault protection delay.
t Drop Retrip
Reset delay for ‘Retrip’, ‘Redundant Trip’ and ‘External Trip
Initiate’.
3-281
ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. F
t Drop BuTrip
Reset delay for backup tripping attempt.
t Puls RemTrip
Transfer tripping impulse width.
t1 active
defines whether timer t1 is enabled or disabled.
‘on’ Timer t1 enabled
‘off’ Timer t1 disabled.
t2 active
defines whether timer t2 is enabled or disabled.
‘on’ Timer t2 enabled
‘off’ Timer t2 disabled.
RemTrip active
defines whether transfer tripping is enabled or disabled.
‘on’ Transfer tripping enabled
‘off’ Transfer tripping disabled.
EFP active
defines whether the end fault protection is enabled or disabled.
‘on’ End fault protection enabled
‘off’ End fault protection disabled.
Red active
defines whether the redundant logic is enabled or disabled.
‘on’ Redundant tripping logic enabled
‘off’ Redundant tripping logic disabled.
Start Ext active
defines whether the unconditional tripping logic is enabled or
disabled.
‘on’ Unconditional tripping logic enabled
‘off’ Unconditional tripping logic disabled.
RemTrip after
defines the delay for transfer tripping.
‘t1’ after BFP time t1
‘t2’ after BFP time t2.
NrOfPhases
defines the number of phases supervised.
‘1’ single-phase operation
‘3’ three-phase operation.
CurrentInp
defines the c.t. input channel. Single and three-phase c.t’s
can be set. The first channel (R phase) of the group of three
selected must be specified for three-phase c.t’s.
3-282
REG 316*4 1MRB520049-Uen / Rev. F ABB Switzerland Ltd
Block BFP
Input for blocking the function.
F: not blocked
T: blocked
xx: all binary inputs (or outputs of protection functions).
Start L1, L2 or L3
BFP or RED Start in phase L1, L2 or L3
F: disabled
T: enabled
xx: all binary inputs (or outputs of protection functions).
Start L1L2L3
BFP or RED Start in all three phases
F: disabled
T: enabled
xx: all binary inputs (or outputs of protection functions).
External Start
starts the unconditional trip.
F: disabled
T: enabled
xx: all binary inputs (or outputs of protection functions).
CB Off
signals that the circuit-breaker is fully open and also used to
start the end zone fault protection.
F: CB not fully open
T: CB fully open
xx: all binary inputs (or outputs of protection functions).
CB On
signals that the circuit-breaker is fully closed.
F: CB not fully closed
T: CB fully closed
xx: all binary inputs (or outputs of protection functions).
3-283
ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. F
Ext Trip t2
Input for signals from the other BFP units in the station.
F: No external trip after t2
T: External trip after t2
xx: all binary inputs (or outputs of protection functions).
Trip t1
signals a trip which is activated by one of the following logics:
· Repeat trip (see “Retrip t1”)
· External trip (see “Ext Trip t1”)
· Unconditional trip (see “UnconTrip t1”).
Trip t1 L1, L2 or L3
signals a repeat trip of phase L1, L2 or L3.
Trip t2
signals a backup trip. This signal is activated by the following
logics:
· Backup trip after t2 (see “Backup Trip t2”)
· Unconditional trip after t2 (see “UnconTrip t2”).
Remote Trip
signals a transfer trip.
3-284
REG 316*4 1MRB520049-Uen / Rev. F ABB Switzerland Ltd
Retrip t1
signals a repeat trip after t1. This signal is generated when
the BFP timer t1 in one of the phases has timed out.
Uncon Trip t1
signals an unconditional trip after t1. This signal is generated
when the UT timer t1 has timed out.
Ext Trip t1
signals an external trip. This signal is generated when either
the input “Ext Trip t2” or “Ext Trip EFP” is enabled.
Backup Trip t2
signals a backup trip after t2. This signal is generated when
the BFP timer t2 has timed out.
Uncon Trip t2
signals an unconditional trip after t2. This signal is generated
when the UT timer t2 has timed out.
3-285
ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. F
E. Setting instructions
Settings:
Pick-up current setting: I Setting
Tripping delay: Delay t1
Delay t2
Delay tEFP
3-286
REG 316*4 1MRB520049-Uen / Rev. F ABB Switzerland Ltd
Fault CB Repeat
incidence (1) Start (2) open (3) trip (4)
CB Backup
open (5) trip (6)
Delay t1
Delay t2
3-287
ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. F
(6) After a further reset delay tReset plus a safety margin tMargin ,
the BFP either detects that the fault current has been inter-
rupted and the protection function resets, or the fault cur-
rent continues to flow and the BFP initiates backup tripping.
If the BFP is only required to carry out a single breaker failure
step, timer t1 can be disabled (see ‘t1 active’). The response of
the BFP corresponds once again to Fig. 3.5.28.1, but with timer
t1 set to zero.
3-288
REG 316*4 1MRB520049-Uen / Rev. F ABB Switzerland Ltd
CB CB EFP
tripping signal (1) open (3) tripping signal (4)
tCB open
tReset + tMargin
CB
tripped (2)
3-289
ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. F
‘t Drop BuTrip’ determines the reset delay for the following sig-
nals: 23310 Trip t2
23370 EFP Bus Trip
23335 Backup Trip t2
23365 Uncon Trip t2.
3-290
REG 316*4 1MRB520049-Uen / Rev. F ABB Switzerland Ltd
t1 active
This setting provides facility for disabling the timer t1. When it is
disabled, none of the “repeat trip” group of signals is generated.
t2 active
This setting provides facility for disabling the timer t2. When it is
disabled, none of the “backup trip” group of signals is generated.
RemTrip active
This setting provides facility for disabling transfer tripping. When
it is disabled, none of the “remote trip” group of signals is gener-
ated.
EFP active
This setting provides facility for disabling the end fault protection.
When it is disabled, none of the “end fault” group of signals is
generated.
Red active
This setting provides facility for disabling the redundant protec-
tion. When it is disabled, none of the “redundant” group of sig-
nals is generated.
3-291