MECHANICAL SERVICES
- Air Conditioning & Mechanical Ventilation Services PAGE 1 OF 6
1.1 GENERAL
Unit shall be Air Cooled, consisting of one outdoor unit and plural indoor units, each
having capability to cool independently of requirements of the rooms.
The system shall be equipped with variable refrigerant volume controller, enable it to
reduce minimum load down to 10% of total with the air of inverter control compressor
(inverter control).
Unit shall be suitable for mix-match connection of Ceiling Cassettes (4 way & 2 way),
Semi-Concealed type, Concealed-Duct type, Ceiling-Mounted type, Wall-Mounted
type, Floor Standing type indoors units as shown on the drawing.
The refrigerant piping shall be extended up to 100m with 50m level differences without
any oil traps,
Both indoor unit and outdoor unit are assembled, tested and charged with refrigerant
R410a at the factory.
The air cooled condensing unit shall be a factory assembled unit housed in a sturdy
weatherproof casing constructed from rust-proof mild steel panels coated with a baked
enamel finish. The condensing unit shall be designed to operate safely when connected
to multiple indoor units. It is possible to connect indoor units with a capacity of up to
130% of the outdoor unit capacity.
The sound level shall not be more than 59dBA measured horizontally 1m away and 1m
above ground. The condensing unit shall come equipped with two numbers of vertical
scroll compressors (8 and 10 Hp).
The condensing unit shall be modular in design and should be allowed for side by side
installation.
a. COMPRESSOR
b. CONDENSER ASSEMBLY
The air cooled condenser shall be constructed with copper tubes mechanically
bonded to aluminium fins to form a cross fins coil. The condenser shall have
large face area to minimize noise give a high EER for heat transfer. Condenser
should be of high performance louver fins and inner grooved tubes design for
high efficiency performance.
TECHNICAL SPECIFICATIONS ACMV/TS/VRF
MECHANICAL SERVICES
- Air Conditioning & Mechanical Ventilation Services PAGE 2 OF 6
The newly developed 570mm diameter large condenser fan shall be of low noise
level (59dB) type made from pressed out aluminium and dynamically and
statically balanced for minimum noise and vibration. The condenser fan shall be
directly coupled to a induction motor. The condenser fan and motor shall be of
the high efficiency type with minimum power consumption. The fan motor shall
be equipped with tap-change control so that it can be stepped down to low speed
when the requirement is low.
d. REFRIGERANT CIRCUIT
The refrigerant circuit shall include an accumulator, liquid and gas shut off
valves and an electronic expansion valve. All necessary safety operation,
devices should be provided to ensure the safely operation of the system.
e. SAFETY DEVICE
f. PRESSURIZE TESTING
g. TUBE MATERIAL
Inc.
Association
TECHNICAL SPECIFICATIONS ACMV/TS/VRF
MECHANICAL SERVICES
- Air Conditioning & Mechanical Ventilation Services PAGE 3 OF 6
e) JIS
Unit shall be equipped with an oil recovery system to ensure stable operation
with long refrigerant tubing.
Each indoor unit shall be equipped with mode selector cooling, dry and fan and a self
diagnosis remote controller and having the features of setting of room temperature (with
digital indicator of room temperature), timer, air discharge direction (for cassette units).
Auto and 3 fan speed selection, self diagnosis circuit with malfunction code display.
The unit shall have adequate external static pressure for connection to ductwork as
shown on the drawings (for concealed duct unit).
a. EVAPORATOR
The evaporator coil shall be constructed from strong clean copper tubes bonded to
aluminium fins suitably spaced to ensure maximum heat transfer. The inlet of coil shall
be factory brazed to an electronic control valve. The face velocity shall be exceptionally
low to ensure quiet operation.The evaporator coil shall be constructed from strong clean
copper tubes bonded to aluminum fins suitably spaced to ensure maximum heat
transfer. The inlet of coil shall be factory brazed to an electronic control valve. The face
velocity shall be exceptionally low to ensure quiet operation.
The coil shall be of hi-performance fins and OD 7 mm inner grooved tubes design for
high efficiency performance.
An electronic expansion valve shall be factory brazed to the inlet of the coil. It shall
modulate the refrigerant volume continuously in respond to load variations of the room.
Thus maintain a precise constant temperature of +-0.5 C.
c. EVAPORATOR FAN
The evaporator fan shall be of the multi-blade type with its performance designed to
match the coil performance. The fan dynamically and statically balanced for minimum
noise and vibration. It shall be directly driven by a 3 speed induction motor.
For concealed duct unit the fan shall be able to cater for the static pressure for
connection to ductwork as shown on the drawings.
The motor shall operate on 220 ~ 240 volts single phase 50Hz.
TECHNICAL SPECIFICATIONS ACMV/TS/VRF
MECHANICAL SERVICES
- Air Conditioning & Mechanical Ventilation Services PAGE 4 OF 6
1.4 CONTROL
The indoor and outdoor units each have communications terminals that allow
connection of as many as 48 units and can be able to group control up to 16 number of
groups to a single communications line (polarity-free twin line main bus).
In addition the control system must come equipped with automatic address setting
function (No manual setting of address is allowed). An automatic checking function for
connections error of wiring and piping must come standard with system.
It shall also be equipped with a self diagnosis circuit for easy and quick maintenance
and service.
a. SOFT START
The inverter control compressor shall be able to start at the minimum frequency and
increased to the required frequency (refrigerant volume) according to the actual load
requirement.
A recycling guard timer shall be provided to prevent the compressor to restart again
immediately after it was stopped.
A centralized control system shall consists of a System Controller and a Weekly Timer.
They shall be provided to control all the functions of the indoor units either together as a
central control system or individually as the specification call for. They must be able to
connect to a Building Management System (BMS).
System Controller
Weekly Timer
The timer should be able to connected up to 16 groups or 48 nos. Fan Coil Units and it
should have the following functions: -
Program covering a week, in which the operation can be stopped 3 times per day,
can be set.
It must be able to combine with the System Controller and the Remote Controller.
General
All units shall be delivered completely factory tested. Units must be manufactured in
accordance with International Standards Organisation (ISO) 9000.
Casing
The casing shall be electro-galvanised mild steel (1-2.3 mm gauge) with epoxy
polyester powder coating. Polyethylene insulation shall be provided to the internal sides
of the units.
Low noise centrifugal fan shall be used. The fan section must be statically and properly
balanced at the factory to minimise vibration. Automatic or manual airflow swing
adjustment shall be provide for the wall and cassette units.
Coils
The coils shall be configurated aluminium fins bonded to seamless copper tubes. All
coils are to be factory pressure tested. All units shall be furnished complete with a drain
pan of either electro-galvanised mild steel with epoxy polyester powder coating and
polyethylene insulation or polyester construction.
Control Box
The units controls shall be mounted in a box, in a separate compartment in the cabinet.
All controls are prewired and tested at the factory.
TECHNICAL SPECIFICATIONS ACMV/TS/VRF
MECHANICAL SERVICES
- Air Conditioning & Mechanical Ventilation Services PAGE 6 OF 6
The insulation must be machine injected polyurethane foam with an overall density of
50 kg/m3 . Below are the properties for the polyurethane foam insulation :-
The jacket shall be galvanised steel spiral external lockseamed with a minimum
thickness of 0.5mm thick.