Submittal Ref. #: 552321.

1 rev1

Design envelope split coupled vertical in line pump with parallel sensorless controller
Model: Series Design Envelope Sensorless 4300 0810-050.0

Project name: LA CURVA


Location: Lima Representative:
Date submitted: 5/16/2016 4:15:53 PM Phone number:
Engineer: e-mail: Noel@dbamericas.com
Contractor: Submitted by: Noel Garcia
Application design data
Tag number: BPV-1,2,3 Pipe orientation: Parallel
Service: Suction pressure: 0 psig
Location: Fluid: Non-Potable Fluid - Water
Quantity: 3 Operating temperature: 60 F
Pump/motor run qty: 2 Viscosity: 31 SSU
Duty flow per pump: 1440 USgpm Specific gravity: 1.0000
Duty head: 85 ft Safety factor % head: 0%
Environment: Indoors Total dissolved solids: 0 ppm
Materials of construction
Construction: BF Impeller: Bronze (B584-844)
Rating: ANSI-125 Pump shaft: SS ASTM A276 Type 416
Connections: Inlet: 8 in, Outlet: 8 in Flush line: Braided Stainless Steel
Casing (volute): Cast Iron (A48-30) Casing gasket: Confined Non-Asbestos Fiber

Mechanical seal data


Seal type: Outside Balanced Rotating face: Resin Bonded Carbon
Manufacturer code: C-SSC AB2 Stationary seat: Sintered Silicon Carbide
Springs: Stainless Steel Secondary seal: Viton
Rotating hardware: Stainless Steel

Motor electrical data


Supplier: Factory Choice Insulation class: Class F Insulation
Size: 50 hp Inverter motor type: Inverter Duty
Frame number: 326TC Efficiency: NEMA Prem (12.12)
Enclosure: ODP Operating speed @ 100% flow: 1742 rpm
Motor Electrics: 380/3/60 Operating speed @ 50% flow: 1228 rpm

IVS102 controller data


Sensorless control: Yes-Quadratic press control Communication port: RS 485
BMS protocol: BACnet Native Analog inputs: 2 (current or voltage)
Enclosure: UL Type 12 Analog outputs: 1 (current)
Fused disconnect switch: No Digital inputs: 4 (programmable)
Control orientation: L1 Digital outputs: 2 (programmable)
Expansion card: None Cooling: Fan cooled through back channel
BHP at 50% load/flow and
9.34 hp Ambient temperature: 14F to 113F (up to 3280ft elevation)
55% of design head:
Meets ASHRAE 90.1: No EMI/RFI control: Integrated fliter to meet EN61800-3
Min. maintained sys. pressure: 34 ft Harmonic suppression: Integrated DC link reactor**
*If minimum maintained system pressure is not known, default is 40% of design head.
** The IVS 102 control is a low harmonic control with a built-in DC link reactor equivalent in performance to a 5% AC line reactor. This does not
guarantee performance to any system wide harmonic specification or the costs to meet a system wide specification. If supplied with the system
electrical details, Armstrong will run a computer simulation of the system wide harmonics. If system harmonic levels are exceeded, Armstrong
can also recommend additional harmonic mitigation and the cost for such mitigation.

www.armstrongfluidtechnology.com 5/16/2016, Ref. # 552321.1 rev1 Page 1 of 15


Performance curve

--- Admin Data ---


Head Series 4300 PT112-2-0 (3.23.0.1)
ANSI/HI 14.6.3.4 2B
Tag Num: BPV-1,2,3
Service:
(ft)
Design Envelope: 0810-050.0 @ 58.4 Hz Location:
Integrated Intelligent Variable Speed with Sensorless Control --- Motor Data ---
120 Motor Size: 50 hp

--- Design Duty Point ---


10.19 in 35 Flow: 1440 usgpm
100 10.19 in 50 62 Head: 85 ft
71 Impeller: 10.19 in
79
83 --- Performance Data ---
80 85 • NPSHR: 14.5 ft
• Eff. @ Design: 82.69 %
83 • BHP @ Design: 37.38 hp
• Mtr Capability @ Rated Spd: 45.61 hp
79 • %Mtr Safety: 22.02%
60 • BEP @ Design Imp.:
8.00 in 71 84.82 % @ 1661.5 usgpm
• %max imp. range: 100.00 %
• Outlet Velocity: 9.24 ft/s
40 62% 50 hp • VFD Op.Speed: 1742 rpm
40 hp • VFD Setting: 58.4 Hz
30 hp
25 hp
20 System

0
0 0.5 1 1.5 2 2.5 3
Water, spgr= 1.0000 Flow ( 1,000 usgpm)

--- Admin Data ---


Head Series 4300 PT112-2-0 (3.23.0.1)
ANSI/HI 14.6.3.4 2B Tag Num: BPV-1,2,3
(ft)
Design Envelope: 0810-050.0 Service:
Location:
Integrated Intelligent Variable Speed with Sensorless Control
160 Index Flow (25.0% Duty Flow) --- Motor Data ---
Motor Size: 50 hp
140
--- Design Duty Point ---
Flow: 1440 usgpm
120 62.2 Hz 50
Head: 85 ft
62 Impeller: 10.19 in
71
58.4 Hz 79
100 83 --- Control Data ---
85 1. Hmax @ 58.4 Hz:
1
• 1440 @ 85, 37.38 hp
80 83
2 2. Control (QPC) @ 54.0 Hz:
79 • 1275.5 @ 74, 29.24 hp
3 3. Control (QPC) @ 49.3 Hz:
60 4 71
• 1090.1 @ 63.2, 21.92 hp
5 4. Control (QPC) @ 44.9 Hz:
40 35.7 Hz
6 Avg.Load (QPC) 50 hp • 903.1 @ 54.1, 16.26 hp
5. Control (QPC) @ 40.2 Hz:
33.6 Hz • 670.8 @ 45.1, 11.23 hp
20 System 6. Index @ 35.7 Hz:
• 360 @ 37.2, 7.22 hp
0 18.0 Hz 7. Hmin: 34 ft 33.6 Hz:
• Setting= 40.00% Hmax
0 0.5 1 1.5 2 2.5 3
Water, spgr= 1.0000 Flow ( 1,000 usgpm)

www.armstrongfluidtechnology.com 5/16/2016, Ref. # 552321.1 rev1 Page 2 of 15


Head Parallel Pump Curve PT112-2-0 (3.23.0.1) --- Admin Data ---
Design Envelope: 0810-050.0 Tag Num: BPV-1,2,3
(ft)
Integrated Intelligent Variable Speed with Sensorless Control Service:
Location:
100 --- Motor Data ---
Motor Size: 50 hp

80 --- System Design Data ---


Piping: Parallel, Run Qty = 2
Fluid: Water
Sp.Gr.= 1.0000, vis= 31 ssu, 60 F
60 Suction: 0 psi
System: Closed, M.Head: 0 psi
Total Design Flow = 2880 usgpm
Total Design Head = 85 ft
40 1 2
1 2 --- Pump Data @ Curve# 2 ---
1 2 NPSHR: 14.5 ft
20 1
System 2 Flow: 2880 usgpm
1 2 Head: 85 ft
1 2
Eff: 82.7%, BEP: 84.8%
0 %BEP (Flow): 86%
0 1 2 3 4 5 BHP = 74.71 hp
BHP/Pump= 37.36 hp

Water, spgr= 1.0000 Flow ( 1,000 usgpm)

Design envelope pumping unit capability


Operating point Flow Head Efficiency
Full capability at 100% design flow 1440 USgpm 99.2 ft 80.89 %
Design point 1440 USgpm 85 ft 82.69 %
50% average flow (with default load profile) 720 usgpm 46.8 ft 70.04 %

Dimensional data (not for construction)


Side view Top view

Weight: 725 lb
• Not to scale
• R = minimum lifting clearance required above motor
• Units of measure : inches [millimeters]
• Coupling guard and flush line (not shown) are supplied
• Tolerance of ± 0.125 inch (± 3 mm) should be used
• For certified dimensions, please contact your Armstrong representative
• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports

www.armstrongfluidtechnology.com 5/16/2016, Ref. # 552321.1 rev1 Page 3 of 15


Connection details
Connection Size Rating OD Bolt quantity* BCD Bolt size
Inlet 8 ANSI-125 13.5 8 11.75 0.75
Outlet 8 ANSI-125 13.5 8 11.75 0.75
*Equally spaced straddling centreline

Special instructions

Armstrong Motor Specification AES 05007


The program has defaulted to a NEMA Premium Efficiency motor supplied with NEMA MG-1 Part 31.4.4.2 insulation standards for inverter-fed
polyphase motors.

OSHPD Seismic Certification OSP-0422-10


UL STD 778 & CSA STD C22.2 no.108 certified

Selected options
Motor 60 Hertz (380 volts)
Casing Wear Ring - Not included
Environmental Application: Indoors
Parallel Sensorless BMS Comm Protocol: Standard (no card)
PSPC Controller Model: PSPC-N
PSPC Controller Part Number: 710000-000

Additional equipment
Flotrex: FTV-8FA (570200-481)
Suction Guide: SG-88 (516860-028)

www.armstrongfluidtechnology.com 5/16/2016, Ref. # 552321.1 rev1 Page 4 of 15


Submittal Ref. #: 552321.1 rev1

Split coupled vertical in line pump


Model: Series 4300-12x12x13-40 hp Pump (Motor supplier: Armstrong choice)

Project name: LA CURVA


Location: Lima Representative:
Date submitted: 5/16/2016 4:15:53 PM Phone number:
Engineer: e-mail: Noel@dbamericas.com
Contractor: Submitted by: Noel Garcia
Application design data
Tag number: BCV-1,2,3 Pipe orientation: Parallel
Service: Suction pressure: 0 psig
Location: Fluid: Non-Potable Fluid - Water
Quantity: 3 Operating temperature: 60 F
Pump/motor run qty: 2 Viscosity: 31 SSU
Duty flow per pump: 1880 USgpm Specific gravity: 1.0000
Duty head: 45 ft Total dissolved solids: 0 ppm

Materials of construction
Construction: BF Impeller: Bronze (B584-844)
Rating: ANSI-125 Pump shaft: SS ASTM A276 Type 416
Connections: Inlet: 12 in, Outlet: 12 in Flush line: Braided Stainless Steel
Casing (volute): Cast Iron (A48-30) Casing gasket: Confined Non-Asbestos Fiber

Mechanical seal data


Seal type: Outside Balanced Rotating face: Resin Bonded Carbon
Manufacturer code: C-SSC AB2 Stationary seat: Sintered Silicon Carbide
Springs: Stainless Steel Secondary seal: Viton
Rotating hardware: Stainless Steel

Motor electrical data


Supplier: Factory Choice Insulation class: Class F Insulation
Size: 40 hp Inverter motor type: Not applicable
Frame number: 364TC Efficiency: NEMA Prem (12.12)
Enclosure: ODP Speed: 1190 rpm
Motor Electrics: 380/3/60

Operating limits (temperature - pressure)

Maximum pressure: 175 psi

Maximum temperature: 200 F


Pump casings are hydrostatically tested to 150% of maximum pump working
pressure rating.

www.armstrongfluidtechnology.com 5/16/2016, Ref. # 552321.1 rev1 Page 5 of 15


Performance curve

--- Admin Data ---


Head Series 4300 PT22-2-0 (3.23.0.1) Tag Num: BCV-1,2,3
ANSI/HI 14.6.3.4 2B Service:
(ft) 12x12x13 @ 1190 rpm Location:
100 --- Motor Data ---
Motor Size: 40 hp
Motor Speed: 1200 rpm

13.00 in --- Design Duty Point ---


80 41 56 Flow: 1880 usgpm
67 75 Head: 45 ft
80
84 Impeller: 10.88 in
85
84 --- Performance Data ---
60 10.88 in 80
• NPSHR: 9.026 ft
• Eff. @ Design: 74.76 %
• BHP @ Design: 28.57 hp
75 • Mtr Capability @ Rated Spd: 40.00 hp
• %Mtr Safety: 25.38%
67 75 • BEP @ Design Imp.:
40 80.45 % @ 2504.7 usgpm
60 • Impeller Max BHP @ Flow:
8.88 in 33.08 hp @ 3431.9 usgpm
50
• %max imp. range: 48.54 %
40 • Outlet Velocity: 5.39 ft/s
20 56% 2530
20
System 15 hp
0
0 0.8 1.6 2.4 3.2 4 4.8

Water, spgr= 1.0000 Flow ( 1,000 usgpm)

Head Parallel Pump Curve


PT22-2-0 (3.23.0.1) --- Admin Data ---
Tag Num: BCV-1,2,3
(ft) Series 4300 Service:
12x12x13 @ 1190 rpm Location:

80 --- Motor Data ---


Motor Size: 40 hp
Motor Speed: 1200 rpm

--- System Design Data ---


60
Piping: Parallel, Run Qty = 2
Fluid: Water
Sp.Gr.= 1.0000, vis= 31 ssu, 60 F
Suction: 0 psi
40 System: Open, S.Head: 0 psi
Total Design Flow = 3760 usgpm
Total Design Head = 45 ft

20 1 2 --- Pump Data @ Curve# 2 ---


NPSHR: 9.0433 ft
Flow: 3760 usgpm
System Head: 45 ft
0 Eff: 74.8%, BEP: 80.4%
0 2 4 6 8 10 %BEP (Flow): 75%
BHP = 57.09 hp
BHP/Pump= 28.54 hp
Water, spgr= 1.0000 Flow ( 1,000 usgpm)

www.armstrongfluidtechnology.com 5/16/2016, Ref. # 552321.1 rev1 Page 6 of 15


Dimensional data (not for construction)
Side view Top view

Weight: 2550 lb
• Not to scale
• R = minimum lifting clearance required above motor
• Units of measure : inches [millimeters]
• Coupling guard and flush line (not shown) are supplied
• Tolerance of ± 0.125 inch (± 3 mm) should be used
• For certified dimensions, please contact your Armstrong representative
• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports
Connection details
Connection Size Rating OD Bolt quantity* BCD Bolt size
Inlet 12 ANSI-125 19 12 17 0.875
Outlet 12 ANSI-125 19 12 17 0.875
*Equally spaced straddling centreline

Special instructions

Armstrong Motor Specification AES 05007

Selected options
Motor 60 Hertz (380 volts)
Casing Wear Ring - Bronze CWR

Additional equipment
Flotrex: FTV-10FA (570200-482)

www.armstrongfluidtechnology.com 5/16/2016, Ref. # 552321.1 rev1 Page 7 of 15


Submittal Ref. #: 552321.1 rev1

Split coupled vertical in line pump


Model: Series 4300-6x6x11.5-30 hp Pump (Motor supplier: Armstrong choice)

Project name: LA CURVA


Location: Lima Representative:
Date submitted: 5/16/2016 4:15:53 PM Phone number:
Engineer: e-mail: Noel@dbamericas.com
Contractor: Submitted by: Noel Garcia
Application design data
Tag number: BC-4,5,6 Pipe orientation: Parallel
Service: Suction pressure: 0 psig
Location: Fluid: Non-Potable Fluid - Water
Quantity: 3 Operating temperature: 60 F
Pump/motor run qty: 2 Viscosity: 31 SSU
Duty flow per pump: 750 USgpm Specific gravity: 1.0000
Duty head: 89 ft Total dissolved solids: 0 ppm

Materials of construction
Construction: BF Impeller: Bronze (B584-844)
Rating: ANSI-125 Pump shaft: SS ASTM A276 Type 416
Connections: Inlet: 6 in, Outlet: 6 in Flush line: Braided Stainless Steel
Casing (volute): Cast Iron (A48-30) Casing gasket: Confined Non-Asbestos Fiber

Mechanical seal data


Seal type: Outside Balanced Rotating face: Resin Bonded Carbon
Manufacturer code: C-SSC AB2 Stationary seat: Sintered Silicon Carbide
Springs: Stainless Steel Secondary seal: Viton
Rotating hardware: Stainless Steel

Motor electrical data


Supplier: Factory Choice Insulation class: Class F Insulation
Size: 30 hp Inverter motor type: Not applicable
Frame number: 286TC Efficiency: NEMA Prem (12.12)
Enclosure: ODP Speed: 1780 rpm
Motor Electrics: 380/3/60

Operating limits (temperature - pressure)

Maximum pressure: 175 psi

Maximum temperature: 200 F


Pump casings are hydrostatically tested to 150% of maximum pump working
pressure rating.

www.armstrongfluidtechnology.com 5/16/2016, Ref. # 552321.1 rev1 Page 8 of 15


Performance curve

--- Admin Data ---


Head Series 4300 PT105-1-0 (3.23.0.1) Tag Num: BC-4,5,6
ANSI/HI 14.6.3.4 2B Service:
(ft) 6x6x11.5 @ 1780 rpm Location:
160 --- Motor Data ---
Motor Size: 30 hp
Motor Speed: 1800 rpm
140
11.50 in 42 57 68 --- Design Duty Point ---
77 Flow: 750 usgpm
82
120 84 Head: 89 ft
85 Impeller: 10.06 in
84
10.06 in 82 --- Performance Data ---
100 • NPSHR: 9.2702 ft
77 • Eff. @ Design: 83.01 %
9.50 in • BHP @ Design: 20.31 hp
80 68 • Mtr Capability @ Rated Spd: 30.00 hp
• %Mtr Safety: 26.05%
• BEP @ Design Imp.:
40 hp 83.18 % @ 810.9 usgpm
60 • Impeller Max BHP @ Flow:
30 hp 24.07 hp @ 1114.4 usgpm
25 hp • %max imp. range: 28.00 %
40 20 hp
• Outlet Velocity: 8.33 ft/s
15 hp
10 hp
20 System

0
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6

Water, spgr= 1.0000 Flow ( 1,000 usgpm)

Head Parallel Pump Curve


PT105-1-0 (3.23.0.1) --- Admin Data ---
Tag Num: BC-4,5,6
(ft) Series 4300 Service:
160 6x6x11.5 @ 1780 rpm Location:

140 --- Motor Data ---


Motor Size: 30 hp
Motor Speed: 1800 rpm
120
--- System Design Data ---
100 Piping: Parallel, Run Qty = 2
Fluid: Water
Sp.Gr.= 1.0000, vis= 31 ssu, 60 F
80 Suction: 0 psi
System: Open, S.Head: 0 psi
60 Total Design Flow = 1500 usgpm
Total Design Head = 89 ft
1 2
40 --- Pump Data @ Curve# 2 ---
NPSHR: 9.3112 ft
20 System Flow: 1500 usgpm
Head: 89 ft
0 Eff: 83.0%, BEP: 83.2%
0 0.4 0.8 1.2 1.6 2 2.4 2.8 3.2 %BEP (Flow): 92%
BHP = 40.61 hp
BHP/Pump= 20.3 hp
Water, spgr= 1.0000 Flow ( 1,000 usgpm)

www.armstrongfluidtechnology.com 5/16/2016, Ref. # 552321.1 rev1 Page 9 of 15


Dimensional data (not for construction)
Side view Top view

Weight: 913 lb
• Not to scale
• R = minimum lifting clearance required above motor
• Units of measure : inches [millimeters]
• Coupling guard and flush line (not shown) are supplied
• Tolerance of ± 0.125 inch (± 3 mm) should be used
• For certified dimensions, please contact your Armstrong representative
• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports
Connection details
Connection Size Rating OD Bolt quantity* BCD Bolt size
Inlet 6 ANSI-125 11 8 9.5 0.75
Outlet 6 ANSI-125 11 8 9.5 0.75
*Equally spaced straddling centreline

Special instructions

Armstrong Motor Specification AES 05007

Selected options
Motor 60 Hertz (380 volts)
Casing Wear Ring - Not included

Additional equipment
Flotrex: FTV-6FA (570200-480)

www.armstrongfluidtechnology.com 5/16/2016, Ref. # 552321.1 rev1 Page 10 of 15


Submittal Ref. #: 552321.1 rev1

Flo-trex valve
Model: FTV-F (2.5 to 12 inch)

Project name: LA CURVA


Location: Lima Representative:
Date submitted: 5/16/2016 4:15:53 PM Phone number:
Engineer: e-mail: Noel@dbamericas.com
Contractor: Submitted by: Noel Garcia

Application design data


Design Pressure
Tag Qty Model Size Config Flange rating Associated pump
flowrate Drop*
BPV-1,2,3 3 FTV-8FA 8 in Angle ANSI-125 1440.0 USgpm 1.7 psi BPV-1,2,3 Design Envelope Sensorless
Flanged 4300 0810-050.0
BCV-1,2,3 3 FTV-10FA 10 in Angle ANSI-125 1880.0 USgpm 1.2 psi BCV-1,2,3 4300-12x12x13-40 hp Pump
Flanged (Factory Choice Motor)
BC-4,5,6 3 FTV-6FA 6 in Angle ANSI-125 750.0 USgpm 1.5 psi BC-4,5,6 4300-6x6x11.5-30 hp Pump
Flanged (Factory Choice Motor)
*at design flow

Materials of construction
FTV-8FA-Flo-Trex Valve-ANSI-125-Angle Flanged FTV-Flanged-2.5-12
Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302
Disc: Bronze ASTM B584-C84400 O rings: BUNA (STEM) Elastomers & EPDM
Seat: EPDM 2 metering ports: Brass Body with EPDM Check and
Gasketed Cap
Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug

FTV-10FA-Flo-Trex Valve-ANSI-125-Angle Flanged FTV-Flanged-2.5-12


Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302
Disc: Bronze ASTM B584-C84400 O rings: BUNA (STEM) Elastomers & EPDM
Seat: EPDM 2 metering ports: Brass Body with EPDM Check and
Gasketed Cap
Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug

FTV-6FA-Flo-Trex Valve-ANSI-125-Angle Flanged FTV-Flanged-2.5-12


Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302
Disc: Bronze ASTM B584-C84400 O rings: BUNA (STEM) Elastomers & EPDM
Seat: EPDM 2 metering ports: Brass Body with EPDM Check and
Gasketed Cap
Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug

Operating limits (temperature - pressure)

www.armstrongfluidtechnology.com 5/16/2016, Ref. # 552321.1 rev1 Page 11 of 15


FTV-8FA-Flo-Trex Valve-ANSI-125-Angle Flanged

Maximum pressure: 175 psi


Maximum temperature: 230 F

Dimensional data (not for construction)


Model: FTV-8FA-Flo-Trex Valve-ANSI-125-Angle Flanged Weight: 344 lb
Side view Front view

Model: FTV-10FA-Flo-Trex Valve-ANSI-125-Angle Flanged Weight: 603 lb


Side view Front view

www.armstrongfluidtechnology.com 5/16/2016, Ref. # 552321.1 rev1 Page 12 of 15


Model: FTV-6FA-Flo-Trex Valve-ANSI-125-Angle Flanged Weight: 167 lb
Side view Front view

Not to scale
Units of measure: inches [millimeters]
Tolerance of +/- 0.125 inch (+/- 3 mm) should be used
For certified dimensions, please contact your Armstrong representative

www.armstrongfluidtechnology.com 5/16/2016, Ref. # 552321.1 rev1 Page 13 of 15


Submittal Ref. #: 552321.1 rev1

Suction guide
Model: SG (2 to 12 inches)

Project name: LA CURVA


Location: Lima Representative:
Date submitted: 5/16/2016 4:15:53 PM Phone number:
Engineer: e-mail: Noel@dbamericas.com
Contractor: Submitted by: Noel Garcia

Application design data


Design Pressure
Tag Qty Model System Pump Associated pump
flowrate Drop*
BPV-1,2,3 3 SG-88 8 in 8 in 1440.0 USgp 0.9 psi BPV-1,2,3 Design Envelope Sensorless 4300 0810-
050.0

*at design flow

Materials of construction
SG-88
Body: Cast Iron Cover gasket: Synthetic fiber
Guide vanes: Cast Iron Strainer: Stainless Steel,0.125"(3mm)Perf.
Cover plate: Cast Iron Start-up strainer*: Fine Mesh Galvanized Steel

*Remove start up strainer after 24 hours

Operating limits (temperature - pressure)


SG-88-Suction Guide-ANSI-125

Maximum pressure: 175 psi


Maximum temperature: 230 F

Units are hydrostatically tested to 150% of maximum working pressure

www.armstrongfluidtechnology.com 5/16/2016, Ref. # 552321.1 rev1 Page 14 of 15


Dimensional data (not for construction)
SG-88 Weight: 213 lb
Side view Top view

Not to scale
Units of measure: inches [millimeters]
Tolerance of +/- 0.125 inch (+/- 3 mm) should be used
For certified dimensions, please contact your Armstrong representative

www.armstrongfluidtechnology.com 5/16/2016, Ref. # 552321.1 rev1 Page 15 of 15