www.hilti.us Profis Anchor 2.7.

5
Company: Page: 1
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 2/1/2018
E-Mail:

Specifier's comments:

1 Input data
Anchor type and diameter: Heavy Hex Head ASTM F 1554 GR. 36 3/4
Effective embedment depth: hef = 180 mm
Material: ASTM F 1554
Proof: Design method ACI 318-08 / CIP
Stand-off installation: eb = 0 mm (no stand-off); t = 13 mm
Anchor plate: lx x ly x t = 256 mm x 544 mm x 13 mm; (Recommended plate thickness: not calculated
Profile: no profile
Base material: cracked concrete, , fc' = 6237 psi; h = 230 mm
Reinforcement: tension: condition B, shear: condition B;
edge reinforcement: none or < No. 4 bar
Corner reinforcement acc. to ACI 318-08 Part D.6.2.3 (c) present
Seismic loads (cat. C, D, E, or F) no

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.7.5
Company: Page: 2
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 2/1/2018
E-Mail:

2 Load case/Resulting anchor forces y


Compression
Load case: Design loads
2
Anchor reactions [kN]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 0.741 31.491 31.491 0.000
x
2 0.132 8.491 -8.491 0.000

max. concrete compressive strain: 0.00 [‰]


max. concrete compressive stress: Tension
0.10 [N/mm2] 1
resulting tension force in (x/y)=(-38/-85): 0.872 [kN]
resulting compression force in (x/y)=(-77/236): 0.272 [kN]

3 Tension load
Load Nua [kN] Capacity f Nn [kN] Utilization bN = Nua/f Nn Status
Steel Strength* 0.741 64.628 2 OK
Pullout Strength* 0.741 141.528 1 OK
Concrete Breakout Strength** 0.872 86.134 2 OK
Concrete Side-Face Blowout, direction ** N/A N/A N/A N/A
* anchor having the highest loading **anchor group (anchors in tension)

3.1 Steel Strength


Nsa = Ase,N futa ACI 318-08 Eq. (D-3)
f Nsa ≥ Nua ACI 318-08 Eq. (D-1)

Variables
Ase,N [mm2] futa [N/mm2]
215 399.90
Calculations
Nsa [kN]
86.171
Results
Nsa [kN] f steel f Nsa [kN] Nua [kN]
86.171 0.750 64.628 0.741

3.2 Pullout Strength


NpN = y c,p Np ACI 318-08 Eq. (D-14)
Np = 8 Abrg f'c ACI 318-08 Eq. (D-15)
f NpN ≥ Nua ACI 318-08 Eq. (D-1)

Variables
y c,p Abrg [mm2] f'c [psi]
1.000 588 6237
Calculations
Np [kN]
202.183
Results
Npn [kN] f concrete f Npn [kN] Nua [kN]
202.183 0.700 141.528 0.741

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.7.5
Company: Page: 3
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 2/1/2018
E-Mail:

3.3 Concrete Breakout Strength

Ncbg = (AA ) y
Nc
Nc0
ec,N y ed,N y c,N y cp,N Nb ACI 318-08 Eq. (D-5)
f Ncbg ≥ Nua ACI 318-08 Eq. (D-1)
ANc see ACI 318-08, Part D.5.2.1, Fig. RD.5.2.1(b)
ANc0 = 9 h2ef ACI 318-08 Eq. (D-6)

( )
1
y ec,N = 2 e'N ≤ 1.0 ACI 318-08 Eq. (D-9)
1+
3 hef
y ed,N = 0.7 + 0.3 (ca,min
1.5hef )
≤ 1.0 ACI 318-08 Eq. (D-11)

y cp,N = MAX (
ca,min 1.5hef
cac
,
cac )
≤ 1.0 ACI 318-08 Eq. (D-13)
1.5
Nb = kc l √fc hef
'
ACI 318-08 Eq. (D-7)

Variables
hef [mm] ec1,N [mm] ec2,N [mm] ca,min [mm] y c,N
180 0 98 158 1.000

cac [mm] kc l f'c [psi]


0 24 1 6237

Calculations
ANc [mm2] ANc0 [mm2] y ec1,N y ec2,N y ed,N y cp,N Nb [kN]
350960 291600 1.000 0.734 0.876 1.000 159.049
Results
Ncbg [kN] f concrete f Ncbg [kN] Nua [kN]
123.049 0.700 86.134 0.872

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.7.5
Company: Page: 4
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 2/1/2018
E-Mail:

4 Shear load
Load Vua [kN] Capacity f Vn [kN] Utilization bV = Vua/f Vn Status
Steel Strength* 31.491 33.607 94 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength* 31.491 117.323 27 OK
Concrete edge failure in direction x+** 31.491 34.533 92 OK
* anchor having the highest loading **anchor group (relevant anchors)

4.1 Steel Strength


Vsa = 0.6 Ase,V futa ACI 318-08 Eq. (D-20)
f Vsteel ≥ Vua ACI 318-08 Eq. (D-2)

Variables
Ase,V [mm2] futa [N/mm2]
215 399.90
Calculations
Vsa [kN]
51.703
Results
Vsa [kN] f steel f Vsa [kN] Vua [kN]
51.703 0.650 33.607 31.491

4.2 Pryout Strength

Vcp = kcp [(AA ) y


Nc
Nc0
ed,N y c,N y cp,N Nb] ACI 318-08 Eq. (D-30)
f Vcp ≥ Vua ACI 318-08 Eq. (D-2)
ANc see ACI 318-08, Part D.5.2.1, Fig. RD.5.2.1(b)
ANc0 = 9 h2ef ACI 318-08 Eq. (D-6)

( )
1
y ec,N = 2 e'N ≤ 1.0 ACI 318-08 Eq. (D-9)
1+
3 hef
y ed,N = 0.7 + 0.3 (ca,min
1.5hef )
≤ 1.0 ACI 318-08 Eq. (D-11)

y cp,N = MAX (
ca,min 1.5hef
cac
,
cac )
≤ 1.0 ACI 318-08 Eq. (D-13)
1.5
Nb = kc l √fc hef
'
ACI 318-08 Eq. (D-7)

Variables
kcp hef [mm] ec1,N [mm] ec2,N [mm] ca,min [mm]
2 180 0 0 158

y c,N cac [mm] kc l f'c [psi]


1.000 - 24 1 6237

Calculations
ANc [mm2] ANc0 [mm2] y ec1,N y ec2,N y ed,N y cp,N Nb [kN]
175480 291600 1.000 1.000 0.876 1.000 159.049
Results
Vcp [kN] f concrete f Vcp [kN] Vua [kN]
167.604 0.700 117.323 31.491

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.7.5
Company: Page: 5
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 2/1/2018
E-Mail:

4.3 Concrete edge failure in direction x+

Vcbg = (AA ) y
Vc
Vc0
ec,V y ed,V y c,V y h,V y parallel,V Vb ACI 318-08 Eq. (D-22)
f Vcbg ≥ Vua ACI 318-08 Eq. (D-2)
AVc see ACI 318-08, Part D.6.2.1, Fig. RD.6.2.1(b)
AVc0 = 4.5 c2a1 ACI 318-08 Eq. (D-23)

( )
1
y ec,V = 2e'v ≤ 1.0 ACI 318-08 Eq. (D-26)
1+
3ca1
y ed,V = 0.7 + 0.3 (ca2
1.5ca1 )
≤ 1.0 ACI 318-08 Eq. (D-28)

y h,V = √
1.5ca1
ha
≥ 1.0 ACI 318-08 Eq. (D-29)

(( ) )
0.2
l 1.5
Vb = 7 e √da l √f'c ca1 ACI 318-08 Eq. (D-24)
da

Variables
ca1 [mm] ca2 [mm] ecV [mm] y c,V ha [mm]
158 300 140 1.000 230

le [mm] l da [mm] f'c [psi] y parallel,V


152 1.000 19 6237 1.000

Calculations
AVc [mm2] AVc0 [mm2] y ec,V y ed,V y h,V Vb [kN]
173420 112338 0.629 1.000 1.015 50.078
Results
Vcbg [kN] f concrete f Vcbg [kN] Vua [kN]
49.332 0.700 34.533 31.491

5 Combined tension and shear loads


bN bV z Utilization bN,V [%] Status
0.011 0.937 1.000 80 OK
bNV = (bN + bV) / 1.2 <= 1

6 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.).
This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is
assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum
required anchor plate thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the
rigid base plate assumption is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the
existing conditions and for plausibility! 
• Condition A applies when supplementary reinforcement is used. The Φ factor is increased for non-steel Design Strengths except Pullout
Strength and Pryout strength. Condition B applies when supplementary reinforcement is not used and for Pullout Strength and Pryout
Strength. Refer to your local standard.
• Checking the transfer of loads into the base material and the shear resistance are required in accordance with ACI 318 or the relevant
standard!

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.7.5
Company: Page: 6
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 2/1/2018
E-Mail:

7 Installation data
Anchor plate, steel: - Anchor type and diameter: Heavy Hex Head ASTM F 1554 GR. 36 3/4
Profile: no profile Installation torque: -
Hole diameter in the fixture: df = 21 mm Hole diameter in the base material: - mm
Plate thickness (input): 13 mm Hole depth in the base material: 180 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 205 mm
Drilling method: -
Cleaning: No cleaning of the drilled hole is required

y
-20

136 120

100
2

253
280

x
230

1
291
164

98 158

Coordinates Anchor mm
Anchor x y c-x c+x c-y c+y
1 -38 -127 - 158 355 580
2 -38 153 - 158 635 300

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.7.5
Company: Page: 7
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 2/1/2018
E-Mail:

8 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted
prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the
data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be
put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly
with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an
aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or
suitability for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!