Académique Documents
Professionnel Documents
Culture Documents
ET DE L’ESPACE SOUTERRAIN
AFTES
Recommendations
Geometry, concrete,
formwork and concreting of
tunnel linings :
Construction defects
GT36R1A1 - Appendix 1
440_461RecoGT36uk_Mise en page 1 11/10/12 10:27 Page440
Text presented by A. MERCUSOT (CETU Tunnels Study Centre) Leader of Working Group (GT36)
and A. BOERI (ALTER) Assistant leader
This recommendation has been approved by the AFTES Technical Committee following a critical review by:
P. GOYET (RAZEL-BEC-FAYAT) - M. PRE (SETEC-TPI)
The recommendation N° GT36.R1A1 - “Geometry, concrete, formwork and concreting of tunnel linings” has been published in TES No 202 (July/August 2007).
L'AFTES recueillera avec intérêt toute suggestion relative à ce texte.
3 - Imperfections 451-
3.1 - Recessed joints between lining sections . . . . . . . . . . . . . .451
3.2 - Deformed lining . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .452
Foreword
Tunnels lined with concrete formed on site are subject to ageing and deve- phase of work in progress must be halted and the construction process
lopments that may endanger their stability, functions, safety and the required recommenced. Detailed analysis of the defective component must be
level of service. A certain number of defects are inevitably noted during or performed as a matter of urgency, in order to repair or demolish and rebuild
after tunnel construction. Moreover, depending on the age of the structure, for the safety of the structure and its users. If this defect is not made good,
construction methods and the passage of time, a wide variety of defects the principal sources of future faults are degradation of materials and
may be observed. In older, non-waterproofed tunnels, water inrush is often structures, the behaviour of the surrounding terrain and water action.
at the origin of other defects.
All reproduction, translation and adaptation of articles (partly or totally) are subject to copyrigth.
The following 3 terms have been taken from SETRA Document Reference F In the appendix to GT36 R1A1, 24 “construction defects” and 3 “progressive
9775 – Appendix 2: Quality Assurance Policies. defects” have been drawn up to define the best-known and most typical
defects.
• The term “Defect” is defined in general terms by ISO standard 8402-1994:
“non-fulfilment of a requirement or a reasonable expectation related to For each defect, the section is set out in the same way:
an intended use, including in relation to safety” - Definition
• The term “Anomaly” is defined in French standard NFX50-125 (1995) as - Usual symptoms after concreting
follows: “The discrepancy between the actual and expected situation” - Interpretation
• The term “Risk” is defined as a potential, more or less foreseeable - Precautions to be taken during construction
danger - External inspection
- Repair
However, the term “Fault” has no official definition.
Any diagnosis of the state of the structure or any part affected by the defect
B/ Particular terminology relating to formwork lining of tunnels detected must be able to supply answers to the following key questions in
and classification of defects very short order, so as to decide whether or not to halt construction works:
- what happened?
In this document, an appendix to Recommendation GT36 R1F1, the - what are the reasons for the defect?
term “Construction Defect” has been chosen, broken down into three - had the construction process and the quality of materials used been
sub-categories: validated?
- is the defect liable to develop?
• Severe construction defects: Faults detected immediately during - how urgently is action required?
formwork, concreting or falsework striking affecting part of a structure or a - what work must be done immediately?
component thereof. Such faults may develop gradually or suddenly. The
M
TUNNELS ET ESPACE SOUTERRAIN - n°233 - Septembre/Octobre 2012 441
440_461RecoGT36uk_Mise en page 1 11/10/12 10:27 Page442
1 - Faults-
risk.
The non-reinforced ring is badly cracked and fails to hold up. Some parts of
the section may collapse immediately on formwork striking.
The reinforced ring is not cracked, appears stable and holds up on formwork
striking, but is much thinner than it should be. The defect may develop into a
major risk to the structure.
this appearance. This crack is a construction-related fault and constitutes a zone must be repaired.
major risk to the structure.
1.2.6 - Repair
1.2.2 - Usual symptoms after formwork striking
The defective area may sometimes have to be completely demolished and
The break is often located on one side of the profile only (haunch) or at the rebuilt using properly designed reinforcements. The main section formwork
crown. Several interlocking curved shapes are sometimes visible (crack width: may be used. If demolition can be avoided, injection to seal cracking may be
0.5-2mm). envisaged.
The more recent the structure (in most cases, since 1980) the clearer the
outline and sides of the curved shape.
This type of cracking is non-existent or unclear in pre-1980 structures.
1.2.3 - Interpretation
When the formwork is set up and adjusted on the fresh concrete of the
preceding ring, not filled on contact grouting, excess stress on the crown leads
to major cracking of the lining of this section.
Moreover, if the transverse profile of the rear end of the formwork has a very Dual curved cracking at the crown Curved crack at the haunch on section N-1
different shape from the front end of the machine, due to the major vertical at the end of section N-1. (crack width: 2-3mm).
Cracking when formwork was installed
stress at the crown and on the haunches, the end of the section may crack on section N.
(sometimes referred to as being broken) in a number of places,
In general, this defect does not occur in reinforced rings. WRONG
1.2.4 - Precautions to be taken during construction RING N RING N-1
Modern formwork machines are increasingly rigid and fitted with powerful
FLEXIBLE JOINT
rams, so care must be taken when using them:
• minimise reactions to the pressure of formwork by using pressure limiters, ANGLE BAR
• lock skirting (formwork side wall panels) without forcing, but ensuring
FORMWORK
Formwork in contact with
surfaces in contact with the foundations are watertight, section N-1 and stress
• eliminate direct contact of formwork with fresh sections (especially at the resulting in the curved crack.
crown and haunches) and use a flexible joint system round the entire peri-
meter of the rear end of the machine, RING N JOINT BETWEEN FORMWORK
AND GROOVE
• fix a steel profile (often beak-shaped) on the front end of the formwork to
define the rework groove between sections, RING N-1
• fix a semi-rigid joint on the front end of the machine to preserve the groove
between sections previously formed by the profile at the end of the form-
FLEXIBLE JOINT
work,
• use an asymmetrical reworking profile and a flexible joint to the rear of the
ANGLE BAR
formwork when there is a small radius curve alignment,
• during training, the shift foreman must brief personnel on the importance of FORMWORK
accuracy when formwork is brought up and located. Detail of joint between sections and the angle bar at the rear
of formwork with seal.
M
TUNNELS ET ESPACE SOUTERRAIN - n°233 - Septembre/Octobre 2012 443
440_461RecoGT36uk_Mise en page 1 11/10/12 10:27 Page444
FACING
FORMWORK
1.3.1 - Definition
Clear vertical or oblique cracking of foundations. Vertical cracking of the side ledge (lining foundation).
Running lengthwise along a section, the failure crack is located beneath the
reworking between the foundation and the bottom of the formwork. The edges
of the crack may be offset.
1.3.3 - Interpretation
The number of anchor points for the membrane should be adjusted depending
on the shape of the surface (overbreak and underbreak); in reinforced areas
and adjacent to the facing, there must be mechanical protection of the water-
All reproduction, translation and adaptation of articles (partly or totally) are subject to copyrigth.
proofing membrane.
In the event of the layer being perforated during manoeuvring of the concrete
pump boom, ahead of formwork (known defects), the repair must be carried
out quickly.
Formwork must be manoeuvred and located at slow speed and with due care.
Concreting pipes and vibrating rods must be handled with due care and Cracks and weeping at the crown.
attention.
Any anomaly, regardless of its origin, must be reported immediately.
1.5 - Waterproofing membrane fold in concrete
Prior training of all teams is indispensable.
1.5.1 - Definition
1.4.5 - External inspection
Part of the waterproofing membrane is trapped within the lining concrete. This
The membrane must be examined very closely on acceptance of waterproofing, is referred to as a fold.
particularly the sealing; proper inspection must take place when moving form-
work and during concreting manoeuvres. 1.5.2 - Usual symptoms after formwork striking
1.4.6 - Repair The concrete lining is cracked, the area sounds hollow and the membrane fold
is visible or close to the inward facing surface of the lining.
The membrane must be repaired before concreting the section. If there are a
large number of defects in a single section, the formwork must be moved to 1.5.3 - Interpretation
allow sufficient room for repair work to be carried out.
If concreting has commenced or been completed and repair of the membrane The membrane is not fixed firmly enough to the supporting surface. During
is no longer possible, the affected area must be accurately identified and sub- concreting, the ‘floating’ membrane becomes trapped inside the concrete, but
sequent injection carried out if possible. is not perforated or torn.
If the hole in the membrane is thought to be very large and injection is not
possible, the identified area must be demolished and the perforated membrane 1.5.4 - Precautions to be taken during construction
repaired. The demolished section must be reinforced and concreted (using the
same lining formula) using formwork, not shotcreting. The number of anchor points for the membrane should be adjusted depending
on the shape of the surface (overbreak and underbreak). Particular monitoring
of concreting in areas with overbreak and underbreak is mandatory. If the
membrane starts to get folded into the concrete, concreting must be halted
and the membrane properly fixed to the surface.
1.5.6 - Repair
M
TUNNELS ET ESPACE SOUTERRAIN - n°233 - Septembre/Octobre 2012 445
440_461RecoGT36uk_Mise en page 1 11/10/12 10:27 Page446
protecting the inward facing surface of the membrane, then placing reinforcement and concrete (shotcreting or formwork).
SUPPORTING SURFACE
(SOIL/RETAINING WALL)
CONCRETE RING
MEMBRANE FOLD
All reproduction, translation and adaptation of articles (partly or totally) are subject to copyrigth.
Folded membrane just beneath lining. Slack membrane liable to result in folds Membrane anchor points tear off, fold forms during concreting.
becoming trapped in the concrete.
2 - Poor workmanship-
cient pump power, concrete is too thick, poorly distributed (one pipe is not
2.1 - Air gap between the waterproofing membrane
enough to fill the crown for the entire length of the section), no viewing window
and the support or between the lining and
in the facing, trapped air, etc.
the membrane
Final grouting of the ring at the end of filling has not been properly completed: Gap between the waterproofing membrane and the support surface or between
an air gap is left between the waterproofing membrane and the support or the lining and the membrane
between the lining and the membrane. The membrane must be pressed against the support, increasing anchor density
if necessary, in particular in the event of overbreak.
2.1.2 - Usual symptoms after formwork striking The membrane must never be stretched between two protrusions either side
of a gap.
Concrete sounds hollow with a thin lining, is thinner than the nominal thickness, Concreting must be carried out working upwards, so that air can escape via
and has a clear cavity above it, or a discontinuity close to the inside surface. the facing.
Cavities are encountered most frequently at the crown. They are visible from Sliding concreting pipes, with thrust jacks and shears, must be used. Applying
the section facing (end formwork) during construction or during inspection concrete to the roof should start from the lowest pipe adjacent to the N-1 ring
(hammer test or radar). and end with the highest pipe, towards the facing. This allows air to escape
In recent tunnels, they tend to disappear without incident. via the facing.
If any cavities remain adjacent to the facing, they will be filled when section
2.1.3 - Interpretation N+1 is concreted.
In the event of major overbreak, pipes and vents must be installed to allow the
Gap between the waterproofing membrane and the supporting surface filling of section N+1 to be carried out in two stages.
In lower areas, this is most probably due to the membrane shifting or excess Deformation sensors and mechanical gauges may be used during grouting.
tension. This may halt concreting, but is a rare occurrence. In addition, grouting must be closely monitored through the facing. Finishing
At the crown, anchor points for a membrane stretched too tightly may give vibration treatment must be closely monitored and kept to a minimum.
way during concreting, without the membrane tearing. This leaves the mem-
brane resting on the formwork or rebar, particularly at the haunches or roof. 2.1.5 - External inspection
The pressure of the concrete is not enough to push the membrane back onto
the support surface, leaving an air gap that prevents the lining achieving nomi- • Prior to concreting: The installation of the membrane must be checked,
nal thickness. as must the position and fixing of rebar and any inserts.
In some cases, a large number of small air pockets remain trapped between • During concreting: It should be ensured that the membrane behaves
the membrane and the support, without the anchor points giving way. normally; coating of embedded elements must be monitored.
• During grouting: Grouting must be monitored from the facing.
Gap between the lining and waterproofing membrane • After concreting: In case of doubt, geo-radar may be used to locate and
This occurs only at the crown, and is probably due to defective filling: insuffi- quantify the size of any gaps.
If the lining thickness is not less than nominal, no injection between the Aggregate segregation is visible on the lining; the concrete does not bind well.
concrete and membrane is required. This is all the more the case if the rings This defect is the result of poor vibrating or poor formulation (segregation
were not fitted with grouting pipes during construction of the tunnel (in which occurs due to a lack of fines and/or inappropriate plasticity).
case there is a definite risk of perforating the membrane).
2.2.4 - Precautions to be taken during construction
If the lining is too thin, the area with cavities and the positioning of the mem-
brane (resting on the lining or fixed to the support) must be clearly identified. During construction:
All reproduction, translation and adaptation of articles (partly or totally) are subject to copyrigth.
In both cases, caution must be taken when drilling through the lining in order - adjust the consistency of the concrete,
not to perforate the membrane. Injection (grouting or micro mortar depending - internal vibrating is recommended,
on quantities) should be carried out, keeping the quantities estimated during - avoid vibrating the parts of the formwork that are in contact with the previous
external inspection (and pressure on the lining) to a minimum. section,
- vibrate as close as possible to the formwork skin and not its structural
MEMBRANE SUPPORTING SURFACE
(TERRAIN/RETAINING WALL) elements,
AIR GAPS - reduce the height from which concrete is poured,
- increase the quantity of fines and/or sand in the formulation.
Inspection must:
- ensure deliveries take place regularly,
LINING - check concrete consistency as it leaves the mixer,
Air gap between the waterproofing complex and the lining. - reject concrete that is too firm,
- monitor internal vibrating.
STRETCHED
MEMBRANE
AIR GAPS SUPPORTING SURFACE 2.2.6 - Repair
(TERRAIN/RETAINING WALL)
Repair or rendering of superficial defects is possible if they are minimal, using
mortar, resin, adhesive mortar, etc.
In other cases, highly localised rodding of the lining may be required.
Section N (left):
Honeycombed lining.
LINING
Section N-1 (right):
Air gap between the waterproofing complex and the support on the soil side. Properly vibrated lining.
2.2 - Honeycombing
2.2.1 - Definition
This defect affects the whole of the concrete, not just the surface. The
aggregate is visible.
This was formerly a very common defect, particularly for strips between
batches (filled in between mixer loads) and subsidence, and can sometimes
lead to local weakening of the lining. Honeycombing
It is still to be found, less extensively, at the edges of joints between ring on side walls.
segments.
M
TUNNELS ET ESPACE SOUTERRAIN - n°233 - Septembre/Octobre 2012 447
440_461RecoGT36uk_Mise en page 1 11/10/12 10:27 Page448
Thin strips of laitance covering the area where the formwork rests on the Unlike shrinkage cracks and structural cracks, splits are localised, short and
preceding ring segment (and foundations) are often described as ‘dripping’ open: there are often a small number oriented in the same direction, either
or ‘run-out’. crosswise or horizontally.
2.3.2 - Usual symptoms after formwork striking 2.4.2 - Usual symptoms after formwork striking
All reproduction, translation and adaptation of articles (partly or totally) are subject to copyrigth.
This is quite rare and highly localised. The patches of laitance may be sticky. They are not linked to any particular fault and are observed between batches
with differing consistencies. This defect is increasingly rare.
2.3.3 - Interpretation
2.4.3 - Interpretation
This local defect is the result of the formwork not being watertight and/or using
concrete that is too fluid (‘self-consolidating’ concrete) and/or using formwork The concrete is too consistent or “stiff”.
panels that are too flexible. Vibrating has been poorly controlled if the concrete starts setting too quickly
This leakage is not solely an issue of aesthetics: it can also affect the durability or if there has been no vibrating where the batches join.
of the concrete (sometimes leading to a risk of corrosion in reinforced areas) The consistency of the concrete varies between batches.
due to local alterations in the concrete formula (loss of cement and water). Provided they are not too deep, splits do not endanger the structure.
2.3.4 - Precautions to be taken during construction 2.4.4 - Precautions to be taken during construction
Effective waterproofing where the formwork comes into contact with the Recommendations:
previous section should be designed. - concrete of the same consistency must be supplied at a regular rhythm,
Similarly, complete watertightness of the facing and joints between the - vibrating must be properly controlled.
formwork and any inserts, such as forms for recesses, lighting units, etc. must
be ensured. 2.4.5 - External inspection
2.3.5 - External inspection Inspection must check concrete plasticity prior to concreting operations.
Contact points, watertightness between the machine and the structure to be 2.4.6 - Repair
built and the firmness of the formwork must all be checked prior to the com-
mencement of concreting. Splits may be injected with resin, followed by surface rendering, but this may
adversely affect the appearance of the lining.
2.3.6 - Repair
Crosswise splits • ensure rebar layers do not shift during concreting (concreting spacers
(width ~ 1 mm -
length > 50 cm).
properly fixed to reinforcements),
• protecting rebar awaiting concreting,
• use appropriate spacers,
• use an appropriate number of rebar spacers,
• clean and oil the formwork surface properly.
2.5.6 - Repair
2.5.1 - Definition
This type of defect is rare and usually occurs only in reinforced sections at the
tunnel head. Chips of concrete burst off. If the defect is not repaired, the fault Spalling on rebar.
progresses rapidly over time.
2.5.3 - Interpretation
Spalling
If the rebar is visible or poorly coated, the strength of the lining may be affected around rebar.
and thus the durability of the structure. This may be aggravated by pollution
and the presence of chlorides at the tunnel heads (such as de-icing salts). In
addition, damp penetrates from the inner surface (or even from the soil if the
lining is not waterproof) as far as the outer rebar located in the carbonated
part of the concrete.
Recommendations:
• check the design calculations (adequate coating),
• check that the rebar layers are properly coated on the inward side and at all Formwork removal: chip
points of transverse profiles, burst round rebar.
M
TUNNELS ET ESPACE SOUTERRAIN - n°233 - Septembre/Octobre 2012 449
440_461RecoGT36uk_Mise en page 1 11/10/12 10:27 Page450
2.6.1 - Definition The profile may be reconstituted using resin mortar if the rebar has not shifted.
Supports for slabwork (ventilation, traffic, service) may take the form of occa-
B/ Continuous supports and corbels
sional consoles (corbels), continuous or semi-continuous consoles (on
beams) or notches at intervals determined by the project in question. 2.6.7 - Interpretation
2.6.2 - Usual symptoms after formwork striking When the formwork shutters are removed from the lining, the corbel supports
All reproduction, translation and adaptation of articles (partly or totally) are subject to copyrigth.
The base of the notch can be tapped with a hammer to check the corners The affected element may be repaired using resin mortar, but care should
are sound; a rule and spirit level can be used to check the geometry of the be taken not to impede the ‘knee-joint’ function between the slab and the
support. supports.
LINING SLAB OR
BEAM
BREAK OF
THE EDGE
All reproduction, translation and adaptation of articles (partly or totally) are subject to copyrigth.
Notch spalling.
LINING
PREFAB OR
CAST SLAB
BREAK OF
THE EDGE
Spalling of continuous console beam forming one piece with the lining. Cross-sectional diagram of console beam.
3 - Imperfections-
3.1.1 - Definition The formwork or the end facing have not been cleaned properly.
Rubber or steel moulds for recesses for a recess joint and fixed onto the
This defect (often systematic) occurs at the edges of transverse joints (form front and rear ends of the formwork may shift if they are not held properly
for aesthetic purposes) between lining sections (groove) where there is a chan- in place. If this occurs, the joint is no longer at right angles to the line of the
nel between the two sections. tunnel.
Using a pipe that is too supple, often bonded to the formwork, may result in
3.1.2 - Usual symptoms after formwork striking defects during removal of formwork if the concrete is too fresh, especially
if the concrete sticks to the rubber.
The groove edges are generally fragile and tend to break during formwork remo- Use of a steel mould welded to the formwork can also result in defects during
val or over time; this is easy to see. They create a subsequent risk of small removal of the formwork and the joint mould, especially if the profile of the
pieces of concrete falling off if they have not already done so during striking. joint makes removal difficult (insufficient clearance).
Most of the time, these joints suffer only minor defects, but sometimes these Use of a steel mould bolted to the formwork may also lead to defects if
occur on long sections of wall. Viewed crosswise, the recess is not always removal takes place too soon after and if there is not enough clearance for
straight. the joint profile (trapeze shapes are recommended).
M
TUNNELS ET ESPACE SOUTERRAIN - n°233 - Septembre/Octobre 2012 451
440_461RecoGT36uk_Mise en page 1 11/10/12 10:27 Page452
Poorly executed vibrating and local segregation of concrete around joints may 3.2 - Deformed lining
lead to honeycombing.
3.2.1 - Definition
3.1.4 - Precautions to be taken during construction
Deformations of the formwork skin most often result in lumps or hollows in
If a rubber mould is used, it must be stiff enough and properly fixed to the the concrete on the inner side.
formwork (screwed on from the inward facing side of the formwork). This
profile can remain in contact with the concrete for several days before the 3.2.2 - Usual symptoms after formwork striking
mould is removed, whether it is located in front of the formwork or to the rear.
All reproduction, translation and adaptation of articles (partly or totally) are subject to copyrigth.
These lumps used to appear in each ring segment and were clearly visible on
If a welded or screwed trapeze-shaped steel profile is used on the formwork, the side walls, less so at the crown (sometimes known as “paw marks”). Nowa-
this should be located at the front end of the formwork on the facing side, to days, since the formwork used is heavier, with sheeting thicker than 8 mm,
make it easier to remove formwork (when striking, the formwork machine deformations are far more occasional and affect only one or a few rings at the
moves first vertically, then horizontally). most: in most cases, repair of the form is required.
3.1.5 - External inspection Much larger, significant surface deformations may also occur, due to overpres-
sure during concrete pumping (large bumps): overpressure during grouting is
Inspectors must: a frequent cause of this.
• check the installation of joints (moulds) and facings,
• check removal of the facing and the formwork, Lastly, some very large deformations of formwork (sometimes related to poor
• ensure care is taken when removing the rubber moulds subsequently, location of the machine) may occur during concreting.
• avoid premature rendering, which may entail further risks of instability.
3.2.3 - Interpretation
3.1.6 - Repair
These defects may be caused by skin weakness due to insufficient thickness
Ready-to-use synthetic binders are more resistant than hydraulic mortar. or insufficient formwork reinforcements.
Rendering can be carried out using carefully selected ready-to-use mortar Concrete left sticking to the forms is removed using a hammer, leading to the
resin (adhesive mortar) and careful preparation of the surface using a rigid sheeting sustaining dents and deformations.
mould. These defects do not affect the solidity of the structure unless the resulting
cross-sectional profile is less than the required width.
SECTION N Form skins must use sheet metal that is at least 8 mm thick.
Formwork must be strong, properly located and solidly anchored.
The number of concreting pipes, properly located, must be increased to reduce
SECTION N-1 the risk of overpressure during grouting.
Formwork removed too quickly between sections: groove edges are pulled off. Construction should correspond to the design calculations.
Deformation of skins must not be tolerated.
3.2.6 - Repair
3.3.6 - Repair
All reproduction, translation and adaptation of articles (partly or totally) are subject to copyrigth.
Very local grinding of the offset concrete may be possible but is not desirable.
Lengthwise deformation of the formwork skin at the crown.
OFFSET
Side wall
deformation.
3.3.1 - Definition
One of the edges (sides) of the transverse joint is not aligned with the edge of SECTION N-1
3.3.3 - Interpretation A highly visible pattern reproduces the rebar layer closest to the inner surface
to some degree.
The most widespread cause is incorrect alignment and adjustment of form-
work, especially at curves. The defect is often due to formwork that is poorly 3.4.2 - Usual symptoms after formwork striking
constructed and/or too light and prone to distortion. This results in the front
and rear of the formwork machine having differing cross-sectional profiles. This defect is very common for reinforced rings even when concrete resulting
in a very good surface appearance is used.
3.3.4 - Precautions to be taken during construction
3.4.3 - Interpretation
Adjustment measures for the formwork (using screws or jacks) must be made
more accurate (to the nearest millimetre). The most frequent explanations are the following:
The length of the formwork must be appropriate for the tunnel axis. • insufficient coating of rebar
M
TUNNELS ET ESPACE SOUTERRAIN - n°233 - Septembre/Octobre 2012 453
440_461RecoGT36uk_Mise en page 1 11/10/12 10:27 Page454
• spacers have not stayed in place: the layer of rebar may have shifted slightly,
• wall effect between the rebar and the formwork,
• resonance of rebar during vibrating (rods or formwork vibrators come into
contact with the rebar), which may lead to fine, local segregation,
• formwork release oil splashes onto the rebar,
• poorly executed concrete vibrating.
If the rebar is properly coated, the pattern will have no impact on the structure. 3.5.2 - Usual symptoms after formwork striking
The appearance may be improved by painting.
This defect is usually located on side walls or at the start of the crown.
If not (poor coating and serious structural consequences), demolition and local
or complete reconstruction of the section may be required. 3.5.3 - Interpretation
Recommendations:
• use a water-reducing additive,
• increase the dose of fines,
• use a slightly acid formwork release product,
• observe vibrating procedures.
3.5.6 - Repair
that the aggregate is not likely to react with alkalis, that the cement selected
hydrates gradually and that concrete is manufactured in a uniform
manner.
In terms of pouring the concrete behind the formwork, parts of the structure
with different thicknesses and cross-sections should be filled with the same
batch of concrete; the concrete setting time should be increased and a
curing procedure used.
3.6.6 - Repair
3.6 - Hydraulic and thermal shrinkage cracks
Shrinkage cracks do not need to be repaired unless the crack is too large and
3.6.1 - Definition liable to affect durability of the tunnel by leading to waterproofing defects
and/or rebar corrosion.
This type of cracking is a normal consequence of concrete maturing. The crack In the latter case, the cracks may be injected.
is a mechanical break in material between two independent parts. Slow drying
may lead to a decrease in volume or swelling (relative humidity and tempe-
rature levels).
It may be considered as a defect if it occurs abnormally frequently within a
single ring, if it occurs repeatedly on several rings or if the cracks are too
large.
M
TUNNELS ET ESPACE SOUTERRAIN - n°233 - Septembre/Octobre 2012 455
440_461RecoGT36uk_Mise en page 1 11/10/12 10:27 Page456
3.7.3 - Interpretation
The main cause is formwork overhang for the bottom half: air bubbles are
trapped against the formwork skin and cannot escape to the surface. Poor or
inadequate concrete vibrating may be another probable cause.
Formwork release oil must be chosen carefully, with the possible addition of Reference scale for 7 levels of bug hole.
All reproduction, translation and adaptation of articles (partly or totally) are subject to copyrigth.
a tensioactive agent.
The concreting speed must be constant, and vibration carried out continuously
for overhanging side walls.
3.8 - Black spots
Concrete must not be poured directly in contact with the formwork.
There should be minimal, limited vibrating of formwork adjacent to side 3.8.1 - Definition
walls. Vibrating rods should be used to densify the concrete (volume vibra-
tion). Black spots appear on the inner surface of the concrete (varying shades of
grey) and often on irregularly shaped sections of lining.
3.7.5 - External inspection
3.8.2 - Usual symptoms after formwork striking
Concrete formulation must be checked and must not be altered if the result is
satisfactory (especially the quantity of sand and the selected consistency). They may appear at any point on the ring and on the underside of ventilation
The concreting plan (distribution, filling, vibration) must be regularly slabs.
checked. They may also be found in the centre of sections.
No subsequent treatment. For surfaces to be painted, plan for appropriate Some parts of the lining and slabs may have a higher dose of binder and be
surface preparation: skim coating the walls with paste and then painting will less hydrated than others, with less porous paste. These sections have a ‘satin’
get rid of most bug holes. or ‘glossy’ appearance.
Untreated lining with bug holes. Increase the dose of fines and the mixing time during concrete manufacture
to prevent segregation.
Formwork must be cleaned prior to the release product being applied.
Rebar must not be oily.
Concrete layers that are hardening must not be re-vibrated.
3.9.6 - Repair
3.10.1 - Definition
Vertical black marks
around a concreting pipe.
Brown or black traces of rust on linings become highly visible a few days after
formwork is removed from the lining.
These defects are observed more particularly on the first sections of lining
if the rebar has been insufficiently covered, beneath formed elements and
sometimes in areas affected by honeycombing.
3.9 - Efflorescence
3.10.3 - Interpretation
3.9.1 - Definition
The rust traces are iron hydroxide marks from corrosion of rebar, the formwork
Efflorescence refers to white calcite (calcium carbonate) deposits indicating skin, rebar ties, or even concrete aggregate containing iron sulphides.
thin cracks or local segregation.
3.10.4 - Precautions to be taken during construction
3.9.2 - Usual symptoms after formwork striking
Recommendations:
Efflorescence occurs when there is water on the surface of the concrete. - varnish the formwork skin,
It is rare and faint, and may appear even when there is an external water- - carefully clean the skin after each use (each section),
proofing membrane. - store reinforcements and ties in a dry place,
- sand the formwork machine skin to remove rust.
3.9.3 - Interpretation
3.10.5 - External inspection
Calcium carbonate is precipitated at the outlet of fine capillaries in the concrete,
as the result of high levels of water evaporation. This phenomenon may last Check:
several days. - cleaning of rebar and formwork,
- chemical makeup of aggregate,
3.9.4 - Precautions to be taken during construction - cleanliness of formwork (in particular, rust),
- storing rebar properly.
Particular recommendations:
• spray diluted hydrofluoric acid (10%) immediately after formwork striking,
M
TUNNELS ET ESPACE SOUTERRAIN - n°233 - Septembre/Octobre 2012 457
440_461RecoGT36uk_Mise en page 1 11/10/12 10:27 Page458
The concrete formulation must be confirmed and the concreting and formwork
striking procedure checked.
3.11.6 - Repair
No repairs are required. The phenomenon can be dealt with by applying a coat
of paint.
Traces of rust in
the tunnel.
3.11.1 - Definition
Macro surface cracking.
Surface cracking is a superficial reaction of the coating involving a chemical
reaction between certain types of aggregate and alkalis in the cement.
3.12 - Aggregate transparency
The surface of the concrete reveals a series of micro-cracks with varying Patching is where large aggregates appear in varying degrees of colour
degrees of density. contrast to the base concrete.
The most likely causes are as follows: This phenomenon occurs on hardened concrete, some time after formwork
• concrete quality, striking.
The probable cause is the use of gravel with higher density than other concrete A number of different causes are possible:
ingredients: angular or non-alluvial gravel, for instance. • impurities in the concrete,
• badly cleaned formwork,
3.12.4 - Precautions to be taken during construction • re-use of formwork without it being inspected,
• concrete poured from too great a height,
This phenomenon is minimised if rolled gravel is used. • change in the origin of concrete ingredients during construction,
If crushed aggregates are used: • concrete compacted too tightly.
All reproduction, translation and adaptation of articles (partly or totally) are subject to copyrigth.
Applying paint or veneer is possible: on no account should sanding be carried Check for any changes in origin of the concrete ingredients.
out.
3.13.6 - Repair
3.13 - Changes in hue
The concrete may be tapped locally if the marks are very local.
3.13.1 - Definition Some marks may be removed with a cleaning agent or dilute acid solutions.
Paint may also be applied.
Changes in hue involve large adjacent areas with differing colours.
4 - Other defects-
Three specific defects related not to lining construction but to changes over
time are also discussed in this appendix. • concrete is chemically attacked by aggressive external or internal water,
• leaching,
• frost,
4.1 - Decomposition of concrete
• blocked drain,
4.1.1 - Definition • bursting after injection.
Very advanced destruction of concrete for all or part of a lining section. Aggregates gradually separate from the binder, which becomes “loose”.
The defect may also appear, and begin, in concrete covering drainage or
4.1.2 - Interpretation equipment pipes.
If the concrete is not compact enough, this may be an aggravating factor in
Possible causes include: some cases.
• poor concrete formulation, This defect is ranked as a “Fault”.
M
TUNNELS ET ESPACE SOUTERRAIN - n°233 - Septembre/Octobre 2012 459
440_461RecoGT36uk_Mise en page 1 11/10/12 10:27 Page460
Reconstruction of the defective area or the entire ring is advised. The lining has not been waterproofed or the waterproof membrane has been
perforated: crusts of calcite or sulphides from dissolved salts appear either
from the surrounding terrain or due to decarbonation of the concrete.
4.2 - Shear crack in a lining section
The lining has been waterproofed: concretions may be coloured by iron oxide.
4.2.1 - Definition This may be due to corrosion of the steel rebar at the end of reinforced
sections.
The section is cracked and the panels skewed and the edges of the crack have This defect is classified as ‘Poor workmanship’
All reproduction, translation and adaptation of articles (partly or totally) are subject to copyrigth.
shifted.
Slip: Movement tangential to the lining and parallel to the crack, mismatching: 4.3.3 - Possible repair
Relative movement perpendicular to the surface of the lining or opening: Move-
ment along the surface perpendicular to the crack plane, or a combination of Scraping the defective parts at the end of sections and applying acid may get
all three types of movement. rid of most of the colour marks.
4.2.2 - Interpretation If the lining is not waterproof, injection between sections and between the sec-
tions and the support wall or terrain is possible.
Possible causes: If the lining is waterproofed, the hole in the membrane is thought to be very
• soil thrust, large and injection is not possible, the identified area must be demolished and
• swelling, the perforated membrane repaired. The demolished section must be reinforced
• convergences, and concreted (using the same lining formula) using formwork, not shotcre-
• poorly stabilised foundation soil, ting.
• non-reinforced foundations, Irrespective of whether the lining is waterproofed, oxidised rebar must be
• poor concrete formulation, treated: passivation of visible rebar followed by resin mortar rendering. t
• various types of concrete.
This defect is ranked as a ‘Fault’
4.3 - Concretions
4.3.1 - Definition
These defects are located between the transverse ends of the lining sections
or sometimes in cracked sections, with slight spalling and white, red or brown
marks. Concretions on the crown.
References
• Tunnels Study Centre: Guide du gestionnaire de tunnel routier, CETU, November 1982.
• LCPC Technical guide “Défauts d’aspect des parements en béton” - 1991
• AFTES GT14 Entretien et réparation des ouvrages souterrains - Catalogue des défauts apparents des tunnels (Maintenance and repair of underground structures:
catalogue of visible defects in tunnels)
• LPC Technical Guide, Défauts d’aspect des parements en béton, LCPC, 1991. Intended for use with regard to standard structures.
• PERA J., DEFFAYET M., CHAPEAU C., Domaine d’utilisation du béton non armé pour les revêtements de tunnel,
• Tunnels et ouvrages souterrains magazine, issue 103, 1991
• AGGOUN S. Étude du comportement du béton coffré non armé vis-à-vis de la fissuration – Application aux revêtements de tunnels, Thesis, INSA Lyon, 1992,
• Tunnels Study Centre: Dossier pilote des Tunnels, Civil Engineering section, CETU, July 1998.
• GRIMALDI G., RAHARINAIVO A. Vers une stratégie de réparation du béton armé dégradé, LPC Bulletin, issue 223, December 1999,
• LARIVE C., Quand le béton se met à gonfler, La Recherche, issue 319, April 1999. Economic issues
• CETU (Tunnels study centre): Le guide de l’inspection du génie civil des tunnels routiers, 2004
• Standard FD-P 18/503 – Qualité des parements fin des piédroits
• SETRA document, Reference F 9775
M
TUNNELS ET ESPACE SOUTERRAIN - n°233 - Septembre/Octobre 2012 461
www.aftes.asso.fr
All rights for reproduction or adaptation in whatever format are expressly reserved