Académique Documents
Professionnel Documents
Culture Documents
Jean NOËL
Report n° 0401
Author : Jean NOËL / web site : jnlog.com / mail : contact@jnlog.com Rev. 1.05 - July 2004 p. 1
CoDyBa - BESTEST Qualification
Abstract
The present report describes the BESTEST reference cases and the results obtained with CoDyBa
software.
CoDyBa is a software used to determinate the heat flows in a building. CoDyBa is specially oriented
toward optimisation of energy performance in buildings.
In order to validate this software, its results are compared to results given by other reference programs, on
some test cases defined in the international standard BESTEST (IEA 1995).
These tests treat many typical situations encountered in building construction. The geometry concerns a
heavyweight and a lightweight room located at Denver (USA). This room contains heating and cooling
systems in some cases. Cases with and without windows are treated. Sun shading is also introduced.
Detailed results are annual heating and cooling loads, peaks of heating and cooling loads. Extremes
reached values are given, when free temperature evolution is allowed.
A very good agreement is found : results are presented, which show that CoDyBa passed successfully
through qualification test cases.
Acknowledgements
The author is very grateful to Pr Jean-Jacques ROUX for the general assistance that he brought to him in
the realisation of this work.
Jean-Jacques ROUX
INSA de Lyon - Bât. Freyssinet
40 avenue des Arts
69100 Villeurbanne
France
Author : Jean NOËL / web site : jnlog.com / mail : contact@jnlog.com Rev. 1.05 - July 2004 p. 2
CoDyBa - BESTEST Qualification
Table of contents
I - INTRODUCTION......................................................................................................................................................................6
I - 1 - WHAT BESTEST IS .............................................................................................................................................................6
I - 2 - WHAT CODYBA IS ...............................................................................................................................................................6
II - BESTEST OVERVIEW...........................................................................................................................................................6
II - 1 - BACKGROUND ....................................................................................................................................................................6
II - 2 - SOME REMARKS ON VALIDATION METHODOLOGY ..............................................................................................................7
II - 3 - REFERENCE PROGRAMS LIST...............................................................................................................................................7
III - TESTS INPUT SPECIFICATIONS......................................................................................................................................8
III - 1 - TIME .................................................................................................................................................................................8
III - 2 - WEATHER DATA ................................................................................................................................................................8
III - 3 - GEOMETRY........................................................................................................................................................................9
III - 4 - MATERIALS .....................................................................................................................................................................10
III - 5 - SURFACES .......................................................................................................................................................................10
III - 5 - 1 - Walls .....................................................................................................................................................................10
III - 5 - 2 - Window .................................................................................................................................................................11
III - 5 - 3 - Convective surface coefficients .............................................................................................................................13
III - 6 - INFILTRATION AND INTERNAL LOAD ............................................................................................................................... 13
III - 6 - 1 - Infiltration .............................................................................................................................................................13
III - 6 - 2 - Internally generated heat ......................................................................................................................................13
III - 6 - 3 - Mechanical system ................................................................................................................................................14
IV - TESTS DESCRIPTION........................................................................................................................................................15
IV - 1 - GENERAL CASES DESCRIPTION ........................................................................................................................................15
IV - 2 - QUALIFICATION CASES DESCRIPTION ..............................................................................................................................15
IV - 3 - TEST CASES SUMMARY....................................................................................................................................................16
V - RESULTS ................................................................................................................................................................................17
V - 1 - CODYBA RESULTS IN TABULAR FORM .............................................................................................................................18
V - 1 - 1 - BESTEST and CoDyBa Results in tabular form .....................................................................................................18
V - 1 - 2 - BESTEST and CoDyBa Delta Results ....................................................................................................................19
V - 1 - 3 - BESTEST and CoDyBa Results (Standard/Commercial Version) ..........................................................................20
V - 2 - BESTEST QUALIFICATION CASES...................................................................................................................................21
V - 2 - 1 - BESTEST Qualification : Annual Incident Solar Radiation ...................................................................................21
V - 2 - 2 - BESTEST Qualification : Annual Transmitted Solrad Unshaded...........................................................................22
V - 2 - 3 - BESTEST Qualification : Annual Transmitted Solrad Shaded ...............................................................................22
V - 2 - 4 - BESTEST Qualification : Annual Transmissivity Coefficient of Windows .............................................................23
V - 2 - 5 - BESTEST Qualification : Annual Overhang and Fin Shading Coefficients ...........................................................23
V - 2 - 6 - BESTEST Qualification : Low Mass Building ........................................................................................................24
V - 2 - 7 - BESTEST Qualification : High Mass Building.......................................................................................................25
V - 2 - 8 - BESTEST Qualification : Free-Float Cases ...........................................................................................................26
V - 2 - 9 - BESTEST Qualification : Case 900FF ...................................................................................................................27
V - 2 - 10 - BESTEST Qualifications : Hourly Loads .............................................................................................................31
V - 2 - 11 - BESTEST Qualifications : Case 900FF Annual Hourly Temperature Frequency ...............................................32
V - 3 - BESTEST DIAGNOSTICS CASES ......................................................................................................................................33
VI - CONCLUSIONS ...................................................................................................................................................................34
VI - 1 - CONCLUSIONS .................................................................................................................................................................34
VI - 2 - FINAL CONCLUSION ........................................................................................................................................................34
VII - BIBLIOGRAPHY................................................................................................................................................................35
Author : Jean NOËL / web site : jnlog.com / mail : contact@jnlog.com Rev. 1.05 - July 2004 p. 3
CoDyBa - BESTEST Qualification
List of tables
Author : Jean NOËL / web site : jnlog.com / mail : contact@jnlog.com Rev. 1.05 - July 2004 p. 4
CoDyBa - BESTEST Qualification
Author : Jean NOËL / web site : jnlog.com / mail : contact@jnlog.com Rev. 1.05 - July 2004 p. 5
CoDyBa - BESTEST Qualification
I - Introduction
I - 1 - What BESTEST is
BESTEST (Building Energy Simulation TEST) is conducted by the International Energy Agency (IEA).
BESTEST [BR] is a benchmark for building energy simulation programs. It's a comparative testing
procedure for thermal building simulations applied to a simplified building envelope. These tests build
upon each other and permit the evaluation of a range of features including thermal mass, direct solar gain
windows, window-shading devices, generated heat, infiltration, deadband and setback thermostat control.
The tests are built to permit a diagnostic if the program fails. These tests start with a basic structure, which
is completed by adding windows, exterior shading, or by modifying the wall materials, etc.
I - 2 - What CoDyBa is
CoDyBa [CDB] is a software, jointly developed by the CETHIL (INSA-Lyon Thermal Center, [CET]) and
a freelance engineer [JNL], without any state help. It is aimed for design offices, teaching and research
organisms.
CoDyBa is a software used to determinate the heat flows in a building. It permits to estimate the instant
heating or cooling powers needed to maintain a given set-point, or to calculate the interior temperatures
when the heating or cooling system is insufficient. Humidity is treated in the same way.
The tool is aimed to conduct studies of heating and cooling strategy, air conditioning or ventilation options,
insulating materials to be installed. The room occupancy is included. CoDyBa does not permit the study of
the dynamic behaviour of a set of technological components : the main objective is to forecast the energy
consumption and temperature evolution range.
CoDyBa runs on classical PC. The building is described accurately and the building description is given by
the use of a graphical interface. CoDyBa is based on simply bricks assembled to form a complex building
with its equipment. The assembly is conducted in a form to minimise data size and calculation time. The
physical models of CodyBa are those commonly admitted, but numerical algorithms are specific.
II - BESTEST Overview
II - 1 - Background
Numerous software programs are available to simulate energy performance in buildings. But these
programs often produce divergent results.
BESTEST was created to systematically compare whole-building energy software programs and
diagnose the sources of prediction differences. Field trials of the method were conducted with a
number of selected "reference" programs that represent the best state-of-the-art detailed simulation
capability available in United States and Europe. These included BLAST, DOE2, ESP, SERIRES,
S3PAS, TASE and TRNSYS. Also, several programs were tested later (CLIM2000, DEROB).
The method consists of a series of carefully specified test case buildings that progress from the
extremely simple to the relatively realistic. The more realistic cases test the ability of the programs to
model effects such as thermal mass, direct solar gain windows, window-shading devices, internally
generated heat, infiltration, sun-spaces, earth coupling and deadband and setback thermostat control.
The collective experience of the members of the BESTEST experts group has shown that when a
program exhibits major disagreement with the reference programs, the underlying cause is usually a
bug, faulty algorithm, or documentation problem.
The field trials revealed a large amount of disagreement among the participating programs. The
differences ranged from approximately 20 % to about 66 %.
Author : Jean NOËL / web site : jnlog.com / mail : contact@jnlog.com Rev. 1.05 - July 2004 p. 6
CoDyBa - BESTEST Qualification
An advantage of BESTEST is that a program is examined over a broad range of parametric interactions
based on a variety of output types, minimising the possibility for concealment of problems by
compensating errors. During the project, some bugs were found in the 8 building energy simulation
programs (and corrected), and some of the bugs may well have been present for many years. This fact
shows the interest of using BESTEST to validate simulation programs.
The reference applications are listed in the next table (see BESTEST Report Table 2-1 and Table 2-3) :
Author : Jean NOËL / web site : jnlog.com / mail : contact@jnlog.com Rev. 1.05 - July 2004 p. 7
CoDyBa - BESTEST Qualification
III - 1 - Time
All references to time in this specification are to solar time, and assume that hour 1 = the interval from
midnight to 1 a.m.
The weather characteristics are summarised in Table B (see BESTEST report Table 1-3) :
The sky model used in CoDyBa supposes that the diffuse radiation density is constant for all angles
(isotropic sky model for diffuse insulation).
The meteorological file gave no information about the sky temperature, so the following relation is applied:
TSky = TExterior
Author : Jean NOËL / web site : jnlog.com / mail : contact@jnlog.com Rev. 1.05 - July 2004 p. 8
CoDyBa - BESTEST Qualification
III - 3 - Geometry
The basic geometry of the test case building is a rectangular single zone with no interior partitions, with
one or two window facing the south (see BESTEST Report Figures 1-3, 1-4, 1-5, 1-6) :
8m 2.7 m
6m
0.5 m
3m
1m 0.5 m
2m
0.2 m
1m
0.5 m
1m
3m
BESTEST recommend to include the shading effect on adjacent opaque surface, and also modifications to
long wave interchange due to the shading device. But CoDyBa has not these capabilities.
Author : Jean NOËL / web site : jnlog.com / mail : contact@jnlog.com Rev. 1.05 - July 2004 p. 9
CoDyBa - BESTEST Qualification
III - 4 - Materials
III - 5 - Surfaces
III - 5 - 1 - Walls
The next table summarises the elements of surfaces, from inside to outside (see BESTEST Report, Table 1-
15 to 1-18) :
U R
Thickness
Cases Surface Material (W/m².K) (m².K/W)
(mm)
Air-air Surf-surf Air-air Surf-surf
Plasterboard 12
Wall Fibreglass quilt 66 0.514 0.559 1.944 1.789
Wood siding 9
Plasterboard 10
lightweight
Roof Fibreglass quilt 111.8 0.318 0.334 3.147 2.992
Roof deck 19
Timber flooring 25
Floor 0.039 0.040 25.374 25.254
Insulation (1) 1.003
(1)
The large insulating layer is not used in CoDyBa simulations : this layer is replaced with an adiabatic
boundary condition.
Author : Jean NOËL / web site : jnlog.com / mail : contact@jnlog.com Rev. 1.05 - July 2004 p. 10
CoDyBa - BESTEST Qualification
III - 5 - 2 - Window
Number of panes 2
Pane thickness 3.175 mm
Air-gap thickness 13 mm
Normal direct-beam transmittance through one pane in air 0.862
Thermal conductivity of glass 1.06 W/m².K
Combined radiative and convective coefficient of air gap 6.297 W/m².K
Exterior combined surface coefficient 21 W/m².K
Interior combined surface coefficient 8.29 W/m².K
U-Value from interior air to ambient air 3 W/m².K
Hemispherical infrared emittance of ordinary uncoated glass 0.84 (or 0.9)
Density of glass 2500 kg/m3
Specific heat of glass 750 J/kg.K
Double-pane shading coefficient at normal incidence 0.907
Double-pane solar heat gain coefficient at normal incidence 0.789
Table F : window summary
The height of the wall below the window is 0.2 m, 0.5 for the wall above the window.
Window overhang : the horizontal overhang for the south facing window is assumed to travel the entire
length of the south wall. All other dimensions for shading devices are shown in the drawings (see figures
A, B and C).
Coefficients of two glasses glazing data are calculated by using the following formulas :
Author : Jean NOËL / web site : jnlog.com / mail : contact@jnlog.com Rev. 1.05 - July 2004 p. 11
CoDyBa - BESTEST Qualification
To get CoDyBa results to compare with BESTEST results, the "base data of glass" is used. But in the
standard version of CoDyBa (commercial version), the usual CoDyBa transmission function f is used
instead :
The results obtained with the CoDyBA function are slightly different, but they passed the BESTEST
qualifications test cases (see chapter V-1-3).
For diffuse flux, the parameters are calculated with an integration over the viewed sky.
Interior solar distribution : CoDyBa calculates solar distribution of the incoming radiation. It supposes that
radiation strike the floor first, and that all reflections are diffuse. The method used by CoDyBa is the
method described in appendix F of BESTEST Report, with the restriction that the shape factor of a surface
is calculated by the ratio of its surface to the sum of all the others.
For this case, the short wave radiation absorption coefficient is taken to 0. The absorption coefficient is that
of the opaque walls. Other window properties remain the same (convective surface coefficients, materials,
etc.).
Cases 200 to 250 include an opaque glazing with the following characteristics :
- No solar transmission.
- An external convection coefficient and thermophysical parameters identical to those of a standard
glazing.
- Same emissivity and absorptance as for a wall.
Author : Jean NOËL / web site : jnlog.com / mail : contact@jnlog.com Rev. 1.05 - July 2004 p. 12
CoDyBa - BESTEST Qualification
BESTEST data are given in tables 1-5 and 1-6. The convective surface coefficients used in CoDyBa are
obtained from values given in BESTEST Report by correcting with the emissivity ε and the value of the
radiative portion of the combined coefficients (5 W/m².°C as CoDyBa data). Note that the value taken in
BESTEST Report is 5.7 W/m²/°C, the slight difference may explain some differences in the results.
The convective surface coefficients are detailed in table H (see BESTEST Report Table 1-5 and 1-6) :
Convective surface coefficients (W/m².K)
Surface Emissivity ε = 0.9 Emissivity ε = 0.1
Exterior Interior Exterior Interior
24.8 1.63 24.7 1.07
Roof
(29.3 - 0.9*5) (6.13 - 0.9*5) (25.2 - 0.1*5) (1.57 - 0.1*5)
27.05 3.79 24.95 3.23
Wall
(29.3 - 0.9*5/2) (8.29 - 0.9*5) (25.2 - 0.1*5/2) (3.73 - 0.1*5)
29.3 4.76 25.2 4.2
Floor
(29.3 - 0) (9.26 - 0.9*5) (25.2 - 0) (4.70 - 0.1*5)
18.75 3.8 16.6 3.2
Window
(21 - 0.9*5/2) (16.9 - 0.9*5/2)
Table H : detailed convective surface coefficients summary
The glass exterior and interior convective surface coefficients are supposed as the same as opaque walls.
Since CoDyBa does not allow scheduling of horizontal convective surface coefficients, the interior
coefficients for horizontal surfaces are taken as 8.29 W/m².K for the roof and the floor (see BESTEST
Report, chapter 1.4.6). Then all interior convective surface coefficients have the same value.
In brief, the convective surface coefficients used in CoDyBa simulations are :
Convective surface coefficients (W/m².K)
Surface Emissivity ε = 0.9 Emissivity ε = 0.1
Exterior Interior Exterior Interior
Roof 24.8 3.8 24.7 3.2
Wall 27 3.8 25 3.2
Floor 29.3 3.8 25.2 3.2
Table I : convective surface coefficients summary
For CoDyBa simulations the retained value of air change is 0.5 ACH, with an air density the value of is
0.9873 kg/m3 (see BESTEST Report appendix B) :
Author : Jean NOËL / web site : jnlog.com / mail : contact@jnlog.com Rev. 1.05 - July 2004 p. 13
CoDyBa - BESTEST Qualification
III - 6 - 3 - 1 - Description
The following conditions are assumed : 100% convective air system, no latent loads, the thermostat is
sensing only for the air temperature and is not proportional.
Note that for CoDyBa the thermostat control is based on the temperature of the central zone air node.
The power of each equipment is assumed huge (10 kW), with an effective efficiency of 100%.
The vent fan capacity is 1703.16 m3/h (in addition to specified infiltration rate). As CoDyBa does not
automatically correct the density of air, the fan capacity is adjusted to 13.14 ACH (Air Change per Hour,
see BESTEST Report Table 1.10).
The nominal vent fan capacity is 1703.16 m3/h (in addition to specified infiltration rate). In CoDyBa data a
value of 0.98 for the air density is taken, in order to take into account of the altitude. And the fan capacity
is adjusted to 13.14 ACH (Air Change per Hour, see BESTEST Report Table 1.10).
Author : Jean NOËL / web site : jnlog.com / mail : contact@jnlog.com Rev. 1.05 - July 2004 p. 14
CoDyBa - BESTEST Qualification
IV - Tests description
Author : Jean NOËL / web site : jnlog.com / mail : contact@jnlog.com Rev. 1.05 - July 2004 p. 15
CoDyBa - BESTEST Qualification
Setpoints
Internal load
Orientation
Area (m²)
External
External
ACH
Mass
Internal
Internal
Case
Shade
SWR
SWR
(1)
H,C,V
195 20,20,-- LW No 0 0.1 0.1 NA 0.1 0 S No
200 20,20,-- LW No 0 0.1 0.1 NA 0.1 0 S No
210 20,20,-- LW No 0 0.1 0.9 NA 0.1 0 S No
215 20,20,-- LW No 0 0.9 0.1 NA 0.1 0 S No
220 20,20,-- LW No 0 0.9 0.9 NA 0.1 0 S No
230 20,20,-- LW No 1 0.9 0.9 NA 0.1 0 S No
240 20,20,-- LW Yes 0 0.9 0.9 NA 0.1 0 S No
250 20,20,-- LW No 0 0.9 0.9 NA 0.9 0 S No
270 20,20,-- LW No 0 0.9 0.9 0.9 0.1 12 S No
280 20,20,-- LW No 0 0.9 0.9 0.1 0.1 12 S No
290 20,20,-- LW No 0 0.9 0.9 0.9 0.1 12 S 1m H
300 20,20,-- LW No 0 0.9 0.9 0.9 0.1 6,6 E,W No
310 20,20,-- LW No 0 0.9 0.9 0.9 0.1 6,6 E,W 1mHV
320 20,27,-- LW No 0 0.9 0.9 0.9 0.1 12 S No
(3)
395 20,27,-- LW No 0 0.9 0.9 NA 0.1 S No
400 20,27,-- LW No 0 0.9 0.9 NA 0.1 0 S No
410 20,27,-- LW No 0.5 0.9 0.9 NA 0.1 0 S No
420 20,27,-- LW Yes 0.5 0.9 0.9 NA 0.1 0 S No
430 20,27,-- LW Yes 0.5 0.9 0.9 NA 0.6 0 S No
440 20,27,-- LW Yes 0.5 0.9 0.9 0.1 0.6 12 S No
600 20,27,-- LW Yes 0.5 0.9 0.9 0.6 0.6 12 S No
610 20,27,-- LW Yes 0.5 0.9 0.9 0.6 0.6 12 S 1m H
620 20,27,-- LW Yes 0.5 0.9 0.9 0.6 0.6 6,6 E,W No
630 20,27,-- LW Yes 0.5 0.9 0.9 0.6 0.6 6,6 E,W 1mHV
640 SETBACK LW Yes 0.5 0.9 0.9 0.6 0.6 12 S No
650 --,27,V LW Yes 0.5 0.9 0.9 0.6 0.6 12 S No
800 20,27,-- HW Yes 0.5 0.9 0.9 NA 0.6 0 S No
810 20,27,-- HW Yes 0.5 0.9 0.9 0.1 0.6 12 S No
900 20,27,-- HW Yes 0.5 0.9 0.9 0.6 0.6 12 S No
910 20,27,-- HW Yes 0.5 0.9 0.9 0.6 0.6 12 S 1m H
920 20,27,-- HW Yes 0.5 0.9 0.9 0.6 0.6 6,6 E,W No
930 20,27,-- HW Yes 0.5 0.9 0.9 0.6 0.6 6,6 E,W 1mHV
940 SETBACK HW Yes 0.5 0.9 0.9 0.6 0.6 12 S No
950 --,27,V HW Yes 0.5 0.9 0.9 0.6 0.6 12 S No
600FF NONE
The cases labelled FF (Free-Float) are exactly the same as the non
900FF NONE
FF cases, except there are no heating or cooling systems. Thus the
650FF NONE,V
NONE,V
interior temperatures are allowed to be free-float.
950FF
(1)
Internal Load : the constant heat input is 200 W if "Yes", else 0.
(2)
Emissivity
(3)
Absorption : coefficient of short wave radiation absorption.
(4)
Case 395 has neither a window, nor an "opaque window". It consists of 100% normally insulated wall as
specified for the lightweight case.
Note : interior short wave absorptance does not matter when glass area is 0.
Author : Jean NOËL / web site : jnlog.com / mail : contact@jnlog.com Rev. 1.05 - July 2004 p. 16
CoDyBa - BESTEST Qualification
V - Results
This section presents the results from CoDyBa compared to the results of BESTEST references
applications. The final results from CoDyBa program are presented here in tabular and graphic form.
CoDyBa result values which exceed the BESTEST bounds are indicated in bold in the tables.
The next table (Table L, chapter V-1) shows the results in tabular format and also includes a row for each
comparison indicating the number of times where the CoDyBa values are without the range.
Note that BESTEST does not retain all results of reference applications, because some results are
considered as "bad" in a few cases.
A series of "Delta Results" were also generated (presented in Table N, chapter V-1-2) which compare the
difference in results between certain cases in order to isolate the sensitivity of each program to changes in
building features such as mass construction, addition of windows with and without shading, thermostat
setback, ventilation cooling, etc.
Results obtained with the CoDyBa commercial version are presented in Table M, chapter V-1-3). The data
differences are the specific glass laws.
One measure of comparison as to how well CoDyBa predicted thermal loads compared to the other
programs is to see if the results fall within the range of spread of results for other programs. This can be
visually with the charts presented in next chapters. The comparison charts contain three bars :
- Max BESTEST (the highest result among the reference applications)
- CDB (results from CoDyBa)
- Min BESTEST (the lowest result among the reference applications)
Author : Jean NOËL / web site : jnlog.com / mail : contact@jnlog.com Rev. 1.05 - July 2004 p. 17
CoDyBa - BESTEST Qualification
Author : Jean NOËL / web site : jnlog.com / mail : contact@jnlog.com Rev. 1.05 - July 2004 p. 18
CoDyBa - BESTEST Qualification
Author : Jean NOËL / web site : jnlog.com / mail : contact@jnlog.com Rev. 1.05 - July 2004 p. 19
CoDyBa - BESTEST Qualification
Author : Jean NOËL / web site : jnlog.com / mail : contact@jnlog.com Rev. 1.05 - July 2004 p. 20
CoDyBa - BESTEST Qualification
1500
There is no significant differences
1250
between CoDyBa and BESTEST Min BESTEST
results. 1000 CoDyBa
500
250
0
North East West South Horizontal
Values of incident solar radiation are obtained by integrating the diffuse and direct absorbed solar fluxes on
the walls of the building, and by correcting by the absorption coefficient and the wall surface.
But as can be seen the sky model choice gives different results.
Author : Jean NOËL / web site : jnlog.com / mail : contact@jnlog.com Rev. 1.05 - July 2004 p. 21
CoDyBa - BESTEST Qualification
Diffuse+Direct (kWh/m²)
950
One failure : for the west
orientation, the annual transmitted Min BESTEST
800 CoDyBa
solar flux predicted by CoDyBa is
Max BESTEST
slightly over the BESTEST
maximum. 650
500
West South
0
930 West 910 South
Author : Jean NOËL / web site : jnlog.com / mail : contact@jnlog.com Rev. 1.05 - July 2004 p. 22
CoDyBa - BESTEST Qualification
Min BESTEST
0,6 CoDyBa
Max BESTEST
0,55
0,5
930 West 910 South
0,1
930 West 910 South
Author : Jean NOËL / web site : jnlog.com / mail : contact@jnlog.com Rev. 1.05 - July 2004 p. 23
CoDyBa - BESTEST Qualification
7
Cooling Energy (MWh)
1
600 610 620 630 640 650
6,5
All CoDyBa results are within 6
Peak Heating (kW)
3,5
3
600 610 620 630 640
6,5
cooling predicted by CoDyBa is
6 Min BESTEST
slightly over the BESTEST
5,5 CoDyBa
maximum.
5 Max BESTEST
4,5
4
3,5
3
600 610 620 630 640 650
Author : Jean NOËL / web site : jnlog.com / mail : contact@jnlog.com Rev. 1.05 - July 2004 p. 24
CoDyBa - BESTEST Qualification
3
Cooling Energy (MWh)
0,5
0
900 910 920 930 940 950
5,5
heating predicted by CoDyBa is over
5 Min BESTEST
the BESTEST maximum.
4,5 CoDyBa
4 Max BESTEST
3,5
3
2,5
2
900 910 920 930 940
3,5
One failure : for case 930, the peak
Peak Cooling (kW)
1,5
1
900 910 920 930 940 950
Author : Jean NOËL / web site : jnlog.com / mail : contact@jnlog.com Rev. 1.05 - July 2004 p. 25
CoDyBa - BESTEST Qualification
-5
All CoDyBa results are within
BESTEST range.
-10 Min BESTEST
CoDyBa
-15 Max BESTEST
-20
-25
Temperature 25
23
Four failures : for case 950FF, the
average temperature predicted by 21 Min BESTEST
CoDyBa
CoDyBa are slightly under the 19
Max BESTEST
BESTEST minimum.
17
15
13
600FF 650FF 900FF 950FF
Author : Jean NOËL / web site : jnlog.com / mail : contact@jnlog.com Rev. 1.05 - July 2004 p. 26
CoDyBa - BESTEST Qualification
Author : Jean NOËL / web site : jnlog.com / mail : contact@jnlog.com Rev. 1.05 - July 2004 p. 27
CoDyBa - BESTEST Qualification
Hour
Hour
450
flux density, clear day,
400
south surface 350
300 Min BESTEST
250 CoDyBa
200 Max BESTEST
150
100
50
0
1 3 5 7 9 11 13 15 17 19 21 23
Hour
Hour
Clear cold day (4th of January) Clear hot day (27th of July)
Hour Case 600FF Case 900FF Case 650FF Case 950FF
MinB MaxB CDB MinB MaxB CDB MinB MaxB CDB MinB MaxB CDB
1 -13,04 -8,88 -12,68 -3,46 1,61 -0,94 21,80 22,69 22,5 24,20 25,51 24,77
2 -14,59 -10,48 -14,13 -3,99 0,93 -1,54 20,80 21,33 21,25 23,46 24,74 24,03
3 -15,65 -11,76 -15,14 -4,40 0,49 -1,98 19,90 20,41 20,34 22,86 24,07 23,43
4 -16,46 -12,75 -16,02 -4,80 0,07 -2,44 19,10 19,61 19,52 22,27 23,39 22,79
5 -17,16 -13,69 -16,78 -5,22 -0,41 -2,90 18,80 19,29 19,15 21,86 22,96 22,46
6 -17,9 -14,49 -17,43 -5,60 -0,87 -3,35 19,24 19,91 19,77 22,01 23,08 22,77
7 -18,5 -15,15 -17,99 -5,98 -1,27 -3,78 21,16 22,53 22,28 23,32 24,73 24,39
8 -18,8 -15,63 -18,05 -6,08 -1,64 -4,12 23,47 25,03 24,11 25,62 27,59 26,29
9 -15,47 -13,46 -14,73 -4,72 -1,54 -3,55 25,67 28,33 27,11 26,81 29,42 27,22
10 -10,03 -7,099 -9,10 -2,98 -0,40 -2,40 28,91 32,42 30,86 27,79 30,68 28,15
11 -2,2 3,657 0,65 0,25 1,66 -0,20 32,80 37,12 35,24 28,96 31,98 29,2
12 8,84 13,49 9,84 2,54 4,40 1,74 37,49 42,08 39,62 30,31 33,56 30,32
13 18,75 22,3 17,72 4,38 6,72 3,43 41,94 46,46 43,45 31,54 34,79 31,29
14 25,48 29,82 24,2 5,85 8,66 5,02 45,43 49,69 46,05 32,52 35,65 32,04
15 29,21 34,69 27,62 6,61 10,02 5,87 47,40 51,45 47,43 33,08 35,96 32,52
16 28,97 35,51 27,45 6,33 10,40 5,96 47,33 51,73 47,75 33,22 35,82 32,79
17 22,58 31,46 21,39 4,20 9,41 4,73 46,71 50,74 47,53 33,18 35,61 32,96
18 15,59 23,99 15,5 2,45 7,66 3,69 45,28 48,81 45,85 32,94 34,93 32,69
19 10,2 18,08 10,62 1,71 6,74 3,02 33,10 37,60 34,71 30,00 30,96 30,23
20 6,02 13,02 6,62 1,32 6,00 2,52 30,49 32,09 31,4 29,10 29,97 29,41
21 2,39 8,87 3,07 0,82 5,41 1,98 28,50 29,20 29,09 27,64 29,17 28,62
22 -0,59 5,12 0,17 0,42 4,74 1,54 26,30 26,92 26,8 27,10 28,15 27,48
23 -3,04 2,03 -2,24 0,05 4,20 1,13 25,40 25,90 25,82 26,62 27,72 27,18
24 -5,14 -1,03 -4,33 -0,34 3,66 0,70 23,70 24,26 24,2 25,54 26,74 26,14
Table V : hourly Free Float temperatures
Author : Jean NOËL / web site : jnlog.com / mail : contact@jnlog.com Rev. 1.05 - July 2004 p. 29
CoDyBa - BESTEST Qualification
-10
-20
1 3 5 7 9 11 13 15 17 19 21 23
Hour
Hour
Hour
24
21
1 3 5 7 9 11 13 15 17 19 21 23
Hour
1,5
Heating(+), Cooling(-) Min BESTEST
0,5
CoDyBa
-0,5
Max BESTEST
-1,5
-2,5
-3,5
-4,5
1 3 5 7 9 11 13 15 17 19 21 23
Hour
Hour
Author : Jean NOËL / web site : jnlog.com / mail : contact@jnlog.com Rev. 1.05 - July 2004 p. 31
CoDyBa - BESTEST Qualification
The occurrence frequencies of temperature values over a year are presented in the next table.
°C BR Min BR Max CDB
-14 0 0 0
-13 0 0 0
-12 0 0 0
-11 0 0 0
-10 0 0 0
-9 0 0 0
-8 0 0 0
-7 0 1 0
-6 0 3 0
-5 0 4 0
-4 0 6 0
-3 0 7 3 500
Hourly Occurrences
-2 3 12 2
-1 3 18 8 400
0 8 20 21
1 6 20 15 Min BESTEST
300
2 13 20 19
3 15 25 17 CoDyBa
4 14 24 21 200 Max BESTEST
5 18 30 26
6 19 35 33 100
7 28 45 26
8 30 59 44
0
9 42 73 60
10 51 118 65 -10 -5 0 5 10 15 20 25 30 35 40 45 50
11 67 134 92
12 90 139 130 Temperature bins
13 115 173 148
14 151 183 171
15 165 234 197
16 195 274 217 Fig. R27 : hourly occurrences for each 1 °C bin
17 244 298 278
18 266 350 315
19 317 356 351
20 331 387 386
21 334 398 376
22 329 385 362
23 341 396 359
24 338 401 347
25 357 432 392
26 373 455 422
27 396 465 420
28 390 463 427
29 391 459 386
30 362 422 394
31 335 406 351
32 322 369 310
33 291 339 330
34 242 321 308
35 197 303 264
36 169 254 218
37 136 195 163
38 92 175 139
39 71 112 85
40 35 90 40
41 15 58 19
42 0 36 4
43 0 18 0
44 0 5 0
45 0 0 0
46 0 0 0
47 0 0 0
48 0 0 0
49 0 0 0
50 0 0 0
The temperature values in the range [ T0 -0.5 °C , T0 -0.5 °C ] are assigned to T0.
Author : Jean NOËL / web site : jnlog.com / mail : contact@jnlog.com Rev. 1.05 - July 2004 p. 32
CoDyBa - BESTEST Qualification
10
5
Fig. R29 : Annual Cooling
Heating Energy (MWh)
4
One failure : for case 440, the
Min BESTEST
annual cooling predicted by CoDyBa 3
CoDyBa
is without the range of spread.
Max BESTEST
2
0
395 400 410 420 430 440 800 810
4
Peak Heating (kW)
1,5
1
395 400 410 420 430 440 800 810
0
395 400 410 420 430 440 800 810
Author : Jean NOËL / web site : jnlog.com / mail : contact@jnlog.com Rev. 1.05 - July 2004 p. 33
CoDyBa - BESTEST Qualification
VI - Conclusions
VI - 1 - Conclusions
CoDyBa Version 6.4 was used to model a range of building specifications as specified in BESTEST Report
: the results obtained by CoDyBa are in very good agreement with those found by other classical softwares.
For the 50 qualification individual comparisons (see Table V-1-1) that were performed, the CoDyBa results
were within the range of spread of results for the reference programs for all cases except the following :
- Case 630, Low Mass Building with east and west overhangs and fins, Peak Cooling
- Case 910, High Mass Building with south overhang, Annual Heating
- Case 930, High Mass Building with east and west overhangs and fins, Peak Cooling
- Case 940, High Mass Building with thermostat setback, Peak Heating
- For the free floating cases, the maximum and minimum zone temperatures predicted by CoDyBa
were within the range of spread for all programs except for : case 600FF (maximum zone
temperature), case 650FF (maximum zone temperature), case 600FF (maximum and average zone
temperatures)
Concluding remarks :
Flux transmitted by south and west glazing also show that the yearly flux transmitted by the glazing and
the transmission coefficient are comparable with those of the other codes.
Consumption : the hourly consumption curves for the 4th of January agree fairly well with the reference
results and make one suppose that there are no major problems regarding the thermal dynamics.
Minimum free-float temperatures from cases 600FF and 900FF tend to be at the low end of the reference
results, especially in the high-mass (900FF) where the temperature is about 1 °C less than the next lowest
result. This remark is also made in SCIAQ qualification report (see [SCIAQ]).
An area of discrepancy may be observed for solar radiation : it seems that the model of sky has a great
importance on the solar flows received by the walls. One can observe an unquestionable dispersion on the
values obtained by reference programs, what leads naturally to a dispersion on results for cases where the
solar fluxes transmitted by the windows are important. This is why it is necessary to relativize the
variations of results obtained by CoDyBa whenever are present solar masks.
VI - 2 - Final conclusion
A program may be thought of as having passed successfully through the qualification (see BESTEST
Report 1.3) series when its result compare favourably with the reference program output for both the
qualification cases (600 and 900 series).
Considering the results obtained by CoDyBa, one can consider that the software is on the level of the
reference programs.
Author : Jean NOËL / web site : jnlog.com / mail : contact@jnlog.com Rev. 1.05 - July 2004 p. 34
CoDyBa - BESTEST Qualification
VII - Bibliography
[CET] http://cethil.insa-lyon.fr/
Author : Jean NOËL / web site : jnlog.com / mail : contact@jnlog.com Rev. 1.05 - July 2004 p. 35
CoDyBa - BESTEST Qualification
This procedure requires the evaluation of the internal air temperature of the room specified below at several
time intervals.
I - Test data
Boundary conditions :
- the outdoor air temperature is variable according to Figure 1 : t ≤ 0: θe= 20 °C ; for 0< t ≤ 1 (hour):
linear variation of the outdoor temperature θe from 20 °C to 30 °C; t >1 hour: θe = 30°C;
- the internal air temperature θi is constant at 20 °C for t ≤ 0.
θa,e (°C)
30
linear variation of the outdoor air temperature
20
1 2 3 t (hours)
Figure 1 : Variation of the outdoor air temperature
Test conditions : Tests shall be conducted for the envelope elements given in Table 1.
Thickness Thermal conductivity Density Specific heat capacity
Test n° s [m] λ [W/(m · K)] ρ [kg/ m3] C [kJ/ (kg . K)]
1 0,20 1,2 2000 1,0
2 0,10 0,04 50 1,0
3(*) 0,20 1,2 2000 1,0
0,10 0,04 50 1,0
0,005 0,14 800 1,5
4(*) 0,005 0,14 800 1,5
0,10 0,04 50 1,0
0,20 1,2 2000 1,0
(*) layers from outside to inside
Table 1 : characteristics of the envelope components
Author : Jean NOËL / web site : jnlog.com / mail : contact@jnlog.com Rev. 1.05 - July 2004 p. 36
CoDyBa - BESTEST Qualification
Data to be calculated :
The internal air temperature shall be determined after the following times: 2, 6, 12, 24 and 120 hours.
Expected results :
For each test, the differences between the values of the internal air temperature, for each time considered,
shall be less than 0,5 K from those given in Table 2.
II - Test results
III - Conclusions
The norm requires that "for each test, the differences between the values of the internal air temperature, for
each time considered, shall be less than 0,5 K from those given in Table 3". One can note that it is
practically the case for all the tests, except for which the value is slightly higher.
However the requirement by the norm of a lower deviation than 0.5 is not justified in the CEN report.
Indeed, why a value of 0.5 and not of 0.25 or 0.75? Why does this value lead to a better thermal evaluation
of a building?
The benchmark BESTEST on the contrary do not give a value limiting to the noted result variations. The
validation or not of the test is left with the appreciation of the developers of software: that appears to us to
show of more than flexibility and less dogmatism.
Author : Jean NOËL / web site : jnlog.com / mail : contact@jnlog.com Rev. 1.05 - July 2004 p. 37