Vous êtes sur la page 1sur 26

DriveIT ACS 400V Instructions

Low Voltage Supplement for ACS 400


AC Drives User’s Manual
Safety

Warning! Only a competent electrician may install the ACS 400V.

Warning! Dangerous voltages are present when mains supply is connected. Wait at least 5
minutes after disconnecting the supply before removing the cover. Measure the voltage
at DC terminals (Uc+, Uc-) before servicing the unit. See ACS 400 User’s Manual
Reference Section E.

Warning! Even when the motor is stopped there are dangerous voltages present at Power Circuit
terminals U1, V1, W1 and U2, V2, W2 and Uc+, Uc-.

Warning! Even when the ACS 400V is powered down, there may be dangerous external voltages
at relay terminals RO1A, RO1B, RO1C, RO2A, RO2B, RO2C.

Warning! Never attempt to repair a broken unit; contact the supplier.

Warning! The ACS 400V will start up automatically after an input voltage interruption if the
external run command is on.

Warning! When the control terminals of two or more ACS100/140/160/400/400V units are
connected in parallel, the auxiliary voltage for these control connections must be taken
from a single source which can either be one of the units or an external supply.

Warning! The heat sink may reach a high temperature (see ACS 400 User’s Manual Reference
Section S, Table 11).

Warning! The ACS 400V unit with a RFI filter cannot be used in distribution networks isolated
from earth (floating networks, IT networks). Otherwise the net will be connected with the
earth potential via filter capacitors.

If the drive is connected to IT network, grounding screws and the RFI filter must be removed. Refer to
ACS 400 User’s Manual Reference section I Floating Network for instructions on screw locations.
Note! For more technical information refer to ACS 400 User’s Manual or contact your local ABB
supplier.

3
4
This instruction is a supplement to the ACS 400 User’s Manual which is delivered with the frequency
converter. This instruction describes the unique features of ACS 400V which make it especially suitable
for HVAC (heating, ventilation and air conditioning) applications. The software of this product has been
developed in co-operation with Fläkt Woods Group. In case of other technical information, a reference
to the ACS 400 User’s Manual is made.

Table of Contents

Safety ..................................................................................................... 3
Installing the ACS 400V ........................................................................ 7
Controlling the ACS 400V ................................................................... 10
I/O Configuration ................................................................................. 11
Alternative ACS 400V Operation Modes (Hardwire Connections) .. 12
Start / Stop and External Control Signal 0-10 V ....................................................12
Start / Stop with 1 Constant Speed .......................................................................13
Start / Stop with 2 Constant Speeds .....................................................................14
PID Control with 1 Setpoint ...................................................................................15
PID Control with 2 Setpoints .................................................................................16
Operating with ACS-PAN-A Control Panel ........................................ 17
Control Modes .......................................................................................................17
Actual Values in Output Display ............................................................................18
Menu Structure .....................................................................................................18
Setting Parameter Value .......................................................................................18
Changing Between Basic and Full Parameter Set ................................................19
Diagnostic displays ...............................................................................................19
Resetting the Drive from the Control Panel ..........................................................19
LED Indicators ......................................................................................................19
Parameterising ACS 400V .................................................................. 20
Appendix 1: .......................................................................................... 22
Electro Magnetic Compatibility EMC .....................................................................22

5
6
Installing the ACS 400V
Mount the ACS 400V with the RFI filter on the wall. With ACS 400V for powers 15 kW and more (frame
size R3 and R4) the RFI filter can be mounted either below or next to the drive.

Figure 1 ACS 400V Frame sizes R1 and R2 (3.0 - 11 kW).

Drive Type
RFI Filter Type A (mm) B (mm) C (mm) D (mm) E (mm)
ACS401-
V004 - V006 ACS400-IF11-3 90 361.5 35 98 318
V009 - V011 ACS400-IF21-3 90 461 35 98 417

7
Figure 2 ACS 400V frame sizes R3 and R4 (15 - 37 kW).

,
not delivered
with the unit

Drive Type
RFI Filter Type A (mm) B (mm) C (mm) D (mm) E (mm)
ACS401-
V016 - V020 ACS400-IF31-3 140 230 50 160 528
V025 - V041 ACS400-IF41-3 160 280 50 160 619

8
Connect the RFI filter to the supply (line) side of the drive. See ACS 400V and corresponding RFI filter
mounting dimensions from the table below.
Mount the IP54 protection cover(s) to the RFI filter end(s) to get IP54 protection class for the EMC filter.
The frequency converter unit protection class depends on the ordered type. In frame size R1 and R2
one IP54 filter cover is required on the supply cable entry end of the filter. In frame size R3 and R4 two
IP54 filter covers are required, one on each end. See the following figures for mounting and cabling.

Figure 3 Cabling ACS 400V with IP54 protection cover.

Control Cables

Supply Cable

Cable Motor Cable


Between
RFI Filter
and ACS 400V

Note! ACS-CHK-C is needed and supplied only with ACS400-IF41-3 filter.

9
Controlling the ACS 400V
The ACS400V can be used from external or local control locations.

External control possibilities


1. Control from I/O: Depending on the I/O connections ACS 400V can be used in alternative operation
modes. These modes, which are explained later in more detail, are designed to meet the requirements
of several HVAC applications:
• Speed Control via External Control Signal 0-10 V, see page 12
• Start / Stop with 1 Constant Speed, see page 13
• Start / Stop with 2 Constant Speeds, see page 14
• PID Control with 1 Setpoint, see page 15
• PID Control with 2 Setpoints, see page 16
2. Control via Fieldbus: Modbus protocol is as default fieldbus in ACS 400V. In order to use other
fieldbuses an external fieldbus module and an ACS 400 DDCS adapter must be used, both are
available as options. N2 fieldbus is also available as embedded fieldbus option for ACS 400V.

Local control possibilities


1. Control from control panel: ACS 400V can be directly controlled from control panel without making
any connections to the ACS 400V I/O. In this case motor starts and stops from control panel’s START/
STOP button and required speed (Hz) is set with control panel.
2. Control with PC-tool DriveWindow Light: For set-up and control purposes the PC-tool DriveWindow
Light is also available as an option. For using this tool ACS 400V has to be equipped with an optional
ACS 140 RS 485/232 adapter.
Contact your local ABB supplier for more information on options.

External control Local control

Control Panel ACS-PAN-A

X3 X2 Panel Port “Modified RS232”


Modbus fieldbus

X1

I/O
ACS 140 RS485/232

Optional
Optional fieldbus DDCS
RS-232
Module

DriveWindow Light

Figure 4 ACS 400V control locations.

10
I/O Configuration
The following diagram summarizes the I/O connection alternatives given by the ACS 400V.

DIP switches, set to


Input signals Output signals
voltage signal positions
• Start/stop (DI1) • Analogue output AO: Frequency
0 - 50 Hz <=> 0- 20 mA

ON
AI1: 0 - 10 V
• Control signal 0 - 10 V(AI1) • Relay output 1: Fault
AI2: 0 - 10 V

ON
-> 17 connected to 18
• Actual value 0 - 10 V, eg. from • Relay output 2: Running
pressure sensor (AI2) -> 20 connected to 22
• Activate to select PID control
(DI2)
• Select setpoint1/setpoint2 (DI3)
• Constant speed 1 (DI4)
• Constant speed 2 (DI5)

X1 X1
1 SCR 1 SCR
2 AI1 2 AI1
3 AGND 3 AGND
4 +10V 4 +10V
5 AI2 5 AI2
6 AGND 6 AGND
7 AO1 7 AO1
8 AGND +24V 8 AGND
9 +24V 9 +24V
10 DCOM1 10 DCOM1
11 DI1 11 DI1
12 DI2 12 DI2
13 DI3 13 DI3
14 DI4 14 DI4
15 DI5 15 DI5
16 DCOM2 16 DCOM2
17 17
DI configuration RO1C ±0V RO1C
18 RO1A 18 RO1A
NPN connected
19 RO1B 19 RO1B
(sink) DI configuration PNP
20 RO2C connected (source) 20 RO2C
21 RO2A with external 21 RO2A
22 RO2B power supply 22 RO2B

Figure 5 ACS 400V I/O connection.

11
Alternative ACS 400V Operation Modes (Hardwire Connections)
Start / Stop and External Control Signal 0-10 V
• Set DIP switches to voltage signal positions
• Start signal is given by activating DI1 (11)
• Control signal 0-10 VDC from external regulator is connected to AI1 (2, 3)
• Two constant speeds are possible, if 8, 14 and 8, 15 are connected using a switch between 14 and
15, see page 14

DIP switches

ON
AI1: 0- 10 V
AI2: 0- 10 V

ON
X1
1 SCR Screen control signal cable
External control signal 0-10V 2 AI1 + Control signal 0 - 10V
3 AGND -
4 +10V + Reference voltage 10 VDC
5 AI2 + Pressure sensor 0 - 10V
6 AGND -
7 AO1 Output frq 0 - 50Hz <=> 0 - 20mA
8 AGND
9 +24V + Auxiliary voltage 24 VDC
Start/Stop 10 DCOM1
11 DI1 Start / Stop
12 DI2 Activate PID control
DI3
(

13 Select setpoint1 / setpoint2


14 DI4 Constant speed 1
15 DI5 Constant speed 2
16 DCOM2
17 RO1C Fault = 17-19
18 RO1A breaks
19 RO1B
20 RO2C Running =
21 RO2A 20 connected to 22
22 RO2B

12
Start / Stop with 1 Constant Speed
• Set DIP switches to voltage signal positions
• Motor starts by activating DI1 (11)
• One constant speed can be set
• Constant speed 1 is set with parameter 1202
• Constant speed 1 is selected with DI4 (14)

DIP switches
AI1: 0- 10 V

ON
AI2: 0- 10 V

ON
X1
1 SCR Screen control signal cable
2 AI1 + Control signal 0 - 10V
3 AGND -
4 +10V + Reference voltage 10 VDC
5 AI2 + Pressure sensor 0 - 10V
6 AGND -
7 AO1 Output frq 0 - 50Hz <=> 0 - 20mA
8 AGND
9 +24V + Auxiliary voltage 24 VDC
Start/Stop 10 DCOM1
11 DI1 Start / Stop
12 DI2 Activate PID control
DI3
(

13 Select setpoint1 / setpoint2


14 DI4 Constant speed 1
15 DI5 Constant speed 2
16 DCOM2
17 RO1C Fault = 17-19
18 RO1A breaks
19 RO1B
20 RO2C Running =
21 RO2A 20 connected to 22
22 RO2B

13
Start / Stop with 2 Constant Speeds
• Set DIP switches to voltage signal positions
• Motor starts by activating DI1 (11)
• Two different constant speeds can be set
• Constant speed 1 is set with parameter 1202
• Constant speed 2 is set with parameter 1203
• Constant speed 1 is selected with DI4 (14)
• Constant speed 2 is selected with DI5 (15)

DIP switches

ON
AI1: 0- 10 V
AI2: 0- 10 V

ON
X1
1 SCR Screen control signal cable
2 AI1 + Control signal 0 - 10V
3 AGND -
4 +10V + Reference voltage 10 VDC
5 AI2 + Pressure sensor 0 - 10V
6 AGND -
7 AO1 Output frq 0 - 50Hz <=> 0 - 20mA
8 AGND
9 +24V + Auxiliary voltage 24 VDC
Start/Stop 10 DCOM1
11 DI1 Start / Stop
12 DI2 Activate PID control
DI3
(

13 Select setpoint1 / setpoint2


14 DI4 Constant speed 1
15 DI5 Constant speed 2
Constant speed 1/2 16 DCOM2
17 RO1C Fault = 17-19
18 RO1A breaks
19 RO1B
20 RO2C Running =
21 RO2A 20 connected to 22
22 RO2B

14
PID Control with 1 Setpoint
• Set DIP switches to voltage signal positions
• Connect 8 and 12 together to activate PID Control (DI2 active)
• Motor starts when DI1 is activated (11)
• Reference value 1 is set with parameter 4020 (see Figure 6, page 21)
• Actual value (pressure sensor) is connected to AI2 (5,6)

DIP switches

ON
AI1: 0- 10 V
AI2: 0- 10 V

ON
G 24V
G0

X1
1 SCR Screen control signal cable
2 AI1 + Control signal 0 - 10V
Pressure sensor AGND -
3
G +10V + Reference voltage 10 VDC
4
M B AI2 + Pressure sensor 0 - 10V
5
6 AGND -
7 AO1 Output frq 0 - 50Hz <=> 0 - 20m
8 AGND
9 +24V + Auxiliary voltage 24 VDC
Start/Stop 10 DCOM1
11 DI1 Start / Stop
12 DI2 Activate PID control
DI3 Select setpoint1 / setpoint2
(

13
14 DI4 Constant speed 1
15 DI5 Constant speed 2
16 DCOM2
17 RO1C
Fault = 17-19
G 24V

18 RO1A breaks
G0

19 RO1B
20 RO2C
Running =
21 RO2A 20 connected to 22
22 RO2B

15
PID Control with 2 Setpoints
• Set DIP switches to voltage signal positions
• Connect 8 and 12 together to activate PID Control (DI2 active)
• Motor starts when DI1 is activated (11)
• Select reference value 1 or 2 with DI3
• If DI3 is not active, reference is value 1. If DI3 is active the reference value is 2.
• Reference value 1 is set with parameter 4020 (see Figure 6, page 21)
• Reference value 2 is set with parameter 4120 (see Figure 6, page 21)
• Actual value (pressure sensor) is connected to AI2 (5, 6)

DIP switches

ON
AI1: 0- 10 V
AI2: 0- 10 V

ON
G 24V
G0

X1
1 SCR Screen control signal cable
2 AI1 + Control signal 0 - 10V
Pressure sensor AGND -
3
G +10V
4 + Reference voltage 10 VDC
M B AI2
5 + Pressure sensor 0 - 10V
6 AGND -
7 AO1 Output frq 0 - 50Hz <=> 0 - 20mA
8 AGND
9 +24V + Auxiliary voltage 24 VDC

Start/Stop 10 DCOM1
11 DI1 Start / Stop
12 DI2 Activate PID control
DI3
(

13 Select setpoint1 / setpoint2


Setpoint 1/ 2 14 DI4 Constant speed 1
15 DI5 Constant speed 2
16 DCOM2
17 RO1C
Fault = 17-19
G 24V

18 RO1A breaks
G0

19 RO1B
20 RO2C
Running =
21 RO2A 20 connected to 22
22 RO2B

16
Operating with ACS-PAN-A Control Panel
The ACS 400V is delivered with an ACS-PAN-A control panel, which is an alphanumeric control panel
with LCD display and multiple languages. The control panel can be connected to and detached from
the converter at any time. If the control panel is detached when the panel is in local mode, then the ACS
400V will trip and stop. If the panel is detached in remote mode, then the ACS 400V will continue
operation as before. The panel can be used to copy parameters to other ACS 400V converters with the
same software revision can be viewed from (parameter 3301).

Run indicator

Shaft direction
Control modes
UP/DOWN
Display modes OUTPUT MENU LOC REM RUN

MENU ENTER
Green LED
MENU ENTER
Red LED
RESET START/STOP
LOC
RESET
REM

LOC/REM REVERSE

Control Modes
The very first time the drive is powered up, it is controlled from the Control Terminal Block X1 (remote
control, REM). The ACS 400V is controlled from the control panel when the drive is in local control
(LOC).
Switch to local control (LOC) by pressing and holding the LOC/REM button until first LOCAL
CONTROL or later LOCAL, KEEP RUN is displayed:
• If the button is released while LOCAL CONTROL is displayed, the panel frequency reference is set
to the current external reference and the drive is stopped.
• When LOCAL, KEEP RUN is displayed, the current run/stop status and the frequency reference are
copied from the user I/O.
Start and stop the drive by pressing the START/STOP button.
Change the shaft direction by pressing the REVERSE button (parameter 1003 must be set to
REQUEST).

Switch back to remote control (REM) by pressing and holding the LOC/REM button until REMOTE
CONTROL is displayed.
Shaft Direction
RUN > • Drive is running and at setpoint
< RUN • Shaft direction is forward (>) or reverse (<)
RUN > (or < RUN) Arrow head blinking rapidly Drive is running but not at setpoint.
> (or <) Arrow head blinking slowly Drive is stopped.

17
Actual Values in Output Display
When the control panel is powered up, the panel displays a selection of actual values. Whenever the
MENU button is pressed and held, the control panel resumes this OUTPUT display.

Output current Torque Reference frequency

Cursor is visible when reference


0.0A 0% 50.0 Hz can be modified

0.0 Hz
Actual output frequency
OUTPUT

The frequency reference can be modified using UP/DOWN buttons when it is underlined. Pressing UP
or DOWN buttons changes the reference immediately.
The reference can be modified in local control mode, but also in remote control mode if the ACS 400V
is parameterised in such a way.

Menu Structure
ACS 400V has a large number of parameters which are listed in menus. The so-called basic
parameters are in the short menu. All the parameters are in full menu which is initially visible.
The menu consists of parameter groups and menu functions.
OUTPUT display Menu Parameters

0.0A 0% 50.0 Hz MENU 99 START-UP DATA ENTER 9901 LANGUAGE

0.0 Hz ENGLISH
OUTPUT MENU

MENU MENU

01 OPERATING DATA 9902 APPLIC MACRO


10 COMMAND INPUTS 9905 MOTOR NOM VOLT
... ...
8121 REG BYPASS
81 PFC CONTROL
CTRL
COPY TO DRIVE
8122 REG START DELAY
COPY TO PANEL ...
LONG/SHORT MENU

Setting Parameter Value


Parameter value set mode is entered by pressing ENTER. In set mode, value is underlined. Value is
altered by using UP/DOWN buttons. Modified value is stored by pressing ENTER. Modifications can be
cancelled and set mode inactivated by pressing MENU.

9901 LANGUAGE accept and store


9901 LANGUAGE
ENTER alter
ENGLISH ENTER
ENGLISH value

exit without saving


MENU

18
Note! In the parameter value set mode the cursor blinks, when the parameter value is altered.
Note! To view the parameter default value in the parameter value set mode, press the UP/DOWN
buttons simultaneously.

Changing Between Basic and Full Parameter Set


Press and hold ENTER button to change from basic parameter set to full parameter set. When full
Menu is active, an asterisk appears on the second row of the panel display in Menu. Activate this
function again to resume the short Menu.

Press & hold


FULL/SHORT MENU FULL/SHORT MENU
ENTER

MENU MENU
*

Asterisk (*) is visible if full menu is active.

Diagnostic displays
When the red LED of the ACS-PAN-A is on or blinking, a fault is active. The relevant fault message
flashes in the panel display.
When the green LED of the ACS-PAN-A is blinking, an alarm is active. The relevant alarm message is
shown in the panel display. Alarms 1-7 arise from button operation and green LED does not blink for
them.
The alarm and fault messages disappear when MENU, ENTER or the arrow buttons of control panel
are pressed. The message will reappear after a few seconds if the keypad is not touched and alarm or
fault is still active. Refer to ACS 400 User’s Manual Diagnostics section for complete list of alarms and
faults.

Resetting the Drive from the Control Panel


To reset a fault when the red LED is on, press the RESET button.
Caution! Resetting the fault may start the drive when in remote control.
To reset a fault when the red LED is blinking, turn the power off.
Caution! Turning the power on again may start the drive immediately.

LED Indicators
Status of ACS 400V can be seen from the LED indicators in the control panel and if the control panel is
removed in the unit enclosure.

Red LED Green LED


OFF ON Power ON and drive is operating normally.
OFF BLINKS Alarm is active.
ON ON Fault is active. Drive can be reset from the control panel.
BLINKS ON Fault is active. Turn power off to reset the drive.

19
Parameterising ACS 400V
The parameters of ACS 400V are pre-set to enable operation according to every ACS 400V operation
mode in HVAC applications. In commissioning the drive the user is however required to set a limited
number of parameters according to the motor and application. The table below lists these and the pre-
set HVAC parameter default values. Also all other parameters can be set with the help of ACS 400
User’s Manual. Descriptions of parameters can be found in ACS 400 User’s Manual.
Check that the full Menu is visible in the ACS 400V when starting parameterising. Go through, in the
given order, all the parameters which are marked with an X in the Set column:
• First change the parameter 9902 APPLICATION MACRO to value 6 (PID CONTROL)
• Set the motor parameter.
After this the ACS 400V is ready for operation if connection is according to one of the five ACS 400V
operation modes. If changes are needed to the values of relevant parameters in these connections,
they can easily be changed with the help of the HVAC parameter table (Table 1) and PID regulator
tables (Table 2 and Table 3).
Table 1 HVAC Parameter table.
Code Name Default Set User
9902 APPLIC MACRO FACTORY (O), change this first to PID CONTROL X
9901 LANGUAGE ENGLISH
9905 MOTOR NOM VOLT 400 V X
9906 MOTOR NOM CURR MOTOR CURRENT, SEE MOTOR RATING PLATE (A) X
9907 MOTOR NOM FREQ 50 HZ X
9908 MOTOR NOM SPEED MOTOR SPEED, SEE MOTOR RATING PLATE X
9909 MOTOR NOM POWER MOTOR POWER, SEE MOTOR RATING PLATE X
9910 MOTOR COS PHI MOTOR COS PHI, SEE MOTOR RATING PLATE X
1001 EXT1 COMMANDS DI1
1002 EXT2 COMMANDS DI1
1102 EXT1/EXT2 SEL DI2
1103 EXT REF 1 SELECT AI1
1106 EXT REF 2 SELECT AI1
1201 CONST SPEED SEL DI4, 5
1202 CONST SPEED 1 5 HZ (CONSTANT SPEED 1 IN HZ)
1203 CONST SPEED 2 10 HZ (CONSTANT SPEED 2 IN HZ)
1601 RUN ENABLE NOT SEL
2003 MAX CURRENT 1.1* MOTOR NOMINAL POWER (A), SEE MOTOR X
RATING PLATE
2006 UNDERVOLT CTRL ENABLE (TIME)
2008 MAXIMUM FREQ 50 HZ (DEPENDS ON THE MOTOR SIZE, CHECK X
ALSO YOUR APPLICATION)
2107 START INHIBIT ON
2202 ACCELER TIME 1 10
2203 DECELER TIME 1 10
2606 U/F RATIO SQUARE
3101 NR OF TRIALS 5
3106 AR UNDER VOLTAGE ENABLE

20
The following parameters are needed with pressure or flow control (operation modes PID control with 1
setpoint and PID control with 2 setpoints). The diagrams below are an example how to choose the
value for internal setpoint (parameters 4020 and 4120). For more detailed information on parameters,
refer to ACS 400 User’s Manual, Complete Parameter List, Group 40: PID Control and Group 41: PID
Control (2).
Table 2 PID regulator 1.
Code Name Default Set User
4001 PID GAIN 0.7 (PID GAIN FACTOR)
4002 PID INTEG TIME 10 (PID INTEGRATION TIME)
4003 PID DERIV TIME 0S
4004 PID DERIV FILTER 0S
4016 PID PARAM SET DI3
4019 SET POINT SEL INTERNAL
4020 INTERNAL SETPNT 50 % (SETPOINT 1 IN %, SEE DIAGRAM BELOW)
Table 3 PID regulator 2.
Code Name Default Set User
4101 PID GAIN 0.7 (PID GAIN FACTOR)
4102 PID INTEG TIME 10 (PID INTEGRATION TIME)
4103 PID DERIV TIME 0S
4104 PID DERIV FILTER 0S
4119 SET POINT SEL INTERNAL
4120 INTERNAL SETPNT 100 % (SETPOINT 2 IN %, SEE DIAGRAM BELOW)

Figure 6 Reference value (%) selection from the setpoint.

Setpoint value with pressure range 0-250 Pa Setpoint value with pressure range 0-500 Pa

100 100

90 90
Parameter 4020 and 4120 value [%]
Parameter 4020 and 4120 value [%]

80 80

70 70

60 60

50 50

40 40

30 30

20 20

10 10

0 0
0 25 50 75 100 125 150 175 200 225 250 0 50 100 150 200 250 300 350 400 450 500
Pressure [Pa] Pressure [Pa]

Using Other Features of ACS 400V


With ACS 400V the user can also take advantage of the standard ACS 400 frequency converter
features. All the standard ACS 400 functionality is available.
The parameter default values of the ACS 400V differ from the default values of the standard ACS 400
drive in some points. The ACS 400V parameter values can be manually changed to any other value.
Note! If some another macro from ACS 400 User’s Manual is used, the parameter values need to be
manually changed. Changing parameter 9902 APPLICATION MACRO will always cause the ACS 400V to
show ACS 400V specific default values for parameters specified in tables 1, 2 and 3.

21
Appendix 1:
Electro Magnetic Compatibility EMC
The ACS 400V unit is delivered with a RFI filter. The RFI filter must be used in order to comply with
EN61800-3, First Environment, Restricted Distribution, and AS/NZS 2064, 1997, Class A
requirements.
The motor cable lengths have to be limited as specified in the table below and the cable must have
effective screen. At the motor end, the cable screen must be earthed 360 degrees with an EMC cable
gland (e.g. Zemrex SCG screened cable glands). For more detailed cabling instructions refer to the
ACS 400 User’s Manual Appendix C.

Table 4 Maximum motor cable lengths with input filters ACS400-IF11-3... ACS400-IF41-3 and
switching frequency 4 kHz or 8 kHz.

Switching Frequency
Converter Type Filter
4 kHz 8 kHz
ACS 401-V004-3-x ACS400-IF11-3 100 m -
ACS 401-V005-3-x ACS400-IF11-3 100 m -
ACS 401-V006-3-x ACS400-IF11-3 100 m -
ACS 401-V009-3-x ACS400-IF21-3 100 m 100 m
ACS 401-V011-3-x ACS400-IF21-3 100 m 100 m
ACS 401-V016-3-x ACS400-IF31-3 100 m 100 m
ACS 401-V020-3-x ACS400-IF31-3 100 m 100 m
ACS 401-V025-3-x ACS400-IF41-3 100 m 100 m
ACS 401-V030-3-x ACS400-IF41-3 100 m 100 m
ACS 401-V041-3-x ACS400-IF41-3 100 m 100 m

Conducted emission with input filters ACS400-IF11-3 and ACS400-IF21-3 complies with the limits for
unrestricted distribution class in First Environment as specified in EN61800-3 (EN50081-1) provided
that maximum motor cable length is 30 m and switching frequency 4 kHz.

Distribution Networks Isolated from Earth


Input filters designed for ACS 400V cannot be used in an isolated, or high impedance earthed industrial
distribution networks.

Line current harmonics


The standard EN 61800-3 refers to EN 61000-3-2 which specifies limits for harmonic current emissions
for equipment intended to be connected to public low-voltage distribution systems.

Low-Voltage Public Supply Network


The limits and requirements of the EN 61000-3-2 apply for equipment with rated current ≤16A. The
ACS 400V is a professional equipment to be used in trades, professions or industries and which is not
intended for sale to the general public. Therefore the ACS 400V with a total rated power greater than
1kW conforms with EN 61000-3-2.

22
Industrial Networks
If ACS 400V is used in an industrial installation for which the EN 61000-3-2 is not relevant, a
reasonable economical approach which considers the total installation shall be used.
Typically a single low power equipment like ACS 400V does not cause a significant voltage distortion to
network. However, the user shall be aware of the values of the harmonics currents and voltages
occurring within the power supply system before connecting the ACS 400V, as well as the internal
impedance of the supply system. The current harmonic levels of the ACS 400V under rated load
conditions are available on request and the assessment procedure given in appendix B of the EN
61800-3 may be used as a guide.

23
24
Subject to change without prior notice.
3AFE 64648900 REV B

Effective: 2.9.2002
© 2002 ABB Oy
EN

ABB Oy
BAU Drives
P.O. Box 184
00381 Helsinki
FINLAND
Telephone +358-10-2211
Telefax +358-10-222 2681

Vous aimerez peut-être aussi