Vous êtes sur la page 1sur 12

Copyright 2001, NFPA

Report of the Committee on protection at airport facilities involving construction engineering


but excluding airport fixed fueling systems.
Airport Facilities
This list represents the membership at the time the Committee was
Gene E. Benzenberg, Chair balloted on the text of this edition. Since that time, changes in the
Alison Control Inc., NJ [M] membership may have occurred. A key to classifications is found at the
front of this book.
Michael E. Aaron, The RJA Group, Inc., IL [SE]
Thomas G. Burk, Federal Express Corporation, TN [U] This portion of the Technical Committee Report of the
David J. Burkhart, Code Consultants Inc., MO [SE] Committee on Airport Facilities is presented for adoption.
Bruce G. Carpenter, Aero Automatic Sprinkler Co., AZ [IM]
Rep. NFPA Fire Service Section This Report on Comments was prepared by the Technical
Jeffrey W. DeLong, Industrial Risk Insurers, WA [I] Committee on Airport Facilities, and documents its action on the
James Devonshire, Buckeye Fire Equipment Company, TX [M] comments received on its Report on Proposals on NFPA 409,
James Doctorman, The Boeing Company, KS [U] Standard on Aircraft Hangars, 1995 edition, as published in the
Scott Enides, SRI Fire Sprinkler Corporation, NY [IM] Report on Proposals for the 2001 May Meeting.
Rep. National Fire Sprinkler Association
Joseph E. Gott, U.S. Naval Facilities Engr Command, DC [E] This Report on Comments has been submitted to letter ballot of
L. Matthew Gwinn, Delta Air Lines, GA [U] the Technical Committee on Airport Facilities, which consists of 28
Elwin G. Joyce, Kentucky Division of Building Code Enforcement, voting members, in three Segments.
KY [E]
Rep. International Fire Marshals Association Segment No. 1 consists of Comment 409-1 (Log #CC8).
Michael I. Kemmis, Qantas Airways Limited, Australia [U]
Rep. Fire Protection Association Australia On Segment No. 1, 19 voted affirmatively, 4 negatively after
L. M. Krasner, FM Research, MA [I] circulation of negative ballots (Devonshire Joyce, Maman, Walker),
Keith C. Kremkow, Marsh USA, Inc., IL [I] and 5 ballots were not returned (Burkhart, Gott, Lett, Mazur,
Gene A. LaValle, Interlogix, GA [M] Skinner).
Rep. National Electrical Manufacturers Association
Thomas J. Lett, Albuquerque Fire & Safety Associates, NM [SE] Mr. Devonshire voted negatively stating:
Rep. NFPA Fire Service Section Comment 409-1 (Log #CC8) requires review at committee.
Richard J. Louis, The Port Authority of New York & New Jersey,
NY [E] Mr. Joyce voted negatively stating:
Rep. Airports Council International, Inc. - North America I do not see a problem with ROP 409-4 as each hangar has its
Sarah Maman, Schirmer Engineering Corporation, FL [SE] own protection system and drainage requirements to keep any fuel
Christy J. Marsolo, Tyco International Ltd., GA [M] problem within the hangar. Additionally, if one pump system
Al Mazur, Transport Canada, ON, Canada [E] supplies all hangars there is a redundant requirement for water
John J. O’Sullivan, British Airways, PLC, England [U] supply.
Maurice M. Pilette, Mechanical Designs Ltd, MA [SE]
Jack Poole, Poole Fire Protection Engineering, Inc., KS [SE] Mr. Maman voted negatively stating:
Randy D. Pope, Burns & McDonnell Engineering Company, MO The proposal does not make a significant change to the standard
[SE] since the present “hangar building cluster” requirements would
Robert W. Rees, Sunland Fire Protection, Inc., NC [IM] permit the same level of protection for Class I and II hangars.
Rep. American Fire Sprinkler Association, Inc, Section 2-3.2 in NFPA 409, 1995 edition discusses clear spaces
Robert Saunders, Wasatch Design Consultants, UT [SE] around hangars and introduces the “hanger building cluster”
(Vote Ltd to NFPA 415) concept. As far as I can see, there is no limit on the number of
Michael T. Skinner, Massachusetts Port Authority Fire/Rescue, hangars that may be in a cluster even if they are wood frame.
MA [E] There is presently nothing in NFPA 409 that would disallow an
Fred K. Walker, U.S. Air Force, FL [U] unlimited number of Group I, II or III hangars even if positioned
1 in. apart as long as they are considered as a “hangar building
Alternates cluster”. In addition, the protection requirements for hangars are
identical if they are arranged in a “hangar building cluster” or
Nathaniel J. Addleman, The RJA Group, Inc., TX [SE] separated.
(Alt. to M. Aaron) From a fire protection point of view, if a fire should occur in a
John Robert Boyer, Edwards Systems Technology, Inc., NJ [M] hangar with no separation walls, the spill and subsequent fire
(Alt. to G. LaVelle) could occur between two bays and/or two fire protection systems.
Delbert R. Chase, Jr., Federal Express Corporation, TN [U] However, when walls separate hangars, the fuel will be prevented
(Alt. to T. G. Burk) from spreading to an adjacent bay. This would also hold true in
Ronald B. Coker, Carter & Burgess, TX [IM] the case of two detached hangars separated by unrated walls.
(Alt. to R. W. Rees) While it is true that the unrated walls are not equal in protection to
Ray W. Dillon, APi Group, Inc., TX [IM] a 3 hour rated wall, the exterior wall in the hangar of fire origin
(Alt. to S. Enides) would limit the spread of the fire and more likely the fire
James M. Freeman, Industrial Risk Insurers, GA [I] protection system will activate before exposing the adjacent
(Alt. to J. W. DeLong) building. This assumes that the two adjacent hangars are fully
Kevin M. Green, Schirmer Engineering Corporation, CA [SE] protected.
(Alt. to S. Maman) The bottom line is that the problem is not with the ROP Proposal
Frank M. E. Hughes, British Airways, PLC, England [U] 409-4 but with the cluster requirements in Section 2-3. Presently,
(Alt. to J. J. O’Sullivan) there are no limits as to the number of total area of hangars
Dennis C. Kennedy, Ansul Fire Protection, WI [M] permitted in a “hangar building cluster” even if they are
(Alt. to C. J. Marsolo) constructed of wood. In addition, the protection of hangars in a
John E. Loehle, Air National Guard Readiness Center, MD [U] “hangar building cluster” is based on the individual hangars not the
(Alt. to F. K. Walker) aggregate.
Danny Luey, Port Authority of New York & New Jersey, NY [E] Voting affirmative on this ballot will not address the underlining
(Alt. to R. J. Louis) concern over hangars arranged in clusters and will create
Robert C. Merritt, FM Global, MA [I] confusion with those using the standard as to the level of
(Alt. to L. M. Krasner) protection intended. Accordingly, revisions are required for
Robert J. Tabet, Naval Facilities Engineering Command, VA [E] “hangar building clusters” to address the issues raised in the
(Alt. to J. E. Gott) substantiation section of this ballot and those I have outlined above
including construction and protection of hangars arranged in
Nonvoting clusters. I strongly suggest that if at all possible, these revisions be
made during this code cycle.
Jerome Lederer, Laguna Hills, CA

Staff Liaison: Mark T. Conroy Mr. Walker voted negatively stating:


Committee Scope: This Committee shall have primary The substantiation provided with the comment is technically
responsibility for documents on fire safety for the construction and incorrect in three critical areas:

495
NFPA 409 — May 2001 ROC — Copyright 2001, NFPA

1. First it claims the ROP no longer requires a clear distance Segment No. 2 consists of Comment 409-16 (Log #6)
between Group I and hangars and certain Group II hangars. That
condition is already clearly approved in NFPA 409 Paragraph 2-3.2 On Segment No. 2, 23 voted affirmatively, and 5 ballots were not
which applies equally to both Group I and Group II hangars and returned (Burkhart, Gott, Lett, Mazur, Skinner).
mixed groups of Group I and Group II hangars. The last sentence
states lesser separation distances down to and including zero Mr. Kremow voted affirmative with the following comment:
clearance are acceptable provided you identify the grouping of 6.14.7.3 should delete reference to “within 5 ft of”, as we voted on
hangars as a “cluster”. during meeting.
“2-3.2 For single hangar buildings, the clear space distances
specified in Table 2-3.2 shall be maintained on all sides of the Segment No. 3 consists of the balance of Comments 409-2 through
single hangar. Where mixed types of construction are involved, the 409-15 and 409-17 through 409-18.
less fire-resistant type of construction shall be used to determine
the clear space required. Where the minimum clear space On Segment No. 3, 22 voted affirmatively, 1 abstained (Krasner)
specified in Table 2-3.2 is not met, the buildings shall be and 5 ballots were not returned (Burkhart, Gott, Lett, Mazur,
considered a hangar building cluster.” Skinner).
2. Second, the substantiation claims the ROP would permit
someone to build hangars with less water supply than is now Mr. Krasner abstained stating:
required. Again this is incorrect since the three hangar Reasons for my negative ROP balloting are still valid. However,
configuration shown in the drawing is already permitted under in the interest of moving on after all the chads have been counted
Paragraph 2-3.2 in the current standard. 409 requires protection be and lacking any support from other committee members, I am not
designed based on the floor area of a hangar not based on voting negatively.
exposures. Paragraph 2-3.2 permits any number of Group I and
Group II hangars to be placed adjacent with zero clearance simply
by identifying the grouping as a cluster.
3. Third, the current standard limits the building size (square
footage) for individual Group II hangars, however, applying the
rule in 2-3.2 you can place an unlimited number of Group II
hangars in a cluster and jointly cluster them with Group I hangars.
The ROP corrects this by limiting any cluster including Group II
hangars to the maximum permitted for an individual Group II
hangar.
Then what does the ROP really accomplish?
First, it corrects the significant oversight in the current code
allowing unlimited groups of unseparated Group II and mixed
Group I and II hangars.
Second, it writes in more rational language, similar to that found
in building codes, what NFPA 409 has always permitted. This may
be the first time many committee members have realized what is
actually permitted by the code, but, it does not make good
management to bury it back in the code.
To vote in the affirmative on the proposal based on the
substantiation especially the water flow discussion is to state the
current NFPA 409 is broken and should remain broken. If
members believe the conditions depicted in the substantiation
should not be permitted then the entire document should be
returned to committee because regardless if you vote affirmative or
negative the ability to build the conditions shown, exist now.

496
NFPA 409 — May 2001 ROC — Copyright 2001, NFPA

(Log #CC8) SUBSTANTIATION: I feel that the suggested revision to utilize


409- 1 - (2-3): Accept text instead of a reference to a table is more user friendly in this
SUBMITTER: Technical Committee on Airport Facilities case being there are only two distances in the table and only one
COMMENT ON PROPOSAL NO: 409-4 construction type requiring the second distance.
RECOMMENDATION: Reject Proposal 409-4 and return to COMMITTEE ACTION: Reject.
previous edition text. COMMITTEE STATEMENT: The Manual of Style suggests not
SUBSTANTIATION: This proposal does make a significant using exceptions.
change to the standard as it no longer requires a clear distance
separation between Group I and certain Group II hangars. ___________________
The existing section 2-2 Internal Separations will remain as
written in the 1995 edition of 409. (Log #8)
Consider that we have a three bay 747 hangar without any internal 409- 3 - (2-3.3, 2-3.4): Reject
separations, the same hangar with internal separations, and three SUBMITTER: George M. Lanier, Rome Fire Dept., GA
single bay 747 hangars built next to each other with only a 5 ft. COMMENT ON PROPOSAL NO: 409-4
walkway separating them. What would be the impact to the site RECOMMENDATION: Suggest renumbering proposed 2-3.3 as 2-
water supply assuming that the 100 ft. radius rule is applied and 3.4 and proposed 2-3.4 as 2-3.3. Also, delete Table 2-3.4.
covers two 747 bays? Revise the revised 2-3.3 to read as follows:
Below is a 3 Bay 747 Hangar without internal separations. The 100 "2-3.3 The clear space distances specified in Table 2-3.4 shall to
ft. radius rule requires water supply for 2 of the 3 bays. be maintained on all sides of the hangar building clusters shall be
(crosshatch) 100 ft (30 m)."
Then use exceptions based on existing text to complete the
provisions:
"Exception No. 1: For Type I (443) and (332) and for Type II
(222) construction the minimum distance may be reduced to 75 ft
(23m);
Exception No. 2: For Type V (III) and (000) types of
Below is a 3 Bay 747 Hangar with 3-hour internal separations. The
100 ft. radius rule requires water supply for 1 of the 3 bays. construction, the minimum separation distance shall be 125 ft (38
(crosshatch) m);
Exception No. 3: Where there is mixed types of construction and
Type V (111) or (000) construction is included, the minimum
separation distance shall be 125 ft (38 m).
Exception 4: Where there is mixed types of construction
including Types II(000), Type III, or Type IV construction and not
Type V, the minimum separation distance shall be 100 ft (30 m)."
Also revise the new 2-3.4 to read as follows:
Below is 3 single Bay 747 Hangars separated by only a man "2-3.4 The minimum required clear spaces between structures
walkway as allowed in the ROP. The 100 ft. radius rule requires specified in 2-3.2 and 2-3.3, Tables 2-3.2 and 2-3.4 shall not be used
water supply for 1 of the hangars only. for the storage or parking of aircraft or concentrations of
combustible materials, nor shall buildings of any type be created
therein."
SUBSTANTIATION: I feel that the suggested revision to utilize
text instead of a reference to a table is more user friendly in this
case. Also, I feel that 2-3.3 of the ROP text needs to follow the
provisions that establish the minimum separation distances. Under
separate proposal, I have recommended the revision of 2-3.2.
If you were to examine the impact of the new Low level foam Further, I feel that Type IV construction, which is essentially
systems using these same examples you would find that the first combustible, should be included with Type III construction with
hangar would require water for three bays and the other two regard to separation distances.
examples would still require water for one bay. COMMITTEE ACTION: Reject.
The existing standard would require 3-hour firewalls or more COMMITTEE STATEMENT: The Manual of Style suggests not
separation between the third exampled hangars. using exceptions.
Although questions have been raised regarding the existing text, it
would be best to return to the previous edition text until the ___________________
committee has had a chance to discuss the above concerns and
develop revised text that resolves all of the issues.
COMMITTEE ACTION: Accept. (Log #CC4)
409- 4 - (3-1.2 ): Accept
___________________ SUBMITTER: Technical Committee on Airport Facilities
COMMENT ON PROPOSAL NO: 409-6
RECOMMENDATION: Revise 3.1.2 to read as follows:
(Log #7) 3.1.2 Group I aircraft hangar storage and service areas housing
409- 2 - (2-3.2 ): Reject unfueled aircraft shall be provided with automatic sprinkler
SUBMITTER: George M. Lanier, Rome Fire Dept., GA protection as specified in Sections 4.2 and 4.8.
COMMENT ON PROPOSAL NO: 409-4 SUBSTANTIATION: Corrected the reference for water supply
RECOMMENDATION: Suggest deleting Table 2-3.2 and revising COMMITTEE ACTION: Accept.
2-3.2 to read as follows: ___________________
"The clear space distances in Table 2-3.2 shall to be maintained
on all sides of a hangar or group of hangars meeting 2-3.1.1 (Log #10)
through 2-3.1.3 shall be 50 ft (15 m)." 409- 5 - (3-2.1 ): Reject
Then use exceptions based on existing text to complete the SUBMITTER: Southern Regional Fire Code Dev. Committee
provision to read as follows: COMMENT ON PROPOSAL NO: 409-6
"Exception No. 1: For Type V (111) and (000) construction the RECOMMENDATION: Revise 3.2.1 to read:
minimum separation distance shall be 75 ft (23 m). 3.2.1.1 Automatic Sprinkler Systems.
Exception No. 2 Where there is mixed types of construction and 3.2.1.2 Information supplied in these plans and specifications
shall be in accordance with NFPA 13, Standard for the Installation
Type V (111) or (000) construction is included, the minimum of Sprinkler Systems.
separation distance shall be 75 ft (23 m). 3.2.1.2.1 Working plans shall be drawn to an indicated scale, on
Exception No. 3: Where the minimum clear space requirement sheets of uniform size, with a plan of each floor, and shall show
of 2-3.2 or the exceptions are not met, the building shall be those items from the following list that pertain to the design of the
considered a hangar building cluster." system:

497
NFPA 409 — May 2001 ROC — Copyright 2001, NFPA

(1) Name of owner and occupant. 3.2.1.2.2 The working plan submittal shall include the
(2) Location, including street address. manufacturer’s installation instructions for any specially listed
(3) Point of compass. equipment, including descriptions, applications, and limitations
(4) Full height cross section, or schematic diagram, including for any sprinklers, devices, piping, or fittings. (NFPA 13: 8-1.1.2)
structural member information if required for clarity and including 3.2.1.2 Low-Expansion Foam Systems
ceiling construction and method of protection for nonmetallic 3.2.1.2.1 Plans. Preparation of plans shall be entrusted only to
piping. fully experienced and responsible persons. They shall be submitted
(5) Location of partitions. for approval to the authority having jurisdiction before foam
(6) Location of fire walls. systems are installed or existing systems are modified. These plans
(7) Occupancy class of each area or room. shall be drawn to an indicated scale or shall be suitably
(8) Location and size of concealed spaces, closets, attics, and dimensioned. (NFPA 11:4-4)
bathrooms. 3.2.1.2.2 The plans shall include or be accompanied by the
(9) Any small enclosures in which no sprinklers are to be following information, where applicable:
installed. (a) Physical details of the hazard; including the location,
(10) Size of city main in street and whether dead end or arrangement, and hazardous materials involved
circulating; if dead end, direction and distance to nearest (b) Type and percentage of foam concentrate
circulating main; and city main test results and system elevation (c) Required solution application rate
relative to test hydrant (see A-9-2.1). (d) Water requirements
(11) Other sources of water supply, with pressure or elevation. (e) Calculations specifying required amount of concentrate
(12) Make, type, model, and nominal K-factor of sprinklers. (f) Hydraulic calculations (See Chapter 6 of NFPA 13, Standard
(13) Temperature rating and location of high-temperature for the Installation of Sprinkler Systems, for hydraulic calculation
sprinklers. procedures.)
(14) Total area protected by each system on each floor. (g) Identification and capacity of all equipment and devices
(15) Number of sprinklers on each riser per floor. (h) Location of piping, detection devices, operating devices,
(16) Total number of sprinklers on each dry pipe system, generators, discharge outlets, and auxiliary equipment
preaction system, combined dry pipe-preaction system, or deluge (i) Schematic wiring diagram
system. (j) Explanation of any special features (NFPA 11:4-4.1)
(17) Approximate capacity in gallons of each dry pipe system. 3.2.1.2.3 Complete plans and detailed data describing pumps,
(18) Pipe type and schedule of wall thickness. drivers, controllers, power supply, fittings, suction and discharge
(19) Nominal pipe size and cutting lengths of pipe (or center-to- connections, and suction conditions shall be submitted by the
center dimensions). Where typical branch lines prevail, it shall be engineer or contractor to the authority having jurisdiction for
necessary to size only one typical line. approval before installation. (NFPA 11:4-4.2)
(20) Location and size of riser nipples. 3.2.1.2.4 Where field conditions necessitate any significant change
(21) Type of fittings and joints and location of all welds and from the approved plan, revised "as installed" plans shall be
bends. The contractor shall specify on drawing any sections to be supplied for approval to the authority having jurisdiction. (NFPA
shop welded and the type of fittings or formations to be used. 11:4-4.2.1)
(22) Type and locations of hangers, sleeves, braces, and methods 3.2.1.2.5 Charts that specify head, delivery, efficiency, and brake
of securing sprinklers when applicable. horsepower curves of pumps shall be furnished by the contractor.
(23) All control valves, check valves, drain pipes, and test (NFPA 11:4-4.3)
connections. Renumber the remaining sections.
(24) Make, type, model, and size of alarm or dry pipe valve. SUBSTANTIATION: The revised wording is extracted from NFPA
(25) Make, type, model, and size of preaction or deluge valve. 13 and 11 and should be extracted in this standard to ensure that
(26) Kind and location of alarm bells. no conflicts exist between the design document and the document
(27) Size and location of standpipe risers, hose outlets, hand requiring the system or protection. The extraction of the text from
hose, monitor nozzles, and related equipment. 13 and 11 provides better guidance for the designer, users and
(28) Private fire service main sizes, lengths, locations, weights, enforcer of the code and is consistent with the installation
materials, point of connection to city main; the sizes, types and standards.
locations of valves, valve indicators, regulators, meters, and valve COMMITTEE ACTION: Reject.
pits; and the depth that the top of the pipe is laid below grade. COMMITTEE STATEMENT: The Committee feels that they
(29) Piping provisions for flushing. applied criteria that is appropriate for the occupancy (the hangar).
(30) Where the equipment is to be installed as an addition to an
existing system, enough of the existing system indicated on the ___________________
plans to make all conditions clear.
(31) For hydraulically designed systems, the information on the (Log #3)
hydraulic data nameplate. 409- 6 - (3-2.3.4.6, 3-2.3.5.5, 3-2.5.3.6, 3-2.5.4.6, 3-2.10.8.1, A-3-2.7.2,
(32) A graphic representation of the scale used on all plans. A-3-2.10.7, 4-5.6 ): Accept
(33) Name and address of contractor. SUBMITTER: James L. Boyer, Firetrol, Inc.
(34) Hydraulic reference points shown on the plan that COMMENT ON PROPOSAL NO: 409-6
correspond with comparable reference points on the hydraulic RECOMMENDATION: In new 3-2.3.4.6, 3-2.3.5.5, 3-2.5.3.6, 3-
calculation sheets. 2.5.4.6, 3-2.10.8.1, A-3-2.7.2. A-3.2.10.7, 4-5.6, replace "NFPA 20,
(35) The minimum rate of water application (density), the Standard for the Installation of Centrifugal Fire Pumps" with
design area of water application, in-rack sprinkler demand, and the "NFPA 20, Standard for the Installation of Stationary Pumps for
water required for hose streams both inside and outside. Fire Protection" in all.
(36) The total quantity of water and the pressure required noted SUBSTANTIATION: NFPA 20, was retitled for the 1999 edition.
at a common reference point for each system. COMMITTEE ACTION: Accept.
(37) Relative elevations of sprinklers, junction points, and supply ___________________
or reference points.
(38) If room design method is used, all unprotected wall (Log #9)
openings throughout the floor protected. 409- 7 - (3-2.4 ): Reject
(39) Calculation of loads for sizing and details of sway bracing. SUBMITTER: Southern Regional Fire Code Dev. Committee
(40) The setting for pressure-reducing valves. COMMENT ON PROPOSAL NO: 409-13
(41) Information about backflow preventers (manufacturer, size, RECOMMENDATION: Reject proposal 409-13 and accept
type). proposals 409-14, 409-15 and 409-16.
(42) Information about antifreeze solution used (type and SUBSTANTIATION: Proposals 409-14, 15, & 16 provide the
amount). appropriate guidance in installing these types of systems.
(43) Size and location of hydrants, showing size and number of Proposal 409-13 is inconsistent with the appropriate documents
outlets and if outlets are to be equipped with independent gate for the installation of fire pumps and reference should be made to
valves. Whether hose houses and equipment are to be provided, those documents. Also the NFPA Manual of
and by whom, shall be indicated. Static and residual hydrants that Style policy on extraction should be followed. Designers,
were used in flow tests shall be shown. enforcers and users will get conflicting requirements for these
(44) Size, location, and piping arrangement of fire department systems.
connections. (NFPA 13: 8-1.1.1) COMMITTEE ACTION: Reject.

498
NFPA 409 — May 2001 ROC — Copyright 2001, NFPA

COMMITTEE STATEMENT: ROP proposal 409-13 provides more 3.2.5.4.3 The foam system shall use low-level discharge nozzles.
substance, clarity, definition and guidance than the proposed Where monitor nozzles are used, they shall be provided with
acceptance of proposals 409-14, 409-15 and 409-16. individual manual shutoff valves for each nozzle. The discharge
• ROP 409-14 was rejected by the committee. This proposal nozzles shall be arranged to achieve initial foam coverage in the
recommends that the language be changed to advise the user to expected aircraft parking area.
consult the current version of NFPA 20 standard. This has been 3.2.5.4.4 Nozzles shall be located and installed so that aircraft
done already in 409-13, paragraph 3-2.4.1 with the modified positioning and workstand placement will not necessitate removal
exceptions that the 409 committee discussed, agreed and voted on or repositioning of nozzles. All nozzle settings shall be marked and
that were necessary variances from NFPA 20 for aircraft hangar fire permanently secured in position after installation and acceptance
protection. testing.
• ROP 409-15 was rejected by the committee. This is addressing 3.2.5.4.5 Electric power reliability for oscillating nozzles shall be
the name change of NPFA 20. It is editorial in nature and has in accordance with electric fire pump requirements of NFPA 20,
already been addressed in Comment 409-6 (Log # 3). Standard for the Installation of Centrifugal Fire Pumps.
• ROP 409-16 was rejected by the committee. The same reason 3.2.5.5 Low-Level High-Expansion Foam Systems.
for rejection as earlier, which states, " NFPA 409 is more definitive 3.2.5.5.1 Low-level high-expansion foam systems shall be designed
and provides clear concise requirements in one location." and installed in accordance with NFPA 11A, Standard for Medium-
and High-Expansion Foam Systems, requirements for local
application systems.
___________________ 3.2.5.5.2 The effective application rate shall be a minimum of 3
cfm/ft2 (0.0014 m3/s).
3.2.5.5.3 The discharge rate of the system shall be based on the
(Log #2) application rate multiplied by the entire aircraft storage and
409- 8 - (3-2.4.9 (new), 3-2.4.3 (old) ): Accept servicing floor area. The application total discharge rate shall
SUBMITTER: James L. Boyer, Firetrol, Inc. include the sprinkler breakdown factor specified in 2.3.5.2(b) of
COMMENT ON PROPOSAL NO: 409-13 NFPA 11A, Standard for Medium- and High-Expansion Foam
RECOMMENDATION: Revise text to read as follows: Systems.
3-2.4.9 (Existing 3-2.4.3) Controllers for foam concentrate 3.2.5.5.4 The high-expansion foam generators shall be arranged to
pumps shall be as follows: achieve initial foam coverage in the expected aircraft parking area.
(a) For electric drive foam concentrate pumps greater than 30 3.2.5.5.5 Foam generators shall be supplied with air from outside
horsepower, a listed fire electric foam pump controller shall be the aircraft storage and servicing area. Roof vents shall be located
used. to avoid recirculation of combustion products into the air inlets of
(b) For electric drive foam concentrate pumps greater than 15 the foam generators.
horsepower but not exceeding 30 horsepower, a listed fire electric 3.2.5.5.6* Foam generators shall be powered by reliable water-
foam pump controller or limited service foam pump controller driven or electric motors. Electric power reliability for foam
shall be used. generators shall be consistent with electric fire pump requirements
(c) For electric foam concentrate pumps less than 15 specified in Chapters 6 and 7 of NFPA 20, Standard for the
horsepower, a listed limited service controller shall be used. Installation of Centrifugal Fire Pumps.
(d c For diesel engine driven foam concentrate pumps, a listed SUBSTANTIATION: Editorially moved the title "Low-Level Low
Expansion Foam Systems" and renumbered paragraphs
fire pump controller shall be used. accordingly.
SUBSTANTIATION: (a) and (b): UL 218, Standard for Fire COMMITTEE ACTION: Accept.
Pump Controllers, Section 71.1, requires the "foam pump
controller" marking: 71.1. In addition to the requirements in ___________________
Section 33, Marking, the controller shall be marked "Foam Pump
Controller," preceded by either the term "Electric" or "Limited
Service," depending on the type of controller. (Log #CC3)
(c) There is no technical reason to prevent a motor of less than 409- 10 - (3-2.8 ): Accept
15 HP from being controlled by a limited service controller or a SUBMITTER: Technical Committee on Airport Facilities
fire pump controller. COMMENT ON PROPOSAL NO: 409-1
COMMITTEE ACTION: Accept. RECOMMENDATION: Revise 3.2.8 to read as follows:
3.2.8 Detection/Actuation System Design.
___________________ 3.2.8.1 General.
3.2.8.1.1 Actuation systems shall be provided with complete
circuit supervision and shall be arranged in accordance with
(Log #CC7) Section 3.4 of this chapter.
409- 9 - (3-2.5 ): Accept 3.2.8.1.2 These detectors shall be installed in accordance with
SUBMITTER: Technical Committee on Airport Facilities NFPA 72, National Fire Alarm Code.
COMMENT ON PROPOSAL NO: 409-6 3.2.8.1.3 Detection systems shall be provided with supervision as
RECOMMENDATION: Revise section 3.2.5 as follows: required by NFPA 72, National Fire Alarm Code.
3.2.5 Low-Level Foam Protection Systems. SUBSTANTIATION: Editorial
3.2.5.1 Hangars protected in accordance with Section 3.1.1(b) or COMMITTEE ACTION: Accept.
(c) shall be protected with a listed low-level foam protection
system. ___________________
3.2.5.2 Each low-level foam protection system shall be designed,
installed, and maintained in accordance with NFPA 11, Standard
for Low-Expansion Foam, or NFPA 11A, Standard for Medium- (Log #1)
and High-Expansion Foam Systems. 409- 11 - (3-2.10.8.4 ): Accept
3.2.5.3 The low level foam system shall be designed to achieve SUBMITTER: James L. Boyer, Firetrol, Inc.
distribution of foam over the entire aircraft storage and service COMMENT ON PROPOSAL NO: 409-6
area. The design objective shall be to achieve coverage of the RECOMMENDATION: Revise text to read as follows:
entire aircraft storage and servicing area to within 5 ft of the 3-2.10.8.4* Fire pumps shall be started automatically by either a
perimeter walls and doors within 3 minutes of system actuation. drop in water pressure or a signal from the detection control
3.2.5.4 Low-Level Low Expansion Foam Systems. Foam systems panel. Where two or more electrically driven fire pumps from the
shall be of the fixed type and shall be designed and installed in same electrical feeder are used, they shall be electrically controlled
accordance with the requirements for fixed-type systems in NFPA to prevewnt simultaneous provided with automatic sequential
11, Standard for Low-Expansion Foam. starting.
3.2.5.4.1 Where AFFF concentrate is used, the minimum
application rate shall be 0.10 gpm of foam solution per ft2 (4.1
L/min/m2). The minimum application rate shall be 0.16 gpm of
foam solution per sq ft (6.5 L/min/m2) where protein-based or
fluoroprotein-based concentrate is used.
3.2.5.4.2* The discharge rate of the system shall be based on the
rate of application multiplied by the entire aircraft storage and
servicing floor area.

499
NFPA 409 — May 2001 ROC — Copyright 2001, NFPA

SUBSTANTIATION: "Sequential starting" must be provided refuel the aircraft and then only have to provide a lesser duration.
whether the pumps are electrically driven, supplied by the same It seems illogical to increase a hazard in order to reduce a
feeders, supplied by the same service conductors, or diesel engine protection criteria.
driven to reduce "voltage sag" (for electrically driven) and COMMITTEE ACTION: Reject.
hydraulic-mechinical shock to the piping system. COMMITTEE STATEMENT: The time duration criteria is
{Reference: see NFPA 20-1999, 4-5.2.5 and 9-5.2.4}. appropriate considering that the 30 minute duration is for
COMMITTEE ACTION: Accept. protection utilizing foam and an overhead water sprinkler system.
The 60 minute criteria is for just an overhead water sprinkler
___________________ system.

___________________
(Log #CC5)
409- 12 - (4-1.3 ): Accept
SUBMITTER: Technical Committee on Airport Facilities (Log #CC6)
COMMENT ON PROPOSAL NO: 409-6 409- 15 - (5-1.7 ): Accept
RECOMMENDATION: Revise 4.1.3 to read as follows: SUBMITTER: Technical Committee on Airport Facilities
4.1.3 Automatic closed-head sprinkler protection shall be COMMENT ON PROPOSAL NO: 409-25
provided inside separate shop, office, and storage areas located RECOMMENDATION: The proposal should refer to the second
inside aircraft maintenance and servicing areas. The design shall be paragraph of 5-1.7 as there is no 5-1.7.1
in accordance with hazard classifications specified in NFPA 13, SUBSTANTIATION: Editorial
Standard for the Installation of Sprinkler Systems. COMMITTEE ACTION: Accept.
SUBSTANTIATION: Editorial
COMMITTEE ACTION: Accept. ___________________

___________________
(Log #6)
409- 16 - (Chapter 6): Accept in Principle
(Log #11) SUBMITTER: Lee C. DeVito, FIREPRO Incorporated
409- 13 - (4-3.3 ): Reject COMMENT ON PROPOSAL NO: 409-5
SUBMITTER: Southern Regional Fire Code Dev. Committee RECOMMENDATION: Create a new chapter addressing the use
COMMENT ON PROPOSAL NO: 409-20 of membrane-covered rigid steel frame structures as an acceptable
RECOMMENDATION: Reject Proposal 409-20 and accept construction type for aircraft hangars. This chapter would follow
Proposals 409-19, 409-21, and 409-22. the existing Chapter 5 Group III Aircraft Hangars. Chapter
SUBSTANTIATION: Proposals 409-19, 21, and 22 provide the Membrane-covered Rigid Steel Frame Structure Hangars
appropriate guidance in installing these types of systems. 6.1* Design.
Proposal 409-20 is inconsistent with the appropriate documents 6.1.1 The design, materials, and construction of the building shall
for the installation of fire pumps and foam system pumps and be based on design documents, such as drawings, reports,
reference should be made to those documents. Also the NFPA calculation, and specifications, prepared and signed and sealed by
Manual of a licensed architect or engineer knowledgeable in this type of
Style policy on extraction should be followed. Designers, enforcers construction.
and users will get conflicting requirements for these systems. 6.2 Construction.
COMMITTEE ACTION: Reject. 6.2.1 When membrane-covered rigid steel frame structures are
COMMITTEE STATEMENT: The same reason as rejecting used for the construction of aircraft hangars, they shall be
Comment 409-7 (Log # 9). The ROP proposal 409-20 provides constructed in accordance with this standard.
more substance, clarity, definition and guidance than the proposed 6.2.2 The hangar shall all be limited to one story.
acceptance of proposals 409-19, 409-21 and 409-22. In addition, 6.2.3 The hangar shall contain a single hangar fire area.
proposals 409-19 and 409-22 are referencing high expansion foam 6.2.4 The height and area of the hangar shall be limited by the
generator air sources; not foam pumps or their applications. requirements of the applicable local building codes based on the
• ROP 409-19 was rejected by the committee. This proposal has occupancy and type of construction classification.
nothing to do with foam pumps or foam pump applications. 409-19 6.2.5 Testing of membrane materials for compliance with this
is referring to outside air for high expansion generators. section’s use of the categories of noncombustible and limited-
• ROP 409-21 was rejected by the committee. This proposal is combustible materials shall be performed on weathered membrane
addressing NFPA 20 labeling requirements, is editorial in nature material.
and has been addressed by the 409 committee in previous actions. 6.2.6 Flame spread of all membrane materials exposed within the
NFPA 409 is more definitive and provides clear concise structure shall be Class A as defined in Section 6-5 of NFPA 101,
requirements in one location. Life Safety Code.
• ROP 409-22 was rejected by the committee. This proposal has 6.2.7 Flame Resistance. All membrane structure fabric shall meet
nothing to do with foam pumps or foam pump applications. 409-22 the requirements of both the small-scale and large-scale tests
is referring to outside air for high expansion generators. contained in NFPA 701, Standard Methods of Fire Tests for Flame
Propagation of Textiles and Films.
6.2.7.1 The authority having jurisdiction shall require a certificate
___________________ or other evidence of acceptance by an organization acceptable to
the authority having jurisdiction or the report of tests made by
other inspection authorities or organizations acceptable to the
(Log #5) authority having jurisdiction as evidence that the fabric materials
409- 14 - (4-8.2 ): Reject have the required flame resistance.
SUBMITTER: R. T. Leicht, Delaware State Fire Marshal’s Office 6.2.7.2 Where required by the authority having jurisdiction,
COMMENT ON PROPOSAL NO: 409-6 confirmatory field tests shall be conducted using test specimens
RECOMMENDATION: Revise text to read as follows: from the original material, which shall have been affixed at the
The water supply for closed-head water sprinkler system in aircraft time of manufacture to the exterior of the structure.
storage and servicing areas shall meet one of the following: 6.2.8 Material loading and strength shall be based on physical
(a) In aircraft storage and servicing areas housing other than properties of the materials verified and certified by an approved
unfueled aircraft, the water supply shall have a minimum duration testing laboratory.
of 30 minutes at the rate specified in 4-2.5. 6.2.9 The membrane roof for structures in climates subject to
(b) In aircraft storage and servicing areas housing unfueled freezing temperatures and ice buildup shall be composed of two
aircraft, the water supply shall have a minimum duration of 60 layers with an air space between them through which heated air
minutes at the rate specified in 4-2.5. can be moved to guard against ice accumulation. In lieu of the
SUBSTANTIATION: If a water supply duration of 30 minutes is above, any other approved methods that protect against ice
sufficient for areas housing "other than unfueled" aircraft, it should accumulations shall be permitted.
also be sufficient to protect unfueled aircraft. Present proposed 6.2.10 Where provided, roof drains shall be equipped with
language would require a 60-minute duration for unfueled aircraft. electrical elements to protect against ice buildup, which would
As the proposal reads, in cases where the water supply is not able prevent the drains from functioning. Such heating elements shall
to provide the higher duration for unfueled aircraft, one could be served by on-site standby electrical power in addition to the

500
NFPA 409 — May 2001 ROC — Copyright 2001, NFPA

normal public service. In lieu of the above, any other approved 6.9.6 As entry of fuel, oil, and water into landing gear pits is
methods that protect against ice accumulation shall be permitted. inevitable, drainage or pumping facilities shall be provided. Water-
6.3 Maintenance and Operation trapped vapor seals and appropriate separator fuel traps shall be
6.3.1 Instructions in both operation and maintenance shall be provided. Where automatic pumping facilities are necessary, they
transmitted to the owner by the manufacturer of the membrane- shall be suitable for use with aviation fuel and water. The drainage
covered rigid steel frame structure. shall be fully enclosed pipe runs if drainage is routed through
6.4 Internal Separations ventilation or access tunnels to external discharge points.
6.4.1 Mezzanines, tool rooms, and other enclosures within aircraft 6.9.7 Explosion protection shall be provided in landing gear pits
storage and servicing areas shall be constructed of noncombustible and communicating ducts and tunnel areas in the form of
material or limited combustible material as defined in NFPA 220, pressure-relief venting or by a listed explosion prevention system
Standard on Types of Building Construction, in all membrane- installed in accordance with NFPA 69, Standard on Explosion
covered rigid steel frame structure type hangars. Prevention Systems.
6.4.2 Partitions and ceilings separating aircraft storage and 6.9.8 An approved fire protection system shall be installed to
servicing areas from all other areas, shops, offices, and parts protect each pit unless the hangar fire protection required by 6.17
storage areas shall have at least a 1-hour fire resistance rating with is adequate to protect each pit.
openings protected by listed fire doors or shutters having a 6.10 Exposed Interior Insulation. Exposed interior insulation in
minimum fire resistance rating of 45 minutes. the aircraft storage and servicing area of membrane-covered rigid
6.4.3 Where a storage and servicing area has an attached, steel frame structure hangars shall comply with the requirements of
adjoining, or contiguous structure, such as a lean-to, shop, office, NFPA 101®, Life Safety Code®, special provisions for aircraft storage
or parts storage area, the wall common to both areas shall have at hangars, interior wall and ceiling finish criteria.
least a 1-hour fire resistance rating, with openings protected by 6.11 Drainage of Aprons and Hangar Floors.
listed fire doors having a minimum fire resistance rating of 45 6.11.1 When a membrane-covered rigid steel frame structure
minutes and actuated from both sides of the wall. hangar is placed on an undeveloped site, the drainage of aprons
6.5 Clear Space Distance Around Hangars. Precautions shall be and hangar floors of hangars with a hangar fire area greater than
taken to ensure ready access to membrane-covered rigid steel frame 12,000 ft 2 (1,115 m2 ) shall be as specified in 2.11.
structure hangars from all sides. Adequate separation shall be 6.11.2* When a membrane-covered rigid steel frame structure
provided to reduce fire exposure between buildings. The hangar is to be placed on an existing apron, in establishing its
minimum separation requirements shall be determined as location, consideration shall be given to the drainage pattern of the
specified in 2.3 or 5.2 for the type of construction to which the apron and the water requirements of the fire protection systems if
authority having jurisdiction has determined the membrane- suppression systems other than High-expansion foam are utilized.
covered rigid steel frame structure conforms. 6.12 Heating and Ventilating. Heating, ventilating, and air
6.6 Aprons and Floors. conditioning equipment of membrane-covered rigid steel frame
6.6.1 The surface of the grade floor of aircraft storage and structure hangars shall be installed, as applicable, in accordance
servicing areas shall be noncombustible and above the grade of the with 2-12.
approach or apron at the entrance to the hangar. 6.13 Lighting and Electrical Systems.
6.6.2 Hangar aprons shall slope away from the level of the hangar 6.13.1 Artificial lighting shall be restricted to electric lighting.
floors to prevent liquid on the apron surfaces from flowing into the 6.13.2 Electrical services shall be installed in compliance with the
hangars. provisions for aircraft hangars contained in Article 513 of NFPA 70,
6.7 Doors. National Electrical Code.
6.7.1 In membrane-covered rigid steel frame structure hangars 6.13.3 In hangars with aircraft storage and servicing areas greater
with a hangar fire area greater than 12,000 ft 2 (1,115 m2 ), hangar than 12,000 ft2 (1,115 m2 ), housing other than unfueled aircraft,
doors that accommodate aircraft shall be of noncombustible main distribution panels, metering equipment, and similar
construction. electrical equipment shall be located in a room separated from the
6.7.2 The power source for hangar doors shall operate on aircraft storage and servicing area by a partition having at least a 1-
independent circuits and shall not be de-energized when the main hour fire resistance rating. The partition shall not be penetrated
disconnect switches for general hangar power are shut off. except by electrical raceways, which shall be protected by approved
6.7.3 Vertical traveling doors shall be counterbalanced, and sealing methods maintaining the same fire resistance rating as the
horizontal slide or accordion-type doors shall be arranged, so that partition.
manual or auxiliary operation by means of winches or tractors, for 6.14 Lightning Protection. Where provided, lightning protection
example, is feasible. for membrane-covered rigid steel frame structure hangars shall be
6.7.4 In an area where freezing temperatures can occur, door installed in accordance with NFPA 780, Standard for the Installation
tracks of the bottom edges of doors shall be protected by heating of Lightning Protection Systems.
coils or equivalent means to prevent ice formation that might 6.15 Grounding Facilities for Static Electricity.
prevent or delay operation. 6.15.1 Membrane-covered rigid steel frame structure hangars,
6.8 Curtains. Where curtains are used to enclose a work area, they housing other than unfueled aircraft, shall be provided with
shall be of a listed flame-retardant type. grounding facilities for the removal and control of static electrical
6.9 Landing Gear Pits, Ducts, and Tunnels. accumulations on aircraft, while aircraft are stored or undergoing
6.9.1 Landing gear pits, ducts, and tunnels that are located below servicing in a hangar.
floor level in membrane-covered rigid steel frame structure hangars 6.15.2 An adequate number of floor-grounding receptacles shall
shall be designed on the premise that flammable liquids and be provided. The receptacles shall be either grounded through
vapors will be present at all times. Materials and equipment shall individual driven electrodes or electrically bonded together in a
be impervious to liquids and shall be fire resistant or grid system and the entire system grounded to underground metal
noncombustible. piping, such as cold water or sprinkler piping, or driven electrodes.
6.9.2 Electrical equipment for all landing gear pits, ducts, and Where driven electrodes are used, they shall consist of 5/8 in. (15.9
tunnels that are located below hangar floor level shall be suitable mm) diameter or larger metal rods driven at least 5 ft (1.5m) into
for use in Class I, Division 1, Group D hazardous locations in the ground. Floor-grounding receptacles shall be designed to
compliance with Article 501 of NFPA 70, National Electrical Code. minimize the tripping hazard.
6.9.3 All landing gear pits, ducts, and tunnels that are located 6.15.3 Grounding wires shall be bare and of a gauge that is
below hangar floor level shall be provided with a positive satisfactorily durable to withstand mechanical strains and usage.
mechanical exhaust ventilation system capable of providing a 6.16 Exit and Access Requirements
minimum rate of five air changes per hour during normal 6.16.1 Mean of egress from membrane-covered rigid steel frame
operations and be designed to discharge externally to the hangar. structure hangars shall comply with NFPA 101 ®, Life Safety Code®.
6.9.4 Upon the detection of flammable vapors, the ventilation 6.16.2 Aisles and clear space shall be maintained to ensure access
system shall be capable of providing a minimum ventilation rate of to sprinkler control valves, standpipe hose fire extinguishers, and
30 air changes per hour for the landing gear pit and all associated similar equipment.
ducts or tunnels. 6.17 Fire Protection for Membrane-covered Rigid Steel Frame
6.9.5 The ventilation system shall be controlled by an approved Structure Hangars
continuous-reading combustible gas analyzing system that is 6.17.1 The protection of aircraft storage and servicing areas for
arranged to operate the ventilation system at the rate specified in membrane-covered rigid steel frame structure hangars, having a
6.9.4 automatically upon detection of a specified flammable vapor hangar fire area greater than 12,000 ft 2 (1,115 m2 ), housing either
concentration that is below the lower flammable limit. The fueled or unfueled aircraft, the shall be in accordance with any of
detection system shall have sensors located throughout all ducts the following:
and tunnels.

501
NFPA 409 — May 2001 ROC — Copyright 2001, NFPA

(a) A low-expansion foam system as specified in 6.17.6. 6.17.7 High-Expansion Foam Systems.
(b) A high-expansion foam system as specified in 6.17.7. 6.17.7.1 High-expansion foam systems shall utilize surfactants as
6.17.2 The protection of aircraft storage and servicing areas for the foaming ingredient and shall be designed for local application.
membrane-covered rigid steel frame structure hangars having a 6.17.7.2 These systems shall be designed to discharge at a rate to
hangar fire area less than 12,000 ft 2 , where hazardous operations cover the entire area to a depth of at least 3 ft (0.9 m) within 3
including fuel transfer, welding, torch cutting, torch soldering, minutes.
doping, and spray painting are performed, shall be by an approved 6.17.7.3 If sprinklers are also used, discharge rates shall take into
automatic sprinkler system in accordance with NFPA 13, Standard consideration the sprinkler breakdown factor required in
for the Installation of Sprinkler Systems. 2.3.5.2(b) of NFPA 11A, Standard for Medium-and High-Expansion
6.17.3 All enclosed areas including: separate shops, offices, and Foam Systems.
storage areas located in membrane-covered rigid steel frame 6.17.7.4 The foam generators shall be located at the ceiling or on
structure hangars shall be protected by an approved automatic exterior walls in such a way that only air from outside the aircraft
sprinkler system in accordance with NFPA 13, Standard for the storage and servicing area can be used for foam generation unless
Installation of Sprinkler Systems. data is provided to show that air from inside the hazard can be
6.17.4 Protection Systems successfully employed to generate the foam. The data shall be
6.17.4.1 Aircraft storage and servicing areas shall be protected with specific for the products of combustion to be encountered and
listed protection systems. shall provide factors for increasing foam discharge rates over those
6.17.4.2 Each system shall be designed to cover the entire floor for outside air if fire tests indicate that need. When used, roof
area of the hangar. The design objective shall be to achieve control vents shall be located to avoid recirculation of combustion
of the fire within the protected area within 30 seconds of system products into the air inlets of the foam generators.
actuation and extinguishment of the fire within 60 seconds. 6.17.7.5 Generators shall be powered by reliable water-driven or
6.17.4.3 Each protection system shall be designed, installed, and electric motors. Electric power reliability for generators shall be in
maintained in accordance with NFPA 11, Standard for Low- accordance with electric fire pump requirements of NFPA 20,
Expansion Foam, or NFPA 11A, Standard for Medium- and High- Standard for the Installation of Stationary Pumps for Fire Protection.
Expansion Foam Systems . 6.17.8 Foam Concentrate Supply.
6.17.5 Plans and Specifications. 6.17.8.1 Where foam concentrate is introduced into the water
6.17.5.1 Before systems are installed, complete specifications and stream by pumping, the total foam concentrate pumping capacity
working plans shall be drawn to scale showing all essential details, shall be such that the maximum pressures and flows can be met
and plans shall be easily reproducible to provide necessary copies. with the largest foam concentrate pump out of service.
6.17.5.2 Information supplied in these plans and specifications 6.17.8.2 The quantities of low expansion foam concentrate, either
shall include the following: protein foam, fluoroprotein, or AFFF, shall be sufficient for a 10-
(a) The design purpose of the systems; minute foam discharge based on the supply calculation in 6.17.6.4.
(b) The discharge densities and the period of discharge; 6.17.8.3 The quantity of high expansion foam concentrate shall be
(c) The hydraulic calculations; sufficient for a 12-minute discharge at the water flow rate based on
(d) The details of tests of the available water supply; the supply calculation method required in 6.17.7.2.
(e) The details of proposed water supplies; 6.17.8.4 A reserve supply of foam concentrate of compatible type
(f) The detailed layout of the piping and of the detection for the system shall be directly connected to the system and readily
systems; available. The reserve supply shall be in the same quantity as the
(g) The make and type of discharge devices, operating main supply. To prevent accidental depletion of this reserve
equipment, and foam concentrate to be installed; supply, it shall be available to the system only by intentional
(h) The location and spacing of discharge devices; manual operation.
(i) The pipe hanger and bracing location and installation 6.17.8.5 Control valves, foam concentrate liquid storage tanks,
details; concentrate pumps, controllers, and bypass balancing equipment
(k) The accurate and complete layout of the area to be shall be located outside the aircraft storage and service area.
protected, including drainage layout; 6.17.9 Foam Concentrate Pumps.
(l) The details of any foam concentrate, its storage and 6.17.9.1 Where foam concentrate is introduced into the water
injection, and other pertinent data to provide a clear explanation stream by pumping, the total foam concentrate pumping capacity
of the proposed design. shall be such that the maximum flows and pressures can be met
(m) Location and spacing of supplementary or low-level agent with the largest foam concentrate pump out of service.
distributors, showing the area of coverage; 6.17.9.2 Power supply for the drivers of foam concentrate pumps
(n) Installation layout of the actuation systems; and shall be installed in accordance with NFPA 20, Standard for the
(o) Detailed layout of water supply piping, agent storage, Installation of Stationary Pumps for Fire Protection, and NFPA 70,
pumping and piping, power sources, and location and details of National Electrical Code. Power supplies shall be arranged such that
mechanical foam-liquid concentrate injection equipment. disconnecting power to the protected facility during a fire shall not
6.17.6 Low-Expansion Foam Systems. disconnect the power supply to the foam concentrate pump feeder
6.17.6.1 Low-expansion foam systems shall employ AFFF, protein, circuit.
or fluoroprotein foam-liquid concentrates and shall be designed 6.17.9.3 Controllers for foam concentrate pumps shall be as
for local application. follows:
6.17.6.2 Coverage of the entire floor area of the aircraft hangar (a) For electric drive foam concentrate pumps greater than 30
shall be by means of a horizontal foam discharge from nozzles horsepower, a listed fire pump controller shall be used.
located above floor level. (b) For electric drive foam concentrate pumps greater than 15
6.17.6.3 Where oscillating nozzles are used, the discharge pattern horsepower but not exceeding 30 horsepower, a listed fire pump
limits shall be established for the design. Positive securement of controller or listed limited service controller shall be used.
the limits of oscillation shall be provided by such devices as set (c) For electric drive foam concentrate pumps less than 15
screws, locking pins, or similar methods. When placed in service, horsepower, a listed limited service controller shall be used.
the manual override feature, if any, shall be locked out to provide (d) For diesel engine drive foam concentrate pumps, a listed
for automatic operation only. fire pump controller shall be used.
6.17.6.4 Where protein- or fluoroprotein-based concentrates are 6.17.9.4 Piping shall be arranged so that maximum foam
used, the minimum application density shall be 0.16 gpm of foam concentrate demand can be supplied from either primary or
solution per sq ft (6.5 L/min/m 2 ) of floor area beneath the wing reserve foam concentrate tanks.
and wing center section of the aircraft. Where AFFF concentrate is 6.17.10 Detection / Actuation System Design.
used, the minimum application density shall be 0.10 gpm of foam 6.17.10.1 General. Actuation systems shall be provided with
solution per sq ft (4.1 L/min/m 2 ) of floor area beneath the wing complete circuit supervision and shall be arranged in accordance
and wing center section of the aircraft. with 6.17.13.
6.17.6.5 If any nozzles are removed to allow movement of the 6.17.10.2 Low-Expansion Foam Protection Systems.
aircraft, removal of the nozzles shall not reduce the effectiveness of 6.17.10.2.1* Actuation of fire detectors shall operate the low-
the remaining system. expansion foam protection system.
6.17.6.6 Electric power reliability for oscillating nozzles shall be in 6.17.10.2.2 Manual actuation stations shall be provided for each
accordance with electric fire pump requirements of NFPA 20, low-expansion protection system and shall be located both inside
Standard for the Installation of Stationary Pumps for Fire Protection. and outside the aircraft maintenance and servicing area. Stations
6.17.6.7 Where monitor-type nozzles are used, an individual shall be located as close as possible to the aircraft positions to
manual control valve shall be provided for each unit. This valve facilitate early system actuation in the event of a fire.
shall be supervised. 6.17.10.3 High-Expansion Foam Protection Systems.

502
NFPA 409 — May 2001 ROC — Copyright 2001, NFPA

6.17.10.3.1* Actuation of fire detectors shall operate the high- each section shall be sized to deliver the maximum water supply
expansion foam protection system. requirement.
6.17.10.3.2 Manual actuation stations shall be provided for each 6.17.11.6 Fire Pumps.
high-expansion protection system and shall be located both inside 6.17.11.6.1 Fire pumps shall be installed in accordance with NFPA
and outside the aircraft maintenance and servicing area. Stations 20, Standard for the Installation of Stationary Pumps for Fire Protection ,
shall be located as close as possible to the aircraft positions to and in accordance with the provisions of 6.17.11.6.2 through
facilitate early system actuation in the event of a fire. 6.17.11.6.6.
6.17.11 Hand Hose Systems. 6.17.11.6.2 The total pumping capacity shall be such that
6.17.11.1 Hand hose systems shall be installed in every hangar, to maximum demand can be met with the largest fire pump out of
provide for manual fire control. service.
6.17.11.2 The hand hose systems shall be arranged to permit 6.17.11.6.3 Pump houses and rooms shall be of fire-resistive or
application of water or other extinguishing agents on each side and noncombustible construction. Where internal combustion engines
into the interior of the aircraft located in the aircraft storage and used for driving fire pumps are located inside the fire pump house
servicing area. At least two hose lines shall be considered to be or room, protection shall be provided by automatic sprinklers
operated simultaneously. installed in accordance with NFPA 13, Standard for the Installation of
6.17.11.3 Foam-Water Hand Hose Systems. Sprinkler Systems.
6.17.11.3.1 Foam-water hand hose systems shall be installed in the 6.17.11.6.4 Fire pumps shall be started automatically by either a
aircraft storage and servicing areas having a hangar fire area greater drop in water pressure or a signal from the detection control
than 12,000 ft2 (1,115 m2 ) housing other than unfueled aircraft. panel. Where two or more electrically driven fire pumps supplied
6.17.11.3.2 The systems shall conform with the applicable portions from the same electrical feeder are used, they shall be electrically
of NFPA 14, Standard for the Installation of Standpipe and Hose controlled to prevent simultaneous starting.
Systems , and NFPA 11, Standard for Low-Expansion Foam or NFPA 6.17.11.6.5 Frequent operation of fire pumps shall be avoided by
11A, Standard for Medium- and High-Expansion Foam Systems. the installation of a small auxiliary pressure maintenance pump or
6.17.11.3.3 These foam-water hand hose systems shall be supplied other suitable means to maintain normal system pressures.
from a connection to the low-expansion or high-expansion foam 6.17.11.6.6 Once started, fire pumps shall be arranged to run
system header or from a direct connection to the water source. continuously until they are stopped manually. There shall be an
6.17.11.3.4 Each foam-water hand hose connection shall be a audible “pump running” alarm in a continuously attended area.
minimum of 11/2 in. (38 mm) in size and fitted with a control 6.17.11.7 Flushing Underground Pipe. Underground mains and
valve. The hose shall be of suitable length and diameter to provide each lead-in connection shall be flushed as specified in NFPA 24,
a minimum flow of 60 gpm (227 L/min) at an adequate nozzle Standard for the Installation of Private Fire Service Mains and their
pressure. The stream range shall be calculated based on the Appurtenances.
volume and pressures available under maximum demand 6.17.11.8 Acceptance Tests.
conditions. 6.17.11.8.1 The following tests shall be performed prior to final
6.17.11.3.5 The hose shall be racked or reeled. Hoses shall be acceptance of any fire protection system in an aircraft hangar.
fitted with an approved foam-maker nozzle or a combination-type 6.17.11.8.2 Hydrostatic pressure tests shall be conducted on each
nozzle designed to permit foam application or water spray. Nozzles system as specified in NFPA 11, Standard for Low Expansion Foam ,
shall be of the shutoff type or shall have a shutoff valve at the nozzle NFPA 11A, Standard for Medium- and High-Expansion Foam Systems,
inlet. NFPA 13, Standard for the Installation of Sprinkler Systems, or NFPA
6.17.11.3.6 Foam-liquid concentrate can be supplied from either a 14, Standard for the Installation of Standpipe and Hose Systems, as
central distribution system, separate from or a part of a foam-water applicable.
system, or from stationary foam-liquid concentrate containers fitted 6.17.11.8.3 All devices and equipment installed as part of the
with listed proportioning devices. system shall be tested.
6.17.11.3.7 The minimum supply of foam-liquid concentrate shall 6.17.11.8.4 The maximum number of systems expected to operate
be sufficient to provide operation of at least two hand hose lines shall be simultaneously discharged with foam. This test shall be
for a period of 20 minutes at a foam solution discharge rate of 60 run for a length of time sufficient to stabilize discharge before test
gpm (227 L/min) each. samples are taken to determine foam concentrate percentage.
6.17.11.4 Water Hand Hose Systems. 6.17.11.8.5 Any proportioner not tested under the requirements of
6.17.11.4.1 Water hand hose and standpipe systems shall be 6.17.11.8.4 shall be individually tested with foam concentrate to
installed in accordance with NFPA 14, Standard for the Installation of determine concentrate percentage.
Standpipe and Hose Systems , in aircraft storage and servicing areas 6.17.11.8.6 Low-expansion and high-expansion foam protection
having a hangar fire area greater than 12,000 ft 2 (1,115 m2 ) housing systems shall be subjected to foam flow tests, with foam flowing
unfueled aircraft and all shop, office, and nonaircraft storage areas simultaneously from the maximum number of foam nozzles or
in hangars, except where special hazards that require special generators expected to operate, in order to ensure that the hazard
protection exist. is protected in conformance with the design specification and to
6.17.11.4.2 Water hand hoses shall be fitted with listed adjustable determine whether the flow pressures, agent discharge capacity,
stream pattern nozzles designed to permit straight stream or water foam coverage, percent concentration, and other operating
spray application. characteristics are satisfactory.
6.17.11.5 Water Supply. 6.17.11.8.7 Low-expansion and high-expansion foam protection
6.17.11.5.1 The total water supply shall be sufficient to satisfy the systems shall be examined visually to determine that they have been
protection systems as described in Sections 6.17.1(a), 6.17.1(b), properly installed. Checks shall be made for such items in
6.17.2, and 6.17.3, and the requirements for hose stream and other conformity with installation plans, continuity of piping, tightness of
equipment as determined in 6.17.11. Water shall be available in fittings, removal of temporary blank flanges, and accessibility of
sufficient quantity and pressure to supply the maximum number of valves and controls. Devices shall be properly identified and
discharge devices likely to operate simultaneously. Water shall be operating instructions prominently posted.
suitable for the production of foam. 6.17.11.9 Final Approval. The installing company shall furnish a
6.17.11.5.2 The total water supply duration shall be for a minimum written statement that the work has been completed in accordance
of 45 minutes. with 6.17.5, and tested in accordance with the provisions of
6.17.11.5.3 Hand Hose Systems. The water supply for hand hose 6.17.11.8.
systems shall be capable of satisfying the requirements of 6.17.11.
The demand shall be calculated at the point where supply piping 6.17.11.10 Conversion of Existing Systems.
for the hand hose systems connects to the system piping or fire 6.17.11.10.1 In converting one type of system to another, all
protection underground. provisions of this chapter pertaining to new systems shall apply.
6.17.11.5.4 Exterior Hose Streams. Where the water supply for the 6.17.11.10.2 Converted systems shall be tested in accordance with
systems also serves as a supply for exterior hose streams, a hose 6.17.11.8.
stream allowance of 500 gpm (1893 L/min) shall be included in 6.17.12 Wheeled and Portable Extinguishers
the water supply hydraulic calculations. Calculations for hose 6.17.12.1 Wheeled and portable extinguishers shall be provided in
stream shall be in accordance with NFPA 13, Standard for the accordance with NFPA 10, Standard for Portable Fire Extinguishers.
Installation of Sprinkler Systems. 6.17.12.2 In aircraft storage and servicing areas, the distribution of
6.17.11.5.5 Water Reservoirs. Where a single reservoir is used for such devices shall be in accordance with the extra hazard
the basic water supply, such reservoir shall be divided into classification outlined in NFPA 10, Standard for Portable Fire
approximately equal sections, arranged so at least one-half of the Extinguishers.
water supply will always be maintained in service in order to 6.17.12.3 The distribution of extinguishers in other areas of aircraft
increase the reliability of the water supply. The suction line from hangars shall be in accordance with light, ordinary, or extra hazard

503
NFPA 409 — May 2001 ROC — Copyright 2001, NFPA

occupancy based on an analysis of each room or area following the 2. Southern Building Code, 1999, Section 3104, Temporary
requirements of NFPA 10, Standard for Portable Fire Extinguishers. Structures.
6.17.13 Protection System Alarms . In addition to local alarm 3. Standard Building Code, 1999, Section 3105, Membrane
service, alarms shall be transmitted to a constantly attended Structures.
location. 4. NFPA 102, 1995, Standard for Grandstands, Folding and
Definitions Telescopic Seating, Tents, and Membrane Structures.
Add to the former Chapter 1, Section 1-3 Definitions:
Membrane. A thin, flexible, water impervious material capable of COMMITTEE ACTION: Accept in Principle.
being supported by an air pressure of 1.5 in. (38.1 mm) of water Revise text to read as follows:
column. 1- Add new definition in section 1.3
Weathered-membrane Material. Material that has been subjected Where Specified- Options selected by the purchaser beyond the
to a minimum of 3,000 hours in a weatherometer in accordance minimum requirements of the standard.
with ASTM G26, Practice for Operating Light/Exposure Apparatus Add the following definitions:
(Zenon-Arc Type) With and Without Water for Exposure of Non-Metallic 1. Side Slope: This angle is measured as either the percent of
Materials, or approved equivalent. slope or the tilt angle at which the vehicle would become unstable
Referenced Publications should the vehicle be placed on a side of a steep angled hill or
Add to the former Chapter 7, Section 7-1.1 NFPA Publications: sloped surface.
NFPA 701, Standard Methods of Fire Tests for Flame Propagation of 2. Dynamic Balance: Is a physical condition that exists when a
Textiles and Films , 1989 edition. vehicle is driven into a turn under high speed and the vehicle
Add to the former Chapter 7, a new section 7-1.2 ASTM displays no tendencies to pitch weight forward on the front steering
Publications. wheels nor exhibits of under steer or over steer conditions which
7-1.2 ASTM Publications. American Society for Testing and could make the vehicle unstable.
Materials. 1916 Race Street, Philadelphia, PA 19103. 3. Under Axle Clearance: Is the clearance distance between the
ASTM G26, Practice for Operating Light/Exposure Apparatus (Zenon- ground and the center drive train of the vehicle. Generally this
Arc Type) With and Without Water for Exposure of Non-Metallic measurement is taken at the low point bottom of the drive
Materials, 1993. differentials.
Add to the former Appendix B, Section B-1.1 NFPA Publications: 4. Diagonal Opposite Wheel Motion: Is the measurement of
NFPA 102, Standard for Grandstands, Folding and Telescopic Seating, vertical movement relationship of the wheel and suspension travel.
Tents, and Membrane Structures , 1995 edition. This measurement is compared diagonally right front to left rear
Appendix A wheels of the vehicles or apposing corners of the vehicle.
A-6.1 Membrane-covered rigid steel frame structures are an 5. Service Brake: A system capable of decelerating the vehicle at
evolving construction technology that is recognized by the model a controlled rate to a desired reduced speed or complete stop.
building codes and is being used for a variety of occupancies, 6. Primary Turret: The largest capacity foam turret used to apply
including warehouses and hangars. The use of membrane-covered primary extinguishing agent.
rigid steel frame structures for providing weather protection 7. Ground Sweep Nozzle: Small nozzle(s) mounted in front of
covering for aircraft has become a viable alternative to the the vehicle disperses foam solution in front to provide protection.
traditional construction techniques that have been used for aircraft 8. Under Truck Nozzles: Small nozzles devices which hang
hangars. The fire protection scheme considered for these below the vehicle and disperses foam solution in a manner which
structures anticipates that, in the event of a fire, the structure will provides protection for the vehicles from ground or grass proximity
be self venting. fires. These devices spray agent from wheel to wheel and front to
A-6.11.2 There is little concern for a large volume of water being back of the underside of the truck.
associated with a high-expansion foam solution. In an aggregation 9. Complementary Agent: Agents which provide unique
of mechanically expanded foam, the ratio of air or other gases to extinguishing capability beyond the primary chosen agent. These
foam-water solution ranges from 200:1 to approximately 1000:1. agents can extinguish by means of chemical reaction, cooling or
A-6.17.10.2.1 Additional guidance pertaining to detection systems removal of oxygen and are applied to special fire situations such as
can be found in NFPA 72, National Fire Alarm Code . The selection three dimensional running fuel fires.
of fire detectors should take into account factors such as: the
anticipated fuel, the ability of the detectors to sense fire in the fire 2- Add the following text at 2-1-5 (or where appropriate)
zone, the speed at which the detector will sense the fire, and
potential sources of stimuli that could be falsely detected as a fire. 2-1-5*Additional vehicle options where needed shall be selected
A-6.17.10.3.1 Additional guidance pertaining to detection systems by the purchaser.
can be found in NFPA 72, National Fire Alarm Code . The selection
of fire detectors should take into account factors such as: the Include the following revised appendix material at A 2-1-5 (or
anticipated fuel, the ability of the detectors to sense fire in the fire where appropriate)
zone, the speed at which the detector will sense the fire, and
potential sources of stimuli that could be falsely detected as a fire. Note: Changes from original proposal are identified in the
SUBSTANTIATION: Membrane-covered rigid steel frame margin3- Modify log 15 to leave only 2-4.8* and 2-24.1 (d) (e)
structures are an evolving construction technology that is (j)(k) (l) (m) to be deleted from the body of the standard
recognized by the model building codes and is being used for a
variety of occupancies, including hangars, warehouses, and A 2-1-5 List of available options which can be ordered from the
assemblies. They are most prevalently used for assembly ARFF vehicle manufacturers.
occupancies, and are addressed for those purposes in NFPA 102, General ARFF vehicle options
Standard for Grandstands, Folding and Telescopic Seating, Tents,
and Membrane Structures, in which life safety is a primary issue as · Winterization system providing sufficient insulation and heating
compared to the building and property protection objectives of capacity, by means of hot circulating liquids and forced air
NFPA 409. exchangers, to permit satisfactory operation of the vehicle and fire
By establishing a chapter specifically addressing the membrane- fighting systems for a period of at least 4 hours at ambient
covered rigid steel frame structures for aircraft hangars as a temperatures as low as -40 degree (F&C) with the vehicle fully
construction system more definitive minimum standards can be operational and the engine running. At the end of the 4 hour
established for the construction and protection of these facilities period, the vehicle shall be capable of successfully discharging its
that are consistent with the known concerns for the protection of agent(s). The winterization system shall not detract the
existing construction types and known hazards. performance of the vehicle and fire fighting system in ambient
This chapter anticipates that membrane-covered rigid steel frame temperatures up to 115 degree F (43.5C)
structures will be self venting in the event of a fire, therefore the · Training video tape covering the operation of the vehicle
protection is focused on fire control within the hangar. Thus the · Pintle hook type towing connection rated at 30000 lb gross trailer
two proposed protection schemes are the use of either high weight, attached to the vehicle's frame at the rear of the vehicle.
expansion foam or low expansion foam, which have been used as · Rollup type compartment doors (other than service doors)
supplemental protection to sprinklers for conventional · Windshield deluge system (see 2-11.4.6)
construction hangar applications. Sprinkler protection is proposed · Navigation system of a driver's enhanced vision system (DEVS)
for enclosed offices, shops, and storage areas. (see 2.11.4.7.)
REFERENCES: Monitoring and data acquisition system (MADAS) (see .11.7)
1. The BOCA National Building Code, 1999, Section 3103.0, Dimensional, safety and stability enhancement options
Membrane Structures.

504
NFPA 409 — May 2001 ROC — Copyright 2001, NFPA

· Added payload capacity (GVWR) to carry special equipment · Air suspension type driver (passenger(s)) seat(s) with vertical,
where the purchaser identifies added equipment. fore, and aft adjustment.
· Increased overall width of the vehicle to facilitate increased · Crew seat back(s) with storage of self contained breathing
performance and maneuverability with no concern for movement apparatus with quick release type holders incorporated into me
on public highway(s). seat cushion.
· Audiovisual devices that meet or exceed the field of vision
provided by wide-angle mirrors. Fire Fighting systems options

Engine(s) related options · Water tank design allowing access with each baffled compartment
of the tank for internal and external inspection/service.
· Engine which operate at necessary performance above 2000 ft · Automatic foam proportioning system permitting use of 3 and 6
elevation. percent foam concentrates automatically when selected (change of
· Radiator shutters (see 2-3.2.1.3) proportioning plates not required).
· Engine coolant filter. · Electronic foam proportioning system.
· Silicone coolant and heater hoses. · Foam tank drain valve(s), drain line and hose(s) that facilitate
· Heated diesel fuel water separator draining the tank. into specified container(s) positioned on the
· Automatic drain(s) for the diesel fuel water separator. ground within 10 ft in either horizontal direction of the foam tank
· Auxiliary fuel tank(s) commensurate with need to meet local drainage system.
requirements. · Manual operated roof turret with controls located in the cab.
· Stainless steel exhaust systems and muffler(s) The operation force of the controls requiring less than 30 ft lb
including in cab indicator of turret elevation and azimuth.
Vehicle electrical and lighting options · Manual operated roof turret with controls located on the cab
roof platform. The operation force of the controls requiring less
· Automatic eject type electrical receptacles. than 50 ft lb.
· On-board battery charger/conditioner (see 2-4.5) · Turret controls located in the cab or on the roof platform
· Auxiliary generator(s) installed as per IAW and NFPA 1901, · Manual over ride of roof turret functions in the cab not
Chapter 21. exceeding 30 ft lb operation forces.
· High intensity spotlight(s) on the left and right side of the · Turret(s) controls accessible both to the driver and the crew
windshield, hand adjustable type, with controls for beam member.
adjustment inside the truck cab. · Turret(s) equipped with an auxiliary agent discharge (see 2-23.1)
· High intensity spotlight(s) mounted on the primary turret · Extendible type primary turret (see 2-18.6)
nozzle(s) with controls located in the cab instrument group. · Color camera mounted on the extendible turret.(see 2-18.6)
· Two high intensity floodlights, mounted on each side of the · Video recorder for color and-or flir camera(s)
vehicle. · Aircraft skin penetrator/agent applicator mounted on the
· Two high intensity fog type driving lights mounted on the front extendible turret. (see 2-18.6)
bumper. · Pre-connect hand lines and nozzles.
· Two high intensity driving lights mounted on the front bumper. (water/foam/combined/auxiliary agent/mounted parallel
· Two high intensity floodlights on the rear of the vehicle. entrained streams)
· Map lights on each side of the dash. A control switch on the · Bumper turret. (see 2-20)
instrument group panel in the cab for control of the lights. · High capacity bumper turret.
· Rotating beacon type lights on the top roof deck and visible for · Two or more under truck nozzles (see 2-20.1 and 2-20.3)
360 degrees in the horizontal plane. A control switch on the · Fire system pressure gauge/light/warning on the cab instrument
instrument group panel in the cab for control of the light. panel grouping and/or on the side structural) control panel.
· Strobe type light(s) on the top roof deck and visible for 360 · Foam liquid tank level gauge/light/warning on the cab
degrees in the horizontal plane. A control switch on the instrument instrument panel grouping.
group panel in the cab for control of the light(s). · Remote foam/water liquid level gauge/light/warning on the side
· Fused radio electrical connection in the cab adjacent to the panel and/or re supply/re service locations.
radio mounting location. (Power ratings are to be provided by · Bumper turret and/or ground sweep valve controls located in the
purchaser) cab.
· Under truck nozzle valve control in the cab.
Suspension , mobility and tire options · Auxiliary agent pressurization control on the cab instrument
grouping.
· Reduced under axle and under body clearances to provide a · Remote mounted instrument and control panel (structural
more stable performance on pavement when he vehicle suspension panel).
is designed to permit instantaneous adjustment to the required COMMITTEE STATEMENT: Membrane-covered rigid steel frame
height for off pavement travel. structures are an evolving construction technology that is
· Tag or other none powered axle(s) to assist in weigh distribution recognized by the model building codes and is being used for a
and/or stability requirements. variety of occupancies, including hangars, warehouses, and
· Passive or active suspension components to increase the stability assemblies. They are most prevalently used for assembly
of the vehicle while decreasing the roll over threshold. occupancies, and are addressed for those purposes in NFPA 102,
· Spare tire(s) Standard for Grandstands, Folding and Telescopic Seating, Tents,
· Bead locks on tires and rims. and Membrane Structures, in which life safety is a primary issue as
· Run flat devices in all tires and wheels mounted on the vehicle. compared to the building and property protection objectives of
NFPA 409.
Vehicle brake options By establishing a chapter specifically addressing the membrane-
covered rigid steel frame structures for aircraft hangars as a
· Air brake reservoirs drain valve(s) actuated by the driver form a construction system more definitive minimum standards can be
location or compartment not requiring a creeper to access the established for the construction and protection of these facilities
actuator. that are consistent with the known concerns for the protection of
· Auto-eject type connectors air connection used to change brake existing construction types and known hazards.
air tanks from an external air source. This chapter anticipates that membrane-covered rigid steel frame
structures will be self venting in the event of a fire, therefore the
Vehicle cab, operating and driving options protection is focused on fire control within the hangar. Thus the
two proposed protection schemes are the use of either high
· Tilt and telescoping steering wheel expansion foam or low expansion foam, which have been used as
· Supplementary designated seat positions for additional crew supplemental protection to sprinklers for conventional
members. construction hangar applications. Sprinkler protection is proposed
· Quick access passage to the roof for enclosed offices, shops, and storage areas.
· FLIR heads up display located in the cab.
· Cab air conditioning meeting current automotive-truck and ___________________
environmental protection standards for vehicle air conditioning.
The use of air conditioning shall not change the acceptable pass
fail criteria.

505
NFPA 409 — May 2001 ROC — Copyright 2001, NFPA

(Log #CC1) (Log #CC2)


409- 17 - (A-3-2.8.3.1 ): Accept 409- 18 - (A-3-2.8.5.1 ): Accept
SUBMITTER: Technical Committee on Airport Facilities SUBMITTER: Technical Committee on Airport Facilities
COMMENT ON PROPOSAL NO: 409-1 COMMENT ON PROPOSAL NO: 409-1
RECOMMENDATION: Revise A-3.2.8.3.1 to read as follows: RECOMMENDATION: Revise to read as follows:
A.3.2.8.3.1 Where separate detection systems are provided for A.3.2.8.5.1 When separate detection systems are provided for the
actuation of the supplementary systems, they should be either a actuation of low-level systems, they should be either a radiation
radiation (infrared or ultraviolet) or a heat responsive (continuous (infrared or ultraviolet) or a heat responsive (continuous strip-type
strip-type or thermistor-type) system. When initially installed, if or thermistor-type) system. When initially installed, if there is any
there is any doubt as to the stability of these actuating devices doubt as to the stability of these actuating devices because of
because of environmental factors, it is recommended that the environmental factors, it is recommended that the devices be
devices be utilized to actuate only an alarm rather than trigger the utilized to actuate only an alarm rather than trigger the
extinguishing systems. As soon as operational experience indicates extinguishing systems. As soon as operational experience indicates
that the devices are stable, they should be arranged to automatically that the devices are stable, they should be arranged to automatically
actuate the extinguishing equipment. Spacing of detection devices actuate the extinguishing equipment. Spacing of detection devices
should be no greater than the maximum recommended by the should be no greater than the maximum recommended by the
manufacturer. manufacturer.
SUBSTANTIATION: The supplementary or low level systems are SUBSTANTIATION: The supplementary or low level systems are
required to be actuated by the actuation of any primary system or required to be actuated by the actuation of any primary system or
overhead system. The annex material is only applicable where a overhead system. The annex material is only applicable where a
separate detection system is provided. This is not a substantive separate detection system is provided. This is not a substantive
change, but a clarification of the committee's intent. change, but a clarification of the committee's intent.
COMMITTEE ACTION: Accept. COMMITTEE ACTION: Accept.

___________________ ___________________

Editorial Correction

The Technical Committee on Airport Facilities proposes the


following editorial change to NFPA 409, Standard on Aircraft
Hangars.

In Table A-3-3.1, line #1 under the column Aircraft change Airbus


A-3xx to read Airbus A-380.

506

Vous aimerez peut-être aussi