Académique Documents
Professionnel Documents
Culture Documents
terms:
PSC
PSC – Prospective Short Circuit
PSCC – Prospective Short Circuit Current
PFC
PFC – Prospective Fault Current
PEFC – Prospective Earth Fault Current
Both PFC and PSC tests are designed to calculate the maximum current that will flow within a fault loop
path during the event of an electrical fault as required by regulation 612.11 of BS7671:2008.
A PSC test calculates the current that will flow in the event of a short circuit fault between the live
conductors. That is, Line and Neutral on a single phase installation or Line to Line/ Line to Neutral on a
three phase installation.
A PFC test calculates the current that will flow in the event of an earth fault; i.e., Line to Earth.
It is important that we conduct the tests to make sure that the protective devices installed within a circuit
are rated at the correct breaking capacity. Within a domestic installation, it is common to find 6000A (6kA)
rated MCB’s installed within a circuit. If a domestic premises is situated particularly close to a supply sub-
station and the measured external impedance (Ze) of the property was 0.03 Ohms, Ohm’s law calculates
that 7,666A may flow in the event of a fault on a 230V supply. This may cause concern if the switch gear
is only rated at 6000A.
The test result can be determined by calculation, ascertained by enquiry to the relevant electricity board,
or measured using a Loop Tester. If you are using a Loop Tester, you would measure both PSC and PFC
values and record the highest value. Due to the nature of different supply types, you would expect to find
a PSC value higher than a PFC value on both TT and TN-S systems, however on a TNC-S system both
the PFC and PSC value should be identical.
We supply a range of instruments that are capable of measuring both PFC and PSC values. These are
commonly in the form of either a standalone loop tester, or a multifunction tester capable of measuring
other electrical parameters. Most instruments today display the PFC/PSC value alongside the loop
impedance value and as such, it is no longer necessary to conduct a separate PSC or PSC test.
_________________________________________________________________________________-
PFC tester or the Prospective short circuit function of a multifunctional tester such as
the Megger 1553 is chosen, and we make sure that the supply is ON, but the Main
Switch is in OFF position.
The test leads are joined on the incoming side of the Main Switch, one test lead on
Line and another on the Neutral terminals of the Main Switch.
TEST switch is pushed and a note of the value (kA) is made.
For three phase installations each phase is tested separately and the measured
reading (test between Line 1 and Neutral, then Line 2 and Neutral and last Line 3
and Neutral) is doubled.
Some test meters need that the third (usually green) lead to be connected on the
Neutral during this test. Please refer to the test meter manufacturer’s instruction.
We use PFC tester or select the PFC function of a multifunctional tester such as the
Megger 1553, and it has to be made sure that the supply is ON, but the Main Switch is
in OFF position.
Next, we connect the test leads on the Line and Neutral terminals of the Main Switch,
as well as on the Earth terminal.
The TEST switch is pushed and we make note of the reading (kA).
For three phase installations each phase is checked separately and the measured
reading is doubled (L1 – N – CPC, L2 – N – CPC, L3 – N – CPC).
Having obtained these values by the measurements described above, we will select
the highest value and write it down on the Electrical Installation Certificate as the
value of PFC.
The value of PFC obtained is compared with the breaking capacity of all the
protective devices within the installation. The breaking capacity of the protective
devices should be greater than the value of PFC.