Vous êtes sur la page 1sur 6

Sylodyn NF ®

Material Data Sheet

Material closed cellular polyurethane Standard Sylodyn® range


Colour violet

Standard dimensions on stock


Thickness: 12.5 mm with Sylodyn® NF 12 NF
25 mm with Sylodyn® NF 25
Rolls: 1.5 m wide, 5.0 m long
NE
Stripes: max. 1.5 m wide, up to 5.0 m long
Other dimensions (also thickness) as well as stamped and molded
parts on request. ND

Area of application Compression load Delection NC


(depending on form factor)

Static load limit up to 1.50 N/mm2** approx. 11 %**


Operating load range up to 2.00 N/mm ** 2
approx. 16 %** NB
(static plus dynamic loads)
Load peaks up to 8.0 N/mm2** approx. 50 %**
(short term, infrequent loads)

10 1 0.1 0.01 0.001


Static load limit in N/mm2

Material properties Test methods Comment


Tensile stress at break 7 N/mm2 DIN EN ISO 527-3/5/100* minimum value
Elongation at break 500 % DIN EN ISO 527-3/5/100* minimum value
Tear strength 20 N/mm DIN 53515* minimum value
3
Abrasion 90 mm DIN 53516 load 10 N, bottom surface
Coeficient of friction (steel) 0.7 Getzner Werkstoffe dry
Coeficient of friction (concrete) 0.7 Getzner Werkstoffe dry

Compression set <5% EN ISO 1856 25 %, 23 °C, 70 h, 30 minutes after unloading


2
Static shear modulus 0.80 N/mm DIN ISO 1827* at static load limit

Dynamic shear modulus 1.18 N/mm2 DIN ISO 1827* at static load limit
Mechanical loss factor 0.10 DIN 53513* depending on frequency, load and amplitude (reference value)

Rebound elasticity 70 % DIN 53512 tolerance +/- 10 %


Operating temperature -30 to 70 °C short term higher temperatures possible
Flammability B2 DIN 4102 normal lammable
class E EN ISO 11925-2 EN 13501-1
Speciic volume resistance > 1011 Ω·cm DIN IEC 93 dry

Thermal conductivity 0.11 W/in m·K DIN 52612/1

Further characteristic values on request All information and data is based on our current knowledge. The data can be applied for calculations and as
guidelines, are subject to typical manufacturing tolerances, and are not guaranteed.
* Tests according to respective standards We reserve the right to amend the data.
** At form factor q=3
Further information can be found in VDI Guidline 2062 – Page 2.

www.getzner.com

1
Sylodyn ® NF

Load delection curve

Full surface bearing Form factor: q=6


3

Speciic load in N/mm2


12.5 mm 25 mm 37.5 mm 50 mm

Operating load range


2,5

1,5 Static
load limit

0,5

0
0 1 2 3 4 5 6 7 8 9 10 11 12
Delection in mm

Strip bearing Form factor: q=3


Speciic load in N/mm2

12.5 mm 25 mm 37.5 mm

Operating load range


2,5
50 mm

1,5 Static
load limit

0,5

0
0 1 2 3 4 5 6 7 8 9 10 11 12
Delection in mm

Point bearing Form factor: q=1.5


3
Speciic load in N/mm2

2,5
12.5 mm 25 mm 37.5 mm
Operating load range

2
50 mm

1,5

Static
load limit
1

0,5

0
0 1 2 3 4 5 6 7 8 9 10 11 12
Delection in mm

www.getzner.com Quasi-static load delection curve measured at a velocity of deformation


of 1 % of the thickness per second; testing between lat steel-plates;
recording of the 3rd loading; testing at room temperature

2
Modulus of elasticity Natural frequency

Form factor: q=6 Form factor: q=6


30 3
E-modulus in N/mm2

Speciic load in N/mm2


30 Hz
25 2,5
10 Hz

20 2
12.5 mm

25 mm
15 Static 1,5
37.5 mm

50 mm
10 1

5 0,5

0 0
0 1 2 3 5 10 15 20 25
Speciic load in N/mm2 Natural frequency in Hz

Form factor: q=3 Form factor: q=3


E-modulus in N/mm2

Speciic load in N/mm2

30 3

25 2,5
30 Hz
10 Hz

20 2
12.5 mm

15 1,5 25 mm
Static
37.5 mm

10 1 50 mm

5 0,5

0 0
0 1 2 3 5 10 15 20 25
Speciic load in N/mm2 Natural frequency in Hz

Form factor: q=1.5 Form factor: q=1.5


30 3
E-modulus in N/mm2

Speciic load in N/mm2

50 mm 37 mm

25 2,5
30 Hz
10 Hz
20 2
25 mm 12 mm

15 1,5

Static

10 1

5 0,5

0 0
0 1 2 3 5 10 15 20 25
Speciic load in N/mm2 Natural frequency in Hz

Static modulus of elasticity as a tangent modulus taken from the load Natural frequency of a single-degree-of-freedom system (SDOF system)
delection curve; dynamic modulus of elasticity due to sinusoidal excitation consisting of a ixed mass and an elastic bearing consisting of Sylodyn® NF
with a velocity level of 100 dBv re. 5·10-8 m/s; test according to DIN 53513 based on a stiff subgrade; parameter: thickness of elastomeric bearing

3
Vibration isolation – efficiency
Disturbing frequency in Hz

200
-40 dB/99 % Reduction of the transmitted
180
-30 dB/97 % mechanical vibrations by implemen-
160
tation of an elastic bearing
140
-20 dB/90 %
consisting of Sylodyn® NF
120 Parameter: factor of transmission in
100 dB, isolation rate in %
80 -10 dB/69 %

60
-0 dB/0 %
40

20

0
5 10 15 20 25 30 35 40 45 50
Natural frequency in Hz

Creep behaviour
Relative deflection in % of thickness with unstressed sample

25
Increase in deformation under
consistent loading
20
Parameter: permanent loading
100 % load
Form factor: q=3
15

10
50 % load

1d 1m 1a 10 a
0
0.1 1 10 100 1,000 10,000 100,000 1,000,000
Period of loading in h

Dynamic E-modulus at long term loading


50
Dyn. E-modulus in N/mm2

Change of dynamic modulus of


elasticity under consistent loading
40
100,000 h (at 10 Hz)
1,000 h Parameter: load duration
30 Form factor: q=3
10 h

0.1 h
20

10

0
0 1 2 3
Permanent loading in N/mm2

www.getzner.com

4
Temperature dependency
Dyn. E-modulus in N/mm2

Mechanical loss factor


40 0.4 DMA-test
(Dynamic Mechanical
0.35 Analysis); tests within
linear area of the
load delection curve,
30 0.3 at low speciic loads

0.25

20 0.2

30 Hz
0.15
30 Hz
10 Hz 10 Hz

10 0.1

0.05

0 0
-10 0 10 20 30 40 50 -10 0 10 20 30 40 50
Temperature in °C Temperature in °C

Frequency dependency
20
Dyn. E-modulus in N/mm2

Mechanical loss factor

0.4 DMA-tests; mastercurve


with a reference-tempera-
ture of 21 °C;
tests within the linear area
of the load delection curve,
at low speciic loads

10 0.2

0 0
1 10 100 1,000 1 10 100 1,000
Frequency in Hz Frequency in Hz

Dependency on amplitude Dependency on loading velocity


30 3
Dyn. E-modulus in N/mm2

Speciic load in N/mm2

Dependency on amplitude:
preload at static load limit;
Form factor: q=3, thickness
of material 25 mm
0.15 N/mm2/s
Dependency on loading
velocity:
20 2 1.5 N/mm2/s Form factor: q=3, thickness
of material 25 mm
30 Hz
15 N/mm2/s

10 Hz

10 1

0 0
0.01 0.10 1.00 0 1 2 3 4 5 6 7 8 9
Amplitude in mm Delection in mm

www.getzner.com

5
Form factor
The form factor is a geometric measure for the shape of Loaded area
an elastomeric bearing deined as the ratio of the loaded
area and the area of sum of the perimeter surfaces.

Loaded area
Deinition: Form factor =
Perimeter surface area
Perimeter
surface area
I·w
For a rectangular shape: q =
2·t·(I+w)
(l..length, w..width, t..thickness)
Perimeter surface area

The form factor has an inluence on the delection and


the static load limit respectively.

Elastic Sylodyn®-bearings are considered as


Full surface bearing: Form factor > 6
Strip bearing: Form factor between 2 and 6
Point bearing: Form factor < 2

Inluence of the form factor on the delection at the Inluence of the form factor on the static load limit
static load limit for a homogeneous material for a homogeneous material
Reference value: Form factor q=3 Reference value: Form factor q=3
2.0
Deviation of delection in %

Static load limit in N/mm2

100 %

Increase of
80 %
static load limit

60 % 1.4
Increase of
delection
40 % Decrease of
static load limit
DB SN NF en © Copyright by Getzner Werkstoffe GmbH l 09-2017

20 % 0.8
Decrease
of delection
0%
We reserve the right to amend the data.

-20 % 0.2
0 1 2 3 4 5 6 0 1 2 3 4 5 6
Form factor Form factor

AUSTRIA — Bürs GERMANY — Berlin — Munich — Stuttgart FRANCE — Lyon JORDAN — Amman
JAPAN — Tokyo INDIA — Pune CHINA — Beijing USA — Charlotte www.getzner.com