Applications Summary Features Summary For use by industrial sites, commercial facilities,
utilities, power marketers, and energy service
Power Quality Analysis Measurements companies, the ION 7700 offers incredible
Discover the sources of power quality events, w Revenue certified flexibility and functionality.
harmonics, and voltage sags/swells. Analyze w Instantaneous voltage, current, frequency, It combines high-accuracy, revenue certified
problems and avoid repeat interruptions. power factor power and energy measurements, plus an
w Energy: bi-directional, absolute, net. extensive variety of I/O combinations for
Cost Allocation & Billing
w Demand: sliding window, predicted, thermal universal metering. Detailed power quality
Determine cost centers, identify opportunities for
w Harmonics: individual & total harmonic analysis features keep you informed about your
demand control and check energy consumption
distortion up to the 63rd power distribution system.
patterns. Use comprehensive multi-year
scheduling and time-of-use activity profiles. w Sag/swell recording Integrate the meter with our ION Enterprise™
software or other energy management and
Demand & Power Factor Control Communications SCADA systems through multiple
Avoid penalties with automated load shedding, w Optional built-in modem with ModemGate™ communication channels and protocols.
scheduling, peak shaving or capacitor bank to allow modem access for 31 other devices
w Optional 10Base-T or 10Base-FL Ethernet Patented ION technology lets you customize
control.
port with EtherGate™ for direct data transfer metering or analysis functions at your
Load Studies & Circuit Optimization from Ethernet to RS-485 workstation, without any hard-wiring. Just
Determine the capacity of your electric network graphically link a few drag-and-drop icons, or
w Modbus™ RTU and DNP 3.0 protocol support
and run at peak efficiency. Perform load trending. select default setups, and you're ready to go.
On-Board Data Logging
Equipment Monitoring & Control w Scheduled or event-driven logging of up to
Improve process yields and extend equipment life. 320 parameters
Meter all your utilities including gas, steam, water w Sequence-of-events & min/max logging
and more.
Setpoints for Control and Alarms
Preventative Maintenance w Setpoint on any parameter or condition
Set up alarms to warn of pending problems. Log w 1 second or 1 cycle operation
events and alarms for all critical conditions.
Digital Inputs and Outputs
w 4 optional analog inputs
w 8 digital inputs
w Up to 30 addition I/O points can be ordered
ION 7700 www.pwrm.com
2
www.pwrm.com ION 7700
Performance Indicators Load Profiling View waveforms right at the front panel
The unit can be configured to meter a wide range The ION 7700 incorporates 320 channels via 20
of utility performance indicators, including: data recorders. Channel assignments are
w Total outage time (in seconds) configurable for historical trend recording of
w Out-of-tolerance duration for total harmonic energy, demand, voltage, current, power quality,
distortion, voltage, frequency, power factor or any other measured parameter. Trigger
and hundreds of other definable indices recorders on a time interval basis, a calendar
schedule, by alarm/event condition, or manually.
Harmonic Distortion Metering
Complete harmonic distortion metering, High-Speed Data Recording
recording and real-time reporting, up to the 63rd Use high-speed “burst” recording (as fast as 1-
harmonic, for all voltage and current inputs. cycle intervals) to store detailed characteristics of
w Individual harmonics disturbances or outages. Trigger recording by a
w Total even harmonics user-defined setpoint, or from external
equipment. Gated recording logs data only
w Total odd harmonics
during the critical event so that memory is
w Total harmonics (even + odd)
conserved. Define custom labels for digital input status like “Breaker 5
w K-factor on current inputs open”
Coincident Min/Max Recording
Disturbance Detection Log the values of key parameters or equipment
High-speed setpoint capabilities allow reliable conditions coincident with an extreme condition,
detection and recording of events, sequence-of- complete with date/time stamping. For example,
events, and alarm conditions, including record all feeder voltages and currents at the
magnitude, duration and equipment status. moment a peak demand condition occurs.
Internal waveform recorders are completely
configurable and can record all voltage and Power Quality Recording
current inputs simultaneously. Control the Use ION ENTERPRISE software to automatically
number of pre-event and post-event cycles upload disturbance waveforms, sag/swell data,
recorded. Trigger waveform recording with and harmonic distortion measurements from the
events, external inputs, or manual control. meter to the secure database for detailed visual
analysis at your workstation.
Sag/Swell Detection
Monitor and record disturbances caused by poor Time Synchronization and GPS Odd, even or total harmonics, up to the 31st or 63rd.
power quality. A real-time clock allows internal events and data
w Magnitude and duration data suitable for records to be date-stamped and time-stamped to
plotting on voltage tolerance curves millisecond resolution. The clock can be
w Determine the amount of excess or deficient synchronized to either of two sources:
energy during the disturbance w The meter's internal crystal (+/- 50ppm)
w Per phase triggers for waveform recording or w An external GPS receiver with an accuracy of
control operations +/- 1 millisecond
When using GPS time synchronization, either
Symmetrical Components pre-selected serial port is dedicated exclusively
Zero, negative and positive sequences including as a GPS synchronization input.
phase & magnitude for voltage & current inputs.
Identify harmful voltage & current unbalances in
equipment before they cause damage. The Power of ION
The ION 7700 is based on our patented object-
Transient Capture oriented ION® technology, which ensures the
w Detect and record sub-cycle transients as longevity of your metering solution because it
short as 130ms @60Hz (156ms @50Hz) can adapt as your needs change and lets you
w Analyze transients by plotting them on a take advantage of our ongoing advances in
voltage tolerance (e.g. CBEMA) curve using technology.
PC-based ION ENTERPRISE software The measurements and other functions of the
ION 7700 are provided by ION modules. You can
Data & Event Recording quickly add or rearrange functions with drag-
The meter can be equipped with up to 4 MB of and-drop icons and a few clicks of a mouse.
meter-based nonvolatile memory, ensuring Imagine new features and build them with ION.
important data is never lost, even in the event of
communication or power loss.
3
ION 7700 www.pwrm.com
Alarm Dialing
When equipped with the internal modem, Alarm
Dialing allows the meter to contact the ION
ENTERPRISE monitoring station when an Event
occurs. The ION 7700 can also send an
alphanumeric message to a pager without
ION ENTERPRISE. Contact us for external modem
requirements.
Flash-Based Firmware
w Perform upgrades via communications
without removing the unit from the site.
4
www.pwrm.com ION 7700
(156)
cutouts are required.
6.14" 1.46
(37)
10.20"(259)
MGT Panel Cutout Top view with optional Xpress card installed
0.25" 10.20
(259mm)
(6) 5.90"
(150)
0.187 9.70(246mm)
(4.8 (5mm)
0.20 7.30(185mm)
4 plac 0.44(11mm) 0.64(16mm)
(182)
(28mm)
A1;1.10
(85)
7.16"
3.34"
6.20
(157mm) 4.00
(102mm)
(49)
1.91"
0.2
5(6mm)
5.40"
(137)
0.20
(5mm)
8.20
(208mm)
MGT Back View Optional External I/O, top view Optional External I/O, end view
6.50"
(165) 0.60" 10.00"
(254) 0.25"
5.30"
(135) (15) 9.1
25"(231) (6.4) 3.39"
(47)
3.25"(82.6)
(86.1)
2.75"(70)
(85) 1.86"
max
0.75"(19.1)
(179)
(153)
7.06"
Nylon standof
f
6.03"
(192)
3.34"
Clearancefor#6 0. 25"
(1place) screw(4places) (6.4)
7.56"
0.15"(3.8)diam eter
5.90"
(150)
0.25"
(6)
1.15"
(29
5
ION 7700 www.pwrm.com
Connections
Installation
w 4-wire Wye, 3-wire Wye, 3-wire Delta, and
Single Phase systems
w 3 voltage and 4 current inputs
w Fourth current input for neutral or ground
current monitoring
User Programmable Log Capacity
w All inputs pass ANSI/IEEE C37.90-1989 Example Configurations:
surge withstand and fast transient tests. Standard Memory XMEM Option (extra 512K) Xpress - 3MEG Option
Voltage and Current Inputs Event Log 500 Events 500 Events 500 Events 500 Events 500 Events 500 Events
w No PTs required for Wye (Star) systems up Data Log 25 days A
99 days B
67 days A
270 days B
99 days A
395 days B
to 347/600 VAC. Waveform Log 2 C
8 D
6 C
24 D
100 C
400 D
w For higher voltage systems, PTs with 120 A
16 parameters recorded every 15 minutes B
16 parameters recorded hourly
VAC secondaries may be used. C
6 channels @ 128 samples per cycle for 14 cycles D
6 channels @ 16 samples per cycle for 22 cycles
w 5 Amp nominal full scale current inputs (or
optional 1 Amp current inputs)
Control Power
The ION 7700 can be powered from a dedicated
fused feed, or from the voltage source it is
monitoring (dependent on the power supply).
6
www.pwrm.com ION 7700
7
ION 7700