BASE DE DATOS DE AJUSTE DE PROTECCIONES

Tipo: DISTANCIA Subestación: ANTAPACCAY Región:


Fabricante: ABB Línea: L-2020 Dpto:
Modelo: REL 670 E.T. Origen: ANTAPACCAY Empresa:
Versión: E.T. Destino: TINTAYA Diag.Unif.N°:
N° Serie: Uprim[kV]: 220 Man.Serv.N°:
Tecnología: NUMÉRICA Fases: RSTN Fecha:
Año instal.: Ucc [V]: Respons.:
Código: Uca [V]: 100 Revisión:
Ubic.Tabl: Ica [A]: 1
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES

ANSI COD DESCRIPCION UNIDAD MIN MAX

DATOS GENERALES
DATOS DE LA LINEA TRANSFORMADORES DE CORRIENTE
TRANSFORMADOR DE TENSION RELACIONES DE IMPEDANCIA
DATOS DE LA CARGA

VALORES DE AJUSTE
21 ZONA1 (ZM1) 21 ZONA 2 (ZM2)
21 ZONA 3 ( ZM3 ) 21 ZONA 4 ( ZM4 )
21 ZONA 5 ( ZM5 ) 21 Phase Selection and Load Encroachment
68 Power Swing 21 SOTF
50 Instantaneous Phase Overcurrent 51/67 Four Step Phase Overcurrent
50N Instantaneous Residual Overcurrent 51N/67N
Four Step Residual Overcurrent

26 Thermal Overload Protection 50BF Breaker Failure Protection


50STBStub Protection 52PD Pole discordance protection

27 Undervoltage Protection 59 Overvoltage Protection


59N Residual Overvoltage Protection 21 Current Circuit Supervision
@ Fuse Failure 25 Synchrocheck
79 AutoRecloser 85 Scheme communication logic for distance
85 Current Reversal and WEI 85 Scheme communication logic for 67N
85 Current Reversal and WEI for 67N 21F Fault Locator (RFLO)

DATOS GENERALES
DATOS DE LA LINEA
Generales
Código de la línea - L-2020
E.T. Origen - ANTAPACCAY
E.T. Destino - TINTAYA
Longitud total km 8
Parámetros por km tot.s/corregir tot.corregidos
Resistencia de secuencia positiva ohm/km 0.0691 ohm 0.55 ohm
Reactancia de secuencia positiva ohm/km 0.5091 ohm 4.07 ohm
Conductancia de secuencia positiva us/km 0 us 0.00 us
Susceptancia de secuencia positiva us/km 3.3085 us 26.47 us
Resistencia de secuencia cero ohm/km 0.4187 ohm 3.35 ohm
Reactancia de secuencia cero ohm/km 1.6531 ohm 13.22 ohm
Conductancia de secuencia cero us/km 0 us 0.00 us
Susceptancia de secuencia cero us/km 2.2548 us 18.04 us
Resistencia mutua de secuencia cero ohm/km 0 ohm 0.00 ohm
Reactancia mutua de secuencia cero ohm/km 0 ohm 0.00 ohm
Datos característicos Módulo Angulo
Secuencia positiva
Impedancia de secuencia positiva (Z) ohm/km 0.5138 rad/km
Admitancia de secuencia positiva (Y) us/km 3.3085 rad/km
Impedancia característica ([Z/Y]) ohm/km 394.07 rad/km
Coef. de atenuación (Re[ZY]^0.5) 0 0.01 0.01 1.503 0 1.5 neper/km 0.000088 -
Coef. de fase (Im[ZY]^0.5) 1 ### 1 7E-06 rad/km 0.001301 -
Velocidad de propagación 0.01 1.503 km/seg 289815 -
Impedancia de secuencia positiva total corregida por longitud 8 0.0 ohm 4.11 rad
Admitancia de secuencia positiva total corregida por longitud 8 0.0 ohm 26.47 rad
Potencia natural MW 122.82 -
Secuencia cero
Impedancia de secuencia cero (Z0) ohm/km 1.7053 rad/km
Admitancia de secuencia cero (Y0) us/km 2.2548 rad/km
Impedancia característica ([Z0/Y0]) ohm/km 869.65 rad/km
Coef. de atenuación (Re[Z0Y0]^0.5) 0 0.02 0.02 1.447 0 1.4 neper/km 0.000243 -
Coef. de fase (Im[Z0Y0]^0.5) 1 ### 1 3E-05 rad/km 0.001946 -
Velocidad de propagación 0.02 1.447 km/seg 193743 -
Impedancia total de secuencia cero corregida por longitud 8 0.0 ohm 13.64 rad
Admitancia total de secuencia cero corregida por longitud 8 0.0 ohm 18.04 rad
Relaciones tierra-conductor Módulo Angulo
Relación ZN/ZL sistema europeo (k0=[Z0-Z1]/3Z1) - 0.78 grados
Relación RN/R1 ([R0-R1]/3R1) - 1.69 -
Relación XN/X1 ([X0-X1]/3X1) - 0.75 -
Relación ZN/ZL sistema americano (k0=[Z0-Z1]/Z1) - 2.33 grados
TRANSFORMADORES DE CORRIENTE
Marca - -
Tipo -
Modelo - -
Cantidad de núcleos - -
Corriente nominal A -
Relación de transformación - -
Clase - -
Prestación VA -
TRANSFORMADOR DE TENSION
Marca - -
Tipo - -
Modelo - -
Cantidad de arrollamientos - -
Tensión nominal entre fases V -
Relación de transformación - -
Clase - -
Prestación VA -
RELACIONES DE IMPEDANCIA
Relación secundario/primario (Zs/Zp = Us/Is:Up/Ip) - -
Relación primario/secundario (Zp/Zs = Up/Ip:Us/Is) - -
DATOS DE LA CARGA
Potencia máxima permanente MVA -
Resistencia mínima de carga a Unom ohm -
VALORES DE AJUSTE
21 PROTECCION DE DISTANCIA Disp.s/interr.:
21 HABILITACIÓN DE LA PROTECCIÓN DE DISTANCIA
21 ZONA 1 ( ZM1 )
ZMQPDIS
Operat Operation on/off - ON - OFF
Ibase Base current, i,e. rated current A 1 99999
Ubase Base voltage, i.e. rated voltage kV 0.05 2000.00
Off
Non-directional
OperationDir Operation mode of directionality -
Forward
Reverse
X1 Positive sequence reactance reach ohm 0.10 3000.00
R1 Positive seq. resistance for zone characteristic angle ohm 0.10 1000.00
X0 Zero sequence reactance reach ohm 0.10 9000.00
R0 Zero seq. resistance for zone characteristic angle ohm 0.50 3000.00
RFPP Fault resistance reach in ohm/loop, Ph-Ph ohm 1.00 3000.00
RFPE Fault resistance reach in ohm/loop, Ph-E ohm 0.01 400.00
OperationPP Operation mode Off/On of Phase-Phase loops - ON - OFF
Timer tPP Operation mode Off/On of zoner timer, Ph-Ph - ON - OFF
tPP Time delay of trip, Ph-Ph s 0.000 60.000
OperationPE Operation mode Off/On of Phase-Earth loops - ON - OFF
Timer tPE Operation mode Off/On of zoner timer, Ph-E - ON - OFF
tPE Time delay of trip, Ph-E s 0.000 60.000
IMinOpPP Minimum operate delta current for Phase-Phase loops %IB 10 30
IMinOpPE Minimum operate phase current for Phase-Earth loops %IB 10 30
IMinOpIN Minimum operate residual current for Phase-Earth loops %IB 5 30
21 ZONA 2 ( ZM2 )
ZMQPDIS
Operat Operation on/off - ON - OFF
Ibase Base current, i,e. rated current A 1 99999
Ubase Base voltage, i.e. rated voltage kV 0.05 2000.00
Off
Non-directional
OperationDir Operation mode of directionality -
Forward
Reverse
X1 Positive sequence reactance reach ohm 0.10 3000.00
R1 Positive seq. resistance for zone characteristic angle ohm 0.10 1000.00
X0 Zero sequence reactance reach ohm 0.10 9000.00
R0 Zero seq. resistance for zone characteristic angle ohm 0.50 3000.00
RFPP Fault resistance reach in ohm/loop, Ph-Ph ohm 1.00 3000.00
RFPE Fault resistance reach in ohm/loop, Ph-E ohm 0.01 9000.00
OperationPP Operation mode Off/On of Phase-Phase loops - ON - OFF
Timer tPP Operation mode Off/On of zoner timer, Ph-Ph - ON - OFF
tPP Time delay of trip, Ph-Ph s 0.000 60.000
OperationPE Operation mode Off/On of Phase-Earth loops - ON - OFF
Timer tPE Operation mode Off/On of zoner timer, Ph-E - ON - OFF
tPE Time delay of trip, Ph-E s 0.000 60.000
IMinOpPP Minimum operate delta current for Phase-Phase loops %IB 10 30
IMinOpPE Minimum operate phase current for Phase-Earth loops %IB 10 30
21 ZONA 3 ( ZM3 )
ZMQPDIS
Operat Operation on/off - ON - OFF
Ibase Base current, i,e. rated current A 1 99999
Ubase Base voltage, i.e. rated voltage kV 0.05 400.00
Off
Non-directional
OperationDir Operation mode of directionality -
Forward
Reverse
X1 Positive sequence reactance reach ohm 0.10 3000.00
R1 Positive seq. resistance for zone characteristic angle ohm 0.10 1000.00
X0 Zero sequence reactance reach ohm 0.10 9000.00
R0 Zero seq. resistance for zone characteristic angle ohm 0.50 3000.00
RFPP Fault resistance reach in ohm/loop, Ph-Ph ohm 1.00 3000.00
RFPE Fault resistance reach in ohm/loop, Ph-E ohm 0.01 9000.00
OperationPP Operation mode Off/On of Phase-Phase loops - ON - OFF
Timer tPP Operation mode Off/On of zoner timer, Ph-Ph - ON - OFF
tPP Time delay of trip, Ph-Ph s 0.000 60.000
OperationPE Operation mode Off/On of Phase-Earth loops - ON - OFF
Timer tPE Operation mode Off/On of zoner timer, Ph-E - ON - OFF
tPE Time delay of trip, Ph-E s 0.000 60.000
IMinOpPP Minimum operate delta current for Phase-Phase loops %IB 10 30
IMinOpPE Minimum operate phase current for Phase-Earth loops %IB 10 30
21 ZONA 4 ( ZM4 )
ZMQPDIS
Operat Operation on/off - ON - OFF
Ibase Base current, i,e. rated current A 1 99999
Ubase Base voltage, i.e. rated voltage kV 0.05 400.00
Off
Non-directional
OperationDir Operation mode of directionality -
Forward
Reverse
X1 Positive sequence reactance reach ohm 0.10 3000.00
R1 Positive seq. resistance for zone characteristic angle ohm 0.10 1000.00
X0 Zero sequence reactance reach ohm 0.10 9000.00
R0 Zero seq. resistance for zone characteristic angle ohm 0.50 3000.00
RFPP Fault resistance reach in ohm/loop, Ph-Ph ohm 1.00 3000.00
RFPE Fault resistance reach in ohm/loop, Ph-E ohm 0.01 9000.00
OperationPP Operation mode Off/On of Phase-Phase loops - ON - OFF
Timer tPP Operation mode Off/On of zoner timer, Ph-Ph - ON - OFF
tPP Time delay of trip, Ph-Ph s 0.000 60.000
OperationPE Operation mode Off/On of Phase-Earth loops - ON - OFF
Timer tPE Operation mode Off/On of zoner timer, Ph-E - ON - OFF
tPE Time delay of trip, Ph-E s 0.000 60.000
IMinOpPP Minimum operate delta current for Phase-Phase loops %IB 10 30
IMinOpPE Minimum operate phase current for Phase-Earth loops %IB 10 30
21 ZONA 5 ( ZM5 )
ZMQPDIS
Operat Operation on/off - ON - OFF
Ibase Base current, i,e. rated current A 1 99999
Ubase Base voltage, i.e. rated voltage kV 0.05 400.00
Off
Non-directional
OperationDir Operation mode of directionality -
Forward
Reverse
X1 Positive sequence reactance reach ohm 0.10 3000.00
R1 Positive seq. resistance for zone characteristic angle ohm 0.10 1000.00
X0 Zero sequence reactance reach ohm 0.10 9000.00
R0 Zero seq. resistance for zone characteristic angle ohm 0.50 3000.00
RFPP Fault resistance reach in ohm/loop, Ph-Ph ohm 1.00 3000.00
RFPE Fault resistance reach in ohm/loop, Ph-E ohm 0.01 400.00
OperationPP Operation mode Off/On of Phase-Phase loops - ON - OFF
Timer tPP Operation mode Off/On of zoner timer, Ph-Ph - ON - OFF
tPP Time delay of trip, Ph-Ph s 0.000 60.000
OperationPE Operation mode Off/On of Phase-Earth loops - ON - OFF
Timer tPE Operation mode Off/On of zoner timer, Ph-E - ON - OFF
tPE Time delay of trip, Ph-E s 0.000 60.000
IMinOpPP Minimum operate delta current for Phase-Phase loops %IB 10 30
IMinOpPE Minimum operate phase current for Phase-Earth loops %IB 10 30
DIRECTIONAL IMPEDANCE ELEMENT (ZDRDIR)
ArgNegRes Angle to blinder in second quadrant for forward direction Deg 90 175
ArgDir Angle to blinder in fourth quadrant for forward direction Deg 5 45
IMinOp Minimum operate current in % of IBase %IB 1 99999
IBase Base current A 1 99999
UBase Base Voltage kV 0.05 2000.00
21 PHASE SELECTION WITH LOAD ENCROACHMENT
FDPSPDIS
IBase Base current, i,e. rated current A 1 99999
INBlockPP 3I0 limit for blocking phase-to-phase measuring loops %IPh 10 100
INReleasePE 3I0 limit for releasing phase-to-earth measuring loops %IPh 10 100
RLdFw Forward resistive reach within the load impedance area ohm 1.00 3000.00
RLdRv Reverse resistive reach within the load impedance area ohm 1.00 3000.00
ArgLd Load angle determining the load impedance area Deg 5 70
X1 Positive sequence reactance reach ohm 0.50 3000.00
X0 Zero sequence reactance reach ohm 0.50 9000.00
RFFwPP Fault resistance reach, Ph-Ph, forward ohm 0.50 3000.00
RFRvPP Fault resistance reach, Ph-Ph, reverse ohm 0.50 3000.00
RFFwPE Fault resistance reach, Ph-E, forward ohm 1.00 9000.00
RFRvPE Fault resistance reach, Ph-E, reverse ohm 1.00 9000.00
IMinOpPP Minimum operate delta current for Phase-Phase loops %IB 5 30
IMinOpPE Minimum operate phase current for Phase-Earth loops %IB 5 30
68 POWER SWING DETECTION
ZMRPSB_78
Operat Operation mode on/off - ON - OFF
X1InFw Inner reactive boundary, forward ohm 0.10 3000.00
R1LIn Line resistance for inner characteristic angle ohm 0.10 1000.00
R1FInFw Fault resist coverage to inner resistive line forward ohm 0.10 1000.00
X1InRv Inner reactive boundary, reverse ohm 0.10 3000.00
R1FInRv Fault resist line to inner resistive boundary, reverse ohm 0.10 1000.00
Oper.LdCh Operation of load discrimination characteristic - ON - OFF
RLdOutFw Outer resistive load boundary, forward ohm 0.10 3000.00
ArgLd Load angle determining the load impedance area Deg 5 70
RLdOutRv Outer resistive load boundary, reverse ohm 0.10 3000.00
kLdRFw Mult factor for inner resistive load boundary, forward mult 0.50 0.90
kLdRRv Mult factor for inner resistive load boundary, reverse mult 0.50 0.90
tP1 Timer for detection of initial power swing s 0.000 60.000
tP2 Timer for detection of subsequent power swing s 0.000 60.000
tW Waiting timer for activation of tP2 timer s 0.000 60.000
tH Timer for holding power swing START output s 0.000 60.000
tEF Timer for overcoming single-pole reclosing dead time s 0.000 60.000
tR1 Timer giving delay to inhibit by the residual current s 0.000 60.000
tR2 Timer giving delay to inhibit at very slow swing s 0.000 60.000
IMinOpPE Minimum operate current in % of IBase %IB 5 30
IBase Base setting for current level settings A 1 99999
21 Automatic switch onto fault logic (PSOF)
Operat Operation on/off - ON - OFF
Ibase Base current, i,e. rated current A 1 99999
Ubase Base voltage, i.e. rated voltage kV 0.05 2000.00
IPh< Current level for detection of dead line in % of Ibase %IB 1 100
UPh< Voltage level for detection of dead line in % of Ubase %UB 1 100
50 Instantaneous phase overcurrent protection (PIOC, 50)
Operation Operation on/off - ON - OFF
Base setting for current
IBase A 1 99999
values
2 out of 3
OpMode Operation Mode -
1 out of 3
Iph>> Operate phase current level in % of Ibase %IB 1 2500
StValMult Multiplier for operate current level - 0.5 5.0
51/67 Four step phase overcurrent protection (POCM, 51/67)
Operation Operation on/off - ON - OFF
IBase Base setting for current values A 1 99999
UBase Base setting for voltage levels in kV kV 0.05 2000.00
MaxFwAng Maximun forward angle Deg 40.0 70.0
MinFwAng Minimun forward angle Deg 75.0 90.0
AngleRCA Relay Characteristic angle (RCA) Deg -70.0 -50.0
IMinOpPhSel Minimun current for phase selection in % of IBase %IB 1 100
Not Used
1 out of 3
StartPhSel Number of phases required for op (1of3, 2of3, 3of3) -
2 out of 3
3 out of 3
2ndHarmStab Operate level of 2nd harm restrain op in % of fund. %IB 5 100
51/67 _ 1
Off
Non-directional
DirMode1 Directional mode of step 1 -
Forward
Reverse
ANSI EI, VI, NI, MI, DT
L.T.E. inv
L.T.V. inv
L.T. inv
Characteristic 1 Selection of time delay curve type for step 1 - IEC NI, VI, EI, S.T.I, L.T.I, DT
Reserved
Programmable
RI type
RD type
I1> Operate phase current level for step 1 in % of IBase %IB 1 2500
t1 Independent (definitive) time delay of step 1 s 0.000 60.000
k1 Time multiplier for the dependent time delay for step 1 - 0.05 999.00
I1Mult Multiplier for operate current level for step 1 - 1.0 10.0
t1Min Minimum operate time for IEC IDMT curves for step 1 s 0.000 60.000
Instantaneous
ResetTypeCrv1 Selection of reste curve type for step 1 - IEC Reset
ANSI Reset
tReset1 Reset time delay used in IEC Definite Time curve step 1 s 0.000 60.000
tPCrv1 Param. P for customer programmable curve for step 1 - 0.005 3.000
tACrv1 Param. A for customer programmable curve for step 1 - 0.005 200.000
tBCrv1 Param. B for customer programmable curve for step 1 - 0.00 20.00
tCCrv1 Param. C for customer programmable curve for step 1 - 0.1 10.0
tPRCrv1 Param. PR for customer programmable curve for step 1 - 0.005 3.000
tTRCrv1 Param. TR for customer programmable curve for step 1 - 0.005 100.000
tCRCrv1 Param. CR for customer programmable curve for step 1 - 0.1 10.0
HarmRestrain1 Enabled block of step 1 from harmonic restrain - Disabled - Enabled
51/67 _ 2
Off
Non-directional
DirMode2 Directional mode of step 2 -
Forward
Reverse

ANSI EI, VI, NI, MI, DT


L.T.E. inv
L.T.V. inv
L.T. inv
Characteristic 2 Selection of time delay curve type for step 2 - IEC NI, VI, EI, S.T.I, L.T.I, DT
Reserved
Programmable
RI type
RD type
I2> Operate phase current level for step 2 in % of IBase %IB 1 2500
t2 Independent (definitive) time delay of step 2 s 0.000 60.000
k2 Time multiplier for the dependent time delay for step 2 - 0.05 999.00
I2Mult Multiplier for operate current level for step 2 - 1.0 10.0
t2Min Minimum operate time for IEC IDMT curves for step 2 s 0.000 60.000
Instantaneous
ResetTypeCrv2 Selection of reste curve type for step 2 - IEC Reset
ANSI Reset
tReset2 Reset time delay used in IEC Definite Time curve step 2 s 0.000 60.000
tPCrv2 Param. P for customer programmable curve for step 2 - 0.005 3.000
tACrv2 Param. A for customer programmable curve for step 2 - 0.005 200.000
tBCrv2 Param. B for customer programmable curve for step 2 - 0.00 20.00
tCCrv2 Param. C for customer programmable curve for step 2 - 0.1 10.0
tPRCrv2 Param. PR for customer programmable curve for step 2 - 0.005 3.000
tTRCrv2 Param. TR for customer programmable curve for step 2 - 0.005 100.000
tCRCrv2 Param. CR for customer programmable curve for step 2 - 0.1 10.0
HarmRestrain2 Enabled block of step 2 from harmonic restrain - Disabled - Enabled
51/67 _ 3
Off
Non-directional
DirMode3 Directional mode of step 3 -
Forward
Reverse

ANSI EI, VI, NI, MI, DT


L.T.E. inv
L.T.V. inv
L.T. inv
Characteristic 3 Selection of time delay curve type for step 3 - IEC NI, VI, EI, S.T.I, L.T.I, DT
Reserved
Programmable
RI type
RD type
I3> Operate phase current level for step 3 in % of IBase %IB 1 2500
t3 Independent (definitive) time delay of step 3 s 0.000 60.000
k3 Time multiplier for the dependent time delay for step 3 - 0.05 999.00
I3Mult Multiplier for operate current level for step 3 - 1.0 10.0
t3Min Minimum operate time for IEC IDMT curves for step 3 s 0.000 60.000
Instantaneous
ResetTypeCrv3 Selection of reste curve type for step 3 - IEC Reset
ANSI Reset
tReset3 Reset time delay used in IEC Definite Time curve step 3 s 0.000 60.000
tPCrv3 Param. P for customer programmable curve for step 3 - 0.005 3.000
tACrv3 Param. A for customer programmable curve for step 3 - 0.005 200.000
tBCrv3 Param. B for customer programmable curve for step 3 - 0.00 20.00
tCCrv3 Param. C for customer programmable curve for step 3 - 0.1 10.0
tPRCrv3 Param. PR for customer programmable curve for step 3 - 0.005 3.000
tTRCrv3 Param. TR for customer programmable curve for step 3 - 0.005 100.000
tCRCrv3 Param. CR for customer programmable curve for step 3 - 0.1 10.0
HarmRestrain3 Enabled block of step 3 from harmonic restrain - Disabled - Enabled
51/67 _ 4
Off
Non-directional
DirMode4 Directional mode of step 4 -
Forward
Reverse
ANSI EI, VI, NI, MI, DT
L.T.E. inv
L.T.V. inv
L.T. inv
Characteristic 4 Selection of time delay curve type for step 4 - IEC NI, VI, EI, S.T.I, L.T.I, DT
Reserved
Programmable
RI type
RD type
I4> Operate phase current level for step 3 in % of IBas4 %IB 1 2500
t4 Independent (definitive) time delay of step 4 s 0.000 60.000
k4 Time multiplier for the dependent time delay for step 4 - 0.05 999.00
I4Mult Multiplier for operate current level for step 4 - 1.0 10.0
t4Min Minimum operate time for IEC IDMT curves for step 4 s 0.000 60.000
Instantaneous
ResetTypeCrv4 Selection of reste curve type for step 4 - IEC Reset
ANSI Reset
tReset4 Reset time delay used in IEC Definite Time curve step 4 s 0.000 60.000
tPCrv4 Param. P for customer programmable curve for step 4 - 0.005 3.000
tACrv4 Param. A for customer programmable curve for step 4 - 0.005 200.000
tBCrv4 Param. B for customer programmable curve for step 4 - 0.00 20.00
tCCrv4 Param. C for customer programmable curve for step 4 - 0.1 10.0
tPRCrv4 Param. PR for customer programmable curve for step 4 - 0.005 3.000
tTRCrv4 Param. TR for customer programmable curve for step 4 - 0.005 100.000
tCRCrv4 Param. CR for customer programmable curve for step 4 - 0.1 10.0
HarmRestrain4 Enabled block of step 4 from harmonic restrain - Disabled - Enabled
50N Instantaneous residual overcurrent protection (PIOC, 50N)
Operation Operation on/off - ON - OFF
Base setting for current
IBase A 1 99999
values
IN>> Operate residual current level in % of Ibase %IB 1 2500
StValMult Multiplier for operate current level - 0.5 5.0
51N/
Four step residual overcurrent protection (PEFM, 51N/67N)
67N
Operation Operation on/off - ON - OFF
IBase Base setting for current values A 1 99999
UBase Base setting for voltage levels in kV kV 0.05 2000.00
IMinOpFund Min. fundamental frequency current level in % IBase %IB 1 2500
AngleRCA Relay Characteristic angle (RCA) Deg -180 180
3U0>Dir Minimumu polarizing quatity in % of UBase %UB 1 100
IN>DirCmp Operate residual current level for DirComp in % IBase %IB 1 100
2ndHarmStab 2nd harmonic restrain operation in % of INAMPL % 5 100
UseStartValue Current level blk at parallel transf (Step1,2,3 or 4) - IN1>, IN2>, IN3>, IN4>
BlkParTransf Enable blocking at parallel transformers - ON - OFF
Open
Act. SOTF Select signal that shall activate SOTF - Closed
CloseCommand
Off
SOTF
SOTF SOTF operation mode -
UnderTime
SOTF+UnderTime
tSOTF Time delay for SOTF s 0.000 60.000
HarmResSOTF Enalbed harmonic restrain function SOTF - Disabled - Enabled
t4U Switch-onto-fault active time s 0.000 60.000
CB position
ActUnderTime Select signal to active under time -
CB command
tUnderTime Time delay for under time s 0.000 60.000
51N/67N _ 1
Off
Non-directional
DirMode1 Directional mode of step 1 -
Forward
Reverse

ANSI EI, VI, NI, MI, DT


L.T.E. inv
L.T.V. inv
L.T. inv
Characteristic 1 Selection of time delay curve type for step 1 - IEC NI, VI, EI, S.T.I, L.T.I, DT
Reserved
Programmable
RI type
RD type
IN1> Operate residual current level for step 1 in % of IBase %IB 1 2500
t1 Independent (definitive) time delay of step 1 s 0.000 60.000
k1 Time multiplier for the dependent time delay for step 1 - 0.05 999.00
IN1Mult Multiplier for operate current level for step 1 - 1.0 10.0
t1Min Minimum operate time for IEC IDMT curves for step 1 s 0.000 60.000
Instantaneous
ResetTypeCrv1 Selection of reste curve type for step 1 - IEC Reset
ANSI Reset
tReset1 Reset time delay used in IEC Definite Time curve step 1 s 0.000 60.000
HarmRestrain1 Enabled block of step 1 from harmonic restrain - Disabled - Enabled
tPCrv1 Param. P for customer programmable curve for step 1 - 0.005 3.000
tACrv1 Param. A for customer programmable curve for step 1 - 0.005 200.000
tBCrv1 Param. B for customer programmable curve for step 1 - 0.00 20.00
tCCrv1 Param. C for customer programmable curve for step 1 - 0.1 10.0
tPRCrv1 Param. PR for customer programmable curve for step 1 - 0.005 3.000
tTRCrv1 Param. TR for customer programmable curve for step 1 - 0.005 100.000
tCRCrv1 Param. CR for customer programmable curve for step 1 - 0.1 10.0
51/67 _ 2
Off
Non-directional
DirMode2 Directional mode of step 2 -
Forward
Reverse

ANSI EI, VI, NI, MI, DT


L.T.E. inv
L.T.V. inv
L.T. inv
Characteristic 2 Selection of time delay curve type for step 2 - IEC NI, VI, EI, S.T.I, L.T.I, DT
Reserved
Programmable
RI type
RD type
IN2> Operate residual current level for step 2 in % of IBase %IB 1 2500
t2 Independent (definitive) time delay of step 2 s 0.000 60.000
k2 Time multiplier for the dependent time delay for step 2 - 0.05 999.00
IN2Mult Multiplier for operate current level for step 2 - 1.0 10.0
t2Min Minimum operate time for IEC IDMT curves for step 2 s 0.000 60.000
Instantaneous
ResetTypeCrv2 Selection of reste curve type for step 2 - IEC Reset
ANSI Reset
tReset2 Reset time delay used in IEC Definite Time curve step 2 s 0.000 60.000
HarmRestrain2 Enabled block of step 2 from harmonic restrain - Disabled - Enabled
tPCrv2 Param. P for customer programmable curve for step 2 - 0.005 3.000
tACrv2 Param. A for customer programmable curve for step 2 - 0.005 200.000
tBCrv2 Param. B for customer programmable curve for step 2 - 0.00 20.00
tCCrv2 Param. C for customer programmable curve for step 2 - 0.1 10.0
tPRCrv2 Param. PR for customer programmable curve for step 2 - 0.005 3.000
tTRCrv2 Param. TR for customer programmable curve for step 2 - 0.005 100.000
tCRCrv2 Param. CR for customer programmable curve for step 2 - 0.1 10.0
51N/67N _ 3
Off
Non-directional
DirMode3 Directional mode of step 3 -
Forward
Reverse

ANSI EI, VI, NI, MI, DT


L.T.E. inv
L.T.V. inv
L.T. inv
Characteristic 3 Selection of time delay curve type for step 3 - IEC NI, VI, EI, S.T.I, L.T.I, DT
Reserved
Programmable
RI type
RD type
IN3> Operate residual current level for step 3 in % of IBase %IB 1 2500
t3 Independent (definitive) time delay of step 3 s 0.000 60.000
k3 Time multiplier for the dependent time delay for step 3 - 0.05 999.00
IN3Mult Multiplier for operate current level for step 3 - 1.0 10.0
t3Min Minimum operate time for IEC IDMT curves for step 3 s 0.000 60.000
Instantaneous
ResetTypeCrv3 Selection of reste curve type for step 3 - IEC Reset
ANSI Reset
tReset3 Reset time delay used in IEC Definite Time curve step 3 s 0.000 60.000
HarmRestrain3 Enabled block of step 3 from harmonic restrain - Disabled - Enabled
tPCrv3 Param. P for customer programmable curve for step 3 - 0.005 3.000
tACrv3 Param. A for customer programmable curve for step 3 - 0.005 200.000
tBCrv3 Param. B for customer programmable curve for step 3 - 0.00 20.00
tCCrv3 Param. C for customer programmable curve for step 3 - 0.1 10.0
tPRCrv3 Param. PR for customer programmable curve for step 3 - 0.005 3.000
tTRCrv3 Param. TR for customer programmable curve for step 3 - 0.005 100.000
tCRCrv3 Param. CR for customer programmable curve for step 3 - 0.1 10.0
Step 2 init
Step3ForSOTF Select step3 to be connected to SOTF -
Step 3 init
Off
Non-directional
DirMode4 Directional mode of step 4 -
Forward
Reverse

ANSI EI, VI, NI, MI, DT


L.T.E. inv
L.T.V. inv
L.T. inv
Characteristic 4 Selection of time delay curve type for step 4 - IEC NI, VI, EI, S.T.I, L.T.I, DT
Reserved
Programmable
RI type
RD type
IN4> Operate residual current level for step 3 in % of IBas4 %IB 1 2500
t4 Independent (definitive) time delay of step 4 s 0.000 60.000
k4 Time multiplier for the dependent time delay for step 4 - 0.05 999.00
IN4Mult Multiplier for operate current level for step 4 - 1.0 10.0
t4Min Minimum operate time for IEC IDMT curves for step 4 s 0.000 60.000
Instantaneous
ResetTypeCrv4 Selection of reste curve type for step 4 - IEC Reset
ANSI Reset
tReset4 Reset time delay used in IEC Definite Time curve step 4 s 0.000 60.000
HarmRestrain4 Enabled block of step 4 from harmonic restrain - Disabled - Enabled
tPCrv4 Param. P for customer programmable curve for step 4 - 0.005 3.000
tACrv4 Param. A for customer programmable curve for step 4 - 0.005 200.000
tBCrv4 Param. B for customer programmable curve for step 4 - 0.00 20.00
tCCrv4 Param. C for customer programmable curve for step 4 - 0.1 10.0
tPRCrv4 Param. PR for customer programmable curve for step 4 - 0.005 3.000
tTRCrv4 Param. TR for customer programmable curve for step 4 - 0.005 100.000
tCRCrv4 Param. CR for customer programmable curve for step 4 - 0.1 10.0
26 Thermal overload protection, one time constant (PTTR, 26)
Operation Operation Off/On - ON - OFF
Hyst Temp Hysteresis for start temperature - 0 50
IBase Base current in A A 0 99999
IMult Current multiplier when THOL is used for two or more lines - 1 5
IRef The load current (in % IBase) leading to TRef temp. % IB 0 400
TRef End temperature of the line when loaded with IRef Deg C 0 400
Tau Time constant of the line in minutes. Min 0 1000
TripTemp Temperature level for trip Deg C 0 400
AlarmTemp Temperature level for start (alarm) Deg C 0 200
ReclTemp Temperature for reset of lockout after trip Deg C 0 400
50BF Breaker failure protection (RBRF, 50BF)
Operat Operation Off/On - On - Off
IBase Base setting for current level settings A 1 99999
Current
FunctionMode Detection for back-up trip - Contact
Current&Contact
2 out of 4
BuTripMode Back-up trip mode, - 1 out of 3
1 out of 4
Retrip Off
RetripMode Operation mode of re-trip logic - I> Check
No I> Check
IP> Operate level in % of IBase %IB 5 200
I>BlkCont Curr for blocking of CB contact oper in % of IBase %IB 5 200
IN> Operate residual level in % of IBase %IB 2 200
t1 Time delay of re-trip s 0.000 60.000
t2 Time delay of back-up trip s 0.000 60.000
t2MPh Time delay of back-up trip at multi-phase start s 0.000 60.000
t3 Additional time delay to t2 for a second back-up trip s 0.000 60.000
tCBAlarm Time delay for CB faulty signal s 0.000 60.000
tPulse Trip pulse duration s 0.000 60.000
50ST
Stub protection (PTOC, 50STB)
B
Operat Operation Off/On - On - Off
IBase Base setting for current level settings A 1 99999
Release
ReleaseMode Release of stub protection -
Continuous
2 out of 4
BuTripMode Back-up trip mode, - 1 out of 3
1 out of 4
I> Operate current level in % of IBase %IB 1 2500
t Time delay s 0.000 60.000
52PD Pole discordance protection (RPLD, 52PD)
Operat Operation - On - Off
IBase Base setting for current level settings A 1 99999
TimeDelayTrip Time delay between trip condition and trip signal s 0.000 60.000
Off
ContSel Contact function selection - PD signal from CB
Pole pos aux cont.
Off
CurrSel Current function selection - CB oper monitor
Continuous monitor
CurrUnsymLeve Unsym magn of lowest phase current compared to the
% 0 100
l highest.
CurrRelLevel Curr magnit for release of the function in % of IBase %IB 0 100
27 Two step undervoltage protection (PUVM, 27)
TOV1
Operat Operation - On - Off
UBase Base setting for voltage levels in kV kV 0.05 2000.00
27 - 1 Definite time
Inverse curve A
Characterist1 Operation characteristic selection, step 1 - 1 outcurve
of 3 B
Inverse
OpMode1 Operation Mode - Prog. inv.ofCurve
2 out 3
U1< U setting/start val (DT & IDMT) in % of UBase, step 1 %UB 1 3 out
100of 3
t1 Operate time delay in DT mode, step 1. s 0.000 60.000
tReset1 Time delay in DT reset (s), step 1 s 0.000 60.000
t1Min Minimum operate time in IDMT mode (s), step 1 s 0.000 Instantaneous
60.000
ResetTypeCrv1 IDMT mode reset type selector, step 1 - Frozen timer
tlReset1 Time delay in IDMT reset (s), step 1 s 0.000Linearly decreased
60.000
k1 Time multiplier in IDMT mode, step 1 - 0.05 1.10
ACrv1 Setting A for programmable U< IDMT curve, step 1 - 0.005 200.000
BCrv1 Setting B for programmable U< IDMT curve, step 1 - 0.50 100.00
CCrv1 Setting C for programmable U< IDMT curve, step 1 - 0.0 1.0
DCrv1 Setting D for programmable U< IDMT curve, step 1 - 0.005 200.000
PCrv1 Setting P for programmable U< IDMT curve, step 1 - 0.000 3.000
CrvSat1 Tuning param for prog. U< IDMT curve, step 1 % 0 100
Off
IntBlkSel1 Internal (low level) blocking mode, step 1 - Block of trip
IntBlkStVal1 U setting for internal blocking in % of UBase, step 1 %UB 1 Block
100all
tBlkUV1 U setting for internal blocking in % of UBase, step 1 s 0.000 60.000
HystAbs1 Absolute hysteresis in % of UBase, step 1 %UB 0.0 100.0
HystAbsIntBlk1 Abs hysteresis for int.l block. in % of UBase, step 1 %UB 0.0 100.0
27 - 2 Definite time
Inverse curve A
Characterist2 Operation characteristic selection, step 2 - 1 outcurve
of 3 B
Inverse
OpMode2 Operation Mode - Prog. inv.ofCurve
2 out 3
U2< U setting/start val (DT & IDMT) in % of UBase, step 2 %UB 1 3 out
100of 3
t2 Operate time delay in DT mode, step 2 s 0.000 60.000
tReset2 Time delay in DT reset (s), step 2 s 0.000 60.000
t2Min Minimum operate time in IDMT mode (s), step 2 s 0.000 Instantaneous
60.000
ResetTypeCrv2 IDMT mode reset type selector, step 2 - Frozen timer
tlReset2 Time delay in IDMT reset (s), step 2 s 0.000Linearly decreased
60.000
k2 Time multiplier in IDMT mode, step 2 - 0.05 1.10
ACrv2 Setting A for programmable U< IDMT curve, step 2 - 0.005 200.000
BCrv2 Setting B for programmable U< IDMT curve, step 2 - 0.50 100.00
CCrv2 Setting C for programmable U< IDMT curve, step 2 - 0.0 1.0
DCrv2 Setting D for programmable U< IDMT curve, step 2 - 0.005 200.000
PCrv2 Setting P for programmable U< IDMT curve, step 2 - 0.000 3.000
CrvSat2 Tuning param for prog. U< IDMT curve, step 2 % 0 100
Off
IntBlkSel2 Internal (low level) blocking mode, step 2 - Block of trip
IntBlkStVal2 U setting for internal blocking in % of UBase, step 2 %UB 1 Block
100all
tBlkUV2 U setting for internal blocking in % of UBase, step 2 s 0.000 60.000
HystAbs2 Absolute hysteresis in % of UBase, step 2 %UB 0.0 100.0
HystAbsIntBlk2 Abs hysteresis for int.l block. in % of UBase, step 2 %UB 0.0 100.0
TOV2
Operat Operation - On - Off
UBase Base setting for voltage levels in kV kV 0.05 2000.00
27 - 1
Definite time
Inverse curve A
Characterist1 Operation characteristic selection, step 1 -
Inverse curve B
Prog. inv. Curve
1 out of 3
OpMode1 Operation Mode - 2 out of 3
3 out of 3
U1< U setting/start val (DT & IDMT) in % of UBase, step 1 %UB 1 100
t1 Operate time delay in DT mode, step 1. s 0.000 60.000
tReset1 Time delay in DT reset (s), step 1 s 0.000 60.000
t1Min Minimum operate time in IDMT mode (s), step 1 s 0.000 60.000
Instantaneous
ResetTypeCrv1 IDMT mode reset type selector, step 1 - Frozen timer
Linearly decreased
tlReset1 Time delay in IDMT reset (s), step 1 s 0.000 60.000
k1 Time multiplier in IDMT mode, step 1 - 0.05 1.10
ACrv1 Setting A for programmable U< IDMT curve, step 1 - 0.005 200.000
BCrv1 Setting B for programmable U< IDMT curve, step 1 - 0.50 100.00
CCrv1 Setting C for programmable U< IDMT curve, step 1 - 0.0 1.0
DCrv1 Setting D for programmable U< IDMT curve, step 1 - 0.005 200.000
PCrv1 Setting P for programmable U< IDMT curve, step 1 - 0.000 3.000
CrvSat1 Tuning param for prog. U< IDMT curve, step 1 % 0 100
Off
IntBlkSel1 Internal (low level) blocking mode, step 1 - Block of trip
Block all
IntBlkStVal1 U setting for internal blocking in % of UBase, step 1 %UB 1 100
tBlkUV1 U setting for internal blocking in % of UBase, step 1 s 0.000 60.000
HystAbs1 Absolute hysteresis in % of UBase, step 1 %UB 0.0 100.0
HystAbsIntBlk1 Abs hysteresis for int.l block. in % of UBase, step 1 %UB 0.0 100.0
27 - 2
Definite time
Inverse curve A
Characterist2 Operation characteristic selection, step 2 -
Inverse curve B
Prog. inv. Curve
1 out of 3
OpMode2 Operation Mode - 2 out of 3
3 out of 3
U2< U setting/start val (DT & IDMT) in % of UBase, step 2 %UB 1 100
t2 Operate time delay in DT mode, step 2 s 0.000 60.000
tReset2 Time delay in DT reset (s), step 2 s 0.000 60.000
t2Min Minimum operate time in IDMT mode (s), step 2 s 0.000 60.000
Instantaneous
ResetTypeCrv2 IDMT mode reset type selector, step 2 - Frozen timer
Linearly decreased
tlReset2 Time delay in IDMT reset (s), step 2 s 0.000 60.000
k2 Time multiplier in IDMT mode, step 2 - 0.05 1.10
ACrv2 Setting A for programmable U< IDMT curve, step 2 - 0.005 200.000
BCrv2 Setting B for programmable U< IDMT curve, step 2 - 0.50 100.00
CCrv2 Setting C for programmable U< IDMT curve, step 2 - 0.0 1.0
DCrv2 Setting D for programmable U< IDMT curve, step 2 - 0.005 200.000
PCrv2 Setting P for programmable U< IDMT curve, step 2 - 0.000 3.000
CrvSat2 Tuning param for prog. U< IDMT curve, step 2 % 0 100
Off
IntBlkSel2 Internal (low level) blocking mode, step 2 - Block of trip
Block all
IntBlkStVal2 U setting for internal blocking in % of UBase, step 2 %UB 1 100
tBlkUV2 U setting for internal blocking in % of UBase, step 2 s 0.000 60.000
HystAbs2 Absolute hysteresis in % of UBase, step 2 %UB 0.0 100.0
HystAbsIntBlk2 Abs hysteresis for int.l block. in % of UBase, step 2 %UB 0.0 100.0
59 Two step overvoltage protection (POVM, 59)
Operation Operation - On - Off
UBase Base setting for voltage levels in kV kV 0.05 2000.00
59 - 1
Definite time
Inverse curve A
Characterist1 Operation characteristic selection, step 1 - Inverse curve B
Inverse curve C
Prog. inv. Curve
1 out of 3
OpMode1 Operation Mode - 2 out of 3
3 out of 3
U1> U setting/start val (DT & IDMT) in % of UBase, step 1 %UB 1 200
t1 Operate time delay in DT mode, step 1. s 0.000 60.000
tReset1 Time delay in DT reset (s), step 1 s 0.000 60.000
t1Min Minimum operate time in IDMT mode (s), step 1 s 0.000 60.000
Instantaneous
ResetTypeCrv1 IDMT mode reset type selector, step 1 - Frozen timer
Linearly decreased
tlReset1 Time delay in IDMT reset (s), step 1 s 0.000 60.000
k1 Time multiplier in IDMT mode, step 1 - 0.05 1.10
ACrv1 Setting A for programmable U> IDMT curve, step 1 - 0.005 200.000
BCrv1 Setting B for programmable U> IDMT curve, step 1 - 0.50 100.00
CCrv1 Setting C for programmable U> IDMT curve, step 1 - 0.0 1.0
DCrv1 Setting D for programmable U> IDMT curve, step 1 - 0.005 60.000
PCrv1 Setting P for programmable U> IDMT curve, step 1 - 0.000 3.000
CrvSat1 Tuning param for prog. U> IDMT curve, step 1 % 0 100
HystAbs1 Absolute hysteresis in % of UBase, step 1 %UB 0.0 100.0
59 - 2
Definite time
Inverse curve A
Characterist2 Operation characteristic selection, step 2 - Inverse curve B
Inverse curve C
Prog. inv. Curve
1 out of 3
OpMode2 Operation Mode - 2 out of 3
3 out of 3
U2> U setting/start val (DT & IDMT) in % of UBase, step 2 %UB 1 200
t2 Operate time delay in DT mode, step 2 s 0.000 60.000
tReset2 Time delay in DT reset (s), step 2 s 0.000 60.000
t2Min Minimum operate time in IDMT mode (s), step 2 s 0.000 60.000
Instantaneous
ResetTypeCrv2 IDMT mode reset type selector, step 2 - Frozen timer
Linearly decreased
tlReset2 Time delay in IDMT reset (s), step 2 s 0.000 60.000
k2 Time multiplier in IDMT mode, step 2 - 0.05 1.10
ACrv2 Setting A for programmable U> IDMT curve, step 2 - 0.005 200.000
BCrv2 Setting B for programmable U> IDMT curve, step 2 - 0.50 100.00
CCrv2 Setting C for programmable U> IDMT curve, step 2 - 0.0 1.0
DCrv2 Setting D for programmable U> IDMT curve, step 2 - 0.005 60.000
PCrv2 Setting P for programmable U> IDMT curve, step 2 - 0.000 3.000
CrvSat2 Tuning param for prog. U> IDMT curve, step 2 % 0 100
HystAbs2 Absolute hysteresis in % of UBase, step 2 %UB 0.0 100.0
59N Two step residual overvoltage protection (POVM, 59N)
Operation Operation - On - Off
UBase Base voltage, phase-phase in Kv kV 0.05 2000.00
59N - 1
Definite time
Inverse curve A
Characterist1 Operation characteristic selection, step 1 - Inverse curve B
Inverse curve C
Prog. inv. Curve
U1> U setting/start val (DT & IDMT) in % of UBase, step 1 %UB 1 200
t1 Operate time delay in DT mode, step 1. s 0.000 60.000
tReset1 Time delay in DT reset (s), step 1 s 0.000 60.000
t1Min Minimum operate time in IDMT mode (s), step 1 s 0.000 60.000
Instantaneous
ResetTypeCrv1 IDMT mode reset type selector, step 1 - Frozen timer
Linearly decreased
tlReset1 Time delay in IDMT reset (s), step 1 s 0.000 60.000
k1 Time multiplier in IDMT mode, step 1 - 0.05 1.10
ACrv1 Setting A for programmable U> IDMT curve, step 1 - 0.005 200.000
BCrv1 Setting B for programmable U> IDMT curve, step 1 - 0.50 100.00
CCrv1 Setting C for programmable U> IDMT curve, step 1 - 0.0 1.0
DCrv1 Setting D for programmable U> IDMT curve, step 1 - 0.005 60.000
PCrv1 Setting P for programmable U> IDMT curve, step 1 - 0.000 3.000
CrvSat1 Tuning param for prog. U> IDMT curve, step 1 % 0 100
HystAbs1 Absolute hysteresis in % of UBase, step 1 %UB 0.0 100.0
59N - 2
Definite time
Inverse curve A
Characterist2 Operation characteristic selection, step 2 - Inverse curve B
Inverse curve C
Prog. inv. Curve
U2> U setting/start val (DT & IDMT) in % of UBase, step 2 %UB 1 200
t2 Operate time delay in DT mode, step 2 s 0.000 60.000
tReset2 Time delay in DT reset (s), step 2 s 0.000 60.000
t2Min Minimum operate time in IDMT mode (s), step 2 s 0.000 60.000
Instantaneous
ResetTypeCrv2 IDMT mode reset type selector, step 2 - Frozen timer
Linearly decreased
tlReset2 Time delay in IDMT reset (s), step 2 s 0.000 60.000
k2 Time multiplier in IDMT mode, step 2 - 0.05 1.10
ACrv2 Setting A for programmable U> IDMT curve, step 2 - 0.005 200.000
BCrv2 Setting B for programmable U> IDMT curve, step 2 - 0.50 100.00
CCrv2 Setting C for programmable U> IDMT curve, step 2 - 0.0 1.0
DCrv2 Setting D for programmable U> IDMT curve, step 2 - 0.005 60.000
PCrv2 Setting P for programmable U> IDMT curve, step 2 - 0.000 3.000
CrvSat2 Tuning param for prog. U> IDMT curve, step 2 % 0 100
HystAbs2 Absolute hysteresis in % of UBase, step 2 %UB 0.0 100.0
85 Scheme communication logic for distance protection (PSCH, 85)
Operation Operation - On - Off

Off, Intertrip, Permissive UR,


SchemeType Scheme Type -
Permissive OR, Blocking

tCoord Co-ordination time for blocking communication scheme s 0.000 60.000


tSendMin Minimum duration of a carrier send signal s 0.000 60.000
Unblock Operation mode of unblocking logic - Off, NoRestart, Restart
tSecurity Security timer for loss of carrier guard detection s 0.000 60.000
85 Current reversal and weak-end infeed logic for distance protection (PSCH, 85)
CurrRev Operating mode of current Reversal Logic - Off, On
tPickUpRev Pickup time for current reversal logic s 0.000 60.000
tDelayRev Time delay to prevent carrier send and local trip s 0.000 60.000
OFF
WEI Operating mode of WEI logic - ECHO
ECHO & TRIP
tPickUpWEI Pickup time for the WEI logic s 0.000 60.000
UBase Base value for voltage settings in kV kV 0.05 2000.00
UPP< Phase to Phase voltage for detection of fault condition %UB 10 90
UPN< Phase to Neutral voltage for detection of fault condition %UB 10 90
PLA
Local acceleration logic (PLAL)
L
Operation Operation - On - Off
IBase Base setting for current values A 1 99999
LoadCurr Load current before disturbance in % of IBase %IB 1 100
LossOfLoad Operation of loss of load - On - Off
ZoneExtension Operation of Zone Extension - On - Off
MinCurr Lev taken as curr loss due to remote CB trip in % IBase %IB 1 100
tLowCurr Time delay on pick-up for MINCURR value s 0.000 60.000
tLoadOn Time delay on pick-up for load current release s 0.000 60.000
tLoadOff Time delay on drop off for load current release s 0.000 60.000
85 Scheme communication logic for residual overcurrent protection (PSCH, 85)
Operation Operation - On - Off

Off, Intertrip, Permissive UR,


SchemeType Scheme Type -
Permissive OR, Blocking

tCoord Communication scheme coordination time s 0.000 60.000


tSendMin Minimum duration of a carrier send signal s 0.000 60.000
Unblock Operation mode of unblocking logic - Off, NoRestart, Restart
tSecurity Security timer for loss of carrier guard detection s 0.000 60.000
85 Current reversal and weak-end infeed logic for residual overcurrent protection (PSCH, 85)
CurrRev Operating mode of current Reversal Logic - Off, On
tPickUpRev Pickup time for current reversal logic s 0.000 60.000
tDelayRev Time delay to prevent carrier send and local trip s 0.000 60.000
OFF
WEI Operating mode of WEI logic - ECHO
ECHO & TRIP
tPickUpWEI coordination time for the WEI logic s 0.000 60.000
UBase Base value for voltage settings in kV kV 0.05 2000.00
UPP< Phase to Phase voltage for detection of fault condition %UB 10 90
UPN< Phase to Neutral voltage for detection of fault condition %UB 10 90
CCIONES
Región: ZONA SUR
Dpto: AREQUIPA
Empresa: XSTRATA
Diag.Unif.N°:
Man.Serv.N°:
Fecha: 13-Feb-14
Respons.: EQV
Revisión: 0

ACTUAL (AS BUILT) ECP 2014 OBSERVACIONES


GRUPO 1 GRUPO 1
PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

RRIENTE
A

roachment

or distance
or 67N

L-2020
ANTAPACCAY
TINTAYA
8
tot.corregidos
0.55
4.07
0.00
26.47
3.35
13.22
0.00
18.04
-
-
Angulo

1.4359
1.5708
-0.0675
-
-
-
1.4359
1.5708
-

1.3227
1.5708
-0.1240
-
-
-
1.3227
1.5708
Angulo
-9.2634
-
-
-9.2634

-
-
-
-
- 1 1000 1 1000
- 1000.00 1000.00
-
-

-
-
-
-
- 115 230000 115 230000
- 2000.00 2000.00
-
-
- 0.50 0.50
- 2.00 2.00

- 120 120
- 291.41 291.41

ON - OFF - ON - ON
1 - 1000 - 1000
0.05 - 220 - 220
Off
Non-directional
- Forward - Forward
Forward
Reverse
0.01 1.63 3.25 1.63 3.25
0.01 0.22 0.44 0.22 0.44
0.01 5.46 10.91 5.46 10.91
0.01 1.34 2.68 1.34 2.68
0.01 10.00 20.00 4.88 9.75
0.01 10.66 21.31 7.32 14.63
ON - OFF - ON - ON
ON - OFF - ON - ON
0.001 - 0 - 0
ON - OFF - ON - ON
ON - OFF - ON - ON
0.001 - 0 - 0
1 - 20 - 20
1 - 20 - 20
1 - 5 - 5

ON - OFF - ON - ON
1 - 1000 - 1000
0.05 - 220 - 220
Off
Non-directional
- Forward - Forward
Forward
Reverse
0.01 8.81 17.62 8.81 17.62
0.01 1.19 2.38 1.19 2.38
0.01 28.62 57.23 28.62 57.23
0.01 7.25 14.50 7.25 14.50
0.01 17.50 35.00 17.50 35.00
0.01 31.08 62.16 31.08 62.16
ON - OFF - ON - ON
ON - OFF - ON - ON
0.001 - 0.25 - 0.25
ON - OFF - ON - ON
ON - OFF - ON - ON
0.001 - 0.25 - 0.25
1 - 20 - 20
1 - 20 - 20

ON - OFF - ON - ON
1 - 1000 - 1000
0.01 - 220 - 220
Off
Non-directional
- Reverse - Forward
Forward
Reverse
0.01 6.05 12.10 12.88 25.75
0.01 0.82 1.64 1.74 3.48
0.01 19.65 39.30 41.82 83.64
0.01 4.98 9.96 10.60 21.20
0.01 10.00 20.00 17.50 35.00
0.01 10.66 21.31 31.08 62.16
ON - OFF - ON - ON
ON - OFF - ON - ON
0.001 - 1.50 - 1.00
ON - OFF - ON - ON
ON - OFF - ON - ON
0.001 - 1.50 - 1.00
1 - 20 - 20
1 - 20 - 20

ON - OFF - OFF - OFF


1 - -
0.01 - -
Off
Non-directional
- -
Forward
Reverse
0.01 0.00 0.00
0.01 0.00 0.00
0.01 0.00 0.00
0.01 0.00 0.00
0.01 0.00 0.00
0.01 0.00 0.00
ON - OFF - -
ON - OFF - -
0.001 - -
ON - OFF - -
ON - OFF - -
0.001 - -
1 - -
1 - -

ON - OFF - ON - ON
1 - 1000 - 1000
0.01 - 220 - 220
Off
Non-directional
- Forward - Reverse
Forward
Reverse
0.01 12.88 25.75 6.05 12.10
0.01 1.74 3.48 0.82 1.64
0.01 41.82 83.64 19.65 39.30
0.01 10.60 21.20 4.98 9.96
0.01 17.50 35.00 10.00 20.00
0.01 31.08 62.16 10.66 21.31
ON - OFF - ON - ON
ON - OFF - ON - ON
0.001 - 1.00 - 1.50
ON - OFF - ON - ON
ON - OFF - ON - ON
0.001 - 1.00 - 1.50
1 - 20 - 20
1 - 20 - 20

1 - 115 - 115
1 - 15 - 15
1 - 10 - 10
1 - 1000 - 1000
0.05 - 220 - 220

1 - 1000 - 1000
1 - 40 - 40
1 - 20 - 20
0.01 50.00 100.00 50.00 100.00
0.01 50.00 100.00 50.00 100.00
1 - 30 - 30
0.01 15.45 30.90 15.45 30.90
0.01 50.19 100.37 50.19 100.37
0.01 21.00 42.00 21.00 42.00
0.01 21.00 42.00 21.00 42.00
0.01 37.30 74.59 37.30 74.59
0.01 37.30 74.59 37.30 74.59
1 - 10 - 10
1 - 5 - 5

ON - OFF - ON - ON
0.01 15.45 30.90 15.45 30.90
0.01 2.09 4.17 2.09 4.17
0.01 21.00 42.00 21.00 42.00
0.01 12.10 24.20 12.10 24.20
0.01 21.00 42.00 21.00 42.00
ON - OFF - OFF - OFF
0.01 60.00 120.00 60.00 120.00
1 - 30 - 30
0.01 60.00 120.00 60.00 120.00
0.01 - 0.8 - 0.8
0.01 - 0.8 - 0.8
0.001 - 0.025 - 0.025
0.001 - 0.015 - 0.015
0.001 - 0.25 - 0.25
0.001 - 0.5 - 0.5
0.001 - 3.0 - 3.0
0.001 - 0.3 - 0.3
0.001 - 2.0 - 2.0
1 - 5.0 - 5.0
1 - 1000.0 - 1000.0

ON - OFF - ON - ON
1 - 1000 - 1000
0.05 - 220 - 220
1 - 20 - 20
1 - 20 - 20

ON - OFF - OFF - OFF


1 - - -
2 out of 3
- - -
1 out of 3
1 - - -
0.1 - - -

ON - OFF - ON - OFF
1 - 1000 -
0.01 - 220 -
0.1 - - -
0.1 - - -
1.0 - 55 -
1 - 5 -
Not Used
1 out of 3
- 1 out of 3 -
2 out of 3
3 out of 3
1 - 20 -

Off
Non-directional
- Forward - OFF
Forward
Reverse
EI, VI, NI, MI, DT
L.T.E. inv
L.T.V. inv
L.T. inv
VI, EI, S.T.I, L.T.I, DT - IEC S.T.I -
Reserved
Programmable
RI type
RD type
1 - 15 -
0.001 - 0.00 -
0.01 - 0.13 -
0.1 - 1.00 -
0.001 - 0.00 -
nstantaneous
Instantaneou
IEC Reset - -
s
ANSI Reset
0.001 - 0.00 -
0.001 - -
0.001 - -
0.01 - -
0.1 - -
0.001 - -
0.001 - -
0.1 - -
abled - Enabled - Enabled -

Off
Non-directional
- -
Forward
Reverse

EI, VI, NI, MI, DT


L.T.E. inv
L.T.V. inv
L.T. inv
VI, EI, S.T.I, L.T.I, DT - -
Reserved
Programmable
RI type
RD type
1 - -
0.001 - -
0.01 - -
0.1 - -
0.001 - -
nstantaneous
IEC Reset - -
ANSI Reset
0.001 - -
0.001 - -
0.001 - -
0.01 - -
0.1 - -
0.001 - -
0.001 - -
0.1 - -
abled - Enabled - -

Off
Non-directional
- -
Forward
Reverse

EI, VI, NI, MI, DT


L.T.E. inv
L.T.V. inv
L.T. inv
VI, EI, S.T.I, L.T.I, DT - -
Reserved
Programmable
RI type
RD type
1 - -
0.001 - -
0.01 - -
0.1 - -
0.001 - -
nstantaneous
IEC Reset - -
ANSI Reset
0.001 - -
0.001 - -
0.001 - -
0.01 - -
0.1 - -
0.001 - -
0.001 - -
0.1 - -
abled - Enabled - -

Off
Non-directional
- -
Forward
Reverse
EI, VI, NI, MI, DT
L.T.E. inv
L.T.V. inv
L.T. inv
VI, EI, S.T.I, L.T.I, DT - -
Reserved
Programmable
RI type
RD type
1 - - -
0.001 - - -
0.01 - - -
0.1 - - -
0.001 - - -
nstantaneous
IEC Reset - - -
ANSI Reset
0.001 - - -
0.001 - - -
0.001 - - -
0.01 - - -
0.1 - - -
0.001 - - -
0.001 - - -
0.1 - - -
abled - Enabled - - -

ON - OFF - OFF - OFF


1 - - -
1 - - -
0.1 - - -

ON - OFF - ON - ON
1 - 1000 - 1000
0.01 - 220 - 220
1 - - - -
1 - 65 - 65
1 - -
1 - 10 - 10
1 - 20 - 20
IN2>, IN3>, IN4> - IN4> - IN4>
ON - OFF - OFF - OFF
Open
Closed - Open - Open
loseCommand
Off
SOTF
- OFF - OFF
UnderTime
OTF+UnderTime
0.001 - 0.10 - 0.10
abled - Enabled - OFF - OFF
0.001 - 1.00 - 1.00
CB position
- -
CB command
0.001 - -

Off
Non-directional Non- Non-
- -
Forward directional directional
Reverse

EI, VI, NI, MI, DT


L.T.E. inv
L.T.V. inv
L.T. inv
VI, EI, S.T.I, L.T.I, DT - IEC NI - IEC NI
Reserved
Programmable
RI type
RD type
1 - 10 - 10
0.001 - 0.00 - 0.00
0.01 - 0.10 - 0.10
0.1 - 1.00 - 1.00
0.001 - 0.00 - 0.00
nstantaneous
Instantaneou Instantaneo
IEC Reset - -
s us
ANSI Reset
0.001 - 0.20 - 0.20
abled - Enabled - ON - ON
0.001 - -
0.001 - -
0.01 - -
0.1 - -
0.001 - -
0.001 - -
0.1 - -

Off
Non-directional
- -
Forward
Reverse

EI, VI, NI, MI, DT


L.T.E. inv
L.T.V. inv
L.T. inv
VI, EI, S.T.I, L.T.I, DT - -
Reserved
Programmable
RI type
RD type
1 - -
0.001 - -
0.01 - -
0.1 - -
0.001 - -
nstantaneous
IEC Reset - -
ANSI Reset
0.001 - -
abled - Enabled - -
0.001 - -
0.001 - -
0.01 - -
0.1 - -
0.001 - -
0.001 - -
0.1 - -

Off
Non-directional
- -
Forward
Reverse

EI, VI, NI, MI, DT


L.T.E. inv
L.T.V. inv
L.T. inv
VI, EI, S.T.I, L.T.I, DT - -
Reserved
Programmable
RI type
RD type
1 - -
0.001 - -
0.01 - -
0.1 - -
0.001 - -
nstantaneous
IEC Reset - -
ANSI Reset
0.001 - -
abled - Enabled - -
0.001 - -
0.001 - -
0.01 - -
0.1 - -
0.001 - -
0.001 - -
0.1 - -
Step 2 init
- - -
Step 3 init
Off
Non-directional
- -
Forward
Reverse

EI, VI, NI, MI, DT


L.T.E. inv
L.T.V. inv
L.T. inv
VI, EI, S.T.I, L.T.I, DT - -
Reserved
Programmable
RI type
RD type
1 - -
0.001 - -
0.01 - -
0.1 - -
0.001 - -
nstantaneous
IEC Reset - -
ANSI Reset
0.001 - -
abled - Enabled - -
0.001 - -
0.001 - -
0.01 - -
0.1 - -
0.001 - -
0.001 - -
0.1 - -

ON - OFF - -
1 - - -
1 - - -
1 - - -
1 - - -
1 - - -
1 - - -
1 - - -
1 - - -
1 - - -

On - Off - ON - ON
1 - 394 - 394
Current
Contact - Current - Current
urrent&Contact
2 out of 4
1 out of 3 - 1 out of 3 - 1 out of 3
1 out of 4
Retrip Off
I> Check - Retrip Off - Retrip Off
No I> Check
1 - 50 - 50
1 - 20 - 20
1 - 20 - 20
0.001 - 0.000 - 0.000
0.001 - 0.150 - 0.150
0.001 - 0.150 - 0.150
0.001 - 0.030 - 0.030
0.001 - 5.000 - 5.000
0.001 - 0.200 - 0.200

On - Off - OFF - OFF


1 - - - -
Release
- - - -
Continuous
2 out of 4
1 out of 3 - - - -
1 out of 4
1 - - - -
0.001 - - - -

On - Off - OFF - OFF


1 - - -
0.001 - - -
Off
signal from CB - - -
le pos aux cont.
Off
B oper monitor - - -
ntinuous monitor
1 - - -
1 - - -

On - Off - OFF - OFF


0.01 - -
Definite time
nverse curve A
1 outcurve
of 3 B - OFF - OFF
nverse
rog. inv.ofCurve
2 out 3 - -
3 out of 3 1 - -
0.001 - -
0.001 - -
nstantaneous 0.001 - -
Frozen timer - -
early decreased0.001 - -
0.01 - -
0.001 - -
0.01 - -
0.1 - -
0.001 - -
0.001 - -
Off 1 - -
Block of trip - -
Block all 1 - -
0.001 - -
0.1 - -
0.1 - - -
Definite time
nverse curve A
1 outcurve
of 3 B - -
nverse
rog. inv.ofCurve
2 out 3 - -
3 out of 3 1 - -
0.001 - -
0.001 - -
nstantaneous 0.001 - -
Frozen timer - -
early decreased0.001 - -
0.01 - -
0.001 - -
0.01 - -
0.1 - -
0.001 - -
0.001 - -
Off 1 - -
Block of trip - -
Block all 1 - -
0.001 - -
0.1 - -
0.1 - - -

On - Off - -
0.01 - -

Definite time
nverse curve A
- -
nverse curve B
rog. inv. Curve
1 out of 3
2 out of 3 - -
3 out of 3
1 - -
0.001 - -
0.001 - -
0.001 - -
nstantaneous
Frozen timer - -
early decreased
0.001 - -
0.01 - -
0.001 - -
0.01 - -
0.1 - -
0.001 - -
0.001 - -
1 - -
Off
Block of trip - -
Block all
1 - -
0.001 - -
0.1 - -
0.1 - - -

Definite time
nverse curve A
- -
nverse curve B
rog. inv. Curve
1 out of 3
2 out of 3 - -
3 out of 3
1 - -
0.001 - -
0.001 - -
0.001 - -
nstantaneous
Frozen timer - -
early decreased
0.001 - -
0.01 - -
0.001 - -
0.01 - -
0.1 - -
0.001 - -
0.001 - -
1 - -
Off
Block of trip - -
Block all
1 - -
0.001 - -
0.1 - -
0.1 - - -

On - Off - ON - ON
0.01 - 220 - 220

Definite time
nverse curve A
Definite
nverse curve B - Definite time -
time
nverse curve C
rog. inv. Curve
1 out of 3
2 out of 3 - 1 out of 3 - 1 out of 3
3 out of 3
1 - 130 - 130
0.001 - 3.000 - 3.000
0.001 - 0.000 - 0.000
0.001 - 0.050 - 0.050
nstantaneous
Instantaneou Instantaneo
Frozen timer - -
s us
early decreased
0.001 - 0.025 - 0.025
0.01 - -
0.001 - -
0.01 - -
0.1 - -
0.001 - -
0.001 - -
1 - -
0.1 - -

Definite time
nverse curve A
nverse curve B - OFF - OFF
nverse curve C
rog. inv. Curve
1 out of 3
2 out of 3 - - -
3 out of 3
1 - -
0.001 - -
0.001 - - -
0.001 - - -
nstantaneous
Frozen timer - - -
early decreased
0.001 - - -
0.01 - - -
0.001 - - -
0.01 - - -
0.1 - - -
0.001 - - -
0.001 - - -
1 - - -
0.1 - - -

On - Off - OFF - OFF


0.01 - - -

Definite time
nverse curve A
nverse curve B - OFF - OFF
nverse curve C
rog. inv. Curve
1 - - -
0.001 - - -
0.001 - - -
0.001 - - -
nstantaneous
Frozen timer - - -
early decreased
0.001 - - -
0.01 - - -
0.001 - - -
0.01 - - -
0.1 - - -
0.001 - - -
0.001 - - -
1 - - -
0.1 - - -

Definite time
nverse curve A
nverse curve B - - -
nverse curve C
rog. inv. Curve
1 - - -
0.001 - - -
0.001 - - -
0.001 - - -
nstantaneous
Frozen timer - - -
early decreased
0.001 - - -
0.01 - - -
0.001 - - -
0.01 - - -
0.1 - - -
0.001 - - -
0.001 - - -
1 - - -
0.1 - - -
On - Off - ON - ON

rtrip, Permissive UR, Permissive Permissive


- -
ssive OR, Blocking OR OR

0.001 - 0.035 - 0.035


0.001 - 0.100 - 0.100
NoRestart, Restart - OFF - OFF
0.001 - 0.035 - 0.035

Off, On - OFF - OFF


0.001 - - - -
0.001 - - - -
OFF
ECHO & ECHO &
ECHO - -
TRIP TRIP
ECHO & TRIP
0.001 - - - -
0.01 - - - -
1 - - - -
1 - - - -

On - Off - OFF - OFF


1 - - -
1 - - -
On - Off - - -
On - Off - - -
1 - - -
0.001 - - -
0.001 - - -
0.001 - - -

On - Off - OFF - OFF

rtrip, Permissive UR,


- - -
ssive OR, Blocking

0.001 - - -
0.001 - - -
NoRestart, Restart - - -
0.001 - - -
85)
Off, On - OFF - OFF
0.001 - - -
0.001 - - -
OFF
ECHO - - -
ECHO & TRIP
0.001 - - -
0.01 - - -
1 - - -
1 - - -
NES