1. A mechanical – draft cooling tower receives 115 m 3 per second of atmospheric air at 103
kPa, 32°C dry bulb temperature, 55% RH and discharges the air saturated at 36°C. If the
tower receives 200 of water at 40°C, what will be the exit temperature of the cooled
water?
H2O IN (3)
𝑘𝑔
mH2O = 200
𝑠
T3 = 40°C AIR OUT (2)
T2 = 36°C
AIR IN (1)
Pa = 103 kPa
Tdb = 32°C H2O OUT (4)
RH = 55%
V o = 115 m3/s T4 = ?
@ (1) T db = 32°C
@ (2) T 2 = 36°C
H3 = 167.57 kJ/kg
OMB:
m 4 = m 3 + (Ħ1 - Ħ2) m air in = 200 + (0.0163 kg/kg - 0.0384 kg/kg)( 129.753 kg/s)
m 4 = 197.132 kg/s
Energy Balance:
( 129.753 kg/s) (73.92477 kJ/kg) +200 (167.57 kJ/kg) = 197.132 kg/s (H4) + ( 129.753 kg/s)(
134.7998 kJ/kg)
H4 = 129.9397kJ/kg
By interpolation: T 4 = 31.99 °C
2. An auditorium is to be maintained at 25°C dry bulb temperature and 50% RH. The
supply air enters the auditorium at 17°C. The sensible heat and latent heat loads are 150
kW and 62 kW, respectively. Determine the wet bulb temperature, relative humidity, and
volume flow rate of the supply air.
T wet bulb = 14 °C
RH = 71 %
Ħ1 = 0.0087 kg/kg
VH = 0.834 m 3/kg
Vo = m VH = 18.63 kg/s (0.834 m 3/kg) = 15.537 m3/s
Vo = 15.537 m3/s