2/15/2018 What is the criteria to use 2 or 3 way control valves in chilled water lines?

s? Where to use 2 way and not 3 way and where to use 3 way not 2 way…

Ask a Question
By Muhammad Arsalan Siddiqui (Https://People.Bayt.Com/Engineer-Arsalan/) at 05-Aug-2013
Views (21420) Followers (4) Upvote (3)
And get answers from specialists

HVAC (/En/Specialties/S/Hvac/) HVAC Controls (/En/Specialties/S/Hvac-Controls/) Write a Question

What is the criteria to use 2 or 3 way control


valves in chilled water lines? Where to use 2 Ask a Question
Next Question
(https://www.bayt.com/en/login/)
What is role of
way and not 3 way and where to use 3 way VFD in chilled
water system
not 2 way and why? and where we
used?
Follow (/En/Login/?Return_url=%2Fen%2Fspecialties%2Fq%2F19601%2Fwhat-Is-The-Criteria-To-
Related Questions (https://www.bayt.com/en
is-role-of-vfd-in-
Use-2-Or-3-Way-Control-Valves-In-Chilled-Water-Lines-Where-To-Use-2-Way-And-Not-3-Way-
chilled-water-
And-Where-To-Use-3-Way-Not-2-Way-And-Why%2F) Upvote (/En/Login/?
system-and-
Can a Chilled Water pump be sized
Return_url=%2Fen%2Fspecialties%2Fq%2F19601%2Fwhat-Is-The-Criteria-To-Use-2-Or-3-Way-
where-we-used/)
(Flow & Head) on the Cumulative
Control-Valves-In-Chilled-Water-Lines-Where-To-Use-2-Way-And-Not-3-Way-And-Where-To-Use-
3-Way-Not-2-Way-And-Why%2F) Comments Water ow...
Report Question (/En/Login/?Return_url=%2Fen%2Fspecialties%2Fq%2F19601%2Fwhat-Is- (/en/specialties/q/324275/can-a-
The-Criteria-To-Use-2-Or-3-Way-Control-Valves-In-Chilled-Water-Lines-Where-To-Use-2-Way- chilled-water-pump-be-sized- ow-
(https://people.bayt.com/r
And-Not-3-Way-And-Where-To-Use-3-Way-Not-2-Way-And-Why%2F) amp-head-on-the-cumulative-water-
rashid/)
owrates-of-high-speed-coil-fcu-amp-
Posted by:
fahu-performance/) Rashid Ali RASHID
(https://people.bayt.com/r
Write your answer rashid)
Register to Answer this Question
24-October-2016

Register Answer
(https://www.bayt.com/en/register-
j/) Preventing the chilled water pipes
after the pressure test.?
Log in (https://www.bayt.com/en/login/) if you're already a Bayt.com member. (/en/specialties/q/390011/preventing-
the-chilled-water-pipes-after-the-
pressure-test/)

11 Answers Write your answer

Answer

What is the best way to size chilled


Top Voted First
water pipes? is it correct to use
velocity ...
By
(/en/specialties/q/268010/what-is-the-
Mohamed Abdul Monem Abdulah
best-way-to-size-chilled-water-pipes-
(https://people.bayt.com/mohamed-abdulah/)
National Controls Operation & Services Manager - 4 years ago is-it-correct-to-use-velocity-method-
(https://people.bayt.com/mohamed- for-small-sizes-but-the-pressure-drop-
abdulah/) This is how we look to the the story: for-bigger-ones/)

1. 2Way Valve: Write your answer


2Way (Or2 Ports) Valve is passing the
water in one direction only. so if the Answer
valve is fully close it will trap the water
before it.
this will lead to a pressure increase in
this branch
2. 3 Way Valve:

https://www.bayt.com/en/specialties/q/19601/what-is-the-criteria-to-use-2-or-3-way-control-valves-in-chilled-water-lines-where-to-use-2-way-and-not-3-… 1/8
2/15/2018 What is the criteria to use 2 or 3 way control valves in chilled water lines? Where to use 2 way and not 3 way and where to use 3 way not 2 way…

3Way (Or3 ports) Valve is passing the water


in2 directions. Jobs For You
so if the valve is fully open the full amount of
water will be moving in one direction, if it
closed the water will pass to the other Quality Systems
Manager
direction, if the valve is partially open then
(/en/egypt/jobs/quality-
percent of the water will ow through
systems-manager-
direction1 and the remaining will pass 3310197/)
through the other (for Diverting Valve which Beyti Egypt
installed in the supply line). (/en/company/beyti-
In another cases if we install the valve in the egypt-1760625/) - Cairo,
return line so if the valve is open water will Egypt
ow through the unit (Cooling coil as Jan 08, 2018
example) then pass through main direction. Next Question
if the valve is close the water will by pass the What is role of
unit and then ow through the other Java Software Architect -
VFD in chilled
$30/hr (Work
waterfrom
system
direction through the valve (Mixing Valve
Home) and where we
which installed in the Return line).
(/en/uae/jobs/java-
used?
this will not cause the pressure rising.   (https://www.bayt.com/en
software-architect-30-hr-
is-role-of-vfd-in-
work-from-home-
Why we use the2 way valve? when you use the2
3555000/)chilled-water-
way valves in HVAC system in all the equipments system-and-
Crossoverwhere-we-used/)
in your building this means that you will not need
(/en/company/crossover-
all the chilled water to go through your system all
1726219/) - Dubai, UAE
the time if you don't need much cooling. so you
Jan 15, 2018
will be able to reduce the speed of the secondary (https://people.bayt.com/r
pumps of your system. this will lead to a huge rashid/)

energy saving in the running cost of your building Posted by:


Wessam Alahli Program
Rashid Ali RASHID
(depend on the number of Pumps and thier sizes). (/en/saudi-(https://people.bayt.com/r
Also you will be able to reduce the size of your arabia/jobs/wessam-
rashid)
pumps. But in this case you have to use Variable alahli-program-
24-October-2016
Speed Pumps. Also you should have2 sets of 3600362/)

Pumps, One set constant with Speed for Chillers National Commercial
Bank
and another set to serve the building. ans also By
(/en/company/national-
Pass Valve to gurantee the min ow of the chillers.
commercial-bank-
Otherwise you can use one set with a 1332219/) - Jeddah ,
variable  ow chillers. This has to be a decision in Saudi Arabia
the mechanical design stage depend on the cost Feb 07, 2018
calculation of the project. See More
Bottom line is: (/(https://www.bayt.com/en/international/jobs/search

use the2 way Valve in the system that can


withstand the variable water ow

use the3 way valve in the systems that needs a


constant water ow.

Upvote (7) Downvote Reply (0) Report

Can't nd the answers you're looking for?


Ask your own questions, and get answers from specialists on Bayt.com

Add Topics

https://www.bayt.com/en/specialties/q/19601/what-is-the-criteria-to-use-2-or-3-way-control-valves-in-chilled-water-lines-where-to-use-2-way-and-not-3-… 2/8
2/15/2018 What is the criteria to use 2 or 3 way control valves in chilled water lines? Where to use 2 way and not 3 way and where to use 3 way not 2 way…

Write your question

Enter your contact details to send you the answer or log in (/en/login/?
return_url=%2-fen%2-fspecialties%2-fq%2F19601%2-fwhat-is-the-criteria-to-
use-2-or-3-way-control-valves-in-chilled-water-lines-where-to-use-2-way-and-
not-3-way-and-where-to-use-3-way-not-2-way-and-why%2F)

First Name

Last Name

Your Email Next Question


What is role of
Ask a Certi ed Expert OR Ask the Community (free) VFD in chilled
water system
and where we
used?
(https://www.bayt.com/en
is-role-of-vfd-in-
chilled-water-
By Abdulla Bawadi (https://people.bayt.com/abdulla-bawadi/)
system-and-
Mechanical Construction - 4 years ago
where-we-used/)

WHEN THE PUMPS VFD2 WAY USED, AND IF IT


(https://people.bayt.com/abdulla-
CONSTANT SPEED THE3 WAY VALVE USED.
bawadi/) (https://people.bayt.com/r
Upvote (4) Downvote Reply (1) Report
rashid/)
Posted by:
Rashid Ali RASHID
(https://people.bayt.com/r
By
rashid)
ismail shaikh (https://people.bayt.com/ismail-shaikh- 24-October-2016
20347918/)
hvac technician - 3 years ago
(https://people.bayt.com/ismail-
shaikh- if chilled water pump has varaible speed we
(https://www.bayt.com/en/specialties/q/322284/what-
20347918/) use2way valve . if chilled water pump has is-role-of-vfd-in-chilled-water-system-and-where-we-
constant speed we use3 way valve because when used/)
temperature comes3way valve by pass chilled
water to return line . in varaible speed chilled
water speed decrease and increase according to
temperature requiredment.we use2 way valve.
Upvote (2) Downvote Reply (0) Report

By leoncio garcia jr (https://people.bayt.com/leoncio-garciajr/)


senior mechanical engineer - 4 years ago

The2-ways valve closes when cooling is not


(https://people.bayt.com/leoncio-
required in the space and the set point of the
garciajr/)
room thermostat has been achieved, thus the
CHW pump still running rises the CHW pressure in
the supply lines to the coils, to regulate this
pressure increase a DPT-pressure
transmitter/transducer wired to the PLC sends a
signal to vary the CHW pump ow, by varying the
pump motor speed using a VFD-variable
frequency converter on the motor, by pump

https://www.bayt.com/en/specialties/q/19601/what-is-the-criteria-to-use-2-or-3-way-control-valves-in-chilled-water-lines-where-to-use-2-way-and-not-3-… 3/8
2/15/2018 What is the criteria to use 2 or 3 way control valves in chilled water lines? Where to use 2 way and not 3 way and where to use 3 way not 2 way…

a nity laws, for a constant impeller diameter and


variable speed, new ow= old low x (new speed/
old speed ).

Upvote (2) Downvote Reply (0) Report

By
Adrian Corneleo (https://people.bayt.com/adrian-corneleo/)
Application engineer - 4 years ago

(https://people.bayt.com/adrian-
In Chilled water line Criteria to use2 or3-way valve
corneleo/) depends on the application type: 1.
 2-way valves are recommended in Chilled water Next Question
piping with primary const. What is role of
ow and secondary Variable speed pump.  VFD in chilled
3-way valves are not suitable for this system. water system
and where we
2.
used?
 2-way valves are recommended in Primary only (https://www.bayt.com/en
Variable speed pump.  is-role-of-vfd-in-
to maintain a minimum ow across chiller, a chilled-water-
system-and-
motorised bypass valve is used across the where-we-used/)
headers in this system  3.
 When there is a primary only constant speed
pumping system is used,3-way valve is
(https://people.bayt.com/r
recommended. rashid/)
for this application2-way valves are not best Posted by:
suitable. Rashid Ali RASHID
Upvote (1) Downvote Reply (0) Report (https://people.bayt.com/r
rashid)
24-October-2016

By Ashpak Sheikh (https://people.bayt.com/ashpak-sheikh/)


Sr. Mechanical Engineering consultant - 2 months ago

In secondary VFD pumping system we shall use 2


(https://people.bayt.com/ashpak-
way valve and in constant ow system we shall
sheikh/)
use 3 way valve.

Upvote (0) Downvote Reply (0) Report

By ‫( ﻣﺣﻣد ﻓﺗﺣﻲ‬https://people.bayt.com/mohamel2000/) Facilities


Supervisor - 4 years ago

2 Way is used in the case of a Bay bus line


(https://people.bayt.com/mohamel2000/)
between expulsion and public clouds2 / when
there is a variable speed with cold water pumps /
If not available supply only uses 3 Way
Upvote (0) Downvote Reply (0) Report

By Moamar Alhoushan (https://people.bayt.com/moamar/)


Assistant Professor - 5 months ago

Primary type chiilled water system    3-way valves


(https://people.bayt.com/moamar/)
Primary-secondary type chilled water system 2-
way valve

https://www.bayt.com/en/specialties/q/19601/what-is-the-criteria-to-use-2-or-3-way-control-valves-in-chilled-water-lines-where-to-use-2-way-and-not-3-… 4/8
2/15/2018 What is the criteria to use 2 or 3 way control valves in chilled water lines? Where to use 2 way and not 3 way and where to use 3 way not 2 way…

beyond that initial and running cost issues in


terms of power saving and installation cost  vfs
pumps are so expensive comp to constant speed
ones

pipng cost as high ow requires large diameter


pipes even schedules sometimes play a role

things are interrelated 1st 2 lines i guess the


coclusion

Upvote (0) Downvote Reply (0) Report

Next Question
By
chetan sharma (https://people.bayt.com/chetan-sharma- What is role of
21984980/) VFD in chilled
Mechanical Design Engineer(LEED CERTIFIED) - 2 years ago water system
(https://people.bayt.com/chetan- and where we
used?
sharma- Best way to save working cost we generally use
(https://www.bayt.com/en
21984980/) the system in which chilled water primary pump is is-role-of-vfd-in-
constant ow with varying delta but at same time chilled-water-
secondary pump is varying ow but xed delta system-and-
where-we-used/)
that is  y we use3 way valve to regulate the ow
rate in the system with constant ow rate 

but in case of variable ow the ow adjusts that is (https://people.bayt.com/r


y we use2 way valve  rashid/)
Posted by:
Upvote (0) Downvote Reply (0) Report Rashid Ali RASHID
(https://people.bayt.com/r
rashid)
24-October-2016

By Ismael Hamad (https://people.bayt.com/ismael-hamad/)


HVAC Specialist MM Muehringer Seconded to HAROUGE for Oil
Operations company, Libya. - 2 years ago

(https://people.bayt.com/ismael-
 
hamad/)
The two-way valve that controls the ow of
refrigerant through single line. The three- way
valves with an inlet that is common to two
opposite openings .lt controls refrigerant ow in
two di erent lines The four-way reversing valve
used on heat pumps. Solenoid valves may be
activated by a thermostat. These valves are used
to control the temperature of a regulator or a
room, Three-way solenoid valves are used mainly
on commercial refrigerating units. They may be
used to control two separate refrigerant circuits
for defrosting, two temperature evaporators etc.
In the three way solenoid valve opening is the
common opening and is never closed-As the
electromagnet is de 'energized, the following
occurs :The weight of the solenoid plunger
assembly holds the valve against the lower seat
.The force of the upper spring also holds the valve
rmly against the lower seat .This action closes
port B to the common port and opens C. When
the electrical circuit is closed the solenoid

https://www.bayt.com/en/specialties/q/19601/what-is-the-criteria-to-use-2-or-3-way-control-valves-in-chilled-water-lines-where-to-use-2-way-and-not-3-… 5/8
2/15/2018 What is the criteria to use 2 or 3 way control valves in chilled water lines? Where to use 2 way and not 3 way and where to use 3 way not 2 way…

becomes energized .The Piston with the tow


valves attached to it will move in the opposite
direction.

Upvote (0) Downvote Reply (0) Report

By
sherif abdelhakam fathi rwash
(https://people.bayt.com/sherifabdelhakamfathi-rwash/)
4 - ‫ ﻣدﯾر ﻣﺷﺎرﯾﻊ ﻣﯾﻛﺎﻧﯾك‬years ago
(https://people.bayt.com/sherifabdelhakamfathi-
rwash/) 2way used when scwp have vfdsped

3way valve uosed when schwp is constant speed Next Question


What is role of
2way valve uosed to sa ng power VFD in chilled
water system
Upvote (0) Downvote Reply (0) Report and where we
used?
(https://www.bayt.com/en
is-role-of-vfd-in-
chilled-water-
Show more system-and-
where-we-used/)

(https://people.bayt.com/r
rashid/)
Posted by:
Rashid Ali RASHID
(https://people.bayt.com/r
rashid)
24-October-2016
More Questions Like This

(https://people.bayt.com/nazurudin-ahamed/)

Is there a need of250 Ohm resistor for control valve calibration using HART
protocol? If so how and where to connect the250 Ohm resistor?
(/en/specialties/q/22768/is-there-a-need-of250-ohm-resistor-for-control-
valve-calibration-using-hart-protocol-if-so-how-and-where-to-connect-
the250-ohm-resistor/)

Top Answer: The resistance will be connected in series, from power supply
+ve wire (via Ammeter) to your instrument. ... See More
(/en/specialties/q/22768/is-there-a-need-of250-ohm-resistor-for-control-
valve-calibration-using-hart-protocol-if-so-how-and-where-to-connect-
the250-ohm-resistor/)
Answers (8) (/en/specialties/q/22768/is-there-a-need-of250-ohm-resistor-for-control-
valve-calibration-using-hart-protocol-if-so-how-and-where-to-connect-the250-ohm-
resistor/)

(https://people.bayt.com/issam-dagher/)

HOW YOU CAN CALCULATE CHILLED WATER EXPANSION TANK ?


(/en/specialties/q/89718/how-you-can-calculate-chilled-water-expansion-
tank/)

Top Answer: If you are using some software from some expansion
manufacturers then it is very easy just put some param ... See More

https://www.bayt.com/en/specialties/q/19601/what-is-the-criteria-to-use-2-or-3-way-control-valves-in-chilled-water-lines-where-to-use-2-way-and-not-3-… 6/8
2/15/2018 What is the criteria to use 2 or 3 way control valves in chilled water lines? Where to use 2 way and not 3 way and where to use 3 way not 2 way…
(/en/specialties/q/89718/how-you-can-calculate-chilled-water-expansion-
tank/)

Answers (4) (/en/specialties/q/89718/how-you-can-calculate-chilled-water-expansion-


tank/)

(https://people.bayt.com/valay-patel/)

Chilled water pipe installation Highraised apartment building Working


pressure : 5.5 bar? (/en/specialties/q/237282/chilled-water-pipe-
installation-highraised-apartment-building-working-pressure-5-5-bar/)

Top Answer: Automatic air vent of the highest and lowest point of piping
system. there is no water drain air is drain ... See More Next Question
(/en/specialties/q/237282/chilled-water-pipe-installation-highraised-
What is role of
apartment-building-working-pressure-5-5-bar/)
VFD in chilled
Answers (2) (/en/specialties/q/237282/chilled-water-pipe-installation-highraised- water system
apartment-building-working-pressure-5-5-bar/) and where we
used?
(https://www.bayt.com/en
is-role-of-vfd-in-
chilled-water-
system-and-
(https://people.bayt.com/mahmoud-mahny/) where-we-used/)

‫ اﻟﺳﻼم ﻋﻠﯾﻛم ورﺣﻣﺔ ﷲ وﺣدة‬FCU ‫ ﻧظﺎم‬CHILLED WATER 2‫اﻟﺛرﻣوﺳﺗﺎت اﺗﺣرق ﻏﯾرﻧﺎ ﻣﺣﺑس ال‬WAY
2‫ ازاي اﺗﺄﻛد ان ﻣﺣﺑس ال‬.1‫واﻟﺛرﻣوﺳﺗﺎت وﻟﺳﺔ اﻟﺗﺑرﯾد ﺿﻌﯾف‬WAY ‫اﯾﮫ اﻻﺳﺑﺎب اﻟﻣﺣﺗﻣﻠﺔ‬.2 ‫ﺷﻐﺎل ﻛوﯾس ؟؟‬
‫( اﻟﺗﺎﻧﯾﺔ ﻟﻘﻠﺔ اﻟﺗﺑرﯾد؟‬/en/specialties/q/243698/‫وﺣدة‬-‫ﷲ‬-‫ورﺣﻣﺔ‬-‫ﻋﻠﯾﻛم‬-‫اﻟﺳﻼم‬-fcu-‫ﻧظﺎم‬-chilled- (https://people.bayt.com/r
rashid/)
water-2‫ال‬-‫ﻣﺣﺑس‬-‫ﻏﯾرﻧﺎ‬-‫اﺗﺣرق‬-‫اﻟﺛرﻣوﺳﺗﺎت‬way--‫ان‬-‫اﺗﺄﻛد‬-‫ازاي‬-1‫ﺿﻌﯾف‬-‫اﻟﺗﺑرﯾد‬-‫وﻟﺳﺔ‬-‫واﻟﺛرﻣوﺳﺗﺎت‬
2‫ال‬-‫ﻣﺣﺑس‬way-‫اﻟﺗﺑرﯾد‬-‫ﻟﻘﻠﺔ‬-‫اﻟﺗﺎﻧﯾﺔ‬-‫اﻟﻣﺣﺗﻣﻠﺔ‬-‫اﻻﺳﺑﺎب‬-‫اﯾﮫ‬-2-‫ﻛوﯾس‬-‫ﺷﻐﺎل‬/) Posted by:
Rashid Ali RASHID
Top Answer: 1- ‫ﺗﺎﻛد ﻣن ﻋﻣل اﺧﺗﯾﺎر ﺻﻣﺎم اﻟﺗﺣﻛم ﺑطرﯾﻘﺔ ﺻﺣﯾﺣﺔ ﺑﺣﯾث ان اﻟﺻﻣﺎم ﯾﻌﻣل ﻋﻧد اﻗﺻﻰ‬ (https://people.bayt.com/r
‫ ﻣﻌدل ﺗدﻓق وﯾﻧﺎﺳب ﺿﻐط اﻟﺗﺷﻐﯾل‬... See More (/en/specialties/q/243698/-‫ﻋﻠﯾﻛم‬-‫اﻟﺳﻼم‬ rashid)
‫وﺣدة‬-‫ﷲ‬-‫ورﺣﻣﺔ‬-fcu-‫ﻧظﺎم‬-chilled-water-2‫ال‬-‫ﻣﺣﺑس‬-‫ﻏﯾرﻧﺎ‬-‫اﺗﺣرق‬-‫اﻟﺛرﻣوﺳﺗﺎت‬way--‫واﻟﺛرﻣوﺳﺗﺎت‬ 24-October-2016
2‫ال‬-‫ﻣﺣﺑس‬-‫ان‬-‫اﺗﺄﻛد‬-‫ازاي‬-1‫ﺿﻌﯾف‬-‫اﻟﺗﺑرﯾد‬-‫وﻟﺳﺔ‬way--‫ﻟﻘﻠﺔ‬-‫اﻟﺗﺎﻧﯾﺔ‬-‫اﻟﻣﺣﺗﻣﻠﺔ‬-‫اﻻﺳﺑﺎب‬-‫اﯾﮫ‬-2-‫ﻛوﯾس‬-‫ﺷﻐﺎل‬
‫اﻟﺗﺑرﯾد‬/)

Answers (6) (/en/specialties/q/243698/‫وﺣدة‬-‫ﷲ‬-‫ورﺣﻣﺔ‬-‫ﻋﻠﯾﻛم‬-‫اﻟﺳﻼم‬-fcu-‫ﻧظﺎم‬-chilled-water-


2‫ال‬-‫ﻣﺣﺑس‬-‫ﻏﯾرﻧﺎ‬-‫اﺗﺣرق‬-‫اﻟﺛرﻣوﺳﺗﺎت‬way-2‫ال‬-‫ﻣﺣﺑس‬-‫ان‬-‫اﺗﺄﻛد‬-‫ازاي‬-1‫ﺿﻌﯾف‬-‫اﻟﺗﺑرﯾد‬-‫وﻟﺳﺔ‬-‫واﻟﺛرﻣوﺳﺗﺎت‬way--‫ﺷﻐﺎل‬
‫اﻟﺗﺑرﯾد‬-‫ﻟﻘﻠﺔ‬-‫اﻟﺗﺎﻧﯾﺔ‬-‫اﻟﻣﺣﺗﻣﻠﺔ‬-‫اﻻﺳﺑﺎب‬-‫اﯾﮫ‬-2-‫ﻛوﯾس‬/)

(https://people.bayt.com/eng-mohamed-awad/)

Is it possible to use the swimming pool water as a cooling medium to


condenser water? (/en/specialties/q/93256/is-it-possible-to-use-the-
swimming-pool-water-as-a-cooling-medium-to-condenser-water/)

Top Answer: I dont think so that it is a good idea as swimming pool water
contains many chemicals which is not suitab ... See More
(/en/specialties/q/93256/is-it-possible-to-use-the-swimming-pool-water-as-
a-cooling-medium-to-condenser-water/)

Answers (11) (/en/specialties/q/93256/is-it-possible-to-use-the-swimming-pool-water-


as-a-cooling-medium-to-condenser-water/)

Do you need help in adding the right keywords to


your CV? Let our CV writing experts help you.

Get Help (/en/cv-writing/)

https://www.bayt.com/en/specialties/q/19601/what-is-the-criteria-to-use-2-or-3-way-control-valves-in-chilled-water-lines-where-to-use-2-way-and-not-3-… 7/8
2/15/2018 What is the criteria to use 2 or 3 way control valves in chilled water lines? Where to use 2 way and not 3 way and where to use 3 way not 2 way…

Find Jobs
Jobs in Abu Dhabi Jobs in Dubai Jobs in Algeria Jobs in Bahrain Jobs in Egypt Jobs in India
(https://www.bayt.com/en/uae/jobs/locations/abu-
(https://www.bayt.com/en/uae/jobs/locations/dubai/)
(https://www.bayt.com/en/algeria/jobs/)
(https://www.bayt.com/en/bahrain/jobs/)
(https://www.bayt.com/en/egypt/jobs/)
(https://www.bayt.com/en/india/j
dhabi/) Jobs in Iraq Jobs in Jordan Jobs in Kuwait Jobs in Lebanon Jobs in Libya
(https://www.bayt.com/en/iraq/jobs/)
(https://www.bayt.com/en/jordan/jobs/)
(https://www.bayt.com/en/kuwait/jobs/)
(https://www.bayt.com/en/lebanon/jobs/)
(https://www.bayt.com/en/libya/j
Jobs in Morocco Jobs in Oman Jobs in Pakistan Jobs in Qatar Jobs in Saudi Arabia Jobs in Sri Lanka
(https://www.bayt.com/en/morocco/jobs/)
(https://www.bayt.com/en/oman/jobs/)
(https://www.bayt.com/en/pakistan/jobs/)
(https://www.bayt.com/en/qatar/jobs/)
(https://www.bayt.com/en/saudi-
(https://www.bayt.com/en/sri-
arabia/jobs/) lanka/jobs/)
Jobs in Tunisia Jobs in UAE Jobs in Yemen
(https://www.bayt.com/en/tunisia/jobs/)
(https://www.bayt.com/en/uae/jobs/)
(https://www.bayt.com/en/yemen/jobs/)

Next Question

About Bayt.com Company Quick Links


What is role of
VFD in chilled
Bayt.com is the leading job site in the Gulf and Middle East, connecting job seekers with About Us Mobile
water system
employers looking to hire. Every day, thousands of new job vacancies are listed on the (https://www.bayt.com/en/about-and where we
(https://m.bayt.com/)
used?
award-winning platform from the region's top employers. us/) Blog
(https://www.bayt.com/en
Contact Us (https://www.bayt.com/en/blog/)
is-role-of-vfd-in-
Help chilled-water-
(https://www.bayt.com/en/contact-
details/) system-and-
(https://www.bayt.com/en/help/)
where-we-used/)
Careers A liate Program
(https://www.bayt.com/en/careers/)
(https://www.bayt.com/en/a liat
Press Corner Never Miss an Email
(https://www.bayt.com/en/press-
(https://people.bayt.com/r
(https://www.bayt.com/en/pages/
rashid/)
corner/) miss-an-email/)
Posted by:
Advertise With Us
Rashid Ali RASHID
(https://www.bayt.com/en/advertise/)
(https://people.bayt.com/r
Community Service rashid)
24-October-2016
(https://www.bayt.com/en/charity/)

© 2000-2018 Bayt.com, Inc. All Rights Reserved. Terms of Use (https://www.bayt.com/en/terms/) - Privacy Statement (https://www.bayt.com/en/privacy-
statement/)
‫( اﻟﻌﺮﺑﯿﺔ‬/ar/specialties/q/19601/what-is-the-criteria-to-use-2-or-3-way-control-valves-in-chilled-water-lines-where-to-use-2-way-and-not-3-way-and-
where-to-use-3-way-not-2-way-and-why/)Français (/fr/specialties/q/19601/what-is-the-criteria-to-use-2-or-3-way-control-valves-in-chilled-water-
lines-where-to-use-2-way-and-not-3-way-and-where-to-use-3-way-not-2-way-and-why/)

https://www.bayt.com/en/specialties/q/19601/what-is-the-criteria-to-use-2-or-3-way-control-valves-in-chilled-water-lines-where-to-use-2-way-and-not-3-… 8/8

Vous aimerez peut-être aussi