LOW VOLTAGE SWITCHGEAR – TERMINOLOGY DEMYSTIFIED

(Article published in the March 2007 issue of “HYDEL” – the technical journal of the
KSEB Engineers’ Association)

by: K.Sivakumar, Sr.Executive-Training, Larsen & Toubro Limited, Switchgear


Training Centre, Coonoor (T.N.)

Introduction: About 70% of the Rated Operational Voltage (Ue): It is


electrical engineers working in industry that value of voltage, which combined
happen to work mainly on the Low with a rated operational current,
Voltage Switchgear. But, unfortunately, determines the application of the
this subject is not paid enough attention equipment and to which the relevant
in our electrical engineering academic tests and the utilization categories are
curriculum. Hence, when the field referred. For single pole equipment, the
electrical engineer goes through the rated operational voltage is generally
manufacturers’ catalogues/data sheets
of low voltage switchgear, they are stated as the voltage across the pole. For
bemused. The switchgear specification multiple pole equipment, it is generally
terminology appears a big jargon for stated as the voltage between phases.
them. An attempt is made in this article
to demystify the switchgear jargon. Rated Insulation Voltage (Ui): It is the
value of voltage to which dielectric test
Every type of switchgear will have voltage and creepage distances are
certain set of characteristic quantities referred. In no case shall the maximum
associated with it. These characteristic the value of Ue should be more than Ui.
quantities are normally stated in form
of ratings or specifications in the Rated Impulse Withstand Voltage
product catalogue supplied by the (Uimp): It is the peak value of an impulse
manufacturer. A few of the voltage of prescribed form & polarity,
specifications are also marked on the which the equipment is capable of
nameplate of the equipment. For a user withstanding without failure under
of switchgear, it is important to know specified conditions of test & to which
about what these characteristic the values of the clearances are
quantities mean. Following is the brief referred. The rated impulse withstand
description for commonly used voltage of an equipment shall be equal
characteristic qualities. to or higher than the values stated for
the transient over voltages occurring in
Voltages: An equipment is defined by the circuit in which the equipment is
the following voltages: fitted.
Table 1: Preferred values of Uimp for a Currents: An equipment is defined by
nominal supply system voltage of the following currents:
240/415V, in case of over voltage
protection by surge arrestors according Conventional free air thermal current
to IEC: (Ith): It is the maximum value of current
as stated by the manufacturer to be
Preferred used for temperature–rise tests of
Over voltage category Values of unenclosed equipment in free air. The
Uimp, kV switching device must be capable of
(1.2/50µs) conducting this test current without the
IV Origin of 6 temperature rise limits given in the
installation level relevant Indian Standard being
III Distribution 4 exceeded (temperature rise limits of
circuit level terminals as per IS is 70oC for silver
II Load 2.5 plated copper for all switchgear (except
(equipment) level circuit breaker). It must be at least
I Specially 1.5 equal to the maximum value of the
protected level rated operational current of the
unenclosed equipment in eight-hour
duty. It is not a rating & is not
Rated Control Circuit Voltage (Uc): It is
mandatorily marked on the equipment.
the voltage, which would appear across
the “a” contacts in the control circuit.
Conventional enclosed thermal current
(Ithe): It is the value of current stated by
Rated Control Supply Voltage (Us): It is
the manufacturer to be used for the
the voltage at which generally auxiliary
temperature-rise tests of the equipment
circuits and more precisely the control
when mounted in a specified enclosure.
circuits are operated or to which they
Such tests are mandatory if the
must be connected for correct
equipment is described as enclosed
operation. A distinction is made
equipment in the manufacturer’s
between Uc & Us. Us may be different
catalogues & normally intended for use
from Uc, due to presence of built in
with one or more enclosure of specified
transformers, rectifiers, resisters etc.
type & size. It shall be at least equal to
The rated control circuit voltage and
the maximum value of the rated
the rated frequency, if any, are the
operational current of the enclosed
values on which the operating and
equipment in eight-hour duty. If the
temperature rise characteristics of the
equipment is normally intended for use
control circuit are based. The correct
in unspecified enclosures, the test is not
operating conditions are based upon a
mandatory, if the test for Ith has been
value of the control supply voltage not
made. It is not a rating & is not
less than 85% of its rated value, with
mandatorily marked on the equipment.
the highest value of control circuit
current flowing, nor more than 110% of
its rated value.
Rated Operational Current (Ie): It is Utilization Category: It is a combination
stated by the manufacturer and takes of specified requirements related to the
into account the rated operational conditions in which the switching device
voltage, the rated frequency, the rated or the fuse fulfills its purpose, selected
duty, the utilization category & the type to represent a characteristic group of
of protective enclosure, if applicable. practical applications. The specified
Switchgear may have several rated requirements may concern, for
operational currents. In the case of example, the values of making
equipment for direct switching of capacities (if applicable), breaking
individual motors, the indication of a capacities & other characteristics, the
rated operational current may be associated circuits & the relevant
replaced or supplemented by an conditions of use and behavior.
indication of the maximum rated power
output, at the rated operational voltage Normal Load & Overload
considered, of the motor for which the Characteristics: The ability to make &
equipment is intended. break currents under normal load &
overload conditions is stated in terms of
Rated uninterrupted current (Iu): It is a following two ratings:
value of current, stated by the
manufacturer, which the equipment can Rated Breaking Capacity: The rated
carry in uninterrupted duty (a duty in breaking capacity of an equipment
which the main contacts of equipment is a value of current, stated by the
remain closed, whilst carrying a steady manufacturer, which the equipment
current without interruption for periods can satisfactorily break under
of more than eight hours i.e. weeks, specified breaking conditions. The
months or even years). breaking conditions which shall be
specified are: a) the phase-to-phase
Rated current (In): This rating is voltage across the supply terminals
defined for circuit breaker & fuses. For of the equipment after the breaking
circuit breaker, the rated current is the of the current & b) the
rated uninterrupted current (Iu) & is characteristics of the test circuit.
equal to the conventional free-air The rated breaking capacity is
thermal current (Ith). For fuse-link, the stated by reference to rated
rated current is that value of current, operational current, according to
which it can carry continuously without relevant Indian Standard (IS) on
deteriorating, under specified condition. the product. An equipment shall be
capable of breaking any value of
Rated Frequency: It is the supply current up to and including its
frequency for which equipment is rated breaking capacity. For A.C.,
designed & to which the other it is expressed by the r.m.s. value of
characteristic values correspond. The the symmetrical component of the
same equipment may be assigned a current.
number or a range of rated frequencies
or be rated for both A.C. and D.C.
reference to rated operational voltage &
rated operational current, according to
relevant Indian standard (IS) on the
Short Rated Rated Service product. An equipment shall be capable
Circuit Ultimate S/C S/C Breaking of making any value of current up to
Category Breaking Capacity, Ics and including its rated making capacity.
Capacity, Icu For A.C., it is expressed by the r.m.s.
value of the symmetrical component of
Switching O – t - CO O – t – CO – t the current.
Cycle (O- - CO
Open; Short Circuit Characteristics: Short
CO-Close circuit currents may be encountered
Open; during current making, during current
t-Pause carrying in closed position & during
time) current interruption. The ability of the
Condition A A equipment to make, carry & break
of circuit temperature temperature short circuit currents is stated in terms
breaker rise test is rise test is to of one or more of the following ratings:
after the not be performed
S/C test compulsory. with rated Rated Short-Circuit Making Capacity
The breaker current. The (Icm): The rated short-circuit making
may not be breaker shall capacity of an equipment is the
capable of be able to maximum value of short circuit current,
carrying its conduct its stated by the manufacturer, which the
rated current rated current equipment can satisfactorily make at
continuously. without prior the rated operational voltage, at rated
Limited shift maintenance. frequency and at a specified power
of the Shift of O/L factor of A.C. It is expressed as the
overload characteristics maximum prospective peak current,
release not under prescribed condition.
characteristic permissible.
curve is Rated Short Time Withstand Current
permissible. (Icw): It is the current that an equipment
can carry without damage during
Rating Making Capacity: The rated specified short time under prescribed
making capacity of an equipment is a conditions of use and behavior.
value of current, stated by the
manufacturer, which the equipment can Rated Short-Circuit Breaking Capacity
satisfactorily make under specified (Icn): The rated short-circuit breaking
making conditions. The making capacity of an equipment is the
conditions which shall be specified are: maximum value of short circuit current,
a) the phase-to-phase voltage across the stated by the manufacturer, which the
supply terminals of the equipment just equipment can satisfactorily break at
before the making of the current & the rated operational voltage, at rated
b) the characteristics of test circuit. The frequency and at a specified power
rated making capacity is stated by factor of A.C. It is expressed as the
r.m.s. value of the a.c. component, Table 3: Standard ratios between Icu &
under prescribed condition. Ics

Rated ultimate short circuit breaking Time Intervals: Closing & opening
capacity (Icu): It is the value of ultimate operations of a switching device may be
short circuit breaking capacity (a defined by following times:
breaking capacity for which the
prescribed conditions according to a Opening Time: It is the interval of time
specified test sequence do not include between the specified instant of
the capability of the circuit breaker to initiation of the opening operation & the
carry its rated current continuously) instant when the arcing contacts have
assigned to that circuit breaker by the separated in all poles. The instant of
manufacturer for the corresponding initiation of the opening operation
rated operational voltage, under means the instant of the application of
specified conditions. It is expressed as the opening command, e.g. energizing
the value of the prospective breaking the release etc. In case of a directly
current, in kA (r.m.s.). operated circuit breaker, the instant of
initiation of the opening time is the
Rated service short circuit breaking instant of initiation of a current large
capacity (Icn): It is the value of service enough to cause the circuit breaker to
short circuit breaking capacity (a operate. In the case of a circuit breaker
breaking capacity for which the operated by any form of auxiliary
prescribed conditions according to a power, the instant of initiation of the
specified test sequence include the opening time is the instant of
capability of the circuit breaker to carry application of the auxiliary power to the
its rated current continuously) assigned opening release. For circuit breakers
to that circuit breaker by the opening time is commonly referred to as
manufacturer for the corresponding tripping time, although, strictly
rated operational voltage, under speaking, tripping time applies to the
specified conditions. It is expressed as time between the instant of initiation of
the value of the prospective breaking the opening time and the instant when
current, in kA (r.m.s.), corresponding to the opening command becomes
one of the specified percentages of the irreversible.
rated ultimate short circuit breaking
capacity. Arcing Time: It is the interval of time
between the instant of initiation of the
arc in a pole or a fuse & the instant of
Utilization Utilization final arc extinction in that pole or that
Category A (Ics as Category B (Ics as fuse. In a multiple-pole switching
a % of Icu) a % of Icu) device, it will be the interval of time
25 - between the instant of the first initiation
50 50 of an arc & the instant of final arc
75 75 extinction in all poles.
100 100
Break Time: It is the interval of time
between the beginning of the opening
time of a mechanical switching device Mechanical Life: It is the number of no-
(or the pre-arcing time of a fuse) & the load switching operations (i.e. with
end of the arcing time. no current flowing through the
Make Time: It is the interval of time poles) which the switching device
between the initiation of the closing can perform without mechanical
operation and the instant when the failure.
current begins to flow in the main
circuit.

Closing Time: It is the interval of time Service Conditions: The switchgear


between the initiation of the closing manufacturer claims the ratings after
operation and the instant when the testing as per the procedures specified
contacts touch in all poles. in the standards. The standards also
specify the service conditions under
Pre-arcing Time: It is the time between which the tests are to be carried out.
the commencement of a current large Following are the service conditions
enough to cause the fuse element(s) to considered:
melt & the instant when an arc is
initiated. Ambient air temperature: It is the
temperature existing in the vicinity of
Operating Time: It is the sum of pre- the equipment if supplied without
arcing & the arcing time. enclosure or in vicinity of the enclosure
if supplied with an enclosure.
Operational Life: It is the duration for
which electrical equipment operates Altitude: It is the height above the sea
reliably (or is expected to operate level where the equipment is going to be
reliably) under normal specified installed.
operating conditions. The
operational life of a switching Humidity: It is the moisture content in
device is expressed as the number of air expressed in percentage (i.e.
make-break operations the device relative humidity).
will perform.
Pollution degree: The pollution degree
Electrical Life: It is the number of on- refers to the environmental conditions
load switching operations, which the for which the equipment is intended.
device can perform without any repair For equipment intended for use within
or replacements. The electrical life an enclosure or provided with an
depends on the utilization category, the integral enclosure, the pollution degree
rated operational current & the rated of the environment in the enclosure is
operational voltage. applicable. Unless otherwise stated by
the relevant product standard,
equipment for industrial application is
generally for use in pollution degree 3
environment according to which
conductive pollution occurs, or dry non-
conductive pollution occurs which
becomes conductive due to
condensation. Conclusion: It is hoped that at least
some of the switchgear jargons are
clarified above. Further reference can
be made to IS 13947 (Specification for
Low Voltage Switchgear &
Controlgear) & IS 13703 (Specification
for Low Voltage Fuses).

Service Normal Values


Conditions
Ambient
temperature:
Max. allowable
value + 40°C

Max. allowable
value of 24 hour
average + 35°C

Lowest allowable
value - 5° C

Humidity:
Relative humidity 50% at 40°C

Altitude: Max.
altitude (above
sea level) 2000m

Table 4: Normal service conditions in


terms of Indian Standards.

Switchgears intended to be used in


conditions other than normal service
conditions, should be designed
accordingly or used according to the
relevant product standard, where
applicable, or according to agreement
between manufacturer & user. Many
times certain correction factors are
employed in case actual service
conditions differ from normal.