Académique Documents
Professionnel Documents
Culture Documents
INSTRUCTIONS FOR
DE-ICING SYSTEM
Please read the instructions provided in this section of Instruction Handbook thoroughly.
All plant personnel must be familiar with these instructions. Failure to follow these
instructions may result in injury, fatal accident and plant damage.
0610-0zzz
4009 en
032-7024
GEA Niro
GEA Process Engineering
Copyright © 2015 GEA Process Engineering A/S. All rights reserved.
0610-0zzz CONRAD™ 600 XL eco
4009 en De-Icing System
1.1 General.............................................................................................................................1
GEA Niro
GEA Process Engineering
0610-0zzz CONRAD™ 600 XL eco
4009 en De-Icing System
1.1 General
The de-icing system is used to remove the ice which has condensed on the vapor traps
inside the CONRAD™ cabinet. The ice is removed by injecting vacuum steam from the
de-icing tank C4400 into the top of the vapor traps. The condensed steam and de-icing
water is drained off at the bottom of the vapor trap. During the entire de-icing cycle the
vapor trap is held under vacuum. The vapor trap which is being deiced is isolated from
the cabinet with a gate-plate. The pressure during de-icing is about 20-35 mbar.
The water in the de-icing tank C4400 is heated to a temperature of approx. 25°C by
injection of steam through a heating coil mounted in the de-icing tank.
The analogue regulating valve Q4403 uses the measurement of temperature sensor
K4403 to control the temperature inside the de-icing tank by regulating the steam
supply to the built-in coil in the tank and maintain the pressure at the set point.
The pressure in the de-icing piping system is measured by the pressure transmitter
P4408. The pressure transmitters range is between 4-20mA for 0-100mbar.
Using the correlation of temperature/pressure for saturated water vapor, the
temperature of the water in de-icing tank can be calculated and controlled. Especially
for keeping the temperature in the de-icing tank constant by a quick regulation, when
the vapor traps are operating in de-icing mode and energy is required for the process.
Set points for regulation are set on the display as temperatures; alarms are raised
when too low/high values are measured by the sensor K4403 and transmitter P4408.
During de-icing of the vapor traps the valve Q41x4 between the top of the vapor trap
and the de-icing tank C4400 will be open. Due to a lower pressure in the vapor trap,
the water in the de-icing tank C4400 starts to boil and vacuum steam is led from C4400
to the vapor trap, thus melting the condensed ice.
After approx. 5 minutes the drain valve Q41x5 at the bottom of the vapor trap opens
allowing the water inside the vapor trap to be drained off to a drain tank C4200. The
level switches inside the tank regulate when the water is pumped out of the tank by
means of one of the two drain pumps (G4303 or G4313). Level switch K4402
measures the water level inside the de-icing tank. The pump will stop when level switch
K4201 has been LOW for 10 sec.
The system can be set in two modes, either reusing the de-icing water or adding fresh
process water when necessary. From the pumps, the drain-water is led through the
three-way valve Q4340 where it can either be led back to the de-icing tank C4400 to be
reused, or to the overflow tank C4350 or dumped into a foul condensate drain. The
amount of discharged water to the foul condensate drain is monitored at the flow meter
P4350.
A solenoid valve Q4350 for the overflow tank controlled by level switch K4350 has an
on/off function to ensure a minimum level of water always is maintained in the overflow
tank. If the overflow tank is emptied of water, there is a risk that air can be sucked back
through the de-icing system, thus resulting in vacuum problems in the CONRAD™
cabinet.
GEA Niro
1/19 GEA Process Engineering
CONRAD™ 600 XL eco 0610-0zzz
De-Icing System 4009 en
1.2 Safety
User:
A user is any natural or legal person that uses the de-icing system or at whose request
the de-icing system is being used.
Qualified personnel :
Qualified personnel are persons who, based on their education, experience, special
training and knowledge of relevant standards and stipulations, safety regulations and
operating conditions are authorized by the person responsible for the safety on the
plant to perform the necessary actions and who are able to recognize and avoid
possible dangers.
Warning!
Warning!
The temperature of the surfaces of the hot water supply valves and
pipes is above 80°C during operation, and it is therefore prohibited to
make any service or maintenance on the hot water supply system
while it’s in operation.
Before personnel enter the CONRAD™ cabinet for maintenance it must be secured
that the heating plates are cooled down to a reasonably low temperature. It is
recommended to cool the heating plates to 40°C before entering the CONRAD™
cabinet.
GEA Niro
GEA Process Engineering 2/19
0610-0zzz CONRAD™ 600 XL eco
4009 en De-Icing System
Warning!
If it is, however, absolutely necessary to carry out any work on the hot
water equipment during operation, a full covering suit and gloves
should be worn to avoid exposing bare skin to the heat.
NOTE!
The following points should also be noted and adhered to during the installation and
operation of the plant:
• The de-icing unit and the drain unit must be placed on a firm solid base or
foundation and fixed to the support with bolts as indicated on the drawings.
Loads for the tank and pumps are shown on the foundation drawings.
• Remove or secure the handle of the manual drain valve when the CONRAD™ is in
operation.
• Always check that all manual valves are in the correct position before starting
operation.
Many countries have legislated in the area in the attempt to reduce pollution and
protect the environment. These environmental protection acts that are to be observed
concern all sectors of the industry. It is the obligation of the end user to ensure that
local environmental rules are adhered to, with regard to disposal of consumables and
other waste products from the process.
Lubricants:
At change of oil, the waste oil must be collected in a vessel and sent to an authorized
destructor.
Waste water:
De-icing water being drained from the overflow vessel, C4350 will contain a small
concentration of the product being dried in the CONRAD™.
For operation with sublimation of approx. 1.5 kg/m2/h the contamination will be less
than 0.1% of the production.
The specific contamination will depend on the product and the operation parameters
for the heating, vacuum, refrigeration and transport systems. Changes in vacuum,
sublimation and condenser temperature will influence the contamination.
During start-up and after product change, an analysis of the de-icing water should be
performed, to determine the required treatment of the water before disposal.
GEA Niro
3/19 GEA Process Engineering
CONRAD™ 600 XL eco 0610-0zzz
De-Icing System 4009 en
Connections:
Steam to De-icing Tank C4400
Steam supply Pipe: DN 50
Steam return Pipe: DN 40
Quantity Kg/h 350
Temperature: °C 165
Sealing water
G4303 & G4313:
Inlet; pipe: DN 15
Quantity: L/h 20
Pressure: Barg 2.0
Temperature °C 30
For distribution of compressed air to the pneumatic actuators, please see the
pneumatic diagram drawing 1149463.
GEA Niro
GEA Process Engineering 4/19
0610-0zzz CONRAD™ 600 XL eco
4009 en De-Icing System
1.4 Installation
1.4.1 Storage
If the De-icing system is not installed immediately, suitable storage conditions must be
provided.
1.4.2 Placing
Sufficient space around the components for inspection, operation, cleaning and
maintenance is recommended. Please see de-icing arrangement drawing 1200347
GEA Niro
5/19 GEA Process Engineering
CONRAD™ 600 XL eco 0610-0zzz
De-Icing System 4009 en
All pipes and fittings must be clean inside. After cutting the cutting edge must be
removed and the pipes must be cleaned of scales inside.
Cuttings should always be made at 90° to the pipe axis to ensure parallel pipes and
proper welds. To facilitate welding the pipe must be sharpened after cutting.
Never use flame cutting for cutting of stainless steel pipes. Preferably a mechanical
cold saw should be used for cutting the pipes.
When welding on flanges it must be ensured that the flange has a 90° angle to the pipe
axis. Otherwise it will be difficult to tighten the flange and a lot of stress will be created
in the pipes.
The pipes should be measured out carefully according to the arrangement drawing and
the actual conditions on the site. Do never force pipes into position as it will create
stress or even breaking of the pipes.
Even if the de-icing system is never under any high pressure welding must be
executed by certified welders to ensure a minimum of leaks in the system.
As the de-icing system is entirely of stainless steel, only TIG/Argon welding may be
used. After welding, the surface must be treated with a suitable acid agent to retain the
stainless surface.
When bolting together flanges remember to grease the bolts with suitable grease i.e.
copper grease or Molycote. Please note that non-asbestos gaskets may not be used
as they are too porous and not vacuum tight.
Note:
When using threaded connections a good quality packing yarn and packing grease
should be used. Alternatively Loctite type 572 or similar can be used.
A sufficient number of pipe supports must be used to ensure that load is not applied to
pumps and valves.
When installing components such as pumps and valves it must be checked that
protection covers are removed and that the components are clean inside before
installation.
It must be checked that direction arrows on pumps and valves are according to the flow
diagram.
The circulation pumps and valves must be protected against welding drops and scales
from grinding during erection. The components should be handled with care as
bearings and shaft seals might be damaged by mechanical shock.
GEA Niro
GEA Process Engineering 6/19
0610-0zzz CONRAD™ 600 XL eco
4009 en De-Icing System
When butterfly valves are installed they must always be slightly opened - about 10 %. If
not, the rubber seat may be squeezed when the flanges are tightened.
All valves to the CONRAD™ cabinet must be closed and the overflow pipe from the
drain tank must be blinded, before the leak test is made
Air is filled into the system until a pressure of approx. 500 mm Water gage is obtained
(measured with U-tube manometer). All welds and connections in the plant are then
carefully leak tested by means of soap water. If any leaks are found they are marked
for later repair.
After finished test and repairs have been made a retest following the same procedure
as described above are performed. Leak test and repairs are repeated until no leaks
appear any longer.
Stop!
Warning!
Stop!
The low-pressure steam line is pressure tested with water to a pressure of 1.43 times
the working pressure. If leaks appear, the pressure is taken off and the spotted area
repaired. The procedure is repeated until no more leaks are located.
As the de-icing system forms part of the vacuum system it is vacuum tested together
with this system as described under the test of the vacuum system.
1.4.7 Documentation
Leak test, pressure test and vacuum test to be documented with a report showing test
details and signed up by the responsible person for accepted result.
GEA Niro
7/19 GEA Process Engineering
CONRAD™ 600 XL eco 0610-0zzz
De-Icing System 4009 en
1.5 Operation
The de-icing system is operated – started and stopped – together with the vacuum
system on the main faceplate.
(x represents the vapor trap no., i.e. G1020 is the gate plate for vapor trap 2.)
NOTE!
Before start-up, check that the system is filled with water so that the level is normal in
the de-icing tank C4400 and the overflow tank C4350 is filled.
In this step the preparation for operation of the vapor traps starts one by one.
At start gate plate G1010 OPENS, CO 2 valve Q6112 OPENS the refrigerant supply
branch, cooling media to the coil is now running. Meanwhile valves Q61x3 CLOSES all
refrigerant drainage branches. All de-icing drainage valves Q41x5 stay open.
After time T1 (2 minutes) vacuum valve Q3111 and De-icing valve Q4114 OPEN and
vapor trap no. 1 is put in operation.
At the same time gate plate G1020 OPENS, while CO 2 -valve Q6122 OPENS for
refrigerant flow to the coil.
After time T1 (2 minutes) Vacuum valve Q3121 OPENS and vapor trap no. 2 is put in
operation.
At the same time Gate plate G1030 and CO 2 -valve Q6132 OPENS for refrigerant flow
to the coil.
After time T1 (2 minutes) Vacuum valve Q3131 OPENS and vapor trap no. 3 is put in
operation.
At the same time Gate plate G1040 and 3-way CO 2 -valve Q6142 OPENS for
refrigerant flow to the coil.
After time T1 (2 minutes) Vacuum valve Q3141 OPENS and vapor trap no. 4 is put in
operation.
At the same time Gate plate G1050 and 3-way CO 2 -valve Q6152 OPENS for
refrigerant flow to the coil.
GEA Niro
GEA Process Engineering 8/19
0610-0zzz CONRAD™ 600 XL eco
4009 en De-Icing System
After time T 1 (2 minutes) Vacuum valve Q3151 OPENS and vapor trap no. 5 is put in
operation. At the same time Gate plate G1060 and 3-way CO 2 -valve Q6162 OPENS
for refrigerant flow to the coil.
After time T 1 (2 minutes) Vacuum valve Q3161 OPENS and vapor trap no. 6 is put in
operation. At the same time Gate plate G1070 and 3-way CO 2 -valve Q6172 OPENS
for refrigerant flow to the coil.
After time T 1 (2 minutes) Vacuum valve Q3171 OPENS and vapor trap no. 7 is put in
operation.
NOTE!
When the first vapor trap has been cooled down (after time T1), evacuation of the
cabinet is automatically started. Drain valves Q41x5 are already OPEN, so the de-icing
system is evacuated together with the cabinet.
Remark
De-icing of a vapor trap is based on timer function. The setting of the timer is
dependent on the product being dried and must be determined empirically.
The temperature in the de-icing tank must be regulated in such a way that
• de-icing does not influence the vacuum in the cabinet
• all the ice is melted off during de-icing
It is important for the de-icing time that the temperature in the de-icing tank is kept
above the boiling point when the de-icing valves Q41x4 OPENS.
The pressure in the de-icing tank and in the vapor trap will vary between about 20 to 32
mbar during de-icing depending on the temperature of the de-icing water.
After the de-icing valves have been closed, the analogue regulating valve Q4403,
which controls the supply of steam to the built-in coil in the de-icing tank starts
operating and the water in the tank is heated to approx. 25°C.
GEA Niro
9/19 GEA Process Engineering
CONRAD™ 600 XL eco 0610-0zzz
De-Icing System 4009 en
During the freeze-drying process all seven vapor traps are de-iced one at a time
according to the vapor trap de-icing cycle program. In this way it is secured that at least
six “clean” vapor traps are in operation at any given time.
The time between two consecutive de-icing periods (Timer T 7) and the actual time for
de-icing of the vapor trap coil (Timer T8) should be adjusted during commissioning to
suit the actual product.
During vacuum break, all the vacuum pumps stop. Bypass valve Q9608 is opened and
de-aeration valves are activated.
GEA Niro
GEA Process Engineering 10/19
0610-0zzz CONRAD™ 600 XL eco
4009 en De-Icing System
The purpose of the de-icing tank is to have sufficient water to de-ice the vapor trap
coils and to keep the water at a temperature where it will flash up/boil when the
connection to a vapor trap is opened.
The temperature transmitter (K4403) measures the temperature in the de-icing system.
The analogue regulating valve Q4403 operates any position from 0 % to 100 % to
regulate the steam to the built-in coil of the de-icing tank for maintaining the
temperature in the system controlled by transmitter K4403.
When one of the de-icing valves Q41x4 is opened, the pressure in the de-icing tank
drops and the water flashes up and streams to the vapor trap. As the water is flashed
up, energy is drawn from the de-icing tank and the temperature will drop slightly until
the heat regulation has compensated for the loss after which the water in the tank will
flash up again. This will continue until the vapor trap has been de-iced completely.
The temperature in the de-icing tank thus has a direct influence on the de-icing time
and it is very important that it is maintained stable.
NOTE!
If the temperature is too high, the pressure in the vapor trap during de-icing will be too
high, and the vacuum in the cabinet could be affected by vacuum steam flowing from
the de-icing tank to the CONRAD™ cabinet through the safety valves on the vapor
traps.
During de-icing, water will be removed from the tank C4400, and the level switch
K4401 may go to LOW. If the system is in mode for reusing the de-icing water, this will
cause three-way valve Q4340 to direct drained de-icing water to C4400. If not in mode
for reuse of the de-icing water, this triggers Q4409 to OPEN and fill fresh process
water on the tank until K4402 goes to HIGH causing Q4409 to CLOSE.
GEA Niro
11/19 GEA Process Engineering
CONRAD™ 600 XL eco 0610-0zzz
De-Icing System 4009 en
If the analogue valve Q4403 fails it is possible to maintain the temperature in the de-
icing tank by letting steam through the by-pass valve Q4423 and survey the
temperature on thermometer P4405. An operator must be present at the de-icing tank
to adjust the valve until the fault in the automatic system has been rectified.
The pump unit drains the melted condensate which gathers in the drain tank C4200
during de-icing of the vapor traps. When level switch K4202 reached goes to HIGH the
pumping is STARTED.
There are two pumps which run in parallel and the program are made in such a way,
that the pumps are operated on alternate days in order to ensure even wear. If pump
system G4313 is in operation and an alarm occurs in the system, pump system G4303
will act as spare and vice versa.
As the drain pumps are connected directly to the vapor trap during de-icing inside the
cabinet, there is a pressure of 20-50 mbar on the suction side of the pump. To avoid
breaking the vacuum in the cabinet, the pump has to create a pressure above
atmospheric pressure before the drain valves Q4305 or Q4315 are opened.
A pressure switch K4305 / K4315 monitors the pressure on the outlet side of each
pump. When the set point (approx. 1.1 Bar) for the pressure switch has been reached,
valve Q4305 or Q4315 OPENS, and the water is pumped from the system.
The water is pumped through the outlet line via the overflow vessel C4350 and
dumped into the foul condensate drain. The amount of discharged water to the foul
condensate drain is measured by the flow meter P4350.
The amount of water passing through the flow indicator P4350 will be equal to the
amount of vapor that has been removed by the vapor traps and thereby named as the
capacity of the CONRAD™.
The capacity must be measured over a period of time, 6, 12 or 24 hours, as the loads
on the 7 vapor traps in the CONRAD™ are not equal.
If reuse of the de-icing water is chosen, level switches K4402 and K4401 in the de-
icing tank C4400 control where the steam is led by the three-way valve Q4340. If
K4402 is HIGH when drain pump G43x3 starts, the water is led to the overflow tank
C4350 and dumped into the foul condensate drain. If level switch K4401 in the de-
icing tank C4400 is LOW when the drain pump G43x3 starts, the drain water is led
back to the de-icing tank C4400.
When K4201 is LOW the active drain pump is STOPPED and the corresponding valves
are closed.
If level switch K4350 indicates low level in the overflow tank C4350, the top-up water
valve Q4350 opens until the low-level alarm is gone. This is to prevent air from being
sucked into the system.
The flow device K43x3 regulates and monitors the flow of sealing water to the drain
pumps. A proximity switch is activated when the flow is sufficient and the pump can
start. If K43x3 is low the corresponding pump cannot start.
GEA Niro
GEA Process Engineering 12/19
0610-0zzz CONRAD™ 600 XL eco
4009 en De-Icing System
Stop!
The drain pumps G4303 and G4313 must never run without shaft
sealing water as dry running will immediately destroy the shaft seals.
See details below.
Important:
• There must always be a flow of about 20 l/h through the shaft seal of the pump in
operation
• If K43x3 is LOW for 15 sec. the corresponding pump will stop
• The flow must be manually adjusted on needle valve FC4303/FC4313. The actual
flow can be read on the instrument and must be regulated so that the proximity
switch has a stable signal
• The pressure of the water should only be 0.3 to 0.5 Barg.
GEA Niro
13/19 GEA Process Engineering
CONRAD™ 600 XL eco 0610-0zzz
De-Icing System 4009 en
When the time T 13 + T16 have elapsed, the program automatically moves to Stop –
Step 0 and all vapour traps are out of operation with closed gate plates and open drain
valves as described earlier under the heading Stop – Step 0.
Automatic devices
• If one of the drain pumps G43 fails the other will start automatically and the
corresponding auto valve Q43x3 will close.
• If the pressure switch P43x5 is low for 10 sec. after the corresponding drain pump
has started, the other drain pump will start instead. The pump that failed to give
pressure will stop and give an alarm.
• If a flow switch K43 registers that the flow of sealing water is LOW for 15 seconds,
it is interlocked to a corresponding drain pump G43xx which it will stop and give an
alarm. The other pump will start.
• If the overflow tank has low level (K4350), valve Q4350 will open and top-up the
level.
Alarms
• LOW LEVEL ALARM (K4401) if water level in de-icing tank is LOW for more than
600 seconds during the freeze drying mode.
• HIGH-LEVEL alarm (K4402) if the level in the de-icing tank is HIGH for more than
300 seconds.
• LOW TEMPERATURE ALARM (K4403) if the temperature in the de-icing tank falls
below the alarm set point.
• LOW LEVEL ALARM (K4350) if water level in overflow tank is low for more than
120 sec.
• LOW-PRESSURE alarm if the signal is LOW for 15 sec. (K4305/K4315) when drain
pump G4303/G4313 is running.
GEA Niro
GEA Process Engineering 14/19
0610-0zzz CONRAD™ 600 XL eco
4009 en De-Icing System
• LOW-FLOW alarm if the signal is LOW (K4303/K4313) for more than 15 seconds
with valve Q4303/Q4313 OPEN
• LOW TEMPERATURE ALARM (K4408) if the temperature in the system falls below
the alarm set point.
Set points
GEA Niro
15/19 GEA Process Engineering
CONRAD™ 600 XL eco 0610-0zzz
De-Icing System 4009 en
1.6 Maintenance
The drain pumps G4303 & G4313 can be isolated from the system for maintenance
during operation. The shut-off valves on either side of the pump are closed and the
pneumatic hoses are removed. If the pump is removed for a longer time, the flanges
should be blinded to avoid contamination of the pipeline. Clean the pipeline carefully
before mounting the pump again.
If the hot water regulating valve Q4403 or the steam trap V4412 breaks down during
operation, they can be isolated and bypassed manually.
Warning!
No part of the hot water supply system may be removed while under
pressure or while the temperature is above 40°C.
If the vacuum in the de-icing tank has been lost due to repair or failure, the operating
vacuum level must be re-established before connection to the cabinet.
Warning!
Never try to evacuate the de-icing tank through the vapour trap, as this
will result in a vacuum peak and will influence the product quality
Warning!
GEA Niro
GEA Process Engineering 16/19
0610-0zzz CONRAD™ 600 XL eco
4009 en De-Icing System
• Before removing pneumatically operated valves, the compressed air supply lines
must be disconnected. The disconnected air hoses must be blocked with plugs or
by tongs and cleaned carefully before reassembly.
• It is not possible to manually drain water from the de-icing tank (C4400) while the
cabinet is under vacuum and it should not be attempted, as it would disturb the
operation of the CONRAD™.
• If the de-icing vessel C4400 has to be moved, a forklift or similar must be used.
Before moving the de-icing vessel, all water must be drained from the tank through
the drain valve.
• Specialists only may perform all maintenance work other than leak detection
• If one of the automatic butterfly valves is used to isolate a pump, the control air to
open the valve must be disconnected before any work is done on the pump.
• Only spare parts mentioned in the spare parts list or other spare parts approved by
GEA Niro may be used when repairing any part of the system.
• Prior to any maintenance or repair work on the pumps, the power must be
disconnected at the source, and it must be ensured that the power cannot be
turned on accidentally by locking the safety breaker with a personally kept pad-lock
or similar.
• For details on repair and maintenance of specific items, please find sub supplier’s
instructions in this Instruction Handbook.
The de-icing system is an integrated part of the vacuum system, and it is therefore
important that the system is without leaks.
For further details please see the description of the vacuum system.
GEA Niro
17/19 GEA Process Engineering
CONRAD™ 600 XL eco 0610-0zzz
De-Icing System 4009 en
DE-ICING SYSTEM
CONTROL POINT d w m s y ACTION REMARKS
Drain pumps x Check for leaks If defective, replace
G4303 the packing set.
G4313 x Check flow for shaft Adjust to 20 l/h
sealing water
De-icing tank x Check water quality If contaminated,
C4400 replace water.
x Verify indication from Calibrate/replace if
temperature sensor necessary
K4403
x Verify indication on Calibrate/replace if
thermometer P4405 necessary
x Check level sensors Replace if necessary
K4201/K4402
Filter x Clean filter insert Replace insert if
V4421 damaged
Flow indicator x Check calibration Calibrate if
K4350 necessary.
Kytölä flow controllers x Check adjustment of Adjust if necessary
K4303 and flow
K4313 x Check function of Replace if not
flow switch functional
Flanged connections x Check for leaks If leaking replace
packing.
Butterfly valves x Check for leaks Replace worn parts.
x Check function of Verify full 90 deg
actuator operation
x Check function of Replace if faulty.
position indicator
GEA Niro
GEA Process Engineering 18/19
0610-0zzz CONRAD™ 600 XL eco
4009 en De-Icing System
1.8 Disposal
What? Where?
De-icing system
When contacting the service department of GEA Niro, please state full part number
1293528 from the spare parts list. This part number unambiguously identifies the
requested spare part.
Refer to the original GEA Niro main order (032-7024) for the supplied machinery.
For contact about service or other information, state machine type, serial number and
year of manufacture. Such data appear from the nameplate.
Drives
The type designation appears from the nameplate on the drive.
For ordering of separate parts for drive renovation, please see the supplier’s
instructions for repair, which are enclosed in this manual.
Pneumatic valves
Pneumatic components can be ordered from GEA Niro or according to the supplier’s
diagram and parts list, which are enclosed with this manual.
GEA Niro
19/19 GEA Process Engineering
CONRAD™ 600 XL eco 0610-0zzz
De-Icing System 4009 en
The necessary spares in order to ensure reliable operation have been delivered with
the equipment.
Whenever a spare part is used from the supplied spares the damaged part should be
repaired or replaced.
The spare part lists contain information about spare parts for the various components
in the De-icing System.
GEA Niro
GEA Process Engineering 20/19