Running Script File: CDP

1 - Command CALL - ZS62039A


ZS62039A TEST
2 - Command CLEAR_SW - All switches cleared at 02:07:09.850
3 - Command LOAD - "READY TO START"
SOV 62039 SHOULD BE CLOSED IS OPEN ES TEST (GAS
FUEL)
5 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:12.880
6 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:15.895
7 - Command SETVAR - INPUT SWITCH "N2N47_BI.ZS62039A - 9 -CDP PURGE
DOWNSTREAM VALVE (VA) OPEN-ACT 1 - XCP_VA_GT1 - AI_DEFAULT" set to 1 at
00:05:15.945
8 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:16.995
9 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:20.030
10 - Command VERIFY_BAND - CDP_PURGE.ZS62039A.B_NAME stayed within 0.5 of
1 for 1 seconds within 1 seconds. Completed at 00:05:21.040
11 - Command VERIFY_BAND - CDP_PURGE.ZS62039B.B_NAME stayed within 0.5 of
1 for 1 seconds within 1 seconds. Completed at 00:05:22.055
12 - Command VERIFY - CDP_PURGE.ZAH62039A.B_NAME = 0 within 1 seconds.
Completed at 00:05:22.075
13 - Command VERIFY - CDP_PURGE.ZAHH62039A.B_NAME = 1 within 1 seconds.
Completed at 00:05:22.135
14 - Command VERIFY - CDP_PURGE.ZAL62039B.B_NAME = 0 within 1 seconds.
Completed at 00:05:22.195
15 - Command VERIFY - CDP_PURGE.ZAHH62039B.B_NAME = 0 within 1 seconds.
Completed at 00:05:22.255
16 - Command VERIFY - START_PERM.CDP_VLV.NOR = 1 within 1 seconds.
Completed at 00:05:22.315
17 - Command VERIFY - SHUTDOWN.SD_LAT.LATCH_AE = 1 within 0 seconds.
Completed at 00:05:22.375
SOV 62039 SHOULD BE CLOSED IS OPEN BOTH FAIL ES TEST
(GAS FUEL)
20 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:23.495
21 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:26.515
22 - Command SETVAR - INPUT SWITCH "N2N47_BI.ZS62039A - 9 -CDP PURGE
DOWNSTREAM VALVE (VA) OPEN-ACT 1 - XCP_VA_GT1 - AI_DEFAULT" set to 1 at
00:05:26.575
23 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:27.640
24 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:30.650
25 - Command VERIFY_BAND - CDP_PURGE.ZS62039A.B_NAME stayed within 0.5 of
1 for 1 seconds within 1 seconds. Completed at 00:05:31.655
26 - Command VERIFY_BAND - CDP_PURGE.ZS62039B.B_NAME stayed within 0.5 of
1 for 1 seconds within 1 seconds. Completed at 00:05:32.675
27 - Command VERIFY - CDP_PURGE.ZAH62039A.B_NAME = 0 within 1 seconds.
Completed at 00:05:32.695
28 - Command VERIFY - CDP_PURGE.ZAHH62039A.B_NAME = 1 within 1 seconds.
Completed at 00:05:32.755
29 - Command VERIFY - CDP_PURGE.ZAL62039B.B_NAME = 0 within 1 seconds.
Completed at 00:05:32.815
30 - Command VERIFY - CDP_PURGE.ZAHH62039B.B_NAME = 0 within 1 seconds.
Completed at 00:05:32.875
31 - Command VERIFY - START_PERM.CDP_VLV.NOR = 1 within 1 seconds.
Completed at 00:05:32.935
32 - Command VERIFY - SHUTDOWN.SD_LAT.LATCH_AE = 1 within 0 seconds.
Completed at 00:05:32.995
SOV 62039 SHOULD BE CLOSED IS CLOSED NO SD TEST
(GAS FUEL)
35 - Command CLEAR_SW - All switches cleared at 00:05:33.055
36 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:34.115
37 - Command LOAD - "READY TO START"
38 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:14.755
39 - Command SETVAR - INPUT SWITCH "N2N47_BI.ZS62039A - 9 -CDP PURGE
DOWNSTREAM VALVE (VA) OPEN-ACT 1 - XCP_VA_GT1 - AI_DEFAULT" set to 0 at
00:05:14.815
40 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:15.880
41 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:18.895
42 - Command VERIFY_BAND - CDP_PURGE.ZS62039A.B_NAME stayed within 0.5 of
0 for 1 seconds within 1 seconds. Completed at 00:05:19.955
43 - Command VERIFY_BAND - CDP_PURGE.ZS62039B.B_NAME stayed within 0.5 of
1 for 1 seconds within 1 seconds. Completed at 00:05:20.980
44 - Command VERIFY - CDP_PURGE.ZAH62039A.B_NAME = 0 within 1 seconds.
Completed at 00:05:21.000
45 - Command VERIFY - CDP_PURGE.ZAHH62039A.B_NAME = 0 within 1 seconds.
Completed at 00:05:21.055
46 - Command VERIFY - CDP_PURGE.ZAL62039B.B_NAME = 0 within 1 seconds.
Completed at 00:05:21.115
47 - Command VERIFY - CDP_PURGE.ZAHH62039B.B_NAME = 0 within 1 seconds.
Completed at 00:05:21.175
48 - Command VERIFY - START_PERM.CDP_VLV.NOR = 1 within 1 seconds.
Completed at 00:05:21.235
49 - Command VERIFY - SHUTDOWN.SD_LAT.LATCH_AE = 0 within 0 seconds.
Completed at 00:05:21.295
SOV 62039 SHOULD BE CLOSED IS OPEN DURING STARTUP
SD TEST (LIQ FUEL)
52 - Command CLEAR_SW - All switches cleared at 00:05:21.385
53 - Command LOAD - "READY TO START"
54 - Command TOGGLE - FUEL_SYS.LIQSEL_OR.IN_2 toggled to 1 for 1 seconds.
Completed at 00:05:12.760
55 - Command TOGGLE - SFC_STEP.START_OR.IN_3 toggled to 1 for 1 seconds.
Completed at 00:05:13.835
56 - Command VERIFY - CDP_PURGE.START_INIT.B_NAME = 1 within 100 seconds.
Completed at 00:05:13.855
57 - Command VERIFY - CDP_PURGE.LIQ100PCT.B_NAME = 1 within 300 seconds.
Completed at 00:05:13.975
58 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:15.100
59 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:18.110
60 - Command SETVAR - INPUT SWITCH "N2N47_BI.ZS62039A - 9 -CDP PURGE
DOWNSTREAM VALVE (VA) OPEN-ACT 1 - XCP_VA_GT1 - AI_DEFAULT" set to 1 at
00:05:18.115
61 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:19.175
62 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:22.195
63 - Command VERIFY_BAND - CDP_PURGE.ZS62039A.B_NAME stayed within 0.5 of
1 for 1 seconds within 1 seconds. Completed at 00:05:23.260
64 - Command VERIFY_BAND - CDP_PURGE.ZS62039B.B_NAME stayed within 0.5 of
1 for 1 seconds within 50 seconds. Completed at 00:06:11.730
65 - Command VERIFY - CDP_PURGE.ZAH62039A.B_NAME = 1 within 50 seconds.
Completed at 00:06:15.690
66 - Command VERIFY - CDP_PURGE.ZAHH62039A.B_NAME = 0 within 1 seconds.
Completed at 00:06:15.715
67 - Command VERIFY - CDP_PURGE.ZAL62039B.B_NAME = 0 within 1 seconds.
Completed at 00:06:15.775
68 - Command VERIFY - CDP_PURGE.ZAHH62039B.B_NAME = 0 within 1 seconds.
Completed at 00:06:15.835
69 - Command VERIFY - START_PERM.CDP_VLV.NOR = 0 within 1 seconds.
Completed at 00:06:15.895
70 - Command VERIFY - SHUTDOWN.SD_LAT.LATCH_AE = 1 within 3 seconds.
Completed at 00:06:15.955
SOV 62039 SHOULD BE OPEN IS CLOSED ALARM TEST (LIQ
FUEL)
73 - Command CLEAR_SW - All switches cleared at 00:06:16.075
74 - Command LOAD - "FULL SPEED NO LOAD"
75 - Command TOGGLE - FUEL_SYS.LIQSEL_OR.IN_2 toggled to 1 for 1 seconds.
Completed at 00:31:51.305
76 - Command VERIFY - CDP_PURGE.LIQ100PCT.B_NAME = 1 within 300 seconds.
Completed at 00:33:01.130
77 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:33:02.165
78 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:33:05.185
79 - Command SETVAR - INPUT SWITCH "N2N47_BI.ZS62039A - 9 -CDP PURGE
DOWNSTREAM VALVE (VA) OPEN-ACT 1 - XCP_VA_GT1 - AI_DEFAULT" set to 0 at
00:33:05.215
80 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:33:06.305
81 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:33:09.320
82 - Command VERIFY_BAND - CDP_PURGE.ZS62039A.B_NAME stayed within 0.5 of
0 for 1 seconds within 1 seconds. Completed at 00:33:10.320
83 - Command VERIFY_BAND - CDP_PURGE.ZS62039B.B_NAME stayed within 0.5 of
0 for 1 seconds within 1 seconds. Completed at 00:33:11.340
84 - Command VERIFY - CDP_PURGE.ZAH62039A.B_NAME = 1 within 1 seconds.
Completed at 00:33:11.365
85 - Command VERIFY - CDP_PURGE.ZAHH62039A.B_NAME = 0 within 1 seconds.
Completed at 00:33:11.425
86 - Command VERIFY - CDP_PURGE.ZAL62039B.B_NAME = 0 within 1 seconds.
Completed at 00:33:11.485
87 - Command VERIFY - CDP_PURGE.ZAHH62039B.B_NAME = 0 within 1 seconds.
Completed at 00:33:11.545
88 - Command VERIFY - START_PERM.CDP_VLV.NOR = 0 within 1 seconds.
Completed at 00:33:11.605
89 - Command VERIFY - SHUTDOWN.SD_LAT.LATCH_AE = 0 within 0 seconds.
Completed at 00:33:11.665
SOV 62039 SHOULD BE OPEN IS OPEN NO ALARM TEST (LIQ
FUEL)
92 - Command CLEAR_SW - All switches cleared at 00:33:11.845
93 - Command LOAD - "FULL SPEED NO LOAD"
94 - Command TOGGLE - FUEL_SYS.LIQSEL_OR.IN_2 toggled to 1 for 1 seconds.
Completed at 00:31:51.305
95 - Command VERIFY - CDP_PURGE.LIQ100PCT.B_NAME = 1 within 300 seconds.
Completed at 00:33:01.130
96 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:33:02.165
97 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:33:05.185
98 - Command SETVAR - INPUT SWITCH "N2N47_BI.ZS62039A - 9 -CDP PURGE
DOWNSTREAM VALVE (VA) OPEN-ACT 1 - XCP_VA_GT1 - AI_DEFAULT" set to 1 at
00:33:05.245
99 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:33:06.305
100 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:33:09.320
101 - Command VERIFY_BAND - CDP_PURGE.ZS62039A.B_NAME stayed within 0.5
of 1 for 1 seconds within 1 seconds. Completed at 00:33:10.320
102 - Command VERIFY_BAND - CDP_PURGE.ZS62039B.B_NAME stayed within 0.5
of 0 for 1 seconds within 1 seconds. Completed at 00:33:11.340
103 - Command VERIFY - CDP_PURGE.ZAH62039A.B_NAME = 0 within 1 seconds.
Completed at 00:33:11.365
104 - Command VERIFY - CDP_PURGE.ZAHH62039A.B_NAME = 0 within 1 seconds.
Completed at 00:33:11.425
105 - Command VERIFY - CDP_PURGE.ZAL62039B.B_NAME = 0 within 1 seconds.
Completed at 00:33:11.485
106 - Command VERIFY - CDP_PURGE.ZAHH62039B.B_NAME = 0 within 1 seconds.
Completed at 00:33:11.545
107 - Command VERIFY - START_PERM.CDP_VLV.NOR = 1 within 1 seconds.
Completed at 00:33:11.605
108 - Command VERIFY - SHUTDOWN.SD_LAT.LATCH_AE = 0 within 0 seconds.
Completed at 00:33:11.665
END OF ZS62039A TEST
Return to calling script at 00:33:11.665
2 - Command CALL - ZS62039B
ZS62039B TEST
2 - Command CLEAR_SW - All switches cleared at 00:33:11.965
3 - Command LOAD - "READY TO START"
SOV 62039 SHOULD BE CLOSED IS OPEN ES TEST (GAS
FUEL)
5 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:12.820
6 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:15.830
7 - Command SETVAR - INPUT SWITCH "N2N47_BI.ZS62039B - 10 - CDP PURGE
DOWNSTREAM VALVE (VA) CLOSED-ACT 1 - XCP_VA_GT1 - REVERSE" set to 0 at
00:05:15.835
8 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:16.895
9 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:19.915
10 - Command VERIFY_BAND - CDP_PURGE.ZS62039A.B_NAME stayed within 0.5 of
0 for 1 seconds within 1 seconds. Completed at 00:05:20.980
11 - Command VERIFY_BAND - CDP_PURGE.ZS62039B.B_NAME stayed within 0.5 of
0 for 1 seconds within 1 seconds. Completed at 00:05:21.995
12 - Command VERIFY - CDP_PURGE.ZAH62039A.B_NAME = 0 within 1 seconds.
Completed at 00:05:22.015
13 - Command VERIFY - CDP_PURGE.ZAHH62039A.B_NAME = 0 within 1 seconds.
Completed at 00:05:22.075
14 - Command VERIFY - CDP_PURGE.ZAL62039B.B_NAME = 0 within 1 seconds.
Completed at 00:05:22.085
15 - Command VERIFY - CDP_PURGE.ZAHH62039B.B_NAME = 1 within 1 seconds.
Completed at 00:05:22.195
16 - Command VERIFY - START_PERM.CDP_VLV.NOR = 1 within 1 seconds.
Completed at 00:05:22.255
17 - Command VERIFY - SHUTDOWN.SD_LAT.LATCH_AE = 1 within 0 seconds.
Completed at 00:05:22.315
19 - Command LOAD - "READY TO START"
SOV 62039 SHOULD BE CLOSED IS OPEN BOTH FAIL ES TEST
(GAS FUEL)
21 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:12.820
22 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:15.830
23 - Command SETVAR - INPUT SWITCH "N2N47_BI.ZS62039B - 10 - CDP PURGE
DOWNSTREAM VALVE (VA) CLOSED-ACT 1 - XCP_VA_GT1 - REVERSE" set to 0 at
00:05:15.835
24 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:16.895
25 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:19.915
26 - Command VERIFY_BAND - CDP_PURGE.ZS62039A.B_NAME stayed within 0.5 of
0 for 1 seconds within 1 seconds. Completed at 00:05:20.980
27 - Command VERIFY_BAND - CDP_PURGE.ZS62039B.B_NAME stayed within 0.5 of
0 for 1 seconds within 1 seconds. Completed at 00:05:21.995
28 - Command VERIFY - CDP_PURGE.ZAH62039A.B_NAME = 0 within 1 seconds.
Completed at 00:05:22.015
29 - Command VERIFY - CDP_PURGE.ZAHH62039A.B_NAME = 0 within 1 seconds.
Completed at 00:05:22.075
30 - Command VERIFY - CDP_PURGE.ZAL62039B.B_NAME = 0 within 1 seconds.
Completed at 00:05:22.135
31 - Command VERIFY - CDP_PURGE.ZAHH62039B.B_NAME = 1 within 1 seconds.
Completed at 00:05:22.195
32 - Command VERIFY - START_PERM.CDP_VLV.NOR = 1 within 1 seconds.
Completed at 00:05:22.255
33 - Command VERIFY - SHUTDOWN.SD_LAT.LATCH_AE = 1 within 0 seconds.
Completed at 00:05:22.315
SOV 62039 SHOULD BE CLOSED IS CLOSED NO SD TEST
(GAS FUEL)
36 - Command CLEAR_SW - All switches cleared at 00:05:22.435
37 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:23.495
38 - Command LOAD - "READY TO START"
39 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:14.755
40 - Command SETVAR - INPUT SWITCH "N2N47_BI.ZS62039B - 10 - CDP PURGE
DOWNSTREAM VALVE (VA) CLOSED-ACT 1 - XCP_VA_GT1 - REVERSE" set to 1 at
00:05:14.815
41 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:15.880
42 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:18.895
43 - Command VERIFY_BAND - CDP_PURGE.ZS62039A.B_NAME stayed within 0.5 of
0 for 1 seconds within 1 seconds. Completed at 00:05:19.955
44 - Command VERIFY_BAND - CDP_PURGE.ZS62039B.B_NAME stayed within 0.5 of
1 for 1 seconds within 1 seconds. Completed at 00:05:20.980
45 - Command VERIFY - CDP_PURGE.ZAH62039A.B_NAME = 0 within 1 seconds.
Completed at 00:05:20.995
46 - Command VERIFY - CDP_PURGE.ZAHH62039A.B_NAME = 0 within 1 seconds.
Completed at 00:05:21.055
47 - Command VERIFY - CDP_PURGE.ZAL62039B.B_NAME = 0 within 1 seconds.
Completed at 00:05:21.115
48 - Command VERIFY - CDP_PURGE.ZAHH62039B.B_NAME = 0 within 1 seconds.
Completed at 00:05:21.175
49 - Command VERIFY - START_PERM.CDP_VLV.NOR = 1 within 1 seconds.
Completed at 00:05:21.235
50 - Command VERIFY - SHUTDOWN.SD_LAT.LATCH_AE = 0 within 0 seconds.
Completed at 00:05:21.295
SOV 62039 SHOULD BE CLOSED IS OPEN DURING STARTUP
SD TEST (LIQ FUEL)
53 - Command CLEAR_SW - All switches cleared at 00:05:21.435
54 - Command LOAD - "READY TO START"
55 - Command TOGGLE - FUEL_SYS.LIQSEL_OR.IN_2 toggled to 1 for 1 seconds.
Completed at 00:05:12.760
56 - Command TOGGLE - SFC_STEP.START_OR.IN_3 toggled to 1 for 1 seconds.
Completed at 00:05:13.775
57 - Command VERIFY - CDP_PURGE.START_INIT.B_NAME = 1 within 100 seconds.
Completed at 00:05:13.795
58 - Command VERIFY - CDP_PURGE.LIQ100PCT.B_NAME = 1 within 300 seconds.
Completed at 00:05:13.855
59 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:14.920
60 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:17.930
61 - Command SETVAR - INPUT SWITCH "N2N47_BI.ZS62039B - 10 - CDP PURGE
DOWNSTREAM VALVE (VA) CLOSED-ACT 1 - XCP_VA_GT1 - REVERSE" set to 0 at
00:05:17.935
62 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:18.995
63 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:22.015
64 - Command VERIFY_BAND - CDP_PURGE.ZS62039A.B_NAME stayed within 0.5 of
0 for 1 seconds within 50 seconds. Completed at 00:06:11.730
65 - Command VERIFY_BAND - CDP_PURGE.ZS62039B.B_NAME stayed within 0.5 of
0 for 1 seconds within 50 seconds. Completed at 00:06:12.805
66 - Command VERIFY - CDP_PURGE.ZAH62039A.B_NAME = 0 within 50 seconds.
Completed at 00:06:12.855
67 - Command VERIFY - CDP_PURGE.ZAHH62039A.B_NAME = 0 within 1 seconds.
Completed at 00:06:12.905
68 - Command VERIFY - CDP_PURGE.ZAL62039B.B_NAME = 1 within 50 seconds.
Completed at 00:06:15.690
69 - Command VERIFY - CDP_PURGE.ZAHH62039B.B_NAME = 0 within 1 seconds.
Completed at 00:06:15.775
70 - Command VERIFY - START_PERM.CDP_VLV.NOR = 0 within 1 seconds.
Completed at 00:06:15.835
71 - Command VERIFY - SHUTDOWN.SD_LAT.LATCH_AE = 1 within 0 seconds.
Completed at 00:06:15.955
SOV 62039 SHOULD BE OPEN IS CLOSED ALARM TEST (LIQ
FUEL)
74 - Command CLEAR_SW - All switches cleared at 00:06:16.255
75 - Command LOAD - "FULL SPEED NO LOAD"
76 - Command TOGGLE - FUEL_SYS.LIQSEL_OR.IN_2 toggled to 1 for 1 seconds.
Completed at 00:31:51.360
77 - Command VERIFY - CDP_PURGE.LIQ100PCT.B_NAME = 1 within 300 seconds.
Completed at 00:33:01.130
78 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:33:02.165
79 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:33:05.240
80 - Command SETVAR - INPUT SWITCH "N2N47_BI.ZS62039B - 10 - CDP PURGE
DOWNSTREAM VALVE (VA) CLOSED-ACT 1 - XCP_VA_GT1 - REVERSE" set to 1 at
00:33:05.245
81 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:33:06.360
82 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:33:09.440
83 - Command VERIFY_BAND - CDP_PURGE.ZS62039A.B_NAME stayed within 0.5 of
1 for 1 seconds within 1 seconds. Completed at 00:33:10.440
84 - Command VERIFY_BAND - CDP_PURGE.ZS62039B.B_NAME stayed within 0.5 of
1 for 1 seconds within 1 seconds. Completed at 00:33:11.480
85 - Command VERIFY - CDP_PURGE.ZAH62039A.B_NAME = 0 within 1 seconds.
Completed at 00:33:11.535
86 - Command VERIFY - CDP_PURGE.ZAHH62039A.B_NAME = 0 within 1 seconds.
Completed at 00:33:11.665
87 - Command VERIFY - CDP_PURGE.ZAL62039B.B_NAME = 1 within 1 seconds.
Completed at 00:33:11.765
88 - Command VERIFY - CDP_PURGE.ZAHH62039B.B_NAME = 0 within 1 seconds.
Completed at 00:33:11.845
89 - Command VERIFY - START_PERM.CDP_VLV.NOR = 0 within 1 seconds.
Completed at 00:33:11.965
90 - Command VERIFY - SHUTDOWN.SD_LAT.LATCH_AE = 0 within 0 seconds.
Completed at 00:33:12.025
SOV 62039 SHOULD BE OPEN IS OPEN NO ALARM TEST (LIQ
FUEL)
93 - Command CLEAR_SW - All switches cleared at 00:33:12.315
94 - Command LOAD - "FULL SPEED NO LOAD"
95 - Command TOGGLE - FUEL_SYS.LIQSEL_OR.IN_2 toggled to 1 for 1 seconds.
Completed at 00:31:51.360
96 - Command VERIFY - CDP_PURGE.LIQ100PCT.B_NAME = 1 within 300 seconds.
Completed at 00:33:01.130
97 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:33:02.200
98 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:33:05.265
99 - Command SETVAR - INPUT SWITCH "N2N47_BI.ZS62039B - 10 - CDP PURGE
DOWNSTREAM VALVE (VA) CLOSED-ACT 1 - XCP_VA_GT1 - REVERSE" set to 0 at
00:33:05.320
100 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:33:06.425
101 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:33:09.505
102 - Command VERIFY_BAND - CDP_PURGE.ZS62039A.B_NAME stayed within 0.5
of 1 for 1 seconds within 1 seconds. Completed at 00:33:10.565
103 - Command VERIFY_BAND - CDP_PURGE.ZS62039B.B_NAME stayed within 0.5
of 0 for 1 seconds within 1 seconds. Completed at 00:33:11.645
104 - Command VERIFY - CDP_PURGE.ZAH62039A.B_NAME = 0 within 1 seconds.
Completed at 00:33:11.680
105 - Command VERIFY - CDP_PURGE.ZAHH62039A.B_NAME = 0 within 1 seconds.
Completed at 00:33:11.785
106 - Command VERIFY - CDP_PURGE.ZAL62039B.B_NAME = 0 within 1 seconds.
Completed at 00:33:11.875
107 - Command VERIFY - CDP_PURGE.ZAHH62039B.B_NAME = 0 within 1 seconds.
Completed at 00:33:12.005
108 - Command VERIFY - START_PERM.CDP_VLV.NOR = 1 within 1 seconds.
Completed at 00:33:12.145
109 - Command VERIFY - SHUTDOWN.SD_LAT.LATCH_AE = 0 within 0 seconds.
Completed at 00:33:12.205
END OF ZS62039A TEST
Return to calling script at 00:33:12.205
3 - Command CALL - ZS62038A
ZS62038A TEST
2 - Command CLEAR_SW - All switches cleared at 00:33:13.045
3 - Command LOAD - "READY TO START"
SOV 62038 SHOULD BE CLOSED IS OPEN ES TEST (GAS
FUEL)
5 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:12.860
6 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:15.895
7 - Command SETVAR - INPUT SWITCH "N2N47_BI.ZS62038A - 6 -CDP PURGE
UPSTREAM VALVE (VB) OPEN-ACT 1 - XCP_VB_GT1 - AI_DEFAULT" set to 1 at 00:05:15.915
8 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:17.020
9 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:20.030
10 - Command VERIFY_BAND - CDP_PURGE.ZS62038A.B_NAME stayed within 0.5 of
1 for 1 seconds within 1 seconds. Completed at 00:05:21.040
11 - Command VERIFY_BAND - CDP_PURGE.ZS62038B.B_NAME stayed within 0.5 of
1 for 1 seconds within 1 seconds. Completed at 00:05:22.055
12 - Command VERIFY - CDP_PURGE.ZAH62038A.B_NAME = 0 within 1 seconds.
Completed at 00:05:22.075
13 - Command VERIFY - CDP_PURGE.ZAHH62038A.B_NAME = 1 within 1 seconds.
Completed at 00:05:22.165
14 - Command VERIFY - CDP_PURGE.ZAL62038B.B_NAME = 0 within 1 seconds.
Completed at 00:05:22.305
15 - Command VERIFY - CDP_PURGE.ZAHH62038B.B_NAME = 0 within 1 seconds.
Completed at 00:05:22.375
16 - Command VERIFY - START_PERM.CDP_VLV.NOR = 1 within 1 seconds.
Completed at 00:05:22.435
17 - Command VERIFY - SHUTDOWN.SD_LAT.LATCH_AE = 1 within 0 seconds.
Completed at 00:05:22.495
SOV 62038 SHOULD BE CLOSED IS CLOSED NO SD TEST
(GAS FUEL)
20 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:23.800
21 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:26.870
22 - Command SETVAR - INPUT SWITCH "N2N47_BI.ZS62038A - 6 -CDP PURGE
UPSTREAM VALVE (VB) OPEN-ACT 1 - XCP_VB_GT1 - AI_DEFAULT" set to 0 at 00:05:26.875
23 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:27.980
24 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:31.070
25 - Command VERIFY_BAND - CDP_PURGE.ZS62038A.B_NAME stayed within 0.5 of
0 for 1 seconds within 1 seconds. Completed at 00:05:32.110
26 - Command VERIFY_BAND - CDP_PURGE.ZS62038B.B_NAME stayed within 0.5 of
1 for 1 seconds within 1 seconds. Completed at 00:05:33.155
27 - Command VERIFY - CDP_PURGE.ZAH62038A.B_NAME = 0 within 1 seconds.
Completed at 00:05:33.235
28 - Command VERIFY - CDP_PURGE.ZAHH62038A.B_NAME = 0 within 1 seconds.
Completed at 00:05:33.355
29 - Command VERIFY - CDP_PURGE.ZAL62038B.B_NAME = 0 within 1 seconds.
Completed at 00:05:33.455
30 - Command VERIFY - CDP_PURGE.ZAHH62038B.B_NAME = 0 within 1 seconds.
Completed at 00:05:33.535
31 - Command VERIFY - START_PERM.CDP_VLV.NOR = 1 within 1 seconds.
Completed at 00:05:33.655
32 - Command VERIFY - SHUTDOWN.SD_LAT.LATCH_AE = 0 within 0 seconds.
Completed at 00:05:33.745
SOV 62038 SHOULD BE CLOSED IS OPEN DURING STARTUP
SD TEST (LIQ FUEL)
35 - Command CLEAR_SW - All switches cleared at 00:05:34.075
36 - Command LOAD - "READY TO START"
37 - Command TOGGLE - FUEL_SYS.LIQSEL_OR.IN_2 toggled to 1 for 1 seconds.
Completed at 00:05:12.805
38 - Command TOGGLE - SFC_STEP.START_OR.IN_3 toggled to 1 for 1 seconds.
Completed at 00:05:13.895
39 - Command VERIFY - CDP_PURGE.START_INIT.B_NAME = 1 within 100 seconds.
Completed at 00:05:13.915
40 - Command VERIFY - CDP_PURGE.LIQ100PCT.B_NAME = 1 within 300 seconds.
Completed at 00:05:14.085
41 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:15.155
42 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:18.235
43 - Command SETVAR - INPUT SWITCH "N2N47_BI.ZS62038A - 6 -CDP PURGE
UPSTREAM VALVE (VB) OPEN-ACT 1 - XCP_VB_GT1 - AI_DEFAULT" set to 1 at 00:05:18.295
44 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:19.420
45 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:22.540
46 - Command VERIFY_BAND - CDP_PURGE.ZS62038A.B_NAME stayed within 0.5 of
1 for 1 seconds within 1 seconds. Completed at 00:05:23.605
47 - Command VERIFY_BAND - CDP_PURGE.ZS62038B.B_NAME stayed within 0.5 of
1 for 1 seconds within 50 seconds. Completed at 00:06:11.730
48 - Command VERIFY - CDP_PURGE.ZAH62038A.B_NAME = 1 within 50 seconds.
Completed at 00:06:15.690
49 - Command VERIFY - CDP_PURGE.ZAHH62038A.B_NAME = 0 within 1 seconds.
Completed at 00:06:15.775
50 - Command VERIFY - CDP_PURGE.ZAL62038B.B_NAME = 0 within 1 seconds.
Completed at 00:06:16.015
51 - Command VERIFY - CDP_PURGE.ZAHH62038B.B_NAME = 0 within 1 seconds.
Completed at 00:06:16.135
52 - Command VERIFY - START_PERM.CDP_VLV.NOR = 0 within 1 seconds.
Completed at 00:06:16.315
53 - Command VERIFY - SHUTDOWN.SD_LAT.LATCH_AE = 1 within 1 seconds.
Completed at 00:06:16.495
SOV 62038 SHOULD BE OPEN IS CLOSED ALARM TEST (LIQ
FUEL)
56 - Command CLEAR_SW - All switches cleared at 00:06:16.845
57 - Command LOAD - "FULL SPEED NO LOAD"
58 - Command TOGGLE - FUEL_SYS.LIQSEL_OR.IN_2 toggled to 1 for 1 seconds.
Completed at 00:31:51.480
59 - Command VERIFY - CDP_PURGE.LIQ100PCT.B_NAME = 1 within 300 seconds.
Completed at 00:33:01.290
60 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:33:02.405
61 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:33:05.515
62 - Command SETVAR - INPUT SWITCH "N2N47_BI.ZS62038A - 6 -CDP PURGE
UPSTREAM VALVE (VB) OPEN-ACT 1 - XCP_VB_GT1 - AI_DEFAULT" set to 0 at 00:33:05.560
63 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:33:06.720
64 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:33:09.815
65 - Command VERIFY_BAND - CDP_PURGE.ZS62038A.B_NAME stayed within 0.5 of
0 for 1 seconds within 1 seconds. Completed at 00:33:10.895
66 - Command VERIFY_BAND - CDP_PURGE.ZS62038B.B_NAME stayed within 0.5 of
0 for 1 seconds within 1 seconds. Completed at 00:33:11.970
67 - Command VERIFY - CDP_PURGE.ZAH62038A.B_NAME = 1 within 1 seconds.
Completed at 00:33:12.145
68 - Command VERIFY - CDP_PURGE.ZAHH62038A.B_NAME = 0 within 1 seconds.
Completed at 00:33:12.265
69 - Command VERIFY - CDP_PURGE.ZAL62038B.B_NAME = 0 within 1 seconds.
Completed at 00:33:12.425
70 - Command VERIFY - CDP_PURGE.ZAHH62038B.B_NAME = 0 within 1 seconds.
Completed at 00:33:12.565
71 - Command VERIFY - START_PERM.CDP_VLV.NOR = 0 within 1 seconds.
Completed at 00:33:12.685
72 - Command VERIFY - SHUTDOWN.SD_LAT.LATCH_AE = 0 within 0 seconds.
Completed at 00:33:12.835
SOV 62038 SHOULD BE OPEN IS OPEN NO ALARM TEST (LIQ
FUEL)
75 - Command CLEAR_SW - All switches cleared at 00:33:13.245
76 - Command LOAD - "FULL SPEED NO LOAD"
77 - Command TOGGLE - FUEL_SYS.LIQSEL_OR.IN_2 toggled to 1 for 1 seconds.
Completed at 00:31:51.425
78 - Command VERIFY - CDP_PURGE.LIQ100PCT.B_NAME = 1 within 300 seconds.
Completed at 00:33:01.290
79 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:33:02.395
80 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:33:05.440
81 - Command SETVAR - INPUT SWITCH "N2N47_BI.ZS62038A - 6 -CDP PURGE
UPSTREAM VALVE (VB) OPEN-ACT 1 - XCP_VB_GT1 - AI_DEFAULT" set to 1 at 00:33:05.495
82 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:33:06.690
83 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:33:09.805
84 - Command VERIFY_BAND - CDP_PURGE.ZS62038A.B_NAME stayed within 0.5 of
1 for 1 seconds within 1 seconds. Completed at 00:33:10.860
85 - Command VERIFY_BAND - CDP_PURGE.ZS62038B.B_NAME stayed within 0.5 of
0 for 1 seconds within 1 seconds. Completed at 00:33:11.940
86 - Command VERIFY - CDP_PURGE.ZAH62038A.B_NAME = 0 within 1 seconds.
Completed at 00:33:12.025
87 - Command VERIFY - CDP_PURGE.ZAHH62038A.B_NAME = 0 within 1 seconds.
Completed at 00:33:12.105
88 - Command VERIFY - CDP_PURGE.ZAL62038B.B_NAME = 0 within 1 seconds.
Completed at 00:33:12.285
89 - Command VERIFY - CDP_PURGE.ZAHH62038B.B_NAME = 0 within 1 seconds.
Completed at 00:33:12.445
90 - Command VERIFY - START_PERM.CDP_VLV.NOR = 1 within 1 seconds.
Completed at 00:33:12.685
91 - Command VERIFY - SHUTDOWN.SD_LAT.LATCH_AE = 0 within 0 seconds.
Completed at 00:33:12.820
END OF ZS62038A TEST
Return to calling script at 00:33:12.820
4 - Command CALL - ZS62038B
ZS62038AB TEST
2 - Command CLEAR_SW - All switches cleared at 00:33:14.180
3 - Command LOAD - "READY TO START"
SOV 62038 SHOULD BE CLOSED IS OPEN ES TEST (GAS
FUEL)
5 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:12.995
6 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:16.075
7 - Command SETVAR - INPUT SWITCH "N2N47_BI.ZS62038B - 7 -CDP PURGE
UPSTREAM VALVE (VB) CLOSED-ACT 1 - XCP_VB_GT1 - REVERSE" set to 0 at 00:05:16.165
8 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:17.260
9 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:20.330
10 - Command VERIFY_BAND - CDP_PURGE.ZS62038A.B_NAME stayed within 0.5 of
0 for 1 seconds within 1 seconds. Completed at 00:05:21.395
11 - Command VERIFY_BAND - CDP_PURGE.ZS62038B.B_NAME stayed within 0.5 of
0 for 1 seconds within 1 seconds. Completed at 00:05:22.495
12 - Command VERIFY - CDP_PURGE.ZAH62038A.B_NAME = 0 within 1 seconds.
Completed at 00:05:22.565
13 - Command VERIFY - CDP_PURGE.ZAHH62038A.B_NAME = 0 within 1 seconds.
Completed at 00:05:22.735
14 - Command VERIFY - CDP_PURGE.ZAL62038B.B_NAME = 0 within 1 seconds.
Completed at 00:05:22.815
15 - Command VERIFY - CDP_PURGE.ZAHH62038B.B_NAME = 1 within 1 seconds.
Completed at 00:05:22.995
16 - Command VERIFY - START_PERM.CDP_VLV.NOR = 1 within 1 seconds.
Completed at 00:05:23.095
17 - Command VERIFY - SHUTDOWN.SD_LAT.LATCH_AE = 1 within 0 seconds.
Completed at 00:05:23.290
SOV 62038 SHOULD BE CLOSED IS CLOSED NO SD TEST
(GAS FUEL)
20 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:24.700
21 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:27.780
22 - Command SETVAR - INPUT SWITCH "N2N47_BI.ZS62038B - 7 -CDP PURGE
UPSTREAM VALVE (VB) CLOSED-ACT 1 - XCP_VB_GT1 - REVERSE" set to 1 at 00:05:27.915
23 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:29.080
24 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:32.255
25 - Command VERIFY_BAND - CDP_PURGE.ZS62038A.B_NAME stayed within 0.5 of
0 for 1 seconds within 1 seconds. Completed at 00:05:33.335
26 - Command VERIFY_BAND - CDP_PURGE.ZS62038B.B_NAME stayed within 0.5 of
1 for 1 seconds within 1 seconds. Completed at 00:05:34.425
27 - Command VERIFY - CDP_PURGE.ZAH62038A.B_NAME = 0 within 1 seconds.
Completed at 00:05:34.495
28 - Command VERIFY - CDP_PURGE.ZAHH62038A.B_NAME = 0 within 1 seconds.
Completed at 00:05:34.655
29 - Command VERIFY - CDP_PURGE.ZAL62038B.B_NAME = 0 within 1 seconds.
Completed at 00:05:34.855
30 - Command VERIFY - CDP_PURGE.ZAHH62038B.B_NAME = 0 within 1 seconds.
Completed at 00:05:34.975
31 - Command VERIFY - START_PERM.CDP_VLV.NOR = 1 within 1 seconds.
Completed at 00:05:35.095
32 - Command VERIFY - SHUTDOWN.SD_LAT.LATCH_AE = 0 within 0 seconds.
Completed at 00:05:35.235
SOV 62038 SHOULD BE CLOSED IS OPEN DURING STARTUP
SD TEST (LIQ FUEL)
35 - Command CLEAR_SW - All switches cleared at 00:05:35.675
36 - Command LOAD - "READY TO START"
37 - Command TOGGLE - FUEL_SYS.LIQSEL_OR.IN_2 toggled to 1 for 1 seconds.
Completed at 00:05:12.860
38 - Command TOGGLE - SFC_STEP.START_OR.IN_3 toggled to 1 for 1 seconds.
Completed at 00:05:13.955
39 - Command VERIFY - CDP_PURGE.START_INIT.B_NAME = 1 within 100 seconds.
Completed at 00:05:14.065
40 - Command VERIFY - CDP_PURGE.LIQ100PCT.B_NAME = 1 within 300 seconds.
Completed at 00:05:14.195
41 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:15.335
42 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:18.425
43 - Command SETVAR - INPUT SWITCH "N2N47_BI.ZS62038B - 7 -CDP PURGE
UPSTREAM VALVE (VB) CLOSED-ACT 1 - XCP_VB_GT1 - REVERSE" set to 0 at 00:05:18.475
44 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:19.600
45 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:22.645
46 - Command VERIFY_BAND - CDP_PURGE.ZS62038A.B_NAME stayed within 0.5 of
0 for 1 seconds within 50 seconds. Completed at 00:06:11.890
47 - Command VERIFY_BAND - CDP_PURGE.ZS62038B.B_NAME stayed within 0.5 of
0 for 1 seconds within 1 seconds. Completed at 00:06:12.950
48 - Command VERIFY - CDP_PURGE.ZAH62038A.B_NAME = 0 within 1 seconds.
Completed at 00:06:13.015
49 - Command VERIFY - CDP_PURGE.ZAHH62038A.B_NAME = 0 within 1 seconds.
Completed at 00:06:13.155
50 - Command VERIFY - CDP_PURGE.ZAL62038B.B_NAME = 1 within 50 seconds.
Completed at 00:06:15.850
51 - Command VERIFY - CDP_PURGE.ZAHH62038B.B_NAME = 0 within 1 seconds.
Completed at 00:06:16.015
52 - Command VERIFY - START_PERM.CDP_VLV.NOR = 0 within 1 seconds.
Completed at 00:06:16.135
53 - Command VERIFY - SHUTDOWN.SD_LAT.LATCH_AE = 1 within 3 seconds.
Completed at 00:06:16.250
SOV 62038 SHOULD BE OPEN IS CLOSED ALARM TEST (LIQ
FUEL)
56 - Command CLEAR_SW - All switches cleared at 00:06:16.615
57 - Command LOAD - "FULL SPEED NO LOAD"
58 - Command TOGGLE - FUEL_SYS.LIQSEL_OR.IN_2 toggled to 1 for 1 seconds.
Completed at 00:31:51.480
59 - Command VERIFY - CDP_PURGE.LIQ100PCT.B_NAME = 1 within 300 seconds.
Completed at 00:33:01.290
60 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:33:02.425
61 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:33:05.570
62 - Command SETVAR - INPUT SWITCH "N2N47_BI.ZS62038B - 7 -CDP PURGE
UPSTREAM VALVE (VB) CLOSED-ACT 1 - XCP_VB_GT1 - REVERSE" set to 1 at 00:33:05.615
63 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:33:06.840
64 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:33:09.935
65 - Command VERIFY_BAND - CDP_PURGE.ZS62038A.B_NAME stayed within 0.5 of
1 for 1 seconds within 1 seconds. Completed at 00:33:11.035
66 - Command VERIFY_BAND - CDP_PURGE.ZS62038B.B_NAME stayed within 0.5 of
1 for 1 seconds within 1 seconds. Completed at 00:33:12.135
67 - Command VERIFY - CDP_PURGE.ZAH62038A.B_NAME = 0 within 1 seconds.
Completed at 00:33:12.235
68 - Command VERIFY - CDP_PURGE.ZAHH62038A.B_NAME = 0 within 1 seconds.
Completed at 00:33:12.445
69 - Command VERIFY - CDP_PURGE.ZAL62038B.B_NAME = 1 within 1 seconds.
Completed at 00:33:12.565
70 - Command VERIFY - CDP_PURGE.ZAHH62038B.B_NAME = 0 within 1 seconds.
Completed at 00:33:12.785
71 - Command VERIFY - START_PERM.CDP_VLV.NOR = 0 within 1 seconds.
Completed at 00:33:12.925
72 - Command VERIFY - SHUTDOWN.SD_LAT.LATCH_AE = 0 within 0 seconds.
Completed at 00:33:13.055
SOV 62038 SHOULD BE OPEN IS OPEN NO ALARM TEST (LIQ
FUEL)
75 - Command CLEAR_SW - All switches cleared at 00:33:13.535
76 - Command LOAD - "FULL SPEED NO LOAD"
77 - Command TOGGLE - FUEL_SYS.LIQSEL_OR.IN_2 toggled to 1 for 1 seconds.
Completed at 00:31:51.415
78 - Command VERIFY - CDP_PURGE.LIQ100PCT.B_NAME = 1 within 300 seconds.
Completed at 00:33:01.130
79 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:33:02.220
80 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:33:05.265
81 - Command SETVAR - INPUT SWITCH "N2N47_BI.ZS62038B - 7 -CDP PURGE
UPSTREAM VALVE (VB) CLOSED-ACT 1 - XCP_VB_GT1 - REVERSE" set to 0 at 00:33:05.315
82 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:33:06.490
83 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:33:09.570
84 - Command VERIFY_BAND - CDP_PURGE.ZS62038A.B_NAME stayed within 0.5 of
1 for 1 seconds within 1 seconds. Completed at 00:33:10.740
85 - Command VERIFY_BAND - CDP_PURGE.ZS62038B.B_NAME stayed within 0.5 of
0 for 1 seconds within 1 seconds. Completed at 00:33:11.820
86 - Command VERIFY - CDP_PURGE.ZAH62038A.B_NAME = 0 within 1 seconds.
Completed at 00:33:11.905
87 - Command VERIFY - CDP_PURGE.ZAHH62038A.B_NAME = 0 within 1 seconds.
Completed at 00:33:12.135
88 - Command VERIFY - CDP_PURGE.ZAL62038B.B_NAME = 0 within 1 seconds.
Completed at 00:33:12.255
89 - Command VERIFY - CDP_PURGE.ZAHH62038B.B_NAME = 0 within 1 seconds.
Completed at 00:33:12.385
90 - Command VERIFY - START_PERM.CDP_VLV.NOR = 1 within 1 seconds.
Completed at 00:33:12.530
91 - Command VERIFY - SHUTDOWN.SD_LAT.LATCH_AE = 0 within 0 seconds.
Completed at 00:33:12.730
END OF ZS62038B TEST
Return to calling script at 00:33:12.730
5 - Command CALL - ZS62040A
ZS62040A TEST
2 - Command CLEAR_SW - All switches cleared at 00:33:14.095
3 - Command LOAD - "READY TO START"
SOV 62040 SHOULD BE OPEN IS CLOSED ALARMS TEST (GAS
FUEL)
5 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:12.955
6 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:16.080
7 - Command SETVAR - INPUT SWITCH "N2N47_BI.ZS62040A - 11 - CDP PURGE
VENT VALVE (VV1) OPEN-ACT 1 - XCP_VV1_GT1 - AI_DEFAULT" set to 0 at 00:05:16.135
8 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:17.320
9 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:20.360
10 - Command VERIFY_BAND - CDP_PURGE.ZS62040A.B_NAME stayed within 0.5 of
0 for 1 seconds within 1 seconds. Completed at 00:05:21.485
11 - Command VERIFY_BAND - CDP_PURGE.ZS62040B.B_NAME stayed within 0.5 of
0 for 1 seconds within 1 seconds. Completed at 00:05:22.550
12 - Command VERIFY - CDP_PURGE.ZAL62040A.B_NAME = 1 within 1 seconds.
Completed at 00:05:22.615
13 - Command VERIFY - CDP_PURGE.ZALL62040A.B_NAME = 0 within 1 seconds.
Completed at 00:05:22.775
14 - Command VERIFY - CDP_PURGE.ZAH62040B.B_NAME = 0 within 1 seconds.
Completed at 00:05:22.875
15 - Command VERIFY - CDP_PURGE.ZALL62040B.B_NAME = 0 within 1 seconds.
Completed at 00:05:23.005
16 - Command VERIFY - START_PERM.CDP_VLV.NOR = 0 within 1 seconds.
Completed at 00:05:23.215
17 - Command VERIFY - SHUTDOWN.DM_LAT.LATCH1 = 0 within 1 seconds.
Completed at 00:05:23.335
18 - Command VERIFY - SHUTDOWN.SD_LAT.LATCH_AE = 0 within 0 seconds.
Completed at 00:05:23.515
20 - Command LOAD - "READY TO START"
SOV 62040 SHOULD BE OPEN IS CLOSED BOTH FAIL ALARMS
TEST (GAS FUEL)
22 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:12.935
23 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:16.050
24 - Command SETVAR - INPUT SWITCH "N2N47_BI.ZS62040A - 11 - CDP PURGE
VENT VALVE (VV1) OPEN-ACT 1 - XCP_VV1_GT1 - AI_DEFAULT" set to 0 at 00:05:16.145
25 - Command SETVAR - INPUT SWITCH "N2N47_BI.ZS62040B - 12 - CDP PURGE
VENT VALVE (VV1) CLOSED-ACT 1 - XCP_VV1_GT1 - REVERSE" set to 1 at 00:05:16.255
26 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:17.435
27 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:20.525
28 - Command VERIFY_BAND - CDP_PURGE.ZS62040A.B_NAME stayed within 0.5 of
0 for 1 seconds within 1 seconds. Completed at 00:05:21.580
29 - Command VERIFY_BAND - CDP_PURGE.ZS62040B.B_NAME stayed within 0.5 of
1 for 1 seconds within 1 seconds. Completed at 00:05:22.735
30 - Command VERIFY - CDP_PURGE.ZAL62040A.B_NAME = 1 within 1 seconds.
Completed at 00:05:22.825
31 - Command VERIFY - CDP_PURGE.ZALL62040A.B_NAME = 0 within 1 seconds.
Completed at 00:05:22.995
32 - Command VERIFY - CDP_PURGE.ZAH62040B.B_NAME = 1 within 1 seconds.
Completed at 00:05:23.155
33 - Command VERIFY - CDP_PURGE.ZALL62040B.B_NAME = 0 within 1 seconds.
Completed at 00:05:23.275
34 - Command VERIFY - START_PERM.CDP_VLV.NOR = 0 within 1 seconds.
Completed at 00:05:23.515
35 - Command VERIFY - SHUTDOWN.DM_LAT.LATCH1 = 0 within 1 seconds.
Completed at 00:05:23.635
36 - Command VERIFY - SHUTDOWN.SD_LAT.LATCH_AE = 0 within 0 seconds.
Completed at 00:05:23.815
SOV 62040 SHOULD BE OPEN IS OPEN ALARMS TEST (GAS
FUEL)
39 - Command CLEAR_SW - All switches cleared at 00:05:24.275
40 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:25.455
41 - Command LOAD - "READY TO START"
42 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:14.870
43 - Command SETVAR - INPUT SWITCH "N2N47_BI.ZS62040A - 11 - CDP PURGE
VENT VALVE (VV1) OPEN-ACT 1 - XCP_VV1_GT1 - AI_DEFAULT" set to 1 at 00:05:14.935
44 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:16.055
45 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:19.165
46 - Command VERIFY_BAND - CDP_PURGE.ZS62040A.B_NAME stayed within 0.5 of
1 for 1 seconds within 1 seconds. Completed at 00:05:20.230
47 - Command VERIFY_BAND - CDP_PURGE.ZS62040B.B_NAME stayed within 0.5 of
0 for 1 seconds within 1 seconds. Completed at 00:05:21.330
48 - Command VERIFY - CDP_PURGE.ZAL62040A.B_NAME = 0 within 1 seconds.
Completed at 00:05:21.385
49 - Command VERIFY - CDP_PURGE.ZALL62040A.B_NAME = 0 within 1 seconds.
Completed at 00:05:21.595
50 - Command VERIFY - CDP_PURGE.ZAH62040B.B_NAME = 0 within 1 seconds.
Completed at 00:05:21.755
51 - Command VERIFY - CDP_PURGE.ZALL62040B.B_NAME = 0 within 1 seconds.
Completed at 00:05:21.955
52 - Command VERIFY - START_PERM.CDP_VLV.NOR = 1 within 1 seconds.
Completed at 00:05:22.095
53 - Command VERIFY - SHUTDOWN.DM_LAT.LATCH1 = 0 within 1 seconds.
Completed at 00:05:22.255
54 - Command VERIFY - SHUTDOWN.SD_LAT.LATCH_AE = 0 within 0 seconds.
Completed at 00:05:22.385
SOV 62040 SHOULD BE OPEN IS CLOSED DURING STARTUP
SD TEST (GAS FUEL)
57 - Command LOAD - "START INITIATED"
58 - Command VERIFY - CDP_PURGE.START_INIT.B_NAME = 1 within 100 seconds.
Completed at 00:05:13.095
59 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:14.380
60 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:17.505
61 - Command SETVAR - INPUT SWITCH "N2N47_BI.ZS62040A - 11 - CDP PURGE
VENT VALVE (VV1) OPEN-ACT 1 - XCP_VV1_GT1 - AI_DEFAULT" set to 0 at 00:05:17.575
62 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:20.675
63 - Command VERIFY_BAND - CDP_PURGE.ZS62040A.B_NAME stayed within 0.5 of
0 for 1 seconds within 1 seconds. Completed at 00:05:21.760
64 - Command VERIFY_BAND - CDP_PURGE.ZS62040B.B_NAME stayed within 0.5 of
0 for 1 seconds within 1 seconds. Completed at 00:05:22.895
65 - Command VERIFY - CDP_PURGE.ZAL62040A.B_NAME = 1 within 1 seconds.
Completed at 00:05:23.035
66 - Command VERIFY - CDP_PURGE.ZALL62040A.B_NAME = 0 within 1 seconds.
Completed at 00:05:23.335
67 - Command VERIFY - CDP_PURGE.ZAH62040B.B_NAME = 0 within 1 seconds.
Completed at 00:05:23.520
68 - Command VERIFY - CDP_PURGE.ZALL62040B.B_NAME = 0 within 1 seconds.
Completed at 00:05:23.685
69 - Command VERIFY - START_PERM.CDP_VLV.NOR = 0 within 1 seconds.
Completed at 00:05:23.815
70 - Command VERIFY - SHUTDOWN.DM_LAT.LATCH1 = 0 within 1 seconds.
Completed at 00:05:24.030
71 - Command VERIFY - SHUTDOWN.SD_LAT.LATCH_AE = 1 within 0 seconds.
Completed at 00:05:24.175
SOV 62040 SHOULD BE CLOSED IS OPEN DM TEST (LIQ
FUEL)
74 - Command CLEAR_SW - All switches cleared at 00:05:24.535
75 - Command LOAD - "FULL SPEED NO LOAD"
76 - Command TOGGLE - FUEL_SYS.LIQSEL_OR.IN_2 toggled to 1 for 1 seconds.
Completed at 00:31:51.385
77 - Command VERIFY - CDP_PURGE.LIQ100PCT.B_NAME = 1 within 300 seconds.
Completed at 00:33:01.130
78 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:33:02.405
79 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:33:05.535
80 - Command SETVAR - INPUT SWITCH "N2N47_BI.ZS62040A - 11 - CDP PURGE
VENT VALVE (VV1) OPEN-ACT 1 - XCP_VV1_GT1 - AI_DEFAULT" set to 1 at 00:33:05.665
81 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:33:09.025
82 - Command VERIFY_BAND - CDP_PURGE.ZS62040A.B_NAME stayed within 0.5 of
1 for 1 seconds within 1 seconds. Completed at 00:33:10.200
83 - Command VERIFY_BAND - CDP_PURGE.ZS62040B.B_NAME stayed within 0.5 of
1 for 1 seconds within 1 seconds. Completed at 00:33:11.460
84 - Command VERIFY - CDP_PURGE.ZAL62040A.B_NAME = 0 within 1 seconds.
Completed at 00:33:11.720
85 - Command VERIFY - CDP_PURGE.ZALL62040A.B_NAME = 1 within 1 seconds.
Completed at 00:33:12.035
86 - Command VERIFY - CDP_PURGE.ZAH62040B.B_NAME = 0 within 1 seconds.
Completed at 00:33:12.505
87 - Command VERIFY - CDP_PURGE.ZALL62040B.B_NAME = 0 within 1 seconds.
Completed at 00:33:13.175
88 - Command VERIFY - START_PERM.CDP_VLV.NOR = 1 within 1 seconds.
Completed at 00:33:13.825
89 - Command VERIFY - SHUTDOWN.DM_LAT.LATCH1 = 1 within 1 seconds.
Completed at 00:33:14.200
90 - Command VERIFY - SHUTDOWN.SD_LAT.LATCH_AE = 0 within 0 seconds.
Completed at 00:33:14.810
SOV 62040 SHOULD BE CLOSED IS CLOSED NO DM TEST (LIQ
FUEL)
93 - Command CLEAR_SW - All switches cleared at 00:33:15.605
94 - Command LOAD - "FULL SPEED NO LOAD"
95 - Command TOGGLE - FUEL_SYS.LIQSEL_OR.IN_2 toggled to 1 for 1 seconds.
Completed at 00:31:51.665
96 - Command VERIFY - CDP_PURGE.LIQ100PCT.B_NAME = 1 within 300 seconds.
Completed at 00:33:01.450
97 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:33:02.740
98 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:33:05.980
99 - Command SETVAR - INPUT SWITCH "N2N47_BI.ZS62040A - 11 - CDP PURGE
VENT VALVE (VV1) OPEN-ACT 1 - XCP_VV1_GT1 - AI_DEFAULT" set to 0 at 00:33:06.035
100 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:33:09.200
101 - Command VERIFY_BAND - CDP_PURGE.ZS62040A.B_NAME stayed within 0.5
of 0 for 1 seconds within 1 seconds. Completed at 00:33:10.360
102 - Command VERIFY_BAND - CDP_PURGE.ZS62040B.B_NAME stayed within 0.5
of 1 for 1 seconds within 1 seconds. Completed at 00:33:11.460
103 - Command VERIFY - CDP_PURGE.ZAL62040A.B_NAME = 0 within 1 seconds.
Completed at 00:33:11.545
104 - Command VERIFY - CDP_PURGE.ZALL62040A.B_NAME = 0 within 1 seconds.
Completed at 00:33:11.715
105 - Command VERIFY - CDP_PURGE.ZAH62040B.B_NAME = 0 within 1 seconds.
Completed at 00:33:11.855
106 - Command VERIFY - CDP_PURGE.ZALL62040B.B_NAME = 0 within 1 seconds.
Completed at 00:33:12.025
107 - Command VERIFY - START_PERM.CDP_VLV.NOR = 1 within 1 seconds.
Completed at 00:33:12.175
108 - Command VERIFY - SHUTDOWN.DM_LAT.LATCH1 = 0 within 1 seconds.
Completed at 00:33:12.325
109 - Command VERIFY - SHUTDOWN.SD_LAT.LATCH_AE = 0 within 0 seconds.
Completed at 00:33:12.565
END OF ZS62040A TEST
Return to calling script at 00:33:12.565
6 - Command CALL - ZS62040B
ZS62040B TEST
2 - Command CLEAR_SW - All switches cleared at 00:33:14.055
3 - Command LOAD - "READY TO START"
SOV 62040 SHOULD BE OPEN IS CLOSED ALARMS TEST (GAS
FUEL)
5 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:13.115
6 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:16.200
7 - Command SETVAR - INPUT SWITCH "N2N47_BI.ZS62040B - 12 - CDP PURGE
VENT VALVE (VV1) CLOSED-ACT 1 - XCP_VV1_GT1 - REVERSE" set to 1 at 00:05:16.315
8 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:17.435
9 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:20.525
10 - Command VERIFY_BAND - CDP_PURGE.ZS62040A.B_NAME stayed within 0.5 of
1 for 1 seconds within 1 seconds. Completed at 00:05:21.580
11 - Command VERIFY_BAND - CDP_PURGE.ZS62040B.B_NAME stayed within 0.5 of
1 for 1 seconds within 1 seconds. Completed at 00:05:22.655
12 - Command VERIFY - CDP_PURGE.ZAL62040A.B_NAME = 0 within 1 seconds.
Completed at 00:05:22.755
13 - Command VERIFY - CDP_PURGE.ZALL62040A.B_NAME = 0 within 1 seconds.
Completed at 00:05:22.985
14 - Command VERIFY - CDP_PURGE.ZAH62040B.B_NAME = 1 within 1 seconds.
Completed at 00:05:23.180
15 - Command VERIFY - CDP_PURGE.ZALL62040B.B_NAME = 0 within 1 seconds.
Completed at 00:05:23.375
16 - Command VERIFY - START_PERM.CDP_VLV.NOR = 0 within 1 seconds.
Completed at 00:05:23.515
17 - Command VERIFY - SHUTDOWN.DM_LAT.LATCH1 = 0 within 1 seconds.
Completed at 00:05:23.635
18 - Command VERIFY - SHUTDOWN.SD_LAT.LATCH_AE = 0 within 0 seconds.
Completed at 00:05:23.705
SOV 62040 SHOULD BE OPEN IS OPEN ALARMS TEST (GAS
FUEL)
21 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:25.155
22 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:28.255
23 - Command SETVAR - INPUT SWITCH "N2N47_BI.ZS62040B - 12 - CDP PURGE
VENT VALVE (VV1) CLOSED-ACT 1 - XCP_VV1_GT1 - REVERSE" set to 0 at 00:05:28.335
24 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:29.510
25 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:32.580
26 - Command VERIFY_BAND - CDP_PURGE.ZS62040A.B_NAME stayed within 0.5 of
1 for 1 seconds within 1 seconds. Completed at 00:05:33.700
27 - Command VERIFY_BAND - CDP_PURGE.ZS62040B.B_NAME stayed within 0.5 of
0 for 1 seconds within 1 seconds. Completed at 00:05:34.775
28 - Command VERIFY - CDP_PURGE.ZAL62040A.B_NAME = 0 within 1 seconds.
Completed at 00:05:34.855
29 - Command VERIFY - CDP_PURGE.ZALL62040A.B_NAME = 0 within 1 seconds.
Completed at 00:05:35.035
30 - Command VERIFY - CDP_PURGE.ZAH62040B.B_NAME = 0 within 1 seconds.
Completed at 00:05:35.285
31 - Command VERIFY - CDP_PURGE.ZALL62040B.B_NAME = 0 within 1 seconds.
Completed at 00:05:35.495
32 - Command VERIFY - START_PERM.CDP_VLV.NOR = 1 within 1 seconds.
Completed at 00:05:35.695
33 - Command VERIFY - SHUTDOWN.DM_LAT.LATCH1 = 0 within 1 seconds.
Completed at 00:05:35.815
34 - Command VERIFY - SHUTDOWN.SD_LAT.LATCH_AE = 0 within 0 seconds.
Completed at 00:05:35.975
SOV 62040 SHOULD BE OPEN IS CLOSED DURING STARTUP
SD TEST (GAS FUEL)
37 - Command LOAD - "START INITIATED"
38 - Command VERIFY - CDP_PURGE.START_INIT.B_NAME = 1 within 100 seconds.
Completed at 00:05:13.015
39 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:14.230
40 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:17.360
41 - Command SETVAR - INPUT SWITCH "N2N47_BI.ZS62040B - 12 - CDP PURGE
VENT VALVE (VV1) CLOSED-ACT 1 - XCP_VV1_GT1 - REVERSE" set to 1 at 00:05:17.435
42 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:20.590
43 - Command VERIFY_BAND - CDP_PURGE.ZS62040A.B_NAME stayed within 0.5 of
1 for 1 seconds within 1 seconds. Completed at 00:05:21.635
44 - Command VERIFY_BAND - CDP_PURGE.ZS62040B.B_NAME stayed within 0.5 of
1 for 1 seconds within 1 seconds. Completed at 00:05:22.725
45 - Command VERIFY - CDP_PURGE.ZAL62040A.B_NAME = 0 within 1 seconds.
Completed at 00:05:22.825
46 - Command VERIFY - CDP_PURGE.ZALL62040A.B_NAME = 0 within 1 seconds.
Completed at 00:05:23.035
47 - Command VERIFY - CDP_PURGE.ZAH62040B.B_NAME = 1 within 1 seconds.
Completed at 00:05:23.225
48 - Command VERIFY - CDP_PURGE.ZALL62040B.B_NAME = 0 within 1 seconds.
Completed at 00:05:23.405
49 - Command VERIFY - START_PERM.CDP_VLV.NOR = 0 within 1 seconds.
Completed at 00:05:23.575
50 - Command VERIFY - SHUTDOWN.DM_LAT.LATCH1 = 0 within 1 seconds.
Completed at 00:05:23.735
51 - Command VERIFY - SHUTDOWN.SD_LAT.LATCH_AE = 1 within 0 seconds.
Completed at 00:05:23.915
SOV 62040 SHOULD BE CLOSED IS OPEN DM TEST (LIQ
FUEL)
54 - Command CLEAR_SW - All switches cleared at 00:05:24.315
55 - Command LOAD - "FULL SPEED NO LOAD"
56 - Command TOGGLE - FUEL_SYS.LIQSEL_OR.IN_2 toggled to 1 for 1 seconds.
Completed at 00:31:51.505
57 - Command VERIFY - CDP_PURGE.LIQ100PCT.B_NAME = 1 within 300 seconds.
Completed at 00:33:01.290
58 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:33:02.395
59 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:33:05.515
60 - Command SETVAR - INPUT SWITCH "N2N47_BI.ZS62040B - 12 - CDP PURGE
VENT VALVE (VV1) CLOSED-ACT 1 - XCP_VV1_GT1 - REVERSE" set to 0 at 00:33:05.655
61 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:33:08.815
62 - Command VERIFY_BAND - CDP_PURGE.ZS62040A.B_NAME stayed within 0.5 of
0 for 1 seconds within 1 seconds. Completed at 00:33:10.005
63 - Command VERIFY_BAND - CDP_PURGE.ZS62040B.B_NAME stayed within 0.5 of
0 for 1 seconds within 1 seconds. Completed at 00:33:11.165
64 - Command VERIFY - CDP_PURGE.ZAL62040A.B_NAME = 0 within 1 seconds.
Completed at 00:33:11.255
65 - Command VERIFY - CDP_PURGE.ZALL62040A.B_NAME = 0 within 1 seconds.
Completed at 00:33:11.365
66 - Command VERIFY - CDP_PURGE.ZAH62040B.B_NAME = 0 within 1 seconds.
Completed at 00:33:11.635
67 - Command VERIFY - CDP_PURGE.ZALL62040B.B_NAME = 1 within 1 seconds.
Completed at 00:33:11.855
68 - Command VERIFY - START_PERM.CDP_VLV.NOR = 1 within 1 seconds.
Completed at 00:33:12.155
69 - Command VERIFY - SHUTDOWN.DM_LAT.LATCH1 = 1 within 1 seconds.
Completed at 00:33:12.315
70 - Command VERIFY - SHUTDOWN.SD_LAT.LATCH_AE = 0 within 0 seconds.
Completed at 00:33:12.445
SOV 62040A SHOULD BE CLOSED IS CLOSED NO DM TEST
(LIQ FUEL)
73 - Command CLEAR_SW - All switches cleared at 00:33:13.015
74 - Command LOAD - "FULL SPEED NO LOAD"
75 - Command TOGGLE - FUEL_SYS.LIQSEL_OR.IN_2 toggled to 1 for 1 seconds.
Completed at 00:31:51.360
76 - Command VERIFY - CDP_PURGE.LIQ100PCT.B_NAME = 1 within 300 seconds.
Completed at 00:33:01.130
77 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:33:02.285
78 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:33:05.360
79 - Command SETVAR - INPUT SWITCH "N2N47_BI.ZS62040B - 12 - CDP PURGE
VENT VALVE (VV1) CLOSED-ACT 1 - XCP_VV1_GT1 - REVERSE" set to 1 at 00:33:05.425
80 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:33:08.580
81 - Command VERIFY_BAND - CDP_PURGE.ZS62040A.B_NAME stayed within 0.5 of
0 for 1 seconds within 1 seconds. Completed at 00:33:09.610
82 - Command VERIFY_BAND - CDP_PURGE.ZS62040B.B_NAME stayed within 0.5 of
1 for 1 seconds within 1 seconds. Completed at 00:33:10.685
83 - Command VERIFY - CDP_PURGE.ZAL62040A.B_NAME = 0 within 1 seconds.
Completed at 00:33:10.765
84 - Command VERIFY - CDP_PURGE.ZALL62040A.B_NAME = 0 within 1 seconds.
Completed at 00:33:11.025
85 - Command VERIFY - CDP_PURGE.ZAH62040B.B_NAME = 0 within 1 seconds.
Completed at 00:33:11.205
86 - Command VERIFY - CDP_PURGE.ZALL62040B.B_NAME = 0 within 1 seconds.
Completed at 00:33:11.365
87 - Command VERIFY - START_PERM.CDP_VLV.NOR = 1 within 1 seconds.
Completed at 00:33:11.510
88 - Command VERIFY - SHUTDOWN.DM_LAT.LATCH1 = 0 within 1 seconds.
Completed at 00:33:11.725
89 - Command VERIFY - SHUTDOWN.SD_LAT.LATCH_AE = 0 within 0 seconds.
Completed at 00:33:11.865
END OF ZS62040A TEST
Return to calling script at 00:33:11.865
7 - Command CALL - PT6228
PT6228 SENSOR TEST
2 - Command CLEAR_SW - All switches cleared at 00:33:13.335
3 - Command LOAD - "READY TO START"
SF Alarm LOW PT6228 TEST
6 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:13.235
7 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:16.365
8 - Command SETVAR - INPUT SWITCH "N2N6_AI.PT6228 - 2 -GAS FUEL MANIFOLD
PRESS-PSIG - PGF_GP2_GT1 - AI_DEFAULT,PSIATOPSIG" set to -17 at 00:05:16.405
9 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:17.510
10 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:20.580
11 - Command VERIFY_BAND - FUEL_SYS.PT6228.A_NAME stayed within 0.5 of -17
for 1 seconds within 1 seconds. Completed at 00:05:21.670
12 - Command VERIFY - MMI_INTER.PT6228.B_OUT_1 = 1 within 1 seconds.
Completed at 00:05:21.745
13 - Command VERIFY - MMI_INTER.PT6228.B_OUT_2 = 0 within 1 seconds.
Completed at 00:05:21.895
14 - Command VERIFY - MMI_INTER.PT6228.B_OUT_3 = 0 within 1 seconds.
Completed at 00:05:22.015
15 - Command VERIFY - FUEL_SYS.PT6228FLT.B_NAME = 1 within 1 seconds.
Completed at 00:05:22.255
SF Alarm HIGH PT6228 TEST
18 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:23.675
19 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:26.765
20 - Command SETVAR - INPUT SWITCH "N2N6_AI.PT6228 - 2 -GAS FUEL
MANIFOLD PRESS-PSIG - PGF_GP2_GT1 - AI_DEFAULT,PSIATOPSIG" set to 817 at
00:05:26.905
21 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:28.055
22 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:31.175
23 - Command VERIFY_BAND - FUEL_SYS.PT6228.A_NAME stayed within 0.5 of 817
for 1 seconds within 1 seconds. Completed at 00:05:32.320
24 - Command VERIFY - MMI_INTER.PT6228.B_OUT_1 = 1 within 1 seconds.
Completed at 00:05:32.395
25 - Command VERIFY - MMI_INTER.PT6228.B_OUT_2 = 0 within 1 seconds.
Completed at 00:05:32.575
26 - Command VERIFY - MMI_INTER.PT6228.B_OUT_3 = 0 within 1 seconds.
Completed at 00:05:32.745
27 - Command VERIFY - FUEL_SYS.PT6228FLT.B_NAME = 1 within 1 seconds.
Completed at 00:05:32.885
NO Alarm PT6228 TEST
30 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:34.420
31 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:37.515
32 - Command SETVAR - INPUT SWITCH "N2N6_AI.PT6228 - 2 -GAS FUEL
MANIFOLD PRESS-PSIG - PGF_GP2_GT1 - AI_DEFAULT,PSIATOPSIG" set to 800 at
00:05:37.570
33 - Command TOGGLE - RESET_ACKN.LOC_RESET.IN_2 toggled to TRUE for 1
seconds. Completed at 00:05:38.730
34 - Command RUN - Netsim ran for 3 seconds while the script was paused. Completed
at: 00:05:41.860
35 - Command VERIFY_BAND - FUEL_SYS.PT6228.A_NAME stayed within 0.5 of 800
for 1 seconds within 1 seconds. Completed at 00:05:42.935
36 - Command VERIFY - MMI_INTER.PT6228.B_OUT_1 = 0 within 1 seconds.
Completed at 00:05:43.020
37 - Command VERIFY - MMI_INTER.PT6228.B_OUT_2 = 0 within 1 seconds.
Completed at 00:05:43.195
38 - Command VERIFY - MMI_INTER.PT6228.B_OUT_3 = 0 within 1 seconds.
Completed at 00:05:43.340
39 - Command VERIFY - FUEL_SYS.PT6228FLT.B_NAME = 0 within 1 seconds.
Completed at 00:05:43.495
END OF PT6228 SENSOR TEST
Return to calling script at 00:05:43.730
Script completed successfully at 00:05:43.730