Vous êtes sur la page 1sur 3

Page 1 of 3

TECHNICAL SPECIFICATION
2XS(FL)2Y 1x630RM/95 127/220 (245)kV acc. to IEC 62067
CONSTRUCTION (x) The picture is informative only
– not in scale
Round, stranded and compressed
copper conductor. Class 2. APPLICATION
Extruded semi-conducting Laying in ground
conductor screen (wet or dry locations)
Insulation XLPE – dry cured Laying in air
Extruded semi-conducting Laying in ducts
insulation screen
Semi-conducting swelling tapes Highest permissible conductor
Metallic screen: temperature
copper wires screen and Continuous operation 90°C
copper equalizing tapes Overload 105°C
Semi-conducting swelling tapes Short circuit 250°C
Longitudinal aluminum foil (duration max 5s)
Sheath – black HDPE ST7 type
Laying is possible without any special
measures at natural cable temperatures and
ambient temperature not lower than -5ºC,
MARKING with Tele-Fonika supervising
TF KABLE, product name, date of
manufacture, standard, meter marking

DESCRIPTION UNIT DETAILS


CONSTRUCTION DATA Uo/U/Um 127/220 (245)kV
Conductor
material Copper
number of wires No 58
Nominal cross sectional area mm2 630
Conductor diameter and tolerance mm 30.0-0,2+0,5
Thickness of semi-conducting tape No x mm 2 x ~ 0.1
Min. / Nom. thickness semi-conducting XLPE on conductor mm 0.8 / 1.2
Nominal insulation thickness XLPE mm 22.0
Insulation thickness: minimum at a point mm 19.8
Diameter over insulation – nominal mm 76.4±0,5
Min. / Nom. thickness semi-conducting XLPE on insulation mm 0.8 / 1.2
Thickness of semi-conducting swelling tape No x mm 2 x ~ 0.35
Metallic screen mm2 50
Copper wires No x mm 60 x 1.44
Copper equalizing tapes No x mm x mm 2 x 10 x 0.18
Mean diameter over metallic screen mm 82.6
Thickness of semi-conducting swelling tape No x mm 2 x ~ 0.35
Thickness of aluminum foil mm 0.2
Diameter over aluminum foil mm 84.1
Nominal thickness of outer serving / min. at any point mm / mm 4.0 / 3.3
Approximate overall diameter
completed cable (De) mm 92.2
Weight of complete cable (approx.) kg/km 11980
DELIVERY DATA
Flange diameter of wooden drum m 3.0
Type 30OP
Maximum length per drum m 400
Weight of heaviest reel, including cable kg 6700

(x)
Diameters are calculated values and subject to manufacturing tolerances
Page 2 of 3

ELECTRICAL DATA at 50Hz


Maximum D.C. conductor resistance at 20°C Ω/km 0.0283
Maximum A.C. conductor resistance at 90°C Ω/km 0.0384
Maximum D.C. metallic screen resistance at 20°C Ω/km 0.188
0.137
Maximum D.C. aluminum foil resistance at 20°C Ω/km 0.500
Operating inductance
flat trefoil mH/km 0.414
Induction reactance
flat trefoil Ω/km 0.130
Capacitance µF/km 0.160 (+ 8 %)
Capacitance reactance kΩ/km 20.27
Impedance
flat trefoil Ω/km 0.136
Zero sequence reactance Ω/km 0.080
Max. electric stress at conductor screen / (at insulation) kV/mm 9.1 / 3.9
Dielectric losses (tgδ = 0.001) – per phase W/m 0.786
Partial discharge test – at 1.5Uo pC ≤5
Charging current – per phase A/km 6.27
Charging power kVA/km 796
Earth fault current – per phase A/km 18.80
MECHANICAL DATA
Recommended min. bending radius for laying m 2.32
Recommended permissible bending radius at final installation m 1.86
Maximum permissible pulling force: kN 31.5
SHORT CIRCUIT CURRENTS
Maximum permissible thermal short-circuit (IEC 60949)
Current for 1.0 sec.
Phase conductor 90 → 250°C kA 90.8
Metallic screen 80 → 350°C kA 19.2
AMPACITY (**) – Bonding of the metallic screens Single point
Cables in tunnel
trefoil formation A 993
TESTS
AC voltage test (2.5Uo; 30min.) kV 318
Impulse voltage kV 1050
Partial discharge test (1.5Uo) kV 190

Marking:
TF-KABLE 5 2XS(FL)2Y 1x630RM/95 127/220kV IEC 62067 2017

(**)
Current rating guideline (Calculated with Cymcap 5.3 based on IEC Pub. 60287 and the following conditions)

Ground temperature 30°C


Ground thermal resistivity 2.5 K·m/W

(x)
Diameters are calculated values and subject to manufacturing tolerances
Page 3 of 3
Ampacity 993A
Temperature in tunnel 40.0°C

Date: 2017-09-26; Mp15193


Prepared by: Michał Pstrągowski

(x)
Diameters are calculated values and subject to manufacturing tolerances