#1 A phenomenon that occurs when the battery open circuits while the
engine is running.
LED's
The green LED should always blink. Fast blinking rate indicates existence
of one or more of the following conditions:
1. Normal engine oil pressure (ie In#5 OIL PRESS SHUT = OFF),
2. Engine speed greater than 60 RPM,
3. Gen frequency greater than 15 Hz.
Short-cuts keys:
1. The numeric keys 0 – 9 available on the front panel of the GCM
indicates the most commonly used information for the operators with
information from just a click away.
3 Generator 3 phase L-N and L-L 4 Generator total power and P.F.
OVERVIEW REPORT
COMMAND MEASURE
SET-UP HELP
Select Enter Esc
• Line 1 shows the controller operating mode and the clock. The clock
appears only if the operator initialised the clock by the
COMMAND\SET-CLOCK.
• Line 2 shows the genset current activity and the remaining time to its
end. Asterisk (*) indicates that the genset is running in sync with the
auxiliary phase V4, ie the mains phase A.
• Line 3 shows the genset command or countdown to the command start.
• Line 4 shows the automatic transfer switch status.
REPORT
REPORT examines the log of messages. Each message includes the time it
entered the log. If the clock was not running, "time ???" will appear. Most
messages report some fault such as the example on the left.
Note!
1. Every new message automatically calls REPORT.
2. Clearing a fault message does not "accept" or "clear" the fault. Use the
RESET button to accept faults.
3. REPORT opens the log of messages showing the most recent message
first. The log keeps the last 8 messages.
OFF mode
When in OFF mode, the monitoring system is active except for the relays
R#3 AUDIBLE ALARM.
AUTO Ö OFF
This function changes the operating mode to AUTO. User password
may be required.
OFFÖMAN
This function changes the operating mode to MAN. The genset
immediately starts unless a shutdown fault exists.
When in MAN mode, the genset runs unless a shutdown fault exists. It is
possible to define the MAN mode as a warning fault.
MANÖOFF
This function changes the operating mode to OFF. The genset stops after
cooling down if necessary.
LOAD-GEN
This function instructs the genset to take the load. User password may
be required.
OFF-LOAD
This function instructs the genset running in MAN mode to remove the
load.
AUTOmatic mode
When in AUTO mode, unless a shutdown fault exists, the genset…
1. Starts immediately when Engine selector switch (S2) is put to Man
mode.
2. Starts immediately when Engine selector switch (S2) is put to No Load
Test mode.
Stops after a time delay following Engine selector switch (S2) is put
back to Auto or Off mode.
3. Sleep is a special AUTO mode where genset start is disabled. It is
selected when Engine selector switch (S1) is put to Off mode.
AUTO->OFF RUN-TEST
EXPORT SEQUENCE
SET-CLOCK
Select Enter Esc
EXPORT
** Not Applicable **
SEQUENCE
** Not Applicable **
SET-CLOCK
Upon power up supply to the GCM, the following screen will appears to
remind the operator to set clock for the unit.
The clock has no memory. Set it up after switching on the battery to have
messages logged with time.
MEASURE
Note!
1. %THD is a measure of how "pure" the generator sine wave is. Consider
Total Harmonic Distortion (THD) above 2% as inappropriate for modern
office equipment. Non-linear loads and ground faults at the generator
stator windings are major sources of harmonics.
2. Positive kVAr means that the current is lagging after the voltage.
Normal.
3. Negative kVAr means that the current is leading the voltage. Abnormal!
SYNCscope
Gen ΦA v Bus ΦA V1 gen phase-A vs V4 mains phase-
Freq Slip Hz: -0.07 A
Phase Shift °: 11 V1 frequency - V4 frequency
Voltage Match: -2 V4 to V1 angles: -180°..180°
V1 volts - V4 volts
Activity Counters
Activity Counters
Engine Cranks: 0015
Genset Runs : 0010
Genset Onload: 0008
Input Status
In#:1234567890123456
On :
Off:****************
RUN WITH LOAD :OFF
IN 1..16
This function shows which IOB input channels are active. Use the left←
and right→ push-buttons to move the LCD cursor to any input channel
column to find its name
SET-UP
This menu defines the systems parameters: set-points, delays, etc. The
parameters are non-volatile (unaffected by battery disconnection). You
need to know the installation engineer password to enter the menu.
Please refer to next page for details.
Note!
1. Operators are not allow to change any settings in the controller.
1. After the GCM is powered up, press the ESC button twice.
2. The display as above will appears on the screen in the first column.
3. Use the ← → button to scroll through the screen until the
highlight at
SET-UP and press ENTER.
4. The display as above will appears on the screen in the second
column.
5. Use the numeric button to enter the 4 digit password and press
ENTER.
6. The display as above will appears on the screen in the third column.
7. Use the ← → button to scroll through the screen until the
highlight at Directory you wish to enter and press ENTER.
1. After the screen display the list of settings example as show above.
2. Use the ← → button to scroll through the screen until the
highlight at setting desire.
3. Press ENTER and the cursor will highlight at the value need to be
changed.
4. Key in the new value and press ENTER again.
• BASICS ● OPTION
• SET-POINTS ● DELAYS
• IN1…16 ● FACTORY
BASIC :
Please note that for IOB1 after BASIC is selected, the screen will
display the list of settings. The second page is only applicable to IOB2
only.
Controller ID No
A value between 1 to 8. A unique number should be assigned to each
controller that is connected to the RS485 communication line.
No of Alt Poles
The number of the rotor poles (always an even number).
Pick-up Teeth
Number of teeth on the gear.
CT Ratio
Current transformers ratio. For example, ratio = 160 for 800A:5A
transformers.
PT Ratio
Potential transformers ratio. For example, ratio = 33 for 33KV : 100V
transformers.
Xre: Rated kW
The true (active) power rating of the set (engine), denoted Xre.
Double-up WYE Gen
This option is used to switch between low and high WYE (star)
operation. The voltage is measured through (internal) alternator coil.
The use of this option is preferred to assigning a {PT Ratio} of 2 for the
high WYE case as here all the other parameters are automatically
adjusted -- the {Gen OvCurrent} is halved and all the kW/kVAr related
parameters keep their value.
Ideal Freq Hz
The rated Frequency of the generator set.
OPTIONS :
WRITE PROTECT...!?
1 makes all SET-UP parameters read only!
Generic Configure?
Use only default setting = 0 (Setting depends on Configuration)
Parallelin System?
Use only default setting = 0 (Setting depends on Configuration)
Not In Used?
Use only default setting.
Not In Used?
Use only default setting.
Not In Used?
Use only default setting.
Engine Diesel|Gas
Enter 0 = Diesel engines. Enter 1 = gas engines.
Generator Syn|Asy
Enter 1 for induction generators.
Energize Run|Stop:
0 = fuel solenoid is "energize to run".
1 = fuel solenoid is "energize to stop".
Not In Used?
Use only default setting.
Hi Oil Press Shut?
0 = To allow cranking of genset when oil press is present.
1 = Not to allow cranking of genset when oil press is present.
LowWaterLevel S|W:
In#10 LOW WATER LEVEL fault is: 0 = shutdown, 1 = warning.
SleepClearsFaults?
1 means that switching the operating mode from AUTO to SLEEP by
In#3 clears all the pending faults.
Motor Contactors ?
0 indicates that the contactor(s) are driven by an electromagnet:
1 indicates that the contactor(s) are driven by a motor or by a spring
charged by a motor:
R#2 Alarm|Usable
With the "0" option relay #2 serves as a visual alarm relay, energized
when the genset has a shutdown or a warning fault.
When this option is "1", an energized relay #2 state indicates that the
genset ready to operator.
Not In Used?
Use only default setting.
Not In Used?
Use only default setting.
DELAYS SETPOINTS
OPTIONS IN 1….16
BASIC FACTORY
Select Enter Esc
User Password
The user must enter this 4 digit password to change the operating mode,
change the run-time count, etc. No password is required if this number is
0.
Cranking Attempts
This is the number of engine cranking attempts.
Overspeed RPM
This threshold applies to the speed read from the magnetic pickup.
CrankStop RPM
Engine "firing" speed. This threshold applies to the speed read from the
magnetic pickup.
Bat OvVoltage
Battery over voltage threshold. Fault is declared after a 1 sec delay.
Bat UnVoltage
Battery under voltage threshold. Fault is declared after a 1 sec delay.
Gen UnVoltage
Under voltage threshold. Applies to each gen phase to neutral voltage.
Gen OvFrequen
Generator phase A (V1) over frequency threshold.
Gen UnFrequen
Generator phase A (V1) under frequency threshold.
Gen OvCurrent
Overcurrent threshold, Is. It applies to each generator phase current
separately. Is is usually selected as the 100% (nominal) generator phase
current. The time delay before a fault is declared depends on the extent
the current exceeds Is. If the phase current is just a few amps higher
than Is it will take very long time before GEN OVERCURRENT is
declared.
Gen Revrse kW
Reverse (negative) true power kW threshold. Applies to each gen phase
(V1/I1, V2/I2 & V3/I3). Fault indicates a potential prime mover failure.
V4 Ov Voltage
Over voltage threshold for the mains/bus phase A (V4) input.
V4 Un Voltage
Under voltage threshold for the mains phase A (V4) input.
V4 Un Frequen
Under frequency threshold for the mains phase A (V4) input.
Not In Used?
Use only default setting.
Not In Used?
Use only default setting.
Not In Used?
Use only default setting.
Not In Used?
Use only default setting.
Not In Used?
Use only default setting.
Not In Used?
Use only default setting.
Not In Used?
Use only default setting.
Not In Used?
Use only default setting.
Not In Used?
Use only default setting.
Not In Used?
Use only default setting.
Not In Used?
Use only default setting.
Not In Used?
Use only default setting.
Not In Used?
Use only default setting.
Not In Used?
Use only default setting.
Not In Used?
Use only default setting.
Not In Used?
Use only default setting.
Not In Used?
Use only default setting.
GCM_doc2_V29K Pan-Exp Engineering Pte Ltd 28
Not In Used?
Use only default setting.
Not In Used?
Use only default setting.
Not In Used?
Use only default setting.
Not In Used?
Use only default setting.
Not In Used?
Use only default setting.
Not In Used?
Use only default setting.
Not In Used?
Use only default setting.
Not In Used?
Use only default setting.
Not In Used?
Use only default setting.
Not In Used?
Use only default setting.
Not In Used?
Use only default setting.
Not In Used?
Use only default setting.
Hi Water ° C
The set point value for the sender reading to be active for warning or
shutdown.
Lo Oil BAR
The set point value for the sender reading to be active for warning or
shutdown.
Hi Oil ° C
The set point value for the sender reading to be active for warning or
shutdown.
Over-Charge
The set point value for the sender reading to be active for warning or
shutdown.
Lo Water ° C
The set point value for the sender reading to be active for warning or
shutdown.
Hi Oil BAR
The set point value for the sender reading to be active for warning or
shutdown.
Lo Oil ° C
The set point value for the sender reading to be active for warning or
shutdown.
Under-Charge
The set point value for the sender reading to be active for warning or
shutdown.
DELAYS SETPOINTS
OPTIONS IN 1….16
BASIC FACTORY
Select Enter Esc
Bat UnderVolts
The time delay from detecting under-voltage of genset battery.
Gen OverVolts
The time delay from detecting over-voltage in any gen phase
(V1,V2,V3) to the declaration of fault.
Gen UnderVolts
The time delay from detecting under-voltage in any gen phase
(V1,V2,V3) to the declaration of fault.
Gen OverFreq
The time delay from detecting over-frequency in gen phase A (V1) to
the declaration of fault.
Gen UnderFreq
The time delay from detecting under-frequency in gen phase A (V1) to
the declaration of fault.
G Rvrs kVAr
The time delay from detecting reverse reactive power in any gen phase
(V1,V2,V3) to the declaration of fault, ie generator loss of excitation.
G Over %THD
The time delay from detecting "percentage of harmonic distortion"
higher than the set-point level in any gen phase (V1,V2,V3), to the
declaration of fault.
Not In Used?
Use only default setting.
Not In Used?
Use only default setting.
Not In Used?
Use only default setting.
Test Delay
The time delay from No LOAD Test deactivation to genset stop.
V4 Volts Status
The time delay to reject transient abnormal status in the mains/bus phase
A.
Standby On * Mains Standby ATS = 1
Time delay between Mains(V4) failure to genset start in auto mode.
Standby Off * Mains Standby ATS = 1
Time delay for Mains(V4) return to remove genset load in auto mode.
Engine Preglow
The time delay for engine preglowing before cranking.
GCM_doc2_V29K Pan-Exp Engineering Pte Ltd 32
Engine Crank
The time limit on engine cranking.
CrankFail Rest
The time delay between cranking attempts.
Coolin Down
The genset run time, without load, to cool off the engine.
Stoppin Max
The limit on the time from blocking fuel supply (through FUEL
SOLENOID relay) to reaching genset standstill conditions.
AlarmOn Max
The time limit on R#3 AUDIBLE ALARM relay activity.
LubPump On
K#5 LUBRICATION PUMP cycle: On time.
LubPump Off
K#5 LUBRICATION PUMP cycle: Off time.
Not In Used?
Use only default setting.
Contactor Delay
Limit on the time from applying a command to close the gen or mains
contactors.
Exceeding this time limit is a shutdown fault.
In#08 ~ Alarm
The time delay for input to be active.
In#09 ~ Alarm
The time delay for input to be active.
In#12 ~ Alarm
The time delay for input to be active.
Hi Water ° C
The time delay for alarm or shutdown to be active.
Lo Oil BAR
The time delay for alarm or shutdown to be active.
Hi Oil ° C
The time delay for alarm or shutdown to be active.
Over-Charge
The time delay for alarm or shutdown to be active.
Lo Water ° C
The time delay for alarm or shutdown to be active.
Hi Oil BAR
The time delay for alarm or shutdown to be active.
Lo Oil ° C
The time delay for alarm or shutdown to be active.
Under-Charge
The time delay for alarm or shutdown to be active.
IN 1…16 :
Function:
This option is used to set each input from In#01 to In#16 for either
Normally Closed or Normally opened contact Status.
1. After the screen display the list of settings example as show above.
2. Use the ← → button to scroll through the screen until the
highlight at setting desire.
3. Press ENTER to toggle the asterisk between N/C and N/O.
4. When done, just press the ESC key.
FACTORY :
VARISTOR
DC
ENGINE OVERCRANK
All the engine cranking attempts have failed. See SET-UP\SET-
POINTS.
ENGINE SHUTDOWN FAIL
Engine fuel supply was blocked yet, after delay (see SET-
UP\DELAYS), "signs of life" are still detected. Hint: Check In#5 OIL
PRESS SHUT.
ENGINE SLOW CRANK
The speed, read by the magnetic pickup, 2 seconds after starting to crank
the engine, was found to be lower than 60 RPM.
EXTERNAL OVERLOAD
The result of active In#14 EXTERNAL OVERLOAD. This can be a
shutdown or a warning fault. See SET-UP\OPTIONS. Immediately on
detecting active In#14 status the generator contactor opens (K#7 is de-
energized).
FREQUENCY NOT BUILT
Following detection of engine firing speed, after delay, normal gen
frequency was not reached (see SET-UP\SET-POINTS & DELAYS).
GEN EXCITATION LOSS
Negative kVAr (reactive power) was detected. The generator is expected
to supply kVAr! Is it an AVR fault? See also SET-UP\SET-POINTS &
DELAYS.
GEN HIGH HARMONICS
Heavy non-linear loads? Improper generator type or size? Stator short-
circuit can also cause high harmonics. See also SET-UP\SET-POINTS
& DELAYS.
GEN OVER FREQUENCY
Generator frequency higher than SET-UP\SET-POINT existed for SET-
UP\DELAY.
GEN OVERCURRENT
Note! The larger the overcurrent level is...the shorter gets fault
declaration time delay. See SET-UP\SET-POINTS & DELAYS.
GEN OVERVOLTAGE
Generator voltage higher than SET-UP\SET-POINT existed for SET-
UP\DELAY.