Compliance
Clause No. Item Check List Inspection Report
( Please ✔ )
2.4 Flooded Suction to pump intake port Height Min Effective Water level to Centre line of Pump Suction
Port: +/- ________ m
2.5.1 Check NPSH A ≥ NPSHR + 1m Calculated at 130% Flow NPSH A _______m
NPSH A = 10.1m(ATM) + static height – friction loss NPSH R _______m
2.5.2 Check No Prohibited devices (e.g - Check, Butterfly or Globe Valves Pump Suction Valve
& & Flow switches) on Pump Suction Pipe manifold. Listed OS&Y gate valve Type? YES □ NO □
3.7.2 If strainer fitted check - Free area > 4 times pump suction entry area & If Butterfly type, located 15 pipe
Individual strainer opening < 8mm x 8mm YES □ NO □
diameters of pump inlet?
Flow
3.1 Check fire pump performance curve satisfies: Pump Duty __ LPS @ Head __ KPa
Shut-off Pressure < 140% of duty head. Shut-off Pressure/Duty Head _______ < 1.40
Max Flow capability = 130% duty flow @ > 80% duty head. Max Flow/Duty Flow _______ > 1.3
3.1 Check Pump Casing & System Component (pipe work, valves, flanges, roll Casing Pressure Rating _______ KPa
& groove couplings etc.) pressure rating greater than Pump Shut-off pressure System Component Pressure Rating _______ KPa
3.6.1 + Suction pressure. Shut-off + Max Suction Pressure _______ KPa
3.6.1.2 Request Hydrostatic Pressure test certificate - Pump & Pipework (1.5 times Tested Pressure _______ KPa
working pressure)
3.6.2 Check Suction & Discharge Pipe work sized for < 4m/s velocity Max flow (= Duty Flow x1.3) _______ LPM
(at Maximum flow) Suction Pipe & Valves Diameter _______ mm
Discharge Pipe & Valve Diameter _______ mm
3.6.7 Check pipe Flexible connections if fitted are metallic Braided type Flexible connection is metallic braided? YES □ NO □
3.6.8 Check no pipe loads acting on pump casing – Supports provided Piping supported? YES □ NO □
3.7.3 Check automatic air release valve fitted for horizontal split case & vertical
Automatic air release valve fitted? YES □ NO □
turbine type pump sets (Not a screwed type plug)
3.7.4.1 Check Circulation Relief valve (CRV) fitted & sized as below Pump Minimum Flow _______ LPS
3.7.4.2 Size = 19mm for pump flows to 9,500 LPM
Size = 20mm for pump flows 9,501 to 19,000 LPM Circulation Relief Valve Size _______ mm
8.1.3 Electric Motor Power rating ≥ 115% power required for all flows from shut Min Motor KW =
_______KW X 1.15
head to 130% of duty flow. Pump Max Power Rqd. to 130%
= _______ KW
Flow X 1.15 =
BKB Building Solutions Pty. Ltd.
109-111 Wedgewood Road
Hallam VIC 3803
Tel: 1300 252 227 Fax: (+61) 3 8786 0441
8.2 Electric Fire Pump Controllers Lockable Isolator YES □ NO □
8.2.1 Degree of Protection Minimum IP54 Located within sight of driver YES □ NO □
8.2.2 Location within sight of driver
Floor to Cabinet clearance ______mm
8.2.3 Control Cabinet minimum 300mm clearance from floor level and any
current carrying parts. High impact resistance viewing panel if provided Ratio Viewing Panel/Door Area _______ %
shall be < 40% of door area. IP NEMA
Controller Protection
8.2.4 Pump circuit fitted with lockable isolator and overcurrent protected by a □ □
circuit breaker on supply side to AS/NZS3000 Circuit Breaker Rating _______ Amps
8.2.5 Fire pump motor shall attain full speed within 15s of start signal Time to full speed from signal ______s
8.2.6 Check Variable speed controller, if fitted, limits discharge pressure Set Variable speed controller fitted YES □ NO □
Point to 110% duty pressure.
8.2.8 Touch screens shall not be used for primary operations – start, stop or Ratio Set Point/Duty Pressure ________
reset. Touch screen not for primary
8.2.9 All indicator lights shall be accessible for replacement. functions Start, Stop or Reset - Via YES □ NO □
Check following indicator provided – Power On; Power Fail; Pump Run; push buttons only
Battery Charge Supply Fail; variable Speed Control Malfunction & Aural Access to indicator lights available YES □ NO □
Alarm Silenced Six Indicators listed provided YES □ NO □
8.2.10 Individual Volt Free contacts for Power On, Pump Run & Common Fault Three Volt Free Contact provided YES □ NO □
provided.
Aural alarm operates
8.2.11 Aural alarm Integral or Remote to panel provided to operate YES □ NO □
simultaneously with indicator lights
simultaneously with lights indicating Power Fail, Phase Fail & Pump Run
Monitor Battery Provided YES □ NO □
Indicator & Aural Alarm power supply via monitor Battery
8.2.12 Test facility provided for testing indicator lights & Aural Alarms Test facility provided YES □ NO □
8.2.13 Ammeter provided to indicate motor current for each phase. Read Phase current - L1/L2/L3 _______ Amps
8.2.14 Conductors & Terminal Blocks shall be numbered. Numbered Conductors & Blocks YES □ NO □
8.2.15 Monitor Battery - installed outside control panel on frame 150mm above
Battery Location ________
8.2.16 floor, Terminals covered, 2 years’ service life, 72h capacity, AGM sealed
type & identification plate fixed. 150mm High YES □ NO □
8.2.17 Battery Charger – 3 stage type – Boost, Absorption & Float Charger Terminal Covers YES □ NO □
complete with Ammeter & Voltmeter. Two Yrs. Life YES □ NO □
72Hr Capacity YES □ NO □