Sr. No. Item Description Units
A B
1 132 kV EQUIPMENT
1.1 Power Transformer
i) 50MVA, 132/33kV, 3-ph Power Transformer with 10% extra oil Nos. 1 1
1.2 Circuit Breakers (3 Ph.)
i) 145KV,1600 A, 31.5 kA SF6 CircuitBreaker with support structure,
marshalling boxes, terminal connectors etc. Nos. 1 1
1.3 Isolators (3 Ph.) Motor operated
i) 1250A, 31.5 kA , 145 KV Low Level Isolator without earth switch but
with insulators, marshalling boxes, terminal connectors etc (Motorised) Nos. 3 3

ii) 1250A, 31.5 kA , 145 KV Low Level Isolator without earth switch
(TANDEM) but with insulators, marshalling boxes, terminal connectors Nos. 0 0
etc (Motorised)
iii) 1600A, 31.5 kV , 145 KV high level Isolator without earth switch but
with insulators,marshalling boxes,terminal connectors etc(Motorised ) Nos. 1 1

1.4 Portable discharge rods (1-ph) Nos. 3 3


1.5 Current Transformers (1-Ph.)
i) 600-300-150/1-1-1-1-1A, 31.5kA, 145 KV multicore single phase Current
Transformers (with 5 Core) with 120% extended current rating with Nos. 3 3
marshalling boxes, terminal connectors etc.
1.6 120 kV Gap less Surge Arrestors (1-Ph.) withsurge/discharge counters and
with marshalling boxes, terminal connectors etc Nos. 3 3
1.7 ERECTION HARDWARE WITHOUT BPI
Hardware, Spacers, bus-bar material, Bay MB, clamps, connectors
including equipment connectors (Suitable for Moose , Moose to
Zebra/Panther Conductor - as per site requirement), Junction Box,
earthwire, buried cable trenches/ PVC pipes for equipment , all
accessories etc.(these include all materials required for construction of
all bays/ buses with provision of high level 132 KV Isolator whether
specifically mentioned or not) for the following :

132 kV Main & Transfer bus type


i) Transformer Bay Lot 1 1
1.8 132 kV Bus post Insulators for erection hardware (Quantity to be
furnished by tenderer) Nos. 3 3
2 33 kV EQUIPMENT
2.1 Circuit Breakers (3 Ph.)
i) 1250 A, 25 kA Vacuum CB with support structure, marshalling boxes,
terminal connectors etc Nos. 4 4
2.2 Isolators (3 Ph.) Manually operated
i) 1250A, 25 kA Low Level Isolator without earth switch but with
insulators,marshalling boxes,terminal connectors etc (Double break) Sets 8 12
ii) 1600A, 25 kA High Level Isolator without earth switch but with
insulators,marshalling boxes,terminal connectors etc(Double break) Sets 1 1
2.3 Current Transformers (1-Ph.)
i) 1200-600-300-150/1-1-1-1-1A, 25 kA , 33 KV multicore single phase
Current Transformers(with 5 Core) with 120% extended current rating Nos. 12 12
with marshalling boxes, terminal connectors etc.
2.4 30KV GAPLESS type Surge Arrestors , 1-ph, withsurge/discharge
counters and with marshalling boxes, terminal connectors etc Nos. 12 12
2.5 ERECTION HARDWARE WITHOUT BPI
Hardware, Spacers, bus-bar material, Bay MB, clamps, connectors
including equipment connectors (Suitable for Moose Conductor, Moose to
Zebra/Panther- as per site requirement), Junction Box, earthwire, buried
cable trenches/ PVC pipes for equipment , all accessories etc.(these
include all materials required for construction of all bays/ buses
whether specifically mentioned or not) for the following:

33 kV Main bus type


i) Transformer Bay Lot 1 1
ii) Replacement of existing 33KV main bus conductor with new AAC Bull
conductor alongwith equipment jumpering. Mtr 60 60
2.6 33 kV Bus Post Insulators for erection hardware (Quantity to be
furnished by the tenderer) Nos. 8 8
3 CONTROL & RELAY PANELS
3.1 132kV (Duplex Panels) Control, relay & protection panel
132/33KV Transformer (without auto reclose) Control & Relay Panels
with Numerical type of Differential Protection and Numerical E/F-O/C Sets 1 1
relays. Including Control & Protection of 33kV side
3.2 Control, relay and protection panel (without auto reclose) for 33KV

i) Line Sets 3 3
ii) Transformer Sets 0 0
4 Cable along with associated accessories like clamps,glands, lugs and
straight joints etc. (Quantity to be furnished by the tenderer)
4.1 Power Cables(XLPE) 1.1 kV
a) 1Cx150 sq mm kM 0.23 0.23
b) Any other as per requirement kM
4.2 Power Cables(PVC) 1.1 kV
a) 4Cx16 sqmm kM 0.2 0.2
b) 4Cx6 sqmm kM 0.3 0.3
c) 2Cx6 sqmm kM 0.2 0.2
d) Any other as per requirement kM
4.3 Control Cables Copper(PVC) 1.1 kV
a) 2Cx2.5 sqmm KM 2.1 2.1
b) 3Cx2.5 sqmm KM 0.1 0.1
c) 5Cx2.5 sqmm kM 6.6 6.6
d) 7Cx2.5 sqmm kM 0.1 0.1
e) 10Cx2.5 sqmm kM 2.3 2.3
f) 14Cx2.5 sqmm kM 2.3 2.3
g) 27Cx2.5 sqmm kM 2.8 2.8
h) 4Cx6 sqmm kM 0.1 0.1
i) Any other size as per requirement KM
5 Substation structure MT 20 20
6 Cable rack (Quantity to be furnished by the tenderer) MT 1.5 1.5
7 11KV 90 KN Disc Insulators(Quantity to be furnished by the tenderer)
Nos 364 364
8 Earthing mat with GI flats of following sizes for risers with spikes as per
design including all materials for comlete earthing of the substation
(Quantity to be furnished by the tenderer)
a) i) 75*12mm GI flats for equipments, columns and aux structures MT 11 11
ii) 50*6mm GI Flats for all others MT 5 5
b) M.S.Rod of 40 mm suitable sizes as required as per approved design as
per IEEE80 & IS MT 4 4
c) Materials for earthing for 50 MVA transformer MT 2 2
9 Earthing pits with supply of all materials including base plate Lot 1 1
10 Overhead shielding against lightning by galvanised steel wires &
fittings as required. Lot 1 1
11 Wheel/trolley mounted fire extingusher

a) 22.5 Kg. DCP type No. 2 2


b) 22.5 Kg. CO2 type No. 2 2
12 Light fittings 400 Watts with CG Box, lamps etc complete (bajaj cat. ref.
BGENF-14 or similar) Bajaj/Philips make with MCB switch board, cable
termination at lighting panel/locally complete in all respect for switch yard Sets 5 5
lighting.

13 Spares
A) 132 KV Circuit Breaker
i) Closing coil Nos. 1 1
ii) Tripping Coil Nos. 1 1
iii) Spring Charging Motor Nos. 1 1
B) 33KV VCB
i) Closing coil Nos. 1 1
ii) Tripping Coil Nos. 1 1
iii) Spring Charging Motor Nos. 1 1
C) Transformer
i) HV Bushing No. 1 1
ii) LV Bushing No. 1 1
iii) Neutral Bushing No. 1 1
iv) Buccholz Relay Set 1 1
v) Gasket for Main Transformer (Complete) Set 1 1
vi) OTI No. 1 1
vii) WTI No. 1 1
14 Maintenace equipment for Circuit breaker & transformer
i) BDV Test Kit No. 1 1
ii) Megger 5KV (Motorised) No. 1 1
iii) Digital Multimeter No. 1 1
iv) Oil Sampling Bottle Nos. 3 3
Site wise Quanitity
Total
C D Quantity

1 1 4

1 1 4

2 2 10

1 1 2

1 1 4

3 3 12

3 3 12

3 3 12

1 1 4
3 3 12

4 4 16

12 12 44

3 3 8

12 12 48

12 12 48
1 1 4
0 0 120

8 8 32

1 1 4

3 3 12
1 1 2

0.23 0.23 0.92

0.2 0.2 0.8


0.3 0.3 1.2
0.2 0.2 0.8

2.1 2.1 8.4


0.1 0.1 0.4
6.6 6.6 26.4
0.1 0.1 0.4
2.3 2.3 9.2
2.3 2.3 9.2
2.8 2.8 11.2
0.1 0.1 0.4

20 20 80
1.5 1.5 6
364 364 1456

11 11 44
5 5 20
4 4 16
2 2 8
1 1 4
1 1 4

2 2 8
2 2 8

5 5 20

1 1 4
1 1 4
1 1 4

1 1 4
1 1 4
1 1 4

1 1 4
1 1 4
1 1 4
1 1 4
1 1 4
1 1 4
1 1 4

1 1 4
1 1 4
1 1 4
3 3 12