5P10 & 5P20 Class CTs: They are generally used for Over
current (Instantaneous and IDMT relays) and E/F protection
of Feeders, Transformers etc.
5 signifies the % limit of composite error
P signifies Protection core,
10, 20 signify the quantum of fault current as multiples of
the rated current or ALF(Accuracy Limit Factor) up to which
the CT shall have the defined percentage of composite error
i.e. � 5%.
Standard Accuracy Limit factors as per IS: 2705 and
IEC:60044-1 are 5, 10, 15, 20 & 30.
Accuracy limit factor is inversely proportional to the rated
burden i.e. if the burden is lower than the rated one, the
limit of accuracy shall be maintained beyond the declared one.
The formulae for actual ALF;
ALFACT= ALFRTD x (Sin+Sn(Rated Burden))/( Sin+Sa(Actual
Burden)).
Example:- Calculate actual Accuracy limit factor if
secondary burden is reduced to 1/3rd, if CT rated as 200/5
A,5P10,15VA and Rct =0.15Ω?
ALF Rated=10(From CT data 5P10),
Sin (Burden due to internal resistance of the CT) = (5A)2 x
0.15=25 x 0.15=3.75VA,
Sn (Rated burden) = 15VA (From CT data),
Sa(Actual Burden) = 15�3= 5VA,