Vous êtes sur la page 1sur 5

Simulation of Secondary Arc on 400-kV

Transmission System Consisting of Overhead Line


Section and Power Cable Section
Andrzej Mackow
Mustafa Kizilcay
University Siegen
Chair of Electrical Power System
Siegen, Germany
andrzej.mackow@uni-siegen.de, kizilcay@uni-siegen.de

Abstract— This paper deals with the computation of secondary higher current amplitude is effective till single phase tripping
arc in different 400-kV transmission systems that differ from of the faulty phase. Other two phases are still energized.
each other in their configuration. Two technologies overhead line Capacitive and inductive coupling between the faulted line and
(OHL) and power cable are implemented worldwide to transfer the healthy phases feed the secondary arc further with energy.
energy for longs distances at extreme high voltage (EHV) level. The secondary arc extinguishes usually itself, but its life time
Long EHV lines are generally compensated by shunt reactor. may influence the operation of the system. If the secondary arc
Their connection to the line, compensation level and localization does not extinguish, the single-phase reclosing is endangered.
are factors that could influence fault transients of the system. The Of course disconnected phase could be reclosed firstly, when
representation of the secondary arc should be realistic to
secondary arc disappeared. However the dead time (switched-
determine correctly the auto-reclosure performance. The
off time of faulty phase) is limited by dynamic stability
secondary arc is modelled in the digital transients program
EMTP/ATP. The dynamic behaviour of the arc is determined on constrains. For EHV line his limit is less than 1.5…2 seconds.
the basis of energy balance in the arc column. Simulations with As the arc current becomes zero, the coupling causes a
real transmission lines are very useful to understand the arcing recovery voltage across the arc path. If the rate of rise of
phenomenon in particular when line consists of overhead line, recovery voltage is too great, it reignites the arc.
cable section and shunt reactors.
The characteristic of the secondary arc depends on many
line fault; autoreclosure; secondary arc; mixed line; EMTP factors like wind, ionized surrounding air and electro-dynamic
force. When transmission lines are compensated by shunt
I. INTRODUCTION reactors, the secondary arc extinction can be affected. Other
important factor that has influence on the secondary arc is the
Since it is possible to use cables even at the extreme high line configuration. Connected line-side inductances of shunt
voltage (EHV) levels, cable sections play incessant relevant reactors form with the parallel connected capacitances between
role in power system. Therefore these power cable sections line phases a resonant circuit. This parallel resonant circuit
should be considered in fault simulations in power systems. causes oscillations of the recovery voltage. This phenomenon
Their interaction with other components of electrical system was observed and briefly described in [2].
should be investigated. Furthermore their implementation in
power system involves usage of shunt reactors that could also As mentioned before new electrical grids will be more
interact with other power system components. The shunt complex. Even along a short route it may be necessary to
reactor has the function of compensating capacitive charging switch a few times from OHL to cable sections and vice versa.
current of lines that appears in low load periods [1]. When the Usage of cable sections determines installing of shunt reactors.
shunt reactor is connected to the line-side, the line and the This paper investigates the SPAR phenomenon caused by a
shunt reactor are always energized and deenergized together. SLG on a line with hybrid cable/OHL sections in a 400-kV
Transmission System Operator decides where the shunt reactor transmission system regarding secondary arc excitation
should be installed and what should be the degree of referring to the interaction between OHL, cable and shunt
compensation. reactor. The duration of secondary arc in different line
configurations is brought into focus. In the studied transmission
Single Phase to Ground (SLG) is the most common fault in system the cable section is underground. All computations are
power transmission systems. Single phase auto-reclosing executed with the EMTP/ATP software [3].
(SPAR) is used at EHV level to eliminate arcing faults and
improve system stability. SLG can be caused by lightning
strokes and are mainly temporary. Secondary arc appears
firstly when the circuit breakers at both end of the line open the
corresponding phase to isolate the fault. Primary arc with much

978-1-4673-3059-6/13/$31.00 ©2013 IEEE


II. SYSTEM MODELLING

A. Simulation Model
Both 400-kV transmission lines connect substation A and
substation C. It is possible to switch the lines at the substation
B, too. It’s assumed that the energy can be transmitted in one
direction, from substation A to substation C. At the transition
point between substations B and C one system of the overhead Figure 1. Line structure for all configurations, only one system presented
line (3 four-bundle conductors for 3 phases) is substituted by (configuration 1 without cable section)
the suitable cable system (with 6 single-core cables, one phase
needs 2 cables). Remaining part of the transmission system is
simplified in the substation A and C by a Thevenin equivalent
consisting of the voltage source and short- circuit impedance of
the positive- and zero-sequence systems.

TABLE I. INVESTIGATED LINE CONFIGURATIONS

Line Figure 2. Cable cross-line sections


Compensation OHL Cable
Configuration
1 without 210 km -

2 without 200 km 10 km
2x120 Mvar shunt C. Overheadline Model
3 reactors in each 200 km 10 km
system Transmission towers were designed to carry two electrical
circuits. Both systems are modeled in this study but transient
computations are executed only for one system. Both systems
The simulation studies were performed using EMTP-ATP are identical and results are also valid for the second system.
software version 5.7p5 [3]. Three system configurations have The circuit consists of three four-bundle conductors Al/St
been studied as shown in Table 1. They differ from each other 564/72. Four bundle conductors of each phase are replaced by
by structure and equipment. In the first configuration OHL one equivalent conductor, which has the same electrical
makes up the whole length of line. In second and third features. Skin effect in OHL and earth is considered like in the
configuration one section consists of underground cables and case of cable modelling.
takes around 5 % of total line length. Remaining 200 km
section is realized as OHL. However chosen technology plays For transient computations Constant-Parameter Distributed
important role at this voltage level and can influence on system Line model (CPDL) is used [3]. This model takes into
behaviour significantly. The 10 km long cable section from line consideration travelling waves on lines during transient
configurations 2 and 3 is located between substations B and C operations. For both cables and OHL, implementation of the PI
(20 km far away from substation B). The distance between model [3] is preferred in steady state computations.
substations A and B amounts to 110 km.
D. Shunt Reactor
B. Cable Model Reactive power produced by cable and overhead line should be
The three-phase cable is laid in the flat formation 1.5 m compensated in order to ensure that voltage does not increase
below the surface. The circuit consists of six single-core cables along a low loaded transmission line to unacceptable high
of type 2X(Fl)2Y 1x2500 RMS/400 230/400 kV. Due to the values and to reduce the loading of the line by charging current
transportation limitation a cable section is allowed to be around [1]. The consumption of this inductive reactive power
900 m of maximum length. 900 m long cable weights 36 t. The generated by lines is achieved by using shunt reactors. Shunt
cable sections are divided into main segments, each short as 1 reactors are connected to lines usually at low load periods.
km. The cross-bonding of the cable sheaths is considered in the Under normal conditions reactive power is compensated by the
simulation model. Basic electrical parameters of the circuit are inductive-resistive loads and shunt reactors are normally
compiled with the subroutine CABLE PARAMETERS [3] disconnected. In steady-state operation capacitive charging
based on the physical parameters and dimensions. Cross- current can raise voltages at the end of the line to critical
sectional layout of the cable section is shown in Fig. 2.
values. Long duration of the voltage endanger insulation of
system components. Shunt reactors are often installed at both
ends of the line.
As shunt reactors are connected directly to the line, they are
energized and deenergized together with line. Shunt reactor
modelling details are presented in [4], [5]. The typical model of
a shunt reactor consists of an inductor in series with resistor.
Despite that accuracy of this model is high; to evaluate some
other phenomena, it is necessary to have a more detailed network. The arc current iarc is calculated at each time step
model. The aspects to be considered in modelling of a shunt according to the following equation
reactor are shunt reactor core saturation, core and winding
losses, and mutual inductance between the shunt reactor g ⋅ vth
phases. In this model the latter one is not considered. iarc = (1)
1 + g ⋅ rth
Positive- and zero- sequence impedances of shunt reactors are
not equal depending on the core type. Shunt reactors in this Voltage vth and resistance rth are acquired from rest of
system as inputs. The instantaneous arc conductance is
study are modelled as 3-leg core units. A simplified single-
computed by solving numerically a differential equation which
phase equivalent circuit of the shunt reactor is given in Figure
was described briefly in [2]. Differential equation system is
3. The positive-sequence impedance takes into consideration of solved simultaneously in MODELS with COMBINE
the core saturation that has been represented according to a ITERATE statement iteratively [6]. Variables in differential
voltage-current characteristic shown in Fig. 4. The zero- equations depend on instantaneous arc length. The arc length
sequence reactance is represented by a linear inductance. Shunt variation has to given by the user.
reactor is connected directly to line.
The secondary arc extinguishes when the arc voltage
reaches the level of recovery voltage [8]. Recovery voltage is
the voltage across the fault path at arc location.

Figure 3. Shunt reactor model

Figure 5. Interaction between the electric circuit and the arc modell using
Type-94 component

III. TRANSIENT PHENOMENA DURING ENERGIZATION AND


DEENERGIZATION OF LINES
The analysis of the transmission line consisting of one OHL
and one cable section is based on computations of the steady-
state performance and of the electromagnetic transients, i. e.
switching and fault transients. Steady-state analysis is
associated with the reactive power compensation and the
Figure 4. U-I characteristic of shunt reactor model voltage rise at the end of the unloaded line.

E. Secondary Arc Representation A. Line in Steady State


The representation of arc is realized in EMTP/ATP with the The results are shown in Table II. The line configuration
type-94 component. Type-94 component gives the user the with cable section produces significantly more reactive power
facility to define own electrical component in ATP via than line with only OHL in no-load state. Furthermore voltages
MODELS language. Arc model from [2] serves as basis. at end of the line are higher by configuration with cable
MODELS language is briefly described in [6]. Thevenin type section. Despite the fact that cable makes only 5% of line its
component represents the rest of the grid as a two-pole influence on steady state conditions of the line is significant. In
interfacing the arc model. Voltage vth and resistance rth are practice only part of produced reactive power is compensated
inputs for the arc model. These two inputs are passed at each with shunt reactors. The remaining reactive power is absorbed
time step to the model and used to estimate the resulting arc by rest of electrical system or consumed by line itself in higher
current. Fig. 5 shows the interaction of the arc with remaining loading periods. Two shunt reactors are installed as close as
part of circuit. possible to the cable. First shunt reactor is installed in
substation B. On the other side of cable sections the substation
The computation of secondary arc variables including C is 90 km far away from cable end. Thus second shunt reactor
secondary arc current is performed in MODELS. Accurate is installed directly at the transition point between cable and
derivation was presented briefly in [2], [7]. The usage of type- OHL. One system is compensated by two 120-Mvar shunt
94 component enables simultaneous solution of the arc reactors connected to the line in mentioned before locations.
equations together with the system of equations of the electric
The same configuration (same shunt reactors and their
locations) is chosen for the second system.

TABLE II. STEADY STATE RESULTS

Produced by Line
Line Voltage at End in
Reactive Power under
Configuration Substation C (p.u)
no-load state (Mvar)
1 177 1.03

2 395 1.08

3 153 1.03 Figure 7. Arc voltage of configuration 1 with OHL

It is observed that secondary arc in configuration 1 with


B. Secondary Arc in a 400-kV Transmission Line OHL line alone extinguishes after 1.35 s (Fig. 6). Duration
time of secondary arc at a line with cable section (configuration
During a SLG short circuit secondary arc between line and 2) is shorter and secondary arc extinguishes after 0.9 s (Fig. 8).
overhead line tower can occur. The influence of partial The same operation was repeated for different fault locations
replacement of an OHL by cable sections and line-side along the line. In all investigated cases secondary arc
connected shunt reactors on arcing time of the secondary arcs extinguishes faster for line configuration with cable section.
are investigated in several papers [2], [9], [10]. Both cable and When secondary arc current decreases with time, secondary arc
OHL are represented by CPDL model. The arc model (type-94 voltage increases. The secondary arc does not extinguish
element) which was developed in MODELS simulation before arc voltage reaches level of recovery voltage.
language is connected to the fault phase at transition point Waveforms of arc voltages for both configurations are shown
between overhead line and cable. The type-94 element is in Fig. 7 and 9. For configuration with only OHL recovery
grounded by a 0.1 Ω resistance. Following arc parameters have voltage is reached later as for configuration with cable section.
been used for the simulation. These variables are inserted into In line with cable section arc voltage attains faster recovery
the differential equation system from [2]. voltage and secondary arc can extinguish.
u´0 = 0.9 kV/m, τ0 = 1 ms
r´0 = 22 mΩ/m, α = −0.5

The initial arc length is assumed to be 3.5 m. First


investigated system is in 50% load state. The second parallel
system during the fault is in an error free state (also 50% load
state). SLG fault in phase A is initiated for all configurations of
the line. The primary arc is initiated at t = 0.1 s at transition
point between OHL and cable (20 km far away from substation
B). The pole of phase A of the circuit breaker in substation B
and C opens at t = 0.5 s in voltage zero point. Waveforms of
arc currents and arc voltages for first and second line
configurations are shown in Fig. 6-9.
Figure 8. Arc current of configuration 2 with cable section

Figure 6. Arc current of configuration 1 with OHL

Figure 9. Arc voltage of configuration 2 with cable section


The line configuration with cable section requires a shunt IV. CONCLUSION
reactor to compensate produced in low load periods reactive The number of applications of hybrid lines consisting of
power. Degree of compensation and location of these shunt several OHL and cable sections at EHV level may rise in near
reactors were already presented in previous chapter. The future. Usage of cable sections determines installing of shunt
influence of these line-side connected shunt reactors on reactors to compensate produced in low load periods reactive
secondary arc is investigated. A SLG fault is simulated in the power. Influence of cable sections in EHV line and connected
same location as for previous cases (first transition point). Both line- side shunt reactors was investigated. The secondary arc
shunt reactors do not have neutral coils. Fig. 10, 11 show the life- time for different line configurations was brought into
computed arc current and voltage. focus.
Primary and secondary arc stages can be represented with
the arc model presented in this paper. The arc was modelled
using type-94 component in EMTP/ATP. This model enables
solution of differential equation system in subroutine
MODELS simultaneously with running computations in
EMTP/ATP. The behaviour of secondary arc is extreme
random. However the model used in this paper allows
investigating secondary arc in auto- reclosing studies.

For different line configurations secondary arc extinguishes


after different time intervals. The longest secondary arc life-
Figure 10. Arc current of configuration 3 with cable and shunt reactor time was obtained for configuration with only OHL.
Substitution of short OHL section for cable section causes
much higher production of reactive power. This reactive power
must be compensated. Connected line-side shunt reactors in
configuration 3 with cable section can extend life- time of
secondary arc.

REFERENCES
[1] F. Noack, Einführung in die elektrische Energietechnik,
Fachbuchverlag Leipzig , 2003 (in German).
[2] M. Kizilcay "Simulation of Seconday Arcs on EHV Transmission
Lines using EMTP/ATP, " KEUG International Workshop on ATP-
EMTP 2004
[3] Canadian/American EMTP User Group , ATP Rule Book, Portland;
revised and distributed by EEUG Assosciation 2006.
Figure 11. Arc voltage for configuration 3 with cable and shunt reactor [4] Z. Gajic, B. Hillström, F. Mehic "HV Shunt Reactors. Secrets for
protection engineers , 2003 15th Western Protective Relaying
Conference, Spokane, USA
[5] L. Prikler, G. Ban, G. Banfai "EMTP Models for Simulation of Shunt
It was observed that secondary arc in configuration with Reactor Switching Transients, " 1995 15th International Conference
on Power System Transients, Lisbon, Portugal
cable section and shunt reactors extinguishes after 1,27 s. [6] L. Dube, users guige to MODELS in ATP, 1996
Compared to the line configuration 2 without shunt reactor [7] L. Prikler, M. Kizilcay, G. Ban, P.Handl, Improved Secondary Arc
(Fig. 8, 9) the recovery voltage oscillates causing longer Models Based on Identification of Arc Parameters from Staged Fault
secondary arc duration. If the recovery voltage would be too Test Records, 2002 14th PSCC Conference, Sevilla, Spain
high, secondary arc could not extinguish and re-ignition of the [8] H. J. Haubrich, Single-Phase Auto-Reclosing in EHV Systems,
CIGRE 1974
arc would be likely. [9] IEEE Power System Relaying Committee Report, Single-Phase
tripping and auto-reclosure of transmission lines, IEEE Trans.
Delivery, vol. 7, no.1m pp.182-192, January 1992
[10] E.W. Kimbark, Selective-pole switching of long double-circuit EHV
line, IEEE Trans. Power App. & Systems, vol. PAS-95, no.1, pp. 219-
230, Jan/Feb 1976.F. Noack, Einführung in die elektrische
Energietechnik, Fachbuchverlag Leipzig , 2003 (in German).

Vous aimerez peut-être aussi